RVK & RVS the new controller
generation ABB Jumet REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
El presente tema describe las instrucciones de: INSTALACION, OPERACION Y CONTROL de los reguladores automticos de energa reactiva ABB JUMET RSS RVK.
Adems se tratar lo siguiente :
- Puesta en marcha rpida.
- Carcateristicas avanzadas.
- Pruebas y localizacin de averas.
- Especificaciones tcnicas.
INTRODUCCION
17/04/2013
2
1 2 3 4 5 6
RVS 6 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Standard models
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Types :
RVK or RVS
Number of outputs :
6 or 12
Current inputs :
5 A or 1 A
Voltage :
400 V or 230 V or 120 V
17/04/2013
3
Controller back-side
Voltage range
Identification of model (label on left side):
- ABB article number 20.050.82220
- Controller serial number 13492 40622
- Type RVK 12
- Current input 5A
- Voltage range 220-240 V
- Network frequency 50-60 Hz
17/04/2013
4
LOCK Switch
SET Switch
12 outputs
RVS
RVS
Alarm Relay
Fan Relay
17/04/2013
5
RVS
Plot Output
RS232 Communication
night cos contact
Temperature Input
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
17/04/2013
6
1 2 3 4 5 6
RVS 6 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
RVS 6
1 2 3 4 5 6 7 8 9 10 11 12
RVK 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
V RMS
A RMS
KVA
KVAR
COS
OUTPUT
DELAY
SEQUENCE
SETUP LOCK
RVK 12
17/04/2013
7
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
only for RVS
only for RVS
RVS
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
MODE Menus
Mode choice while pushing on
MODE switch :
- AUTO: Automatic regulation
- MAN: Manual mode
- PRINT: Printer setting mode
- SET: Parameters setting mode
- PLOT: Plot setting mode
- LOG: Data storage mode
17/04/2013
8
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
PLUS and MINUS switches to
modify (sub-)parameters
NEXT switch to walk through
all sub-parameters
DISPLAY Menu
Choice of parameter to
display with DISPLAY
switch:
- Voltage
- Current
- Apparent power
- Reactive power
- THD(U)
- THD(I)
- Power factor
- Temperature
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
LEDs indication :
- Switched on steps
- switching demand + / -
- Fan Relay status
- Alarm contact
(Alarm Relay status)
- RS232 Connection status
- Locked front plate status
17/04/2013
9
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Voltage
- RMS Voltage measurement
- Voltage transformer ratio
- Maximum voltage threshold
(start a LOG-storage/disconnection)
- Minimum voltage threshold
(quick disconnection)
- Nominal voltage
DISPLAY
Measurements and Parameters
NE
XT
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Current
- RMS Current measurement
- CT ratio
- Maximum current LOG-threshold
- Reactive current measurement
- C/k value introduced / calculated
Measurements and Parameters N
EX
T
DISPLAY
17/04/2013
10
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Apparent power
- kVA measurement
- LOG-threshold Smax
Measurements and Parameters
NE
XT
DISPLAY
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Reactive power
- kvar measurement
- LOG-threshold Qmax
- kvar for one step (related to C/k)
- Missing kvar measurement *)
- Missing steps measurement *)
- Number of switched steps
*) related to the minimum-cos
Measurements and Parameters N
EX
T
DISPLAY
17/04/2013
11
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Voltage total harmonic
distortion
THD(U)
- THD (U) measurement
- LOG-threshold THD(U)max
Measurements and Parameters
NE
XT
DISPLAY
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT DISPLAY MODE
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Voltage total harmonic
distortion
THD(I)
- THD (I) measurement
- LOG-threshold THD(I)max
Measurements and Parameters N
EX
T
DISPLAY
17/04/2013
12
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Measurements and Parameters
Power factor ( cos
- Power factor measurement
- Controller reference cos
- Controller night reference cos - Minimum-cos (Tarification)
Alarm activation, LOG-storage
NE
XT
DISPLAY
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Measurements and Parameters
Output
- Number of active outputs
- Individual output deactivation
NE
XT
DISPLAY
17/04/2013
13
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Measurements and Parameters
Delay
- Switch on delay
- Switch off delay
- Starting reset delay
- Alarm delay
- Alarm reset delay
- Printing period
NE
XT
DISPLAY
1 Second
to
120 Minutes
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Measurements and Parameters
Sequence
- Type of sequence
- Linear / Circular
- Progressive / Direct switching
- Normal / Integral measurement
- 1-phase / 3-phase Connection
- Phase correction
NE
XT
DISPLAY
17/04/2013
14
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Measurements and Parameters
Sequence
- Type of sequence
- Linear / Circular
- Progressive / Direct switching
- Normal / Integral measurement
- 1-phase / 3-phase Connection
- Phase correction
NE
XT
DISPLAY
1:1:1:1:1: ... :1
1:2:2:2:2: ... :2
1:2:4:4:4: ... :4
1:2:4:8:8: ... :8
1:1:2:2:2: ... :2
1:1:2:4:4: ... :4
1:1:2:4:8: ... :8
Circular or
Linear
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Measurements and Parameters
Temperature
- Temperature measurement
- Units C / F
- Calibration : V / K
- Calibration : Offset
- Reference T for fan activation
- Maximum T (disconnection /
LOG-Threshold Tmax)
NE
XT
DISPLAY
17/04/2013
15
1 2 3 4 5 6 7 8 9 10 11 12
RVS 12 POWER FACTOR CONTROLLER
NEXT MODE DISPLAY
AUTO
MAN
SET
PLOT
LOG
V RMS
A RMS
KVA
KVAR
THD V
THD A
COS
OUTPUT
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Measurements and Parameters
SETUP
(easy start procedure)
- Voltage transformer ratio
- Current transformer ratio
- Reference cos
- Automatic Ct correction (+ & -)
- Automatic C/k procedure (+ & -)
NE
XT
DISPLAY
Printer output
No required connection
Infrared communication
(HP-Printer)
Free selection of print function
Choice of individual measurements
and printing period
Number of steps when changed
Report of controller settings
Report of Log-datas stored
MODE
AUTO
MAN
SET
PLOT
LOG
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
16
Plot output
Control of a measured value
Choice of 1 Parameter
Quick measurement device
Oscilloscope
XT-recorder
Measurement device
(Ex. Voltmeter) MODE
AUTO
MAN
SET
PLOT
LOG
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
LOG-data storage
Threshold programming (SET)
Free Parameter choice
Free Threshold choice
Stored data
Maximum measured value
Cumulated storage period
Stored data display (LOG)
Retrieve all stored data
MODE
AUTO
MAN
SET
PLOT
LOG
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
17
Temperature measurement
Activation of fan relay
Programmable threshold
Disconnection by over-temperature
Log-storage
Stop regulation until temperature
becomes normal SEQUENCE
TEMP
SETUP
RS 232
LOCK
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Protection capability
Disconnection with under-voltage
avoid brief power outage destruction
Disconnection with over-voltage
avoid over-voltage damages
Disconnection by over-temperature
avoid hot-points damages
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
18
Alarm Function
optimal operation
Free choice of a particular cos
Minimum-cos related to tarification
(Alarm activation when the minimum
cos can not be reached.)
possibility of programming delays
for alarm activation
for alarm reset
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
1:1:2: ...- Sequence
optimal operation
right number of steps
complete modules
alternate switching of both smaller steps
Mini - Circular
switching
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
19
Direct switching
few intermediate switchings
goes right to the target
bigger steps are switched first
rapid regulation
switching-on with 12s delays
switching-off in one shot
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Integral control
Reach the target cos
Compensation of average demand
Regulation even with demand cancellation
Sharp variations doesnt alterate precise regulation
Frequent variations
doesnt influence great amount of steps
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
20
Phase correction
Avoid connection problems
Transformer can be installed in a
preferred phase
Wrong connections
Mixed measurements
No special controller needed
No special phase configuration
needed (for example for voltage)
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
RS232 Connection
RVSlink Software
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
The RS232 connection and the
RVS-Link ABB-Software allows the
communication between the Controller
and a Computer.
This gives then many additional
possibilities related to the use of the
Controller as a measuring device .
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
21
RS232 Connection
RVSlink Software
Display, modify and store all programming parameters
Display and store all measurements
Display the LOG-data
Controller setup by Computer
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Example
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
RS232-Connection
Software RVS-Link
Quick programming utilities
Long time measurements with graphical tools
Instantaneous measurements (Oscillogramme) with harmonic
analysis
...
DELAY
SEQUENCE
TEMP
SETUP
RS 232
LOCK
Example
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
22
RVC : the user-friendly PF Controller
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
User friendly interface
LCD
Display
Key pad
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
23
LCD icons
Alarm
contact Linked to
one output
relay
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
LCD icons
Overtemperature Linked
to one
output
relay
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
24
LCD icons
Inductive /
Capacitive
PF
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Indicates a
demand for
switching on/off
a capacitor step
LCD icons
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Active outputs
17/04/2013
25
Key pad buttons
Parameters
and values
adjustment
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Automatic /
Manual mode
Easy commissioning
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Autoadaptation to
phase rotation CT terminals
Automatic recognition
number of outputs switching sequence
17/04/2013
26
Auto set up
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
C/k Phase shift
Auto set up
Switching
delay time
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
27
Auto set up
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Number of outputs Switching
sequence
Easy programming
MODE + -
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
17/04/2013
28
Highly efficient switching strategy
Integral, direct and circular
Reduce n of switching
Avoid intermediary switching
longer life of capacitors & contactors
Cos phi control with rapidly varying loads.
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
Reliable
Insensitive to the presence of harmonics
Suitable for hot environment
Max. ambient temperature rating of 70C
Range Programmable
RVC-3
RVC-6
RVC-8
RVC-10
RVC-12
3 outputs
6 outputs
8 outputs
10 outputs
12 outputs
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE
230V (220V to 240V)
400V (380V to 440V)
50Hz / 60Hz (automatic adjustment)
Range
voltage
17/04/2013
29
RVC : the user-friendly PF Controller
Unique design
easy commissioning
easy programming
complete auto set-up
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE