Strasshofer GmbH, Am Fernblick 11, 08499 Reichenbach GERMANY Phone: +49 8171 48311 0Email: [email protected] • Web: www.strasshofer.de© Strasshofer 09 / 2021 - Technical changes reserved
®
Application:Our DHW units FW-E 60 are heating the domestic water centrally and are supplying it via hot water pipeline to the domestic water tapping points. A buffer tank is necessary in order to provide the required heating water quantity for heating the domestic water! The DHW water is only heated when "Just in Time" is requested. There is no storage of hot water!
Water heating:The DHW water is heated in the fl ow-through principle only during the request via a stainless steel plate heat exchanger. A special heat exchanger design allows high tap rates and a low return temperature to the buffer tank.
High effi ciency pump:The DHW volume fl ow (speed controlled) is delivered by a high-effi ciency pump from the buffer tank to the plate exchanger for the heating of water.
Control function:The central control element is the electronic controller. This ensures a constant domestic hot water temperature.
Sensors:Fast and very precise control processes are made possible by the use of state-of-the-art sensors. A fl ow sensor according to the vortex principle, determines the fl ow rate and the hot water temperature. Accurate and fast reacting PT-1000 temperature sensors measure the temperatures of: cold water, buffer tank fl ow and circulation return.
Housing:Stylish EPP insulating housing with design front panel.
Circulation module Z3 / Z4 (optional):A drinking water high-effi ciency circulation pump is controlled intelligently (according to pulse, time and temperature) and speed-controlled by the electronic control system (integration on-site).
with high-effi ciency pumps with high-quality sanitary balan-
cing valves all drinking water outlets going
off to the top stable instrument holder made of
galvanized sheet steel design front cascades capable
Specifi cationsType: FW-E 60Item No. : 1620001
Primär SekundärPufferspeicher Trinkwasser
Pressure rating: PN 6 PN 10Max. temperature: 110 °C 75 °CConnection dimensions: DN 32 DN 20Connection threads: 1¼" female thread 1" male threadDimensions (WxHxD): 480 x 675 x 240 mm
Performancecharacteristics PI2* PI1*
DHW capacity: 150 kW 150 kWMass fl ow primary: 2628 kg/h 2922 kg/hSupply temperature: 70 °C 60 °CReturn temperature: 21 °C 16 °CDCW / DHW temperature: 10 °C / 60 °C 10 °C / 45 °CTap performance: 42 l/min 61 l/min* PI 1 = performance indicator 1water temperature set to 45 °Cprimary supply temperature 60 °Ccold water temperature 10 °C
* PI 2 = performance indicator 2water temperature set to 60 °Cprimary supply temperature 70 °Ccold water temperature 10 °C
Desig
n fro
nt
Modules1000203 KF50 stainless steel PHE
DHW module FW-E 60for centralized DHW heating with � ow principle
Strasshofer GmbH, Am Fernblick 11, 08499 Reichenbach GERMANY Phone: +49 8171 48311 0Email: [email protected] • Web: www.strasshofer.de© Strasshofer 09 / 2021 - Technical changes reserved
®
Options
Description1 Temperature sensor DCW2 Vortex sensor temperature and fl ow3 Plate heat exchanger4 Heating pump5 Backfl ow preventer
Specifi cations
Service:
● easy-to-read, illuminated LCD display with full-text and graphic mode
● internationally understandable with up to 6 languages included
● self-explanatory operation: The assigned functions are shown in the display right above the respective input key
● easy and quick installation with the integrated setup wizard
Operating mode:DHW control without circulationDHW control with external circulationVariable storage (with 3-ways switching valve)
Add. functions Buffer charge, cascade
Plate exchanger: Long thermal length, low pressure lossStainless steel AISI 316, copper soldered
Piping: Stainless steel AISI 316, 28x1,5 mm / 22x1 mmPump: Heating pump WILO Stratos PWM 25/1-8
Sensors:
HW temperature and fl ow:Sika VVX20HR- / CW- / buffer- / circulation temperature:Plug-in sensor PT1000/B/2 with cable
Insulating housing: EPP, blackDimensions (WxHxD): 480 x 675 x 240 mm
Delivery: Pre-assembled, wired and leak-proofpacked in carton with operating instructionsand mounting accessories
DCW DHW
1
HS HR
2
3 4
5
(Module SV)
DHW = domestic hot waterDCW = domestic cold waterHS = heating supplyHR = heating return cold
Type Modul SV
Drinking water safety valve DN15 with connecting line 10 bar. / for FW-E/EZ/D 40 and FW-E 60
Item No. 1000131
Type Modul Z3
Drinking water circulation externallyDrinking water high-effi ciency circulation pump Para Z PWM 15/7
with backfl ow preventer and 1" ball valve.
Item No. 1000125
FW-E 60 Item No. 1620001
Image: FW-E 60
DHW module FW-E 60for centralized DHW heating with � ow principle