1
Fires, Firefighting, and Explosions
Fires
Firefighting Equipment
Firefighting
Indirect Firefighting
Explosions
2
Fires
The Fire Triangle
3
Classification of Fire
A (ash) Carbon-paper,wood,coal
B (boil) Liquids-gasoline,diesel fuel
C (current) Electrical- cables, motors
D (ding) Metals- magnesium, titanium
4
Firefighting Equipment
Hand Held Extinguishers Rockdust Water Foam Inert Gases
5
Hand held Extinguishers
Monammonium phosphate Rated for ABC fires, interrupts the basic chemistry of fire. Not recommended for D fires. (Red body & pressure gauge)
CO2
Rated for BC fires, will only extinguish surface area, heated core may reignite. (Red body & horn, no gauge)
Halon Rated for BC fires, used mainly in electronics, dangerous because Halon displaces
oxygen. (Red body and gauge)
Pressurized Water Rated for A fires only, usually a baking soda charge. (Stainless steel body)
6
Using hand held extinguishers
Remember: Select the right type Used mostly for small fires Will usually discharge in less than one minute Training is a must Stay low to avoid fumes Never block escape route
When extinguishing a fire “PASS”
P Pull the pin A Aim low S Squeeze the handle S Sweep from side to side
7
Water
Water is highly effective on Class A fires, by cooling down the fire and surrounding atmosphere.
At most mines, water is usually in plentiful supply. Can be used to cool down the firefighting team to prevent
heat exposure.
8
Disadvantages
Water should not be used to control a B or C fire. Inadequate pressure or too high pressure The volume of water can be restricted to the length of water
lines and hoses(frictional loss- 1/2 lbs. for every ten feet of 1 1/2 inch hose).
The fire nozzle can clog to non-filtered materials in the lines.
Hydrogen can be produced by applying water to super hot fires.
9
Nozzles– Many mines use fixed nozzles that limit
the amount of water to be used– Volume not pressure will put out the fire– Nozzles in the mine today may not handle
the high water pressure and may blow out Hoselines
– Any hoseline under 2 inch diameter will have frictional loss
– Hoselines must a bursting pressure at least 4 times the mine’s outlet pressure
– Multiple walled hoses should only be used– Proper deployment and storage of
hoseline will determine if firefighting efforts are successful
10
Foam
Protein– Animal protein from entrails or blood (Class A & B fires)– Burn back protection, not film forming, adheres well to roof
Fluoroprotein– Animal protein with fluorinated surfactants (Class A & B fires)– Burn back protection, film forming
Aqueous Film Forming Foam (AFFF)– Synthetic (Class A & B fires)– Burn back protection, film forming
Alcohol Type Concentrates (ATC)– Used mainly in alcohol based liquids (Class A & B fires)– Burn back protection, film forming
High Expansion Foam– Special detergent concentrate, expands 1000 times its own volume (Class A
fires)– No burn back protection, not film forming
11
Training All persons directly involved should have hands on
training. Support personal should participate in monthly mine
rescue training and MERD exercises. Mine rescue team members shall have at least 4 hours
training monthly or 8 hours bimonthly(Pa State Trained Teams train at least 6 hours monthly).
State Trained teams participate in simulated exercises at Niosh(Lake Lynn facility and Bruceton.
12
Before Going Underground
Before sending teams underground make sure that: A. The main fan is running B. A guard is monitoring the operation of the fan C. Tests are being made at main returns for any mine gases
All persons should be aware if the fire is spreading or a possible explosion can occur.
13
Do not make any sudden changes in mine ventilation
Determine location of battery or diesel operated equipment
Determine location of storage areas for explosives, oil and grease, diesel fuel, bottled gas
Cut off electric power to affected area, to prevent arcing starting additional fires and safety to mine
rescue teams.
14
Locating Fires & Assessing Conditions
Information given by mine officials and workers where smoke, fumes or heat was last seen
The amount of afterdamp gases could determine what is burning and how much is burning
Laboratory analysis could determine if the fire is still burning
15
Information received from the rescue teams during exploration
Gas readings near the fire area to determine if the atmosphere is potentially explosive
Check on ventilation controls for damage
Roof must continually be evaluated since heat will weaken the strata
16
Direct Firefighting
High volume of water is recommended Use of wide angle fog for team safety and
steady steam for direct contact with fire Hazards include: electrocution, toxic and
asphyxiating gases, explosive gases, heat, smoke and steam
Firefighting teams have to be very close to the fire area
Teams should approach fire from intake side to ensure safety
17
Use of a transverse brattice
18
Indirect Firefighting
Mine hazards include: high temperatures, bad roof, or explosive gases
Necessary to fight the fire from a distance by sealing the area or by filling the fire area with foam or water
19
Six factors to consider sealing the fire area:
1. Volatility of the coal seam- High vol coal burns faster and much more difficult to fight directly
2. Amount of methane liberated by the coal seam 3. Location of the fire and the area involved 4. Presence of head coal and the composition of roof strata 5. Availability of materials and transportation 6. Building sites for the seals
20
Sealing the Area
Purpose: to lower oxygen level so fire may burn out in addition to foaming or flooding the area
Seal area should have good roof Even roof and rib Temporary seals should used before permanent seal are
built Air sampling tubes install for gas and temperature readings Make sure no abrupt ventilation change over fire area All persons should leave mine in case explosive gases
build up in seal area Possible to use boreholes from surface to pump water
and/or nitrogen to fire area
21
Explosions
As in fire, explosions need fuel, oxygen and heat Methane and/or coal dust are the most likely source of fuel(
2% methane and the right amount of coal dust can create an explosion)
Coal dust explosions travel at a speed exceeding 3000 ft. per second
22
Ignition sources include: electric arc, open flame, misuse ox explosives, sparks from continuous cutting heads
Once an explosion occurs, there is a chance of more explosions due to the ventilation systems being damaged
Before going under ground, make sure that the fan is running and guarded
Tests are made at the fan for dangerous gases
Top Related