Belimo Asia Pacific
Technical Databook
Characterised Control Valves with Actuators
Version 5.1
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
2
Product overview and table of contents
Table of contents 2
Control Valves and Actuators
Product overview 3
The Belimo Characterised Control Valves 4
The Belimo Characterised Control Valves/Notes 5
The sizing of Ball Valves 6
Characterised Control Valves
R2..AC Characterised Control Valves 2-way 7
R6..AO Characterised Control Valves 2-way 8
R3.. Characterised Control Valves 2-way 9
Open/Close Ball Valves
R2..AC/R6..AC Open/Close Ball Valves 2-way 10
R3.. Open/Close Ball Valves 3-way 11
Valve dimensions 12
General Rotary Actuators
TR.. series Rotary Actuators 12
LRU.. series Rotary Actuators 15
NRU.. series Rotary Actuators 17
SRVU..-5 Rotary Actuators 19
GRVU..-7 Rotary Actuators 21
Dimensions of Mechanical Fail-Safe Rotary Actuators 23
Dimensions/Auxiliary switch adjustment 24
Installation procedures 25
Mechanical Fail-Safe Rotary Actuators
TRF.. series Mechanical Fail-Safe Rotary Actuators 28
LRF.. series Mechanical Fail-Safe Rotary Actuators 30
NRFU.. series Mechanical Fail-Safe Rotary Actuators 32
SRFU..-5 Mechanical Fail-Safe Rotary Actuators 34
Dimensions and auxiliary switch adjustment 36
Installation procedures of Mechanical Fail-Safe Rotary Actuators 37
Electronic Fail-Safe Actuators
GRKU..-7 Electronic Fail-Safe Actuators 38
Dimensions of GRKU..-7 Electronic Fail-Safe Actuators 43
Installation procedures of Electronic Fail-Safe Rotary Actuators 44
Installation Notes
Installation, direction of flow and commissioning 45
CCV-Notes on installation 46
Notes on maintenance and project design 47
3V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Modulating DV 2(0)...10V
RS-42URNRS-42URLRS-42RT SRVU24-SR-5 GRVU24-SR-7 AC/DC 24V
RS-42UFRNRS-42FRLRS-42FRTefaS-liaF SRFU24-SR-5 GRKU24-MF-7
3-point
)S-(42URN)S-(42URL42RT SRVU24(-S)-5 GRVU24-7 AC/DC 24V
)S-(032URN)S-(032URL3-032RT SRVU230(-S)-5 GRVU230-7 AC 100...240V
*FU(-S2)RN3-42FL2-42RTefaS-liaF SRFU(-S2) GRKU24-7
Modulating DV 2(0)...10V
RS-42URNRS-42URLRS-42RT
RS-42UFRNRS-42FRLRS-42FRTefaS-liaF
3-point
)S-(42URN)S-(42URL42RT
)S-(032URN)S-(032URL3-032RT
(-S2)UFRN3-42FL2-42RTefaS-liaF
61NP egnalFdaerht lanretnInoitcennoC
Kvs[m3/h] 0.63 1.0 1.6 2.5 4.0 4.0 6.3 6.3 10.0 10.0 16.0 16.0 25.0 25.0 40.0 63 100 140 230 320
DN[mm] 15 15 15 15 15 20 20 25 25 32 32 40 40 50 50 65 80 100 125 150
2-way
Characterised Control Valves and Rotary Actuators for modulating control
Product Overview
Flow characteristics of Characterised Control ValvesCharacteristic: equal percentage
Rated pressure: 3-way, 4140kPa (DN15...32), 2760kPa (DN32...50) 2-way, 2500kPa (DN15...50), 1600kPa (DN65...150)
kv
Y
R209AC R210AC R211AC R212AC R213AC R217AC R218AC R222AC R223AC R229AC R231AC R238AC R239AC R248AC R249AC R664AO R679AO R6099AO R6124AO R6149AO
daerht lanretnInoitcennoC
Kvs[m3/h] 0.63 1.0 1.6 2.5 4.0 4.0 6.3 6.3 10.0 10.0 16.0 16.0 25.0
DN[mm] 15 15 15 15 15 20 20 25 25 32 32 40 50
3-way R309 R310 R311 R312 R313 R317 R318 R322 R323 R329 R331 R338 R348
Open/Close Ball Valves and Rotary Actuators for shut-off or change-over functions
Open/Close
)S-(42URN)S-(42URL42RT SRVU24(-S)-5 GRVU24-7
)S-(032URL3-032RT NRU230(-S) SRVU230(-S)-5 GRVU230-7
Fail-Safe2)S-(UFRN)S-(42FRL)S-(42FRT SRFU(-S2)-5 GRKU24-7
)S2-(UFRN)S-(032FRL)S-(032FRT SRFU(-S2)-5 GRKU24-7
Open/Close
TR24 LRU24(-S) NRU24(-S)
TR230-3 LRU230(-S) NRU230(-S)
Fail-SafeTRF24(-S) LRF24(-S) NRFU(-S2)
TRF230(-S) LRF230(-S) NRFU(-S2)
Further contact for more combinations.
61NP egnalFdaerht lanretnInoitcennoC
Kvs[m3/h] 8.6 13 18 31 40 65 120 180 230 390 570
DN[mm] 15 20 25 32 40 50 65 80 100 125 150
2-way R215AC R220AC R225AC R232AC R240AC R250AC R665AO R680AO R6100AO R6125AO R6150AO
Flow characteristics of Open/Close Ball Valves Rated pressure: 3-way, 4140kPa (DN15...32), 2760kPa (DN32...50) 2-way, 2500kPa (DN15...50), 1600kPa (DN65...150)
Connection Internal thread
Kvs[m3/h] 8.6 21 26 16 32 32 49
DN[mm] 15 20 25 32 32 40 50
3-way R315 R320 R325 R330 R332 R340 R350
kv
Y
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
4
An ordinary Ball Valve is unsuitable as a control device
CCV-The Belimo Characterised Control Valve
In order to ensure good stability of control, a Control Valve must have a flow characteristic that complements the nonlinear characteristic of the heat exchanger in the HVAC system.
An equal-percentage valve characteristic is describled in order to produce a linear relationship between the thermal output and the amount of opening of the control device. This means that the flow rate increases slowly as the valve begins to open. Characteristic in ordinary Ball Valves is severely distorted.
The reason for this is that an ordinary Ball Valve has an extremely high flow coefficient (Kvs value) compared with its nominal size, several times that of a comparable globe valve.
Therefore, an ordinary Ball Valve is not very suitable for performing control functions:
Quick-opening flow characteristic
Flow coefficient excessive due to the design
Flow control inadequate in the part-load range
•••
Belimo has succeeded in solving the problem of thedistorted flow characteristic of ordinaryBall Valves. A so-called “characterising disc” in the inlet of the Characterised Control Valve converts the valve’s characteristic to the equal-percentage kind. The side of the characterising disc facing the ball is concave and is in contact with the surface of the ball. Thus, the actual flow is regulated by the hole in the ball and by the V-shaped aperture in the characterising disc.
The Kvs value is reduced and corresponds approximately to that of a Globe Valve of compara-ble size. In order to avoid having to fit pipe reducers in the majority of cases, each size of valve is also available with wide choices of different Kvs values.
Equal-percentage characteristic
No initial jump in flow on opening
Excellent stability of control thanks to the characterising disc
Kvs values comparable with those of Globe Valves of comparable size
Fewer pipe reducers needed
High rangeability
High close-off pressure
Tight-sealing
••••
•
•
••
Belimo has added “control” to the Ball Valve
Advantages of the Belimo Characterised Control Valve
Typ
ical h
eat e
xchanger characteristic
Equal-perce
ntage ch
aracte
ristic
R
esult
ant th
ermal
capa
city
R
esul
tant
th
ermal capacity
Fl
ow c
hara
cter
istic
100%
100%
100%
100%
Characteristic of an ordinary Ball Valve
Characteristic of an ideal Control Valve
Ord
inar
y Ba
ll Va
lve
Amount of opening
Amount of opening
Flow
rate
Flow
rate
Typ
ical h
eat e
xchanger characteristic
Equal-perce
ntage ch
aracte
ristic
R
esult
ant th
ermal
capa
city
100%
100%
Characteristic of the Belimo CCV
Amount of opening
Flow
rate
Belimo Cha
racter
ised
Cont
rol V
alve
Characterising disc
5V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
The elements of the Characterised Control Valve
The Belimo Characterised Control Valve/Notes
Optimum choice of Kvs valves of identical size
Ordering
1
2
3
4
5
10
9
87
6
R6..AO
2R2..AC
9
4
12
6
5
11
Simple direct attachment with a central screw
Square spindle head for form-fit attachment of
the Rotary Actuator
Identical mounting flange for all sizes
Spindle with O-rings for long service life
Ball and spindle made of stainless steel
Characterising disc produces equal-
percentage flow characteristic
Internal screw connection (ISO 7/1)
Forged fitting, nickel-plated brass body
Vent part to prevent the accumulation of
condensation
Thermal decoupling of actuator from valve
Flange (ISO 7005-2)
GG25, polyester coated bod
1
2
3
4
5
5
7
8
9
12
10
11
Notes
Better controllability
Lower installation costs
The Belimo range of Characterised Control Valves includes 2-way and 3-way types that are available in a variety of sizes and with a choice of Kvs value. A Characterised Control Valve is normally supplied as a unit complete with a suitable Belimo Rotary Actuator.
••
The control devices described in this publication are intended for use in the closed water circuits of heating, ventilating and air-conditioning system. Use of the control devices in conjunction with other liquid or gaseous fluids is on request.Select the Characterised Control Valve according to the valve sizing diagram: page 6.Please pay attention to the notes at operation, mounting, commissioning, maintenance and project design: page 38, 39.
•
••
Ordering example* (with LRU24)LRU24 Rotary Actuator with R.. valve fitted**
-Order code: R..+LRU24LRU24 Rotary Actuator and R.. valve supplied separately
-Order code: R../LRU24LRU24 Rotary Actuator packed loose
-Order code: LRU24 *An order for a R.. valve usually includes an actuator
a)
b)
c)
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
6
Sizing diagram for Characterised Control Valves
The sizing of Ball Valves
280220
170140
Sizing table for Characterised Control Valves
Sizing table for Open/Close Ball Valves
— p max Maximum permitted pressure difference for long service life across control path A-AB referred to the whole range of opening.
— p max forlow-noise operation
— p maxpressure difference with Ball Valve fully openV100 Nominal flow rate at Pv100
Legend
h
kVS =
Differential pressure at whichthe actuator can still seal thevalve tightly allowing for the
appropriate leakage rate.
Formula for kVS
V100
pV100
100
V100 [m3/h] pV100 [kPa]
Definition of ps(Pg6...9)
0.1 1 3 10 Kvs[m3/h]
DN[mm]
2-way
0.27 0.86 1.49 2.72 8.6 15 R215AC
0.41 1.3 2.3 4.1 13 20 R220AC
0.57 1.8 3.1 5.7 18 25 R225AC
0.98 3.1 5.4 9.8 31 32 R232AC
1.26 4.0 6.9 12.6 40 40 R240AC
2.06 6.5 11.3 20.6 65 50 R250AC
3.79 12 20.8 37.9 120 65 R665AO
5.70 18 31.2 56.9 180 80 R680AO
7.27 23 39.8 72.2 230 100 R6100AO
12.3 39 67.5 123.3 390 125 R6125AO
18.0 57 98.7 180.2 570 150 R6150AO
Kvs[m3/h] 0.63 1 1.6 2.5 4 4 6.3 6.3 10 10 16 16 25 25 40
DN[mm] 15 15 15 15 15 20 20 25 25 32 32 40 40 50 50
2-wayA209AC A210AC A211AC A212AC A213AC A217AC A218AC A222AC A223AC A229AC A231AC A238AC A239AC A248AC A249AC
3-wayR309 R310 R311 R312 R313 R317 R318 R322 R323 R329 R331 R338 - R348 -
Kvs[m3/h] 63 100 140 230 320
DN[mm] 65 80 100 125 150
R664AO R679AO R6099AO R6124AO R6149AO
FlowV100 [m
3/h]
Differential pressurePv100 [kPa]
7V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Flow medium Cold and hot water, water with max. 50% volume of glycol
Temperature of medium -5...100°C
Rated pressure 2500kPa
Flow characteristic Equal percentage
05>vS *51NDytilibaegnaR
DN15...50** Sv>100
)VI ssalC ISNA( svK %10.0...0etar egakaeL
(No leakage when ex-factory)
Pipe connector Internal thread to ISO7/1
Close-off pressure ps 1400kPa
Differential pressure pmax 350kPa (200kPa for low-noise operation)
Angle of rotation 90°
Installation position Upright to horizontal (in relation to the stem)
eerf-ecnanetniaMecnanetniaM
Materialsydob ssarb detalp-lekcin ,degroFydoB
leets sselniatSllaB
EFTPRtaeS
leets sselniatSmetS
MDPEgnir-O
Characterising disc PPA*= Kvs up to 2.5**= DN15 Kvs 4
R2..AC Characterised Control Valves 2-way
Technical data
Product features
2-way low torque Characterised Control Valves DN15...50
Equal-percentage characteristics for modulating control of cold and hot water
Applications Water-side control of air handling unit in air conditioning systemsWater-side control in heating systems
•
•
Mode of operation
Equal-percentage characteristic
Manual operation
The Characterised Control Valve is operated by a Rotary Actuator. The actuator is controlled by a standard modulating or 3-point control system and drives the ball of the valve - the throt-tling device - to the opening position dictated by the control signal.
Equal-percentage characteristic of the flow rate ensured by the integral characterising disc.
Please refer to page 13...37.
R2..AC Characterised Control Valves 2-way
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
8
Flow medium Cold and hot water, water with max. 50% volume of glycol
Temperature of medium -5...100°C
Rated pressure 1600kPa
Flow characteristic Equal percentage
05>vS 08...56NDytilibaegnaR
DN100...150 Sv>100
)VI ssalC ISNA( svK %10.0...0etar egakaeL
(No leakage when ex-factory)
Pipe connector Flanged ISO 7005-2, PN16
Differential pressure p 350kPa(200kPa for low-noise operation)Close-off pressure pmax DN65...125 700kPa
DN150 300kPa
Angle of rotation 90°
Installation position Upright to horizontal (in relation to the stem)
eerf-ecnanetniaMecnanetniaM
Materialsdetaoc retseyloP ,52GGydoB
leets sselniatSllaB
EFTPRtaeS
leets sselniatSmetS
MDPEgnir-O
Characterising disc Stainless steel
Technical data
Product features
2-way Characterised Control Valves DN65...150
Equal-percentage characteristics for modulating control of cold and hot water
Applications Water-side control of air handling unit in air conditioning systemsWater-side control in heating systems
•
•
Mode of operation
Equal-percentage characteristic
Manual operation
Simplified installation procedureLight weight comparing with same DN size valvesAnti-corrosion treatment inside of the valveSolid linkage in insulation design
The Characterised Control Valve is operated by a Rotary Actuator. The actuator is controlled by a standard modulating or 3-point control system and drives the ball of the valve - the throt-tling device - to the opening position dictated by the control signal.
Equal-percentage characteristic of the flow rate ensured by the integral characterising disc.
Please refer to page 13...37.
••••
R6..AO Characterised Control Valves 2-way
9V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Flow medium Cold and hot water, water with max. 50% volume of glycol
Temperature of medium -5...100°C
Rated pressure DN15... 32 4140kPa
DN32... 50 2760kPa
Flow characteristic Equal percentage
05>vS *51NDytilibaegnaR
DN15...50** Sv>100
)3 traP 0323 NID( thgit-elbbub riA BA-A htap lortnoCetar egakaeL
By path B-AB Approximately 1...2% of Kvs value
Pipe connector Internal thread to ISO7/1
Close-off pressure ps 1400kPa
Differential pressure pmax 350kPa (200kPa for low-noise operation)
Angle of rotation 90°
Installation position Upright to horizontal (in relation to the stem)
eerf-ecnanetniaMecnanetniaM
Materialsydob ssarb detalp-lekcin ,degroFydoB
leets sselniatSllaB
EFTPtaeS
leets sselniatSmetS
MDPEgnir-O
Characterising disc TEFZE*= Kvs up to 2.5**= DN15 Kvs 4
Technical data
Product features
3-way mixing Characterised Control Valves DN15...50
Equal-percentage characteristics for modulating control of cold and hot water
Applications Water-side control of air handling unit in air conditioning systemsWater-side control in heating systems
•
•
Mode of operation
Equal-percentage characteristic
Manual operation
The Characterised Control Valve is operated by a Rotary Actuator. The actuator is controlled by a standard modulating or 3-point control system and drives the ball of the valve - the throt-tling device - to the opening position dictated by the control signal.
Equal-percentage characteristic of the flow rate ensured by the integral characterising disc.
Please refer to page 13...37.
R3.. Characterised Control Valves 3-way
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
10
Flow mediumTemperature of mediumRated pressureLeakage rate
Pipe connectorDifferential pressure pmaxClose-off pressure psAngle of rotationInstallation positionMaintenanceMaterialsBodyBallSeatStemO-ring
R2..AC/R6..AO Open/Close Ball Valves 2-way
R2..AC Technical data (for DN15...50)
Product features
2-way Open/Close Ball Valves DN15...150
Shut-off function and 2-point controls in cold and hot water circuits
Applications
For shutting off cold and hot water circuits in heating and ventilation systems on the water side or for 2-point control of these circuits.
R6..AOTechnical data (for DN65...150)
Cold and hot water, water with max. 50% volume of glycol-5...100°C2500kPa0...0.01% Kvs (ANSI Class IV)(No leakage when ex-factory)Internal thread to ISO 7/11000kPa (200kPa for low-noise operation)1400kPa90°Upright to horizontal (in relation to the stem)Maintenance-free
Forged, nickel-plated brass bodyStainless steelRPTFEStainless steelEPDM
Flow mediumTemperature of mediumRated pressureLeakage rate
Pipe connectorDifferential pressure pmaxClose-off pressure ps
Angle of rotationInstallation positionMaintenanceMaterialsBodyBallSeatStemO-ring
Cold and hot water, water with max. 50% volume of glycol-5...100°C1600kPa0...0.01% Kvs (ANSI Class IV)(No leakage when ex-factory)Flanged ISO 7005-2, PN161000kPa (200kPa for low-noise operation)700kPa (DN65...125)300kPa (DN150)90°Upright to horizontal (in relation to the stem)Maintenance-free
GG25, Polyester coatedStainless steelRPTFEStainless steelEPDM
Mode of operation
Manual operation
The Open/Close Ball Valve is operated by a Rotary Actuator. The Rotary Actuator is controlled by an Open/Close signal.
Please refer to page 13...37.
11V5.
12.2
010•
Sub
ject
to m
odifi
catio
nR3.. Open/Close Ball Valves 3-way
Flow medium Cold and hot water, water with max. 50% volume of glycol
Temperature of medium -5...100°C
Rated pressure DN15... 32 4140kPa
DN32... 50 2760kPa
Flow rate Bypath B-AB Approximately 50% of Kvs
Leakage rate Control path A-AB Air bubble-tight (DIN 3230 Part 3)
By path B-AB 1% of Kvs
Pipe connector Internal thread to ISO7/1
Differential pressure pmax 1000kPa (200kPa for low-noise operation)
Close-off pressure ps 1400kPa
Angle of rotation 90°
Installation position Upright to horizontal (in relation to the stem)
Maintenance Maintenance-free
MaterialsBody Forged, nickel-plated brass body
Ball Stainless steel
Seat PTFE
Stem Stainless steel
O-ring EPDM
Technical data
Product features
3-way Open/Close mixing Ball Valves DN15...50
Change-over function and 2-point controls in cold and hot water circuits
Applications For changing over cold and hot water circuits in heating and ventilation systems on the water side or for 2-point control of these circuits.
Mode of operation
Manual operation
The Open/Close Ball Valve is operated by a Rotary Actuator. The Rotary Actuator is controlled by an Open/Close signal.
Please refer to page 13...37.
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
12
R2..AC 2-way Ball Valves
DN Thread Dimensions[mm] Weight
[Kg]mm lmp Rp L H
R209AC/R210AC/R211ACR212AC/R213AC/R215AC 15 70 43.5 0.38
R217AC/R218AC/R220AC 20 77 46 0.48
R222AC/R223AC/R225AC 25 1 85 47.6 0.63
R229AC/R231AC/R232AC 32 94 51 0.84
R238AC/R239AC/R240AC 40 104 53.5 1.1
R248AC/R249AC/R250AC 50 2 116.5 58.1 1.6
Dimensions
Valve dimensions
H
N-M
D
PN16DNGG25
A
L
H1
H
N-M
H1
D
1
R3.. 3-way Ball Valves
Valve typeDN Dimensions
[mm] Thread Weight[Kg]
mm lmp L H M Rp
R309/R310/R311R312/R313/R315 15 67.4 45.15 36.3 0.45
R317/R318/R320 20 77.9 47.4 41.6 0.6
R322/R323/R325 25 87.6 47.4 44.9 1 0.9
R329/R330 32 105.4 47.4 55.4 1.2
R331/R332 32 105.4 51.9 55.4 1.5
R338/R340 40 110.5 51.9 56 1.5
R348/R350 50 124.6 57.65 67.8 2 2.4
1
R6..AO 2-way Ball Valves
Valve typeDN Dimensions
[mm] Weight[Kg]
mm lmp A D H L N-M
R664AO/R665AO 65 105 145 86 93 4- 18 4.3
R679AO/R680AO 80 125 160 94.5 108 8- 18 6.5
R6099AO/R6100AO 100 148 180 104 120 8- 18 10.5
R6124AO/R6125AO 125 174 210 118.5 142 8- 18 13.0
R6149AO/R6150AO 150 204 240 136.5 170 8- 22 19.5
Disc for Characterised Control Valve
Disc for Characterised Control Valve
Disc for Characterised Control Valve
13V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
General Rotary Actuators for: Torque:Modulating control:Open/Close and floating control:
•
•••
2-way Ball Valves DN15...253-way Ball Valves DN15...202NmTR24-SR (AC/DC 24V)TR24 (AC/DC 24V)TR230-3 (AC 230V)
TR.. series Rotary Actuators
Basic technical data Connection cable 1m, 0.75mm2
Torque 2Nm
Angle of rotation 95°
Sound power level 35dB(A)
Degree of protection IP40
EMC CE according to 89/336/EEC
Ambient temperature -5...+50°C
Non-operating temperature -5...+80°C
Temperature of medium -5...+100°C
Humidity test To EN 60730-1
Maintenance Maintenance-free
TR24-SR Power supply range AC 19.2...28.8V; DC 21.6...28.8V
Power consumption 1.0W
Transformer sizing 1.0VA
Control signal DC 2(0)...10V @ 100kΩ input impedance
Protection class III (safety low voltage)
Running time 90s
Weight 0.3kg
TR24 Power supply range AC 19.2...22.8V; DC 21.6...22.8V
Power consumption 0.5W
Transformer sizing 0.5VA
Protection class III (safety low voltage)
Running time 100s
Weight 0.3kg
TR230-3 Power supply range AC 198...264V
Power consumption 1.0W
Transformer sizing 1.0VA
Low voltage directive CE according to 73/23/EEC
Protection class II (Totally insulated)
Running time 105s
Weight 0.3kg
Technical data
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
14
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
Product features
TR..series Rotary Actuators
Simple direct mounting
Manual operation
Simple direct mounting on the Ball Valve using only one screw.
Manual operation by lever (the gearing latch remains disengaged as long as the self-resetting lever is pressed).
Wiring digrams
T ~
- +
~
Y
T
- +
TR24-SR
!
- +
T ~
0
- +
T ~
TR24-SR
TR24
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
!
TR24 TR24
TR230-3
0
TR230-3
Notes:Caution: Power supply voltage!• !
Modulating control
AC 24VDC 24V
AC 24VDC 24V
AC 24VDC 24V
AC 230V
Open/Close control
Open/Close and Floating control
Floating control
Y DC 2(0)...10VControl signal
N L1
1 2 3
1 2 3
1 2 3 1 2 3
15V5.
12.2
010•
Sub
ject
to m
odifi
catio
nLRU.. series Rotary Actuators
Basic technical data Connection cable 1m, 0.75mm2
Torque 5Nm
Angle of rotation 90°
Running time 90s
Sound power level Max. 35dB(A)
Position indication Mechanical
Direction of rotation Selectable by switch (covered): Factory preset
change to to reverse the direction of rotation
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Ambient temperature -5...+50°C
Non-operating temperature -5...+80°C
Temperature of medium -5...+100°C
Humidity test To EN 60730-1
Maintenance Maintenance-free
LRU24-SR Nominal voltage range AC/DC 19.2...28.8V
Power consumption 1.5W @ running/0.4W @ holding
Transformer sizing 3VA
Control signal DC 2(0)...10V(input impedance) 100kΩ
Feedback signal DC 2...10V, max. 1mA
Protection class III (safety low voltage)
Weight 0.55kg
LRU24(-S) Nominal voltage range AC/DC 19.2...22.8V
Power consumption 1.5W @ running/0.2W @ holding
Transformer sizing 2VA
Protection class III (safety low voltage)
Auxiliary switch(LRU24-S) 1XSPDT, 1mA...3(0.5)A, AC 250V
0...100%adjustable
Weight 0.55kg
LRU230(-S) Nominal voltage range AC 85...265V
Power consumption 2.0W @ running/0.5W @ holding
Transformer sizing 4VA
Low voltage directive CE according to 73/23/EEC
Protection class II (Totally insulated)
Auxiliary switch(LRU230-S) 1XSPDT, 1mA...3(0.5)A, AC 250V
0...100%adjustable
Weight 0.60kg
General Rotary Actuators for: Torque:Modulating control:Open/Close and floating control:
•
•••
2-way Ball Valves DN32...403-way Ball Valves DN25...325NmLRU24-SR (AC/DC 24V)LRU24(-S) (AC/DC 24V)LRU230(-S) (AC 100...240V)
Technical data
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
16
LRU.. series Rotary Actuators
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
Product features
Simple direct mounting
Manual operation
High function reliability
Simple direct mounting on the Ball Valve using only one screw.
Manual operation by pushbutton when necessary.
The actuator is overload-proof, needs no limit switches and stops automatically at the end stops.
Wiring digrams
LRU24-SR
!
LRU24(-S)
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
!
LRU230(-S)
Notes:Caution: Power supply voltage!Other actuators can be connected in parallel.
Please note the performance data.
••
!
Modulating controlAC 24VDC 24V
AC 24VDC 24V
AC 24VDC 24V
AC 100V...240V
Open/Close control Floating control
Y DC 2(0)...10V
N L1
S1 S2 S3
Y U-
T ~
+
- +
T ~
LRU24-SR
U DC 2...10V
1 2 3 5
- +
T ~
0
- +
T ~
1
0
1
0
1
0
1 2 3
LRU24 LRU24
LRU24-SLRU24-S
Auxiliary switch
1 2 3
0
1
0
1
0
1
0
Auxiliary switch
S1 S2 S3 S1 S2 S3
S1 S2 S31 2 3 1 2 3
AC 100V...240VN L1
LRU230-SLRU230-S
LRU230 LRU230
S1 S2 S3 S1 S2 S3
0...100% 0...100%
0...100%0...100%
S1 S3S2 S1 S2 S3
Open/Close control Floating control
17V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
General Rotary Actuators for: Torque:Modulating control:Open/Close and floating control:
•
•••
2-way Ball Valves DN503-way Ball Valves DN32...5010NmNRU24-SR (AC/DC 24V)NRU24(-S) (AC/DC 24V)NRU230(-S) (AC 100...240V)
NRU.. series Rotary Actuators
Basic technical data Connection cable 1m, 0.75mm2
Torque 10Nm
Angle of rotation 90°
Running time 90s
Sound power level Max. 45dB(A)
Position indication Mechanical
Direction of rotation Selectable by switch (covered): Factory preset
change to to reverse the direction of rotation
Degree of protection IP54 in any direction
EMC CE according to 89/336/EEC
Ambient temperature -5...+50°C
Non-operating temperature -5...+80°C
Temperature of medium -5...+100°C
Humidity test To EN 60730-1
Maintenance Maintenance-free
NRU24-SR Nominal voltage range AC/DC 19.2...28.8V
Power consumption 2.5W @ running/0.4W @ holding
Transformer sizing 5VA
Control signal DC 2(0)...10V(input impedance) 100kΩ
Feedback signal DC 2...10V, max. 1mA
Protection class III (safety low voltage)
Weight 0.85kg
NRU24(-S) Nominal voltage range AC/DC 19.2...22.8V
Power consumption 2.0W @ running/0.2W @ holding
Transformer sizing 4VA
Protection class III (safety low voltage)
Auxiliary switch(NRU24-S) 1XSPDT, 1mA...3(0.5)A, AC 250V
0...100%adjustable
Weight 0.85kg
LRU230(-S) Nominal voltage range AC 85...265V
Power consumption 3.0W @ running/0.6W @ holding
Transformer sizing 7VA
Low voltage directive CE according to 73/23/EEC
Protection class II (Totally insulated)
Auxiliary switch(NRU230-S) 1XSPDT, 1mA...3(0.5)A, AC 250V
0...100%adjustable
Weight 0.90kg
Technical data
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
18
Product Overview/Contents
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
Product features
Simple direct mounting
Manual operation
High function reliability
Simple direct mounting on the Ball Valve using only one screw.
Manual operation by pushbutton when necessary.
The actuator is overload-proof, needs no limit switches and stops automatically at the end stops.
Wiring digrams
NRU24-SR
!
NRU24(-S)
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
!
NRU230(-S)
Notes:Caution: Power supply voltage!Other actuators can be connected in parallel.
Please note the performance data.
••
!
Modulating controlAC 24VDC 24V
AC 24VDC 24V
AC 24VDC 24V
AC 100V...240V
Open/Close control Floating control
Y DC 2(0)...10V
N L1
S1 S2 S3
Y U-
T ~
+
- +
T ~
NRU24-SR
U DC 2...10V
1 2 3 5
- +
T ~
0
- +
T ~
1
0
1
0
1
0
1 2 3
NRU24 NRU24
NRU24-SNRU24-S
Auxiliary switch
1 2 3
0
1
0
1
0
1
0
Auxiliary switch
S1 S2 S3 S1 S2 S3
S1 S2 S31 2 3 1 2 3
AC 100V...240VN L1
NRU230-SNRU230-S
NRU230 NRU230
S1 S2 S3 S1 S2 S3
0...100% 0...100%
0...100%0...100%
S1 S3S2 S1 S2 S3
Open/Close control Floating control
19V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Nominal voltageNominal voltage rangePower consumption -running
-holdingFor transformer/wiring sizingConnecting cable -Motor -Auxiliary switch(-S)Protection classWeightManual override
Nominal voltageNominal voltage rangePower consumption -running
-holdingFor wiring sizingConnecting cable -Motor -Auxiliary switch(-S)Protection classWeightManual override
Nominal voltageNominal voltage rangePower consumption -running
-holdingFor transformer/wiring sizingConnecting cableControl signal YFeedback signal USynchronisationProtection classWeightManual override
TorqueAuxiliary switch (SRVU..(-S)-5)
Angle of rotationDirection of rotationSound power levelPosition indicatorRunning timeMode of operationAmbient temp.Non-operation temp.Humidity testDegree of protectionLow Voltage Directive
Maintenance
AC 24V 50/60Hz, DC 24VAC/DC 19.2...28.8V2.5W0.2W5.5VACable 1m, 3x0.75mm2
Cable 1m, 3x0.75mm2
III (safety low voltage)SRVU24 approximately 1000g,SRVU24-S approximately1050gGearing disengaged by pressing the push button,manual operate while the button is held depressedAC 100...240V 50/60HzAC 85...265V3.0W0.6W7VACable 1m, 3x0.75mm2
Cable 1m, 3x0.75mm2
II (Totally insulated)1050g~1100gGearing disengaged by pressing the push button,manual operate while the button is held depressedAC 24V 50/60Hz, DC 24VAC/DC 19.2...28.8V2.5W0.4W5VACable 1m, 4x0.75mm2
DC 2(0)...10V @ input resistance 100kΩDC 2...10V @ max.1mA
5%III (safety low voltage)1050gGearing disengaged by pressing the push button,manual operate while the button is held depressedMin. 20Nm @ nominal voltage1xSPDT1mA...3(0.5)A, AC 250V0...100% adjustableMax.90°Pre-setting to close (switch hidden under a label)Max. 45dB(A)Mechanical, remote visible90sType 1 (EN 60730-1)-30...+50°C-40...+80°C95% RH, non condensing (EN60730-1)IP54 in any directionCE according to 89/336/EECCE according to 73/23/EECMaintenance-free
SRVU..-5 General Rotary Actuators
General Rotary Actuators for: Torque:Open/Close or 3-point control: Modulating control:
••••
DN65...80 CCV20NmSRVU24(-S)-5, SRVU230(-S)-5SRVU24-SR-5
Technical data
SRVU24(-S)-5
SRVU230(-S)-5
SRVU24-SR-5
Common technical data
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
20
SRVU230-S-5 SRVU230-S-5
SRVU24-S-5
SRVU..-5 Rotary Actuators
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
Product features
Mode of operation
Adjustable angle of rotation
High function reliability
Flexible signalisation
the position defined by this signal. The feedback signal U allows the valve position (0...100%) to be electrically indicated and serves as a follow-up control signal for other actuators.
Adjustable angle of rotation with mechanical end stops.
The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.Flexible signalisation of the SRVU..-S-5 with adjustable auxiliary switch (0...100%).
Wiring digrams
SRVU24(-S)-5
!
Open/Close control
AC 100V...240V
Auxiliary switch(-s)
N L1
~
- +
T
0
3-point controlAC 24VDC 24V
1 2 3
SRVU24-5
S1 S2 S3
0...100%
~
- +
T
1
0
1
0
SRVU24-S-5
SRVU24-5
AC 24VDC 24V
1
0
1(Y2)
0(Y1)
Direction of rotation(factory setting, switch hidden)
0
1
0
1
0
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
SRVU230(-S)-5
!
Auxiliary switch(-s)
1
0
1(Y2)
0(Y1)
Direction of rotation(factory setting, switch hidden)
SRVU230-5SRVU230-5
1 2 3 S1 S2 S3
1 2 3 S1 S2 S3 1 2 3 S1 S2 S3
AC 100V...240V
S1 S3S2 S1 S2 S3
0...100%
0...100%0...100%
S1 S3S2 S1 S2 S3
N L1Open/Close control 3-point control
Y
T ~
T ~+
U
-
Modulating control
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
SRVU24-SR-5
!
1(Y2)
0(Y1)
Direction of rotation(factory setting, switch hidden)
AC 24VDC 24V
SRVU24-SR-5
Y DC 2(0)...10V
U DC 2...10V Feedback signal U for positionindicating or as master-slavecontrol signal.
1 2 3 5
21V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
General Rotary Actuators for: Torque:Open/Close control: Modulating control:
••••
DN100...150 CCV40NmGRVU24-7, GRVU230-7GRU24-SR-7
GRVU..-7 General Rotary Actuators
Nominal voltageNominal voltage rangePower consumption -running
-holdingFor transformer/wiring sizingConnecting cableProtection classWeightManual override
Nominal voltageNominal voltage rangePower consumption -running
-holdingFor wiring sizingConnecting cableProtection classWeightManual override
Nominal voltageNominal voltage rangePower consumption -running
-holdingFor transformer/wiring sizingConnecting cableControl signal YFeedback signal USynchronisationProtection classWeightManual override
TorqueAngle of rotationDirection of rotationSound power levelPosition indicatorRunning timeMode of operationAmbient temp.Non-operation temp.Humidity testDegree of protectionLow Voltage Directive
Maintenance
AC 24V 50/60Hz, DC 24VAC/DC 19.2...28.8V4W2W6VACable 1m, 3x0.75mm2
III (safety low voltage)approximately 1550gGearing disengaged by pressing the push button,manual operate while the button is held depressedAC 100...240V 50/60HzAC 85...265V4W2W7VACable 1m, 3x0.75mm2
II (Totally insulated)approximately 1550gGearing disengaged by pressing the push button,manual operate while the button is held depressedAC 24V 50/60Hz, DC 24VAC/DC 19.2...28.8V4.5W2W6.5VACable 1m, 4x0.75mm2
DC 2(0)...10V @ input resistance 100kΩDC 2...10V @ max.1mA
5%III (safety low voltage)1550gGearing disengaged by pressing the push button,manual operate while the button is held depressedMin. 40Nm @ nominal voltageMax.95°Pre-setting to close (switch hidden under a label)Max. 45dB(A)Mechanical, remote visible150sType 1 (EN 60730-1)-30...+50°C-40...+80°C95% RH, non condensing (EN60730-1)IP54 in any directionCE according to 89/336/EECCE according to 73/23/EECMaintenance-free
Technical data
GRVU24-7
GRVU230-7
SRVU24-SR-5
Common technical data
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
22
Open/Close control
GRVU..-7 General Rotary Actuators
Product features
Accessories
AC 24VDC 24V
Open/Close control
N L1
1 2 3
1 2 3
Wiring digrams
Manual operation
Adjustable angle of rotation
High function reliability
GRVU24-SR-7 is controlled by means of a standard control signal DC 2(0)...10V and travels to the position defined by this signal. The feedback signal U allows the valve position (0...100%) to be electrically indicated and serves as a follow-up control signal for other actuators.
Adjustable angle of rotation with mechanical end stops.
The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.
Description
Electrical accessories Positioner SG..24
(available on request) Digital position indication ZAD24
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
GRVU24-SR-7
!
1(Y2)
0(Y1)
Direction of rotation(factory setting, switch hidden)
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
GRVU24-7
!
1(Y2)
0(Y1)
Direction of rotation(factory setting, switch hidden)
Notes:Connection via safety isolating transformer.Other actuators can be connected in parallel.
Please note the performance data.
••
GRVU230-7
!
1(Y2)
0(Y1)
Direction of rotation(factory setting, switch hidden)
~
- +
T
Y
T ~
U
~
- +
T
GRVU24-7
1 2 3
GRVU230-7
AC 24VDC 24V
GRVU24-SR-7
5
Y DC 2(0)...10V
U DC 2...10V Feedback signal U for positionindicating or as master-slavecontrol signal.
Modulating control
23V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Dimensions[mm]: TR..
Dimensions of General Actuators
Dimensions[mm]: LRU..
Dimensions[mm]: NRU..
Dimensions[mm]: SRVU..
78
69
55
67
2284
7156
13.2 4
50
19.5
8.2 1
167.2
94 8.2
64.4
1166
46.9
6
24.5
63
50
70.9
74
5.2
172.2
11.5
4
58.5
24.7
6
48.4
12.5
99
5.2
64.5
8.6
8.2
50.9
65.9
66
41.7
83
19.5
1
33
9393
117
21
150
84
70176
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
24
Dimensions: GRVU..
Dimensions/Auxiliary switch adjustment
Auxiliary switch adjustment: LRU..-S/NRU..-S/SRVU..-S-5
Press the pushbutton and operate manually the universal clamp to favoured switch position.Turn switch pointer to the middle line.When actuator moves clockwise (counter-clockwise) to switch position, switch indicator passes counter-clockwise (clockwise) the middle line.The contact between S1 and S3 is cut off (established) and the contact between S1 and S2 is established (cut off).
Note: The switching point should be about 5° from the mechanical end stops (1 short step on the scale).
1.
2.3.
2
1S1
S2 S3
S1
S2 S3
GRVU24-7GRVU230-7
GRVU24-SR-7
69
6
15144
59 183
R10
97
6
50
45°
47.5°11
6
44 151
183
47.5°
124
97
50
45°
124
25V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Installation instructions: TR..
Installation instructions
Installation procedures: LRU../NRU.. (DN15...50)
12
1 2
3
5
4
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
26
Installation instructions
Installation instructions: SRVU..+DN65...80 CCV
1 2
0%
0%
1 2
4
3
27V5.
12.2
010•
Sub
ject
to m
odifi
catio
nInstallation instructions
1 2
0%
17
0%
Installation procedure: GRVU..+DN100..150 CCV
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
28
TRF..series Mechanical Fail-Safe Rotary Actuators
Connection cableTorqueAngle of rotationPosition indicationDegree of protectionEMCAmbient temperatureNon-operation temperatureTemperature of mediumHumidity testMaintenancePower supply rangePower consumption Sound power levelFor transformer sizingControl signal Feedback signal Direction of rotation
Protection classRunning timeWeightPower supply rangePower consumption Sound power levelFor transformer sizingDirection of rotation
Protection classRunning timeWeightPower supply rangePower consumption Sound power levelFor transformer sizingDirection of rotationAuxiliary switch (TRF24-S)Protection classRunning timeWeightPower supply rangePower consumption Sound power levelFor transformer sizingDirection of rotationLow voltage directiveAuxiliary switch (TRF230-S)Protection classRunning timeWeight
1m, 3x0.75mm2
Motor: 2Nm; spring return: 2Nm95°MechancialIP42CE according to 89/336/EEC-5...+50°C-5...+80°C-5...+100°CTo EN 60730-1Maintenance-freeAC 19.2...28.8V/DC 21.6...28.8V2.5W @ running/1W @ holdingMotor: Max. 45dB(A), spring return: 62dB(A)4VADC 2(0)...10V @ 100kΩ input resistanceDC 2...10VMotor: reversible with L/R switchSpring return: reversible by mounting L/RIII (safety low voltage)Motor: 90s; spring return: < 25s (-5...+50°C) / max. 60s (-30°C)0.6kgAC 19.2...28.8V/DC 21.6...28.8V2.5W @ running/1W @ holdingMotor: Max. 45dB(A), spring return: 62dB(A)4VAMotor: reversible with L/R switchSpring return: reversible by mounting L/RIII (safety low voltage)Motor: 90s; spring return: < 25s (-5...+50°C) / max. 60s (-30°C)0.6kgAC 19.2...28.8V/DC 21.6...28.8V2.5W @ running/1.5W @ holdingMax. 45dB(A)5VASpring return: reversible by mounting L/R1XSPDT, 1mA...3(0.5)A, AC 250V , 0...100% adjustableIII (safety low voltage)Motor: 40...75s; spring return: <75s0.6kgAC 85...265V2.5W @ running/1.5W @ holdingMax. 45dB(A)5VASpring return reversible by mounting L/RCE according to 73/23/EEC1XSPDT, 1mA...3(0.5)A, AC 250V , 0...100% adjustableII (Totally insulated)Motor: 40...75s; spring return: <75s0.6kg
Mechanical Fail-Safe Rotary Actuators for:
Torque:Modulating control:Floating(3-point) control:Open/Close control:
•
••••
2-way Ball Valves DN15...25 3-way Ball Valves DN15...202NmTRF24-SR (AC/DC 24V)TRF24-2 (AC/DC 24V)TRF24(-S) (AC/DC 24V)TRF230(-S) (AC 100...240V)
Technical data
Basic technical data
TRF24-SR
TRF24-2
TRF24(-S)
TRF230(-S)
29V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Other actuators can be connected in parallel.Please note the performance data.
Connection via safety isolating transformer.
Other actuators can be connected in parallel.Please note the performance data.
Connection via safety isolating transformer.
Connection via safety isolating transformer.
TRF24TRF230
TRF24-STRF230-S
TRF24-2
TRF24-SR
AC 100V...240V
AC 24VDC 24V
AC 24V
AC 24VDC 24V
TRF24(-S)TRF230(-S)
Open/Close control
TRF24-2Floating control
TRF..series Mechanical Fail-Safe Rotary Actuators
Product features
Wiring diagrams
Simple direct mounting
Manual operation
High function reliability
Simple direct mounting on the Ball Valve using only one screw.
No manual operation.
The actuator is overload-proof, needs no limit switches and stops automatically at the end stops.
– +
T ~
!
Y1 Y2
T ~
!
M> x
< x
– +~
T
M
!
!
TRF24-SRModulating control
Other actuators can be connected in parallel.Please note the performance data.
Caution: Power supply voltage!
1 2 3
S1 S2 S3
x=0...100%
N L1
1 2 3 5
4
a b
DC 2(0)...10VDC 2...10V
YU
1 2
1 2
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
30
Connection cableTorqueAngle of rotationSound power levelPosition indicationDegree of protectionEMCAmbient temperatureNon-operation temperatureTemperature of mediumHumidity testMaintenanceManual operationLRF..LingkagePower supply rangePower consumption For transformer sizingControl signal Feedback signal Direction of rotationProtection classRunning timeWeightPower supply rangePower consumption For transformer sizingDirection of rotationProtection classRunning timeWeightPower supply rangePower consumption For transformer sizingDirection of rotationAuxiliary switch (LRF24-S)Protection classRunning timeWeightPower supply rangePower consumption For transformer sizingDirection of rotationAuxiliary switch (LRF230-S)Low voltage directiveProtection classRunning timeWeight
1m, 0.75mm2
Motor: 4Nm; spring return: 4Nm95°Motor: Max. 50dB(A), spring return: 62dB(A)MechancialIP54CE according to 89/336/EEC-5...+50°C-5...+80°C-5...+100°CTo EN 60730-1Maintenance-freeBy manual override key(Only when power supply is disconnected for LRF24-SR)Lingkage included in LRF..AC 19.2...28.8V/ DC 21.6...28.8V2.5W @ running/1W @ holding5VADC 2(0)...10V @ 100kΩ input resistanceDC 2...10VMotor: reversible by L/R switch; spring return: reversible by mounting L/RIII (safety low voltage)Motor:<150s; spring return: ~20s (-5...+50°C) / max. 60s (-30°C)1.4kgAC 19.2...28.8V/DC 21.6...28.8V2.5W @ running/1W @ holding5VAMotor: reversible by L/R switch; spring return: reversible by mounting L/RIII (safety low voltage)Motor:40...75s; spring return: ~20s (-5...+50°C) / max. 60s (-30°C)1.4kgAC 19.2...28.8V/DC 21.6...28.8V5W @ running/2.5W @ holding7VASpring return: reversible by mounting L/R2XSPDT, 1mA...3(0.5)A, AC 250V , fixed at 10° , 85°III (safety low voltage)Motor:40...75s; spring return: ~20s (-5...+50°C) / max. 60s (-30°C)1.4...1.54kgAC 198...264V5W @ running/3W @ holding7VASpring return: reversible by mounting L/R2XSPDT, 1mA...3(0.5)A, AC 250V , fixed at 10° , 85°CE according to 73/23/EECII (Totally insulated)Motor:40...75s; spring return: ~20s (-5...+50°C) / max. 60s (-30°C)1.55...1.68kg
L(R)F.. series Mechanical Fail-Safe Rotary Actuators
Mechanical Fail-Safe Rotary Actuators for:
Torque:Modulating control:Floating(3-point) control:Open/Close control:
•
••••
2-way Ball Valves DN32...40 3-way Ball Valves DN25...324NmLF24-SR,LRF24-SR (AC/DC 24V)LF24-3 (AC/DC 24V)LRF24(-S) (AC/DC 24V)LRF230(-S) (AC 230V)
Technical data
Basic technical data
LF24-SRLRF24-SR
LRF24-3
LRF24(-S)
LRF230(-S)
31V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
(Y2)(Y1)ba
Mounting side
Position feedback signal
Control signal
<85°<10°
<85°<10°
S4 S5 S6
Other actuators can be connected in parallel.Please note the performance data.
Other actuators can be connected in parallel.Please note the performance data.
Other actuators can be connected in parallel.Please note the performance data.
Other actuators can be connected in parallel.Please note the performance data.
LRF230-SLRF230
LRF24-SLRF24
LF24-3
AC 230V
AC 24VDC 24V
Connection via safety isolating transformer.
Connection via safety isolating transformer.
AC 24VDC 24V
AC 24VDC 24V
LRF230(-S)Open/Close control
LRF24(-S)Open/Close control
LF24-3Floating control
Connection via safety isolating transformer.!
L(R)F24-SR
L(R)F24-SRModulating control
U DC 2...10V
Y DC 2(0)...10V
AC 24VDC 24V
L(R)F.. series Mechanical Fail-Safe Rotary Actuators
Caution: Power supply voltage!
Product features
Wiring diagrams
Simple direct mounting
Manual operation
High function reliability
Simple direct mounting on the Ball Valve using only one screw.
LRF.. have manual operation with integral position stop.
The actuator is overload-proof, needs no limit switches and stops automatically at the end stops.
1 2
Y
T ~
~
– +
– +
T
MPZU
L0
.2
.4
.6
.8
1
R0
.2
.4
.6
.8
1
T ~
– +
Y1 Y2
T ~
- +
a bL
0.2
.4
.6
.8
1
R0
.2
.4
.6
.8
1!
T ~
+–
M
T ~
+–
M
! !
M
N L1
M
!
Connection via safety isolating transformer.
1 2 3 5
1 2 3 4
1 2
1 2
N L1
1 2
S1 S2 S3
S4 S5 S6S1 S2 S3
CCW CW
Reversible switch
CCW
Mounting side
CW
Reversible switch
Stop
Y=0 Y=0 Y=0 Y=0
Stop Stop Stop
R L R L
R L R L
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
32
Mechanical Fail-Safe Rotary Actuators for:
Torque:Modulating control:Open/Close control:
•
•••
2-way Ball Valves DN50 3-way Ball Valves DN32...5010NmNRFU24-SR (AC/DC 24V)NRFU,NRFU-S2 (AC 24...240V) (DC 24...125V)
NRFU.. series Mechanical Fail-Safe Rotary Actuators
Connection cableTorqueAngle of rotationSound power levelPosition indicationDegree of protectionEMCAmbient temperatureNon-operation temperatureTemperature of mediumHumidity testMaintenanceManual operationLingkagePower supply rangePower consumption For transformer sizingControl signal Feedback signal Protection classRunning timeWeightPower supply rangePower consumption For transformer sizingDirection of rotationProtection classRunning timeWeightPower supply rangePower consumption For transformer sizingDirection of rotationAuxiliary switch
Low voltage directiveProtection classRunning timeWeight
3x1m, 0.75mm2 (NRFU..) 4x1m, 0.75mm2(NRFU24-SR)Motor: 10Nm; spring return: 10Nm90°Motor: Max. 50dB(A), spring return: ~62dB(A)MechancialIP54CE according to 2004/108/EEC-30...+50°C-40...+80°C-5...+100°CTo EN 60730-1Maintenance-freeBy manual override keyLingkage included in NRFU..AC 19.2...28.8V/ DC 21.6...26.4V5.5W @ running/3W @ holding9VADC 2(0)...10V @ 100kΩ input resistanceDC 2...10VIII (safety low voltage)Motor:150s; spring return:<20s (-5...+50°C) / max. 60s (-30°C)Approx. 2kgAC 19.2...264V/DC 20.4...126.5V6W @ running/2.5W @ holding9.5VAMotor: reversible by L/R switch; spring return: reversible by mounting L/RIII (safety low voltage)Motor:<75s; spring return: ~20s (-20...+50°C) / max. 60s (-30°C)Approx. 1.7kgAC 19.2...264V/DC 21.6...143V6W @ running/2.5W @ holding9.5VASpring return: reversible by mounting L/R2XSPDT, 1mA...3(0.5)A, AC 250V One fixed at 10° , one adjustable 10°...95°CE according to 2006/95/ECII (Totally insulated) Motor:<75s; spring return: ~20s (-20...+50°C) / max. 60s (-30°C)Approx. 1.7kg
Technical data
Basic technical data
NRFU24-SR
NRFU
NRFU-S2
33V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
NRFU24-SRModulating control
NRFU-S2Open/Close control
NRFUOpen/Close control
NRFU.. series Mechanical Fail-Safe Rotary Actuators
Connection via safety isolating transformer.
AC 24VDC 24V
Product features
Wiring diagrams
Simple direct mounting
Manual operation
High function reliability
Simple direct mounting on the Ball Valve using only one screw.
NRFU..have manual operation with integral position stop. Only when power supply is discon-nected for NRFU24-SR.The actuator is overload-proof, needs no limit switches and stops automatically at the end stops.
Other actuators can be connected in parallel.Please note the performance data.
S1 S2 S3
1 2 3 5
DC 0...10VDC 2...10V
YU
!
~
– +
T
M
M
!~T
– +
Connection via safety isolating transformer.
NRFU
1 2
1 2
NRFU24-SR
S4 S5 S6
N L
Control signalPosition feedback signal
10% 10%...90% adjustable
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
34
Nominal voltageNominal voltage rangePower consumptionFor transformer/wiring sizing
ConnectionNominal voltageNominal voltage rangePower consumption For transformer/wiring sizing
Connection -Motor -Auxiliary switches
Nominal voltageNominal voltage rangePower consumption For transformer/wiring sizingConnectionControl signalPosition feedbackPosition AccuracyTorque -Motor -Spring returnAuxiliary switch (SRFU-S2-5)
Angle of rotation
Sound power levelPosition indicatorManual overrideRunning time -SRFU-S25,SRFU-5 -SRFU24-SR-5Ambient temp.Non-operation temp.Humidity testDegree of protectionEMCLow Voltage DirectiveMaintenanceWeight
AC 24...240V, 50/60Hz, DC 24...125VAC 19.2...264V/ DC 21.6...126.5V7.0W @ running / 3.5W @ holding7.0VA @ AC 24V8.5VA @ AC 120V18.0VA @ AC 240VCable 1m, 2x0.75mm2
AC 24...240V, 50/60Hz, DC 24...125VAC 19.2...264V/ DC 21.6...126.5V7W @ running / 3.5W @ holding7.0VA @ AC 24V8.5VA @ AC 120V18.0VA @ AC 240VCable 1m, 2x0.75mm2
Cable 1m, 6x0.75mm2
AC 24V, 50/60Hz, DC 24VAC 19.2...28.8V/ DC 21.6...28.8V5W @ running / 3W @ holding7VACable 1m, 2x0.75mm2
DC 2(0)...10V @ 100kΩ input resistanceDC 2...10V @ max.0.5mA
5%Min. 20Nm @ nominal voltageMin. 20Nm2xSPDT, 1mA...3(0.5)A, AC 250VOne fixed at 10%, one adjustable 10%...90%Max.95°by means of adjustable mechanical end stopsMax. 45dB(A), spring ≈ 62dB(A)MechanicalHex crankMotor ≈75s, spring return Max. 20s @ -20..+50°CMotor ≈150s, spring return Max. 20s @ -20..+50°C-30...+50°C-40...+80°C95% RH, non condensingIP54CE according to 2004/108/ECCE according to 2006/95/ECMaintenance-freeApprox. 2.2kg
SRFU..-5 Mechanical Fail-Safe Rotary Actuators
Mechanical Fail-Safe Rotary Ac-tuators for operation of: Torque:Open/Close control: Modulating control:
•
••••
DN65...80 CCV20NmSRFU-5, SRFU-S2-5 (AC 24...240V) (DC 24V...125V)SRFU24-SR-5 (AC/DC 24V)
Technical data
SRFU-5
SRFU-S2-5
SRVU24-SR-5
Common technical data
35V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
SRFU24-SR-5Modulating control
AC 24VDC 24V
SRFU-S2-5
Notes:Caution: Power supply voltage!Other actuators can be connected in parallel.
Please note the performance data.
••
AC 24...240VDC 24...125V
SRFU-5
Wiring diagrams
Product Overview/Contents
SRFU-5Open/Close control
Product features
Simple direct mounting
Manual operation
Adjustable angle of rotation
High function reliability
Mode of Operation
Simple direct mounting on the butterfly valve.
Manual operation is possible with the manual override key
Adjustable angle of rotation with mechanical end stops.
The actuator is overload-proof, requires no limit switches, and stops automatically when the end stop is reached.The actuator is controlled with a standard of DC 2(0)...10V and moves the butterfly valve to the operating position at the same time as tensioning the return spring. The butterfly valve is turned back to the emergency position by spring force if the supply voltage is interrupted.
S1 S2S3
DC 2(0)...10VDC 2...10V
YU
S4 S5 S6
Control signalPosition feedback signal
B=10...90° adjustable
~
– +
T
M
Notes:Caution: Power supply voltage!Other actuators can be connected in parallel.
Please note the performance data.
••
1 2
l
<A°
>A°
<B°
>B°
+–
T ~
M
SRFU-S2-5Open/Close control
AC 24...240VDC 24...125V
1 2
A=10°
SRFU24-SR-5
~T
– +
1 2 3 5
Notes:Caution: Power supply voltage!Other actuators can be connected in parallel.
Please note the performance data.
••
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
36
Dimensions and auxiliary switch adjustment
Dimensions[mm]
Adjusting A..-S auxiliary switches
151115
61
21.5
81m
in.7
0 80min.40
TRF..
57
15525 m
in.7
087
.5
min.4098
59
27
101
min
.70
103min.40
L(R)F..
22140
NRFU..
Initial situation: Actuator in safety position
3mm (1/8’’) hexagonal key not included with the actuator
1 2 3
37V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
NC NO
Installation instructions of General Actuators
Installation instructions: TRF..
Installation instructions: LF../LRF..
Installation instructions: NRFU../SRFU
AB
A–AB=100%
B–AB=0%
A B
AB
A–AB=0%
B–AB=100%
A B
AB
A–AB =0%
B–AB=1 00%
A B
Made in Switzland
0
.2
.4
.6
.8
R
R M
RMade in Switzland
R M
0 .2 .4.6
.81
AB
A–AB =100%
B–AB =0%
A B
L
Made in SwitzlandR M
.2.4
.6.8 1
0.2
.4.6 .8 1
R MMade in Switzland
0.2 .4
.6.8
1
0.2 .4
.6.8
1
NC NO
2 2
1 1
.9.8.7
6
NO
SRFU
.9.8
.76
NC
4
3
NRFU
3
4
11
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
38
GRKU..-7 Electronic Fail-Safe Actuators
GRKU24-7 Nominal voltage AC 24V, 50/60Hz / DC 24V
Nominal voltage range AC 19.2...28.8V/DC 21.6...28.8V
Power consumption -running 12W @ norminal torque
-holding <3W
For wiring sizing ≤21VA
Connecting cable Cable1m, 2x0.75mm2
Protection class III (safety extra- low voltage)
g0022 .xorppAthgieW
GRKU24-MF-7 Nominal voltage AC 24V, 50/60Hz / DC 24V
Nominal voltage range AC 19.2...28.8V/DC 21.6...28.8V
Power consumption -running 12W @ norminal torque
-holding <3W
For wiring sizing ≤21VA (1max 20 A @ 5ms)
Connecting cable Cable1m, 4x0.75mm2
Control signal Y DC 2(0)...10V @ input impedance100kΩ
Position feedback U DC 0.5...10V@ max. 0.5mA
Sychronisation 5%
Protection class III (safety extra- low voltage)
g0022 .xorppAthgieW
Common technical data mN04 ≤euqroT
Direction of rotation Max. 90° At switch position 1or 0 , respectively
Angle of rotation Max. 95° , can be limited at both ends with
adjustable mechanical end stops
Sound power level Max. 61dB(A)
Position indicator Mechanical, pluggable
Manual override Gearing disengaged by pressing the pushbutton
Running time -Standard operation 150s/95°
-Emergency setting position 35s @ 0...50 °C
Mode of operation Type 1.AA
C°05+...03-.pmet tneibmA
Non-operation temp. -40...+80°C
gnisnednoc non ,HR %59tset ytidimuH
Degree of protection IP54NEMA 2, UL Enclosure Type 2
CE/801/4002 ot gnidrocca ECCME
eerf-ecnanetniaMecnanetniaM
Electronic Fail-Safe Actuators for operation of:Torque:Open/Close control: Modulating control:
•
•••
DN100...150 CCV40NmGRKU24-7GRKU24-MF-7
Technical data
39V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Technical data (continued)
GRKU..-7 Electronic Fail-Safe Actuators
Safety notes
Product features
Dimensions Dimensions See «Dimensions» on page 6
The actuator is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.It may only be installed by suitably trained personnel. Any legal regulations or regulations issued by authorities must be observed during assembly.The device may only be opened at the manufacturer’s site. It does not contain any parts that can be replaced or repaired by the user.The cable must not be removed from the device.The device contains electrical and electronic components and is not permitted to be disposed of as household refuse. All locally valid regulations and requirements must be observed.
•
•
•
••
!
Mode of operation The actuator is controlled with a standard modulating signal of DC 0 ... 10 V and travels to the position defined by the control signal. The measuring voltage U serves for the electrical display of the damper position 0 ... 100%.
Pre-charging time (start up) The capacitor actuators require a pre-charging time. This time is used for charging the capaci-tors up to a usable voltage level. This ensures that, in the event of a voltage interruption, the actuator can be moved at any time from its current position into the preset emergency setting position (POP).The duration of the pre-charging time depends mainly on the following factors:–Duration of the voltage interruption–PF delay time (bridging time)
Typical pre-charging times
Duration of voltage interruption [Days]
PF delay[s]
Duration of voltage interruption[Days]
0 1 2 7 ≥10
0 5 8 10 15 19
2 6 9 11 16 20
5 8 11 13 18 22
10 12 15 17 22 26
Pre-charging time[s]
Calculation example:In the event of a voltage interruption of 3 days and a set bridging time (PF) of 5 s, the actuator requires a pre-charging time of 14s (see graphic on page 2) after the voltage has been recon-nected.
Delivery condition (capacitors) The actuator is completely discharged after delivery from the factory, which is why the actuator requires approximately 20 s pre-charging time before initial commissioning in order to bring the capacitors up to the required voltage level.
High operational reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.
Home position / Start The clamp of the actuator is set ex-works to 0°After the supply voltage has been applied, the actuator moves into the position defined by the control signal.
00
5
10
15
20
25
30
2 4 6 8 10 12
0 s
5 s2 s
10 s
0
5
10
15
20
25
30
Pre
-cha
rgin
g t
ime
[ s]
PF delay
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
40
Product features (continued)
GRKU..-7 Electronic Fail-Safe Actuators
Accessories
Wiring diagrams
Emergency setting position (POP) rotary button
The «Emergency setting position» rotary button can be used to adjust the desired emergency setting position (POP) between 0 and 100% in 10% increments.The rotary button applies only to the adapted angle of rotation range of between 30 and 95° . No minimum or maximum set values are taken into account.In the event of a voltage interruption, the actuator will move into the selected emergency set-ting position, taking into account the bridging time.
Settings The rotary button must be set to the «Tool» position for retroactive settings of the emergency setting position with the BELIMO service tool MFT-P.Once the rotary button is set back to the range 0 … 100%, the manually set value will have positioning authority.
Bridging time (PF) Voltage interruptions can be bridged up to a maximum of 10 s.In the event of a voltage interruption, the actuator will remain stationary in accordance with the set bridging time. If the voltage interruption is greater than the set bridging time, then the actuator will move into the selected emergency setting position (POP).The bridging time set ex-works is 2 s. This can be modified at the site of operations with the use of the BELIMO service tool MFT-P.
Settings The rotary button must not be set to the «Tool» position!Only the values need to be entered for retroactive adjustments of the bridging time with the BELIMO service tool MFT-P.
Electrical accessoriesDescription Data sheetAuxiliary switch S..A.. S..A..
Feedback potentiometer P..A.. P..A..
Notes:Caution: Power supply voltage! Other actuators can be connected parallel.
Please note the performance data.
••
GRKU24-7
!
Open/Close control
– +
T ~
1 2
Cable colors:1=black2=red
GRKU24-MF-7
Note:Connect via safety isolation transformer. !
1 2
1 2
3 5
T
– +
~T
+
T ~
–
+–
~Open/Close control
Cable colors:1=black2=red3=white5=orange
3 5
U
YU
Y
U
Measuring voltageControl signal
41V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Electrical installation
GRKU..-7 Electronic Fail-Safe Actuators
T
– +
~
Notes:A maximum of eight actuators can be connected in parallel.Parallel operation is permitted only on separated axes.It is imperative that the performance data be observed with parallel operation.
•
•
•
Wiring diagram for parallel operation
Actuator 1 Actuator 2 Actuator X
U1
1
UXY
2 3 5 1 2 3 5 1 2 3 5
T ~
T
Cable lengths
Note:When several actuators are connected in parallel, the maximum cable length must be divided by the number of actuators.
Note:There are no special restrictions on installation if the supply and data cable are routed separately.
L1
A
Ltot
2
Y
CU
1
U
Y
C
A
L1
L2
53
21 53
A = ActuatorC = Control unitL1 = Belimo connection cable, 1m (4x 0.75mm2)
A = ActuatorC = Control unitL1 = Belimo connection cable, 1m (4x 0.75mm2)L2 = Customer cableLtot = Maximum cable length
N L
AC 230V
AC 24V
Cross section L2
┴ / ~
Max. cable lengthLtot = L1+ L2 Example for DC
AC DC0.75mm2 ≤40m ≤20m 1m (L1) + 19m (L2)
1.00mm2 ≤50m ≤30m 1m (L1) + 29m (L2)
1.50mm2 ≤80m ≤45m 1m (L1) + 44m (L2)
2.50mm2 ≤130m ≤80m 1m (L1) + 79m (L2)
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
42
Operating controls and indicators
GRKU..-7 Electronic Fail-Safe Actuators
Status
10
0.1
0.5
1
0
0.9
TOOL
PowerAdaption
POP
GRKU24-MF
6
7
1
2
34
58
9
1 Direction of rotation switch
2 Cover, POP button
3 POP button
4 Scale for manual adjustment
5 Position for adjustment with tool
6 Tool socket
7 Disengagement switch
LED displaysMeaning / function
8 yellow 9 green
Off Illuminated Operation OK / without fault
Illuminated Off Fault
Off Off Not in operation
Illuminated Illuminated Adaptation procedure running
Blinking Illuminated Communication with programming tool
Operating controls and indicators
RRRRRRGRKU24-MF
10
0.1
0.5
0.9
TOOL
10
0.1
0.5
0.9
TOOL
POP %0...100
POP >PC- Tool
Setting the POP Power Off position
43V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Dimensions [mm]
Dimensions of GRKU..-7 Electronic Fail-Safe Actuators
97
17444
GRKU24-7
GRKU24-MF-7
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
44
M
M
POPPOP
POP direction
direction
direction
1322Nm
10
10NmF05
F07
0%
0%
Installation procedures of Electronic Fail-Safe Rotary Actuators
2
3
2
1
4
A
B
45V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
Separate supplyWhen Ball Valve and Rotary Actuator are supplied separately, they can be assembled on-site.Recommended mounting positionsThe Ball Valves maybe mounted vertical (Fig. 1) or horizontal (Fig. 2). However, mount-ing the Ball Valves with the spindle pointing downwards, i.e. upside down (Fig. 3), is not recommended.
No special tools are needed for assembly. Instructions will be found packed with the valve and actuator.
CommissioningMust not be carried out until the Ball Valve and Rotary Actuator have been assembled in accordance with the instructions.
Installation, direction of flow and commissioning
Standard directions of flow
Flow characteristics of Charactersied Control Valves
Mounting, installation and commissioning
Characterised Control Valves
2-wayR2..AC, R6..AO
3-wayR3..
Open/Close Ball Valves
2-wayR2..AC, R6..AO
3-wayR3..
Spindle position for corresponding
valve flowFor 2-way and 3-way
Ball Valves
Actuator position corresponding
to ball valve flow direction
kv
Y
kv
Y
Between 0° and 12.5° angle of rotation, 2-way and 3-way Characterised Control Valves function as tight-sealing shut-off devices. Be-tween 12.5° and 90° angle of rotation, Control Ball Valves operate
as regulating devices. In case of the 3-way Characterised Control Valve, the bypass flow rate (B-AB) is 70% of the nominal flow rate (A-AB).
Note:Due to its spherical design, the 3-way Characterised Control Valve is of limited ap-plication for conventional supply temperature control systems only. Therefore, it is recom-mended that supply temperature control systems are of the double-mixing circuit type (see diagram below). There are no restric-tions when using mixing-type circuits for air preheaters and for injection circuits.
Fig.1 Fig.2 Fig.3
M
Open Closed
A-AB Open A-AB Closed
A
AB
B
Open Closed
A-AB Open A-AB Closed
A
AA
B
B
B
AB AB
AB
2-way Characterised Control Valve 3-way Characterised Control Valvekv/kvs
100%
Angle ofrotation10° 90°
70%
12.5°
A-AB
B-AB
kv/kvs
70° 90°
100%
Angle ofrotation0 0
V5.
12.2
010•
Sub
ject
to m
odifi
catio
n
46
CCV-Notes on installation
DN15...50 CCV
Clean pipe by compress air or steam
Teflon tape or other sealing filler is recommended for pipe and valve thread end, pipe dope is not allowed on thread
Make sure the correct wrench position (fig.1)
Support pipeline to avoid pipe distortion
1.
2.
3.
4.
DN15...50 CCV
(fig.1)
Clean the joint
Insert the rest of the bolts, tighten all of the bolts evenly by the cross-over method to eliminate concentrated stresses.
1.
2.
3.
Insert the gasket
Put two or three screws (loose)
7 1 5 4 8 2
6
3
47V5.
12.2
010•
Sub
ject
to m
odifi
catio
nNotes on maintenance and project design
Maintenance
Project design
Differential pressures PV100 with Characterised Control Valves full open
Ball Valves and Rotary Actuators are both maintenance free. Before any kind of service work is carried out on control devices of this type, it is essential to isolate the actuator from the power supply (by unplugging the power lead). Any pumps in the particular part of the piping system concerned must also be switched off and the appropriate isolating fittings closed (also al-low everything to cool down first if necessary and reduce the pressure in the system to atmospheric).
•
•
The systems must not be returned to service until the Ball Valve and the Actuator have been properly re-installed and connected and the pipe work has been refilled in the proper manner.
Subsequent removalIn the case of applications where subsequent removal of Ball Valve will be necessary, it is advisable to make appropriate preparations before hand.
DisposalWhen a control device (Ball Valve and Actuator) has come to the end of its service life, the two parts must be dismantled and sorted into different materials before being disposed of.
Installing R2..AC, R6..AO CCV, 2-wayThe R2.. Characterised Control Valve is a throttling device, installed in the return line of systems in order to ensure less thermal stress on the seals of the device. The direc-tion of flow specified must be adhered to.
Installing R3.. CCV, 3-wayThe R3.. Characterised Control Valve is a mixing device. Whatever type of installation is employed, it is essential to adhere to the directions of flow specified. Whether a valve is installed in the supply or the return of a system depends on the type of
hydraulic circuit being employed. No balanc-ing valve is needed in the bypass line of a diverting circuit because of the reduced flow in the bypass.
Water quality requirementsThe water quality requirements specified in VDI2035 must be adhered to.
Dirt filters recommendedCharacterised Control Valves are relatively sensitive control devices and in order to en-sure that they give long service life, the fitting of dirt filters is recommended.
Sufficient isolating valvesIt is essential to ensure that sufficient isolat-ing valves are provided.
Correct rating and sizingIn order to ensure that the control device (Characterised Control Valve and Rotary Actuator) achieves a long service life, it is es-sential for the valve to be rated for the correct differential pressure PV100 across the valve, i.e. with adequate valve authority (Pv>0.5). The differential pressure PV100 depends on the type of hydraulic circuit in which the valve is being used.
PV100R2..AC, R6..AO Characterised Control Valves, 2-way PV100 R3.. Characterised Control Valves, 3-way
Throttling circuit
PV100 > PVR/2
Typical values:15kPa > PV100 > 150kPa
Injection circuit with throt-tling device
PV100 > PVR/2
Typical values:10kPa > PV100 > 100kPa
Diverter circuit
PV100 > PMV
Typical values:5kPa > PV100 > 50kPa
Mixing circuitPV100 > PMV
Typical values:PV100 >
3kPa(unpressurise manifold).
For other mixing
3kPa > PV100 > 30kPa
Injection circuit with 3-way Characterised Control Valve
PMV1 + PMV2≈0
Typical values:PV100 < 3kPa
Geo
grap
hic
Pres
enta
tion
Syno
ptic
Pres
enta
tion
VLVL
RL RL
VL
RL
VL
RL
VL
RL
VL
RL
VL
RL
VL
RL
VL
RL
VL
RL
PVR
PMV2 ≈0
PMV2
PMV1
PMV
PVR
PVR PVR
PMVPMV ≈0
PMV1
PMV2
Legend
Characterised Control Valve, 2-way with Rotary Actuator
Characterised Control Valve, 3-way with Rotary Actuator
Differential pressure across specified section at rated load
Differential pressure across variable-flow section at rated load (e.g. heat exchanger) Note: Dirt traps and isolating fittings are not shown.
Pump Non-Return Damper Balancing throttle VL — SupplyRL…Return
PVR PMV
Trade Selection by Belimo
Asia Pacific Headquarters and Shanghai Office:Belimo Actuators (Shanghai) Trading Ltd.479 Chun Dong Road, Building C-2Xin Zhuang Industry ParkShanghai 201108, P.R. ChinaTel: +86 21 5483 2929Fax: +86 21 5483 2930E-mail: [email protected]: [email protected]
INDIAMumbai Office:Belimo Actuators India Pvt. Ltd.204 Jaisingh Business Center, ParsiwadaSahar Road, Andheri (East)Mumbai 400099, IndiaTel: +91 22 6733 2525 / 6733 2501Fax: +91 22 2822 2643E-mail: [email protected]
New Delhi Office:Belimo Actuators India Pvt. Ltd.A-230, Okhla Phase INew Delhi 110020, IndiaTel: +91 11 2637 1644Fax: +91 11 2637 1699E-mail: [email protected]
Bangalore Office:Belimo Actuators India Pvt. Ltd.60/1, 1st Floor, Coles Road, Frazer TownBangalore 560001, IndiaTel: +91 80 2558 0421 / 6565 6978Fax: +91 80 2558 0422E-mail: [email protected]
JAPANBelimo Actuators Ltd.7th Floor, Honjo-Azumabashi DJ Building4-19-3, Honjo, Sumida-kuTokyo 130-0004, JapanTel: +81 3 6823 6961Fax: +81 3 3626 3911E-mail: [email protected]
MALAYSIABelimo Actuators Ltd.12-1, Jalan PJS 10/2, Subang Indah46000 Petaling Jaya Selangor, MalaysiaTel: +603 5631 2188Fax: +603 5638 2189E-mail: [email protected]
SINGAPOREBelimo Actuators Ltd.1 Tannery Road #08-04, One TannerySingapore 347719Tel: +65 6842 1626Fax: +65 6842 1630E-mail: [email protected]
THAILANDBelimo Actuators Ltd.90/2 Pensiri PlaceSoi Phaholyothin 32, Phaholyothin RoadChandrakasem, JatujakBangkok 10900, ThailandTel: +662 9415582-3Fax: +662 9415584E-mail: [email protected]
AUSTRALIAMelbourne Office:Belimo Actuators Pty. Ltd.12 Enterprise CourtMulgrave Business ParkMulgrave, VIC 3170, AustraliaTel: +61 (0)3 9545 0844Fax: +61 (0)3 9545 0855E-mail: [email protected]
Sydney Office:Belimo Actuators Pty. Ltd.Suite 2.20, 32 Delhi RoadNorth Ryde, NSW 2113AustraliaTel: +61 (0)2 9805 1777Fax: +61 (0)2 9805 1722E-mail: [email protected]
GREATER CHINA Beijing Office:Belimo Actuators (Shanghai) Trading Ltd.Beijing Branch OfficeRoom 605, Hai Chang Edifice44 Liang Ma Qiao RoadBeijing 100016, P.R. ChinaTel: +86 10 6462 1382Fax: +86 10 6462 1383E-mail: [email protected]
Guangzhou Office:Belimo Actuators (Shanghai) Trading Ltd.Guangzhou Branch OfficeRoom 1202, Skyline Plaza644 Tong Fu East Road, Haizhu AreaGuangzhou 510240, P.R. ChinaTel: +86 20 3435 1860Fax: +86 20 3435 1870E-mail: [email protected]
Chongqing Office:Belimo Actuators (Shanghai) Trading Ltd.Chongqing Branch OfficeRoom 4, 9th floor, Unit 7, Luoma Jiari GardenNo. 36, QingLong Road, Nan’an DistrictChongqing 400060, P.R. ChinaTel: +86 23 6275 3155Fax: +86 23 6280 3380 *519E-mail: [email protected]
Hong Kong Office:Belimo Actuators Ltd.Room 207, 2/F, New Commerce Center19 On Sum Street, Shatin, N.T., Hong KongTel: +852 2687 1716Fax: +852 2687 1795E-mail: [email protected]
Taiwan Office:Belimo Actuators Ltd.7F-2, No. 343, Jhonghe Road, Yonghe CityTaipei County 234, TaiwanTel: +886 2 2922 8805Fax: +886 2 2922 8806E-mail: [email protected]
Market Asia Pacific
Belimo regional head offices
EU BELIMO Automation AGBrunnenbachstrasse 1 8340 Hinwil, Switzerland Tel: +41 43 843 61 11Fax: +41 43 843 62 68E-mail: [email protected]
AP BELIMO Actuators (Shanghai) Trading Ltd.479 Chun Dong Road, Building C-2Xin Zhuang Industry ParkShanghai 201108, P.R. ChinaTel: +86 21 5483 2929Fax: +86 21 5483 2930E-mail: [email protected]
US BELIMO Aircontrol (USA), Inc.43 Old Ridgebury RoadDanbury, CT 06813-2928, USATel: +800 543-9038 / 203 791-9915Fax: +800 228-8283 / 203 791-9919
Innovation, Quality and Consultancy:A partnership for motorising HVAC actuators
www.belimo.com