HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
I. SCOPE :This specification covers the supply of semiautomatic
electricity meter test bench.
II. STANDARD OF MANUAFACTURE AND TEST :The equipment shall conform to the latest edition of theappropriate IEC standards and/or other international standards.
III. DESCRIPTION :1. Function of equipment :Semiautomatic test equipment for simultaneously testing of 10
three or single phases meter . Typical accuracy on the energymeasurement of 0.05% within a continuous range. Theequipment shall be designed for an easy testing of electricitymeters. It consist of :
Fictitious and variables shift power supply.
Measuring devices of the different parametersconsidered. The measurement on each phase, of thevoltage, the current and the power, by means ofvoltmeters, amperemeters, phasemeters and the
reference standard meter. Regulation, control and protection elements.
Calculation and data acquisition system.
It permits individual or group calibration of the followingelectricity meters :
- Single or multi-phase.- Any type of active or reactive energy.- Direct connection or to measurement energy.- Induction or electronic meters.
2. Technical specification of semi-automatic electricity metertest bench :
The measuring equipment is formed of three main component :- Test bench : A metallic modular test bench or console, withthe different measuring elements and manual controlsassembled on it. Testing and control software.- Meter test rack.- Test console with built in PC.
2.1. Test bench :
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 1/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
2/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
Fictitious power supply of measuring circuits of the meters tobe tested by means of :
2.1.1. Test Voltage circuit :Three test voltage ranges :
Range 1 2 3Star 45-80 V 80-160 V 160-290 VDelta 80-138 V 138-277 V 277-502 V
Every range continuously adjustable in each phase, with coarse
and fine regulators. Every range is automatically selected bysoftware.- Rotator Switch for no load testing with 80 100 120% Un.- Voltage symmetrization system.- Inver sequence RST/SRT selector.- The voltage range and coupling ( delta or star ) are
automatically selected by software as a function of thedesired test.
2.1.2. Test Voltage circuit :Two current ranges : 10mA 2A, 2A 150A continuouslyadjustable in each phase, with coarse and fine regulators.- Illuminated push button to decide the testing current by a
factor of 10.- Illuminated push button to decide the testing current by a
factor of 100.- Three illuminated push button for the individually switching
on and off the test current in each phase.
-Current symmetrization system.
2.1.3. Phase Shift :Phase angle adjustment by AC motor.Phase shifter with continuous adjustment within 0
180( lagging and leading )One quick selector illuminated push button for power factorcos = 1 to cos = 0.5 ( or Sin = 1 to Sin = 0.5 ).
2.1.4. Power output :Voltage power output 300VA per phase.
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 2/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
3/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
Current power output 1000VA per phase.
2.1.5. Reference standard meter :- Reference standard meter with a built in multimeter.- Built in solid state reference standard meter with a typical
accuracy of 0.05% for active energy.- Testing of following meters :
Star Wh : single phase and three phase four wire metersfor active energy.
Delta Wh : three phase three wire meters for activeenergy.
Star Varh : three phase four wire for reactive energy of thecross connected variety ( class 90 ).
Delta Varh : : three phase three wire meters for reactive
energy of the cross connected variety ( class 90, 60 orartificial neutral ).
Star Varh : single phase and three phase four wire metersfor reactive energy of the true varmetric variety (class 0 ).
Delta Varh : three phase three wire meters for reactiveenergy of the true varmetric variety (class 0 ).
2.1.6. Error calculator :This component, programmable from PC, calculates the error ofone meter by using the scanning head provided.
2.1.7. Built in PC :In charge of the control of the bench and the meter tests. Allthe measured parameters are shown on the VGA screen,allowing also an important reduction in space in the testlaboratories. The PC built in the test bench. The console also
includes a 80 column printer.
2.1.8. Safety devices :Fuses, differential breakdown and overload protection.
2.1.9. Test bench console :The testing unit is mounted in a welded steel rack with wheels.The front, rear and side panels are removable, the input andoutput connections and the grounding connector, are located
and protected at the back side.
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 3/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
4/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
2.2. Meter Test Rack :The meter test rack with capacity for 10 meters each. The test
rack is equipped with the following items :A scanning head capable to detect the disk mark withoutremove the meter cover, or the led of a static meters ( forthose static meters with a LED with the following characteristics: 20 milicandela, red spectrum, centered on 630 nanometers ).
The scanning head is mounted in moving supporters, designedto facilitate its displacement along the rack to test any meter.Under request, are available scanning heads for infra-redemitters.
Error calculators, for individual error display having severalfunctions :- Error calculations.- Tolerance indication system, it display will blink in order to
attract the operators attention when the error of the metersis out of the defined tolerance.
- Individual reset push button.- Also used in the starting and creeping automatic test.- LED type error display each with sign and three digits with
one decimal +/- 00.0 ( with the provided software, it ispossible to have on the screen four digits, +/- 00.00 ).
2.3. Testing and control software :The testing procedure is controlled by an easy to manage menudriven software.
The software controls practically all the task performed by thetest bench.During the execution of attest, it is possible to visualize on the
screen, all the measurements taken by the reference standardmeter and the multimeter. There are two displays showing allthe parameters measured by the standard, on the screen.Pressing a key will show the basic testing information or thegeneral testing information.
The most important functions performed by the software are :- Error calculation control ( capacity standard software up to
128 meters ).- Automatic verification of meter registers ( constant ).-
Automatic verification of maximum load indicators( electronics or mechanical )- Calculation of average error and standard deviation./var/www/apps/conversion/tmp/scratch_5/139052675.doc 4/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
5/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
- All the results are stored in a file compatible with DBASE III.- Plotting of the error meter curve on the screen and printer.
-Capacity it test meters with different constant, at the sametime.
IV. REQUIREMENT OF TECHNICAL DOCUMENTSUBMITTED WITH THE QUOTATION :
- Technical description, data sheet, catalogues and othermaterial submitted with the quotation must enable thePurchaser to thoroughly evaluate the proposals as to itscompliance with the inquiry specification.
-Minimum requirements :
+ Detail summary of deviations to the inquiryspecification.
+ Completed inquiry datasheet expressed at section V.+ Catalogues containing outline dimension, technical
data+ List of main equipment and completed accessorieswhich can perform all function described in section IIIhave the following requirements :
. Individual cost of main equipment and each accessory. Total cost of main equipment and completed accessory
. Manufactures code of main equipment and eachaccessory
+ Connection diagram.+ Certificate of quality management.
V. REQUIREMENT OF DOCUMENT INCASE OF BIDWINNING :
1. Documents required to be provide for commission :In order to ensure the quality of supplied goods, in case ofbid winning, the Tenderer shall supply the following documentsfor the Purchaser :- Manufacturers Certificate of Quality.- Certificate of Origin issued by Chamber of Commerce of the
manufacturing country.- Certificate of calibration of equipment approved by an
independent lawful organization.
2. Documents required to be provide in accompany withsupplied products :
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 5/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
6/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
The Supplier shall enclose the following documents for suppliedproducts :
- 01 catalog- 01 instruction manual of installation, operation and
maintenance.
VI. REQUIREMENT OF INSTALLATION AND INSTRUCTIONFOR USE :
The Supplier shall ensure to supply the following service :- Installation the equipment completely.- Instruction to Purchasers staff how to use this equipment on
site.- Trial run this equipment.
VII. DATA SHEET :
N DESCRIPTION REQUIREMENT QUOTED
1. Manufacturer2. Country of origin
3. Manufacturers code4. Standards of manufacture
and test5. Standards of quality
management6. Organization which
approved certificate ofquality management
7. In case of bid winning, the
Tenderer shall supply thefollowing documents for thePurchaser :- Manufacturers Certificateof Quality.- Certificate of Origin issuedby Chamber of Commerce ofthe manufacturing country.- Certificate of calibration of
equipment approved by anindependent lawfulorganization.
Yes
Yes
Yes
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 6/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
7/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
8. List of main equipment andcompleted accessories met
all requirements of sectionIV is supplied in tenderproposal.
Yes
9. Quoted main equipment andcompleted accessoriesdescribed in above list canperform all functiondescribed in section IIIwithout addition of other
necessary materials.
Yes
10. The Supplier shall ensure tosupply the following service:
- Installation the equipmentcompletely.
- Instruction to Purchasersstaff how to use thisequipment on site.
-Trial run this equipment.
Yes
Yes
Yes
11. Function of equipment :* Semiautomatic testequipment forsimultaneously testing of 10three or single phasesmeter.* Typical accuracy on theenergy measurement of
0.05% within a continuousrange.* The equipment shall bedesigned for an easy testingof electricity meters. Itconsist of : Fictitious and variablesshift power supply. Measuring devices of the
different parametersconsidered. Themeasurement on each
Yes
Yes
Yes
Yes
Yes/var/www/apps/conversion/tmp/scratch_5/139052675.doc 7/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
8/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
phase, of the voltage, thecurrent and the power, by
means of voltmeters,amperemeters,phasemeters and thereference standard meter. Regulation, control andprotection elements.
Calculation and dataacquisition system. It permits individual or
group calibration of thefollowing electricity meters :- Single or multi-phase.- Any type of active orreactive energy.- Direct connection or tomeasurement energy.- Induction or electronicmeters.
Yes
YesYes
Yes
Yes
12. The measuring equipment isformed of three maincomponent :- Test bench :
- Meter test rack.- Test console with built in
PC.
- A metallic modulartest bench orconsole, with thedifferentmeasuringelements andmanual controls
assembled on it.-Testing andcontrol software issuppiled.
YesYes
13. Test bench Fictitious powersupply of measuring circuits
of the meters14. Test Voltage circuit :
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 8/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
9/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
+ Three test voltage ranges- Star
+ Three test voltage ranges Delta
+ Every range isautomatically selected bysoftware.+ Every range continuously
adjustable in each phase,with coarse and fineregulators :. Rotator Switch for no loadtesting with 80 100 120%Un.. Voltage symmetrizationsystem.. Inver sequence RST/SRT
selector.. The voltage range andcoupling (delta or star) areautomatically selected bysoftware as a function of thedesired test.
45-80V80-160V
160-190V80-138V
138-277V277-502V
Yes
Yes
YesYes
Yes
15. Test current circuit :+ Two current ranges :
+ Illuminated push buttonto decide the testing currentby a factor of 10+ Illuminated push buttonto decide the testing currentby a factor of 100
+ Three illuminated pushbutton for the individuallyswitching on and off the test
10mA 2A, 2A 150A continuously
adjustable in eachphase, with coarseand fine regulators.
Yes
Yes
Yes
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 9/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
10/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
current in each phase.+ Current symmetrization
system.
Yes
16. Phase Shift :+ Phase angle adjustmentby AC motor.+ Phase shifter withcontinuous adjustmentwithin 0 180( laggingand leading )+ One quick selector
illuminated push button forpower factor cos = 1 to
cos = 0.5 (or Sin = 1 to
Sin = 0.5).
Yes
Yes
Yes
17. Power output :+ Voltage power output300VA per phase.+ Current power output1000VA per phase.
YesYes
18. Reference standard meter :- Reference standardmeter with a built inmultimeter.- Built in solid state
reference standard meterwith a typical accuracy of0.05% for active energy.
- Testing of following
meters :+ Star Wh : single phase andthree phase four wire metersfor active energy.+ Delta Wh : three phasethree wire meters for activeenergy.+ Star Varh : three phasefour wire for reactive energy
of the cross connectedvariety ( class 90 ).
Yes
Yes
Yes
Yes
Yes
Yes
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 10/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
11/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
+ Delta Varh : : three phasethree wire meters for
reactive energy of the crossconnected variety ( class90, 60 or artificial neutral ).+ Star Varh : single phaseand three phase four wiremeters for reactive energyof the true varmetric variety(class 0 ).+ Delta Varh : three phase
three wire meters forreactive energy of the truevarmetric variety (class 0).
Yes
Yes
19. Error calculator This component,programmable fromPC, calculates theerror of one meterby using thescanning head
provided.20. Built in PC :
- In charge of the control ofthe bench and the metertests.
- All the measuredparameters are shown onthe VGA screen, allowingalso an important
reduction in space in thetest laboratories.
- The PC built in the testbench. The console alsoincludes a 80 columnprinter.
Yes
Yes
Yes
21. Safety devices Fuses, differentialbreakdown andoverload protection
22. Test bench console :- The testing unit is Yes
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 11/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
12/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
mounted in a welded steelrack with wheels.
-The front, rear and sidepanels are removable.
- The input and outputconnections and thegrounding connector, arelocated and protected atthe back side
Yes
Yes
23. Meter Test Rack :The meter test rack with
capacity for 10 meters each.The test rack is equippedwith the following items:- A scanning head capable
to detect the disk markwithout remove the metercover, or the led of astatic meters (for thosestatic meters with a LED
with the followingcharacteristics: 20milicandela, redspectrum, centered on630 nanometers).
- The scanning head ismounted in movingsupporters, designed tofacilitate its displacement
along the rack to test anymeter. Under request, areavailable scanning headsfor infra-red emitters.
- Error calculators, forindividual error displayhaving several functions :
+ Error calculations.+ Tolerance indication
system, it display will blinkin order to attract theoperators attention when
Yes
Yes
YesYes
Yes
Yes
Yes/var/www/apps/conversion/tmp/scratch_5/139052675.doc 12/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
13/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
the error of the meters is outof the defined tolerance.
+ Individual reset pushbutton.+ Also used in the startingand creeping automatic test.+ LED type error displayeach with sign and threedigits with one decimal +/-00.0 ( with the providedsoftware, it is possible to
have on the screen fourdigits, +/- 00.00 ).
24. Testing and control software:- The testing procedure is
controlled by an easy tomanage menu drivensoftware.
- The software controls
practically all the taskperformed by the testbench.
- During the execution ofattest, it is possible tovisualize on the screen, allthe measurements takenby the reference standardmeter and the multimeter.
-
There are two displaysshowing all theparameters measured bythe standard, on thescreen. Pressing a key willshow the basic testinginformation or the generaltesting information.
- The most important
functions performed bythe software are :+ Error calculation control
Yes
Yes
Yes
Yes
Yes
Yes
Yes
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 13/14
7/28/2019 10-Semi Automatic Electricity Meter Test Bench
14/14
HCMC PC SPECIFICATION
SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH
(capacity standard softwareup to 128 meters).
Automatic verification ofmeter registers (constant ).+ Automatic verification ofmaximum load indicators(electronics or mechanical)+ Calculation of averageerror and standarddeviation.+ All the results are stored
in a file compatible withDBASE III.+ Plotting of the error metercurve on the screen andprinter.+ Capacity it test meterswith different constant, atthe same time.
Yes
Yes
Yes
Yes
25. - Dimensions :
+ Width+ Height+ Depth
- Weight
The tendered has to
quote thedimensions andweight of Semiautomaticelectricity metertest bench, Metertest rack.
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 14/14