//CATALOGUE 2008
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 2/36
pag 20
pag 12
pag 23
pag 26
pag 2
pag 8
pag 6
pag 17
Product reliability, quality and longlife are ZANI’s main objectives.Over thirty years of experienceguarantee the technical expertiseof our designers, masters inapplying principles and standardsto the design phase.
Deliveries are punctual andprecise, in accordance withagreed terms. The extensive and
prompt distribution allows to reachcustomers wherever they are.
In addition to the attention paid tocathodic protection systems, ZANIalso stands out for the importancegiven to internal coatings(SmaltoPLAST®, Stainless steel, Glass-liningand Galvanization) used to make theproduct food-safe and reliable: amust for our creations.
pag 24
pag 29
3
ZANI SPA V.le del Lavoro, 1845100 Rovigo - ItaliaTel. +39 0425 474815Fax +39 0425 [email protected]
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 3/36
HOT WATER
HEATERS
with removable exchanger rigid insulation SmaltoPLAST®
with removable exchanger flexible insulation SmaltoPLAST®
with removable exchanger AISI 316Lwith removable exchanger flexible insulation Galvanized
BVSBVSBVX
BVZ-C
2345
STEAM WATER
HEATERS
solar integrated water heaters with removable exchanger SmaltoPLAST®
with removable exchanger SmaltoPLAST®
BSIBVS-VA
67
RAPID WATER
HEATERS
with fixed coil Glass-liningGlass-liningGlass-lining
with double wall Smaltiflon
BRV DRV
BRMV BIS
89
1011
HOT WATER
STORAGE TANKS
domestic hot water storage tanks rigid insulation SmaltoPLAST®
domestic hot water storage tanks flexible insulation SmaltoPLAST®
domestic hot water storage tanks rigid insulation Glass-liningdomestic hot water storage tanks AISI 316L
domestic hot water storage tanks flexible insulation Galvanized
ACS
ACS ACV ACX
ACZ-E
12
13141516
COMBINED
heating water storage tanksheating water storage tanks with coil
combined solar heat accumulators with double coilscombined solar heat accumulators
PUPUWKMB
KOMBI
17171819
COLD WATER
STORAGE TANKS
storage tanks for chilled water external aluminium jacketstorage tanks for chilled water external SCAI jacket
autoclaves
AR AR AZ
202122
VESSELS air receiver buffer vessels SAC 23
GAS WATER
HEATERS
balanced flue industrial gas water heaters Glass-liningindustrial gas water heaters with piezoelectric ignition
VGFGE
2425
ACCESSORIEShot water heat exchangers / heads / hot water gasket kits
steam heat exchangersmagnesium anodes / anoden tester / correx / control panel
262728
WARRANTIES
COATINGS
CONDITIONS OF SALE
protectionsSmaltoPLAST®
coatings and warrantiesgeneral conditions of sale
29303132
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 4/36
Catalogue 20082
AMSMS
AMSMS≥1500500
AMSMS
r11
BOS ≤ 1000
BVSWATER HEATERS WITH REMOVABLE EXCHANGER
SmaltoPLAST ®
// RIGID INSULATION
HEAT UP TIME(1) 1 HOUR
LITRES COPPER STAINLESS STEEL HEAT OUTPUT DHW PRODUCTION (2) 6p(3) WEIGHT
CODE CODE kW l/h l/10’ l/60’ m H2O kg
200 BVSR 0200 P BVSX 0200 P 12 300 278 528 0,32 60
300 BVSR 0300 P BVSX 0300 P 18 450 418 793 0,48 70
500 BVSR 0500 P BVSX 0500 P 24 600 671 1171 0,64 105
750 BVSR 0750 P BVSX 0750 P 36 900 1007 1757 1,80 130
1000 BVSR 1000 P BVSX 1000 P 48 1200 1343 2343 2,60 170
1500 BVSR 1500 P BVSX 1500 P 73 1800 2014 3514 4,50 250
2000 BVSR 2000 P BVSX 2000 P 97 2400 2686 4686 6,30 295
HORIZONTAL FLEXIBLE INSULATION (PUF50): code BOSR, BOSX.
(1) Rated time to heat domestic water 10÷60°C(2) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)(3) Exchanger head loss.
LITRES DIMENSIONS mm ø CONNS. ANODES
A B B1 C C1 ø D ø De E ø F H H1 L M N e1-u1 e2-u2 TYPE
200 295 320 230 450 360 450 520 1195 300 1380 620 1400 330 185 1” 1/4 1” 1/4 AMS 1
300 325 350 225 480 355 550 620 1215 300 1410 715 1450 350 205 1” 1/4 1” 1/4 AMS 1
500 345 370 235 500 365 650 720 1485 300 1710 825 1760 385 240 1” 1/4 1” 1/4 AMS 4
750 370 395 220 525 350 750 820 1610 300 1855 910 1900 405 260 1” 1/4 1” 1/2 AMS 4
1000 375 438 218 562 342 800 870 1915 300 2170 955 2205 420 270 1” 1/4 1” 1/2 AMS 4
1500 435 484 -- 666 -- 950 1020 2055 380 2400 -- -- -- -- 1” 1/2 2” 2 x AMS 4
2000 450 500 -- 682 -- 1100 1170 2070 380 2450 -- -- -- -- 1” 1/2 2” 2 x AMS 4
e1 primary inletu1 primary outlete2 secondary inlet
u2 secondary outletr circulation (ø 3/4” up to 1000 l,
ø 1” 1/4 > 1000 l)
sc drain ø 1”1/4r1 circulation ø 1” 1/4
AMS Magnesium Anode
t thermometer ø 1/2”ts thermostat ø 1/2”
USE
Water heater for production and storageof Domestic Hot Water (DHW).Working temperature: max 80°C.Working pressure: max 8 bar.
ANTICORROSIVE COATING
SmaltoPLAST
®
: thermoplastic coatingsuitable for contact with potable water;grey colour RAL 7038.
EXCHANGER
U-tube bundle expanded on plate,suitable for contact with potable water.-Copper tubes Cu-DHP (99,9%).-Stainless Steel tubes AISI 316L.Working temperature: max 99°C.Working pressure: max 12 bar.
GASKETS
EPDM food-grade dielectric rubbergaskets code GGE.
INSULATION
VERTICAL VERSION:Hard polyurethane, thickness 30mm(PUR30).HORIZONTAL VERSION:Soft polyurethane, thickness 50mm(PUF50).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ 63, to be periodicallyreplaced.
ACCESSORIES ON REQUEST (page 28)
Electronic impressed-current anode oftitanium for PERMANENT CATHODICPROTECTION.
PACKING
Polythen bubble sheet.
ANTICORROSION WARRANTY
3 years.
80 °C 8 bar 120 °C 3 years Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS GASKETS WARRANTY PED
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 5/36
Catalogue 20083
USE
Water heater for production and storageof Domestic Hot Water (DHW).Working temperature: max 80°C.Working pressure: max 8 bar.
ANTICORROSIVE COATING
SmaltoPLAST
®
: thermoplastic coatingsuitable for contact with potable water;grey colour RAL 7038.
EXCHANGER
U-tube bundle expanded on platesuitable for contact with potable water.-Copper tubes Cu-DHP (99,9%).-Stainless Steel tubes AISI 316L.Working temperature: max 99°C.Working pressure: max 12 bar.
GASKETS
EPDM food-grade dielectric rubbergaskets code GGE.
INSULATION
Soft polyurethane thickness 50mm(PUF50).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ 63, to be periodicallyreplaced.
ACCESSORIES ON REQUEST (page 28)
Electronic impressed-current anode oftitanium for PERMANENT CATHODICPROTECTION.
PACKING
Polythen bubble sheet.AMSMS
AMSMS
AMSMS
AMSMS
sc1c1
BVSWATER HEATERS WITH REMOVABLE EXCHANGER
SmaltoPLAST ®
/ / FLEXIBLE INSULATION
HEAT UP TIME(1) 1 HOUR
LITRES COPPER STAINLESS STEEL HEAT OUTPUT
kW
DHW PRODUCTION (2) 6p(3) WEIGHT
CODICE CODICE l/h l/10’ l/60’ m H2O kg
1500 BVSR 1500 BVSX 1500 73 1800 2014 3514 4,50 230
2000 BVSR 2000 BVSX 2000 97 2400 2686 4686 6,30 270
2500 BVSR 2500 BVSX 2500 122 3000 3357 5857 8,30 306
3000 BVSR 3000 BVSX 3000 146 3600 4029 7029 10,00 345
4000 BVSR 4000 BVSX 4000 195 4800 5371 9371 5,50 470
5000 BVSR 5000 BVSX 5000 244 6000 6714 11724 9,30 550
HORIZONTAL version: codes BOSR BOSX
(1) Rated time to heat domestic water 10÷60°C(2) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)(3) Exchanger head loss.
LITRES DIMENSIONS mm ø CONNS. ANODES
A B B1 C C1 ø D E ø F H H1 L M N e1-u1 e2-u2 TYPE
1500 435 484 274 666 456 950 2055 380 2400 1155 2380 465 315 1” 1/2 2” 2 x AMS 4
2000 450 500 254 682 436 1100 2070 380 2450 1285 2450 500 350 1” 1/2 2” 2 x AMS 4
2500 510 560 244 742 426 1200 2180 380 2540 1375 2560 530 380 1” 1/2 2” 2 x AMS 4
3000 520 570 229 752 411 1300 2190 380 2570 1460 2600 550 400 1” 1/2 2” 2 x AMS 8
4000 570 625 295 845 515 1400 2440 430 2870 1565 2910 625 440 2” 2” 1/2 2 x AMS 8
5000 580 635 330 855 550 1600 2450 430 2920 1780 2970 655 470 2” 2” 1/2 2 x AMS 8
ANTICORROSION WARRANTY
3 years.
e1 primary inletu1 primary outlete2 secondary inlet
u2 secondary outletr circulation ø1” 1/4
sc drain (ø 1” 1/4 up to2000 l, ø 2” > 2000 l)
sc1 drain ø 1” 1/4AMS Magnesium Anode
S exchanger support with teflon
slide (4000l)t thermometer ø 1/2”
ts thermostat ø 1/2”
H O T W A T E R
H E A T E R S
80 °C 6 bar 120 °C 3 years Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS GASKETS WARRANTY PED
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 6/36
Catalogue 20084
a*3000000
BVX
aø1” 1/4
BVX WATER HEATERS WITH REMOVABLE EXCHANGER AISI 316L
HEAT UP TIME(1) 1 HOUR
LITRES STAINLESS STEEL HEAT OUTPUT DHW PRODUCTION (2) 6p(3) WEIGHT
CODE kW l/h l/10’ l/60’ m H2O kg
300 BVXX 0300 P 18 450 418 793 0,48 65
500 BVXX 0500 P 24 600 671 1171 0,64 103
750 BVXX 0750 P 36 900 1007 1757 1,80 128
1000 BVXX 1000 P 48 1200 1343 2343 2,60 135
1500 BVXX 1500 73 1800 2014 3514 4,50 220
2000 BVXX 2000 97 2400 2686 4686 6,30 250
2500 BVXX 2500 122 3000 3357 5857 8,30 290
3000 BVXX 3000 146 3600 4029 7029 10,00 320
4000 BVXX 4000 195 4800 5371 9371 5,50 475
5000 BVXX 5000 244 6000 6714 11714 9,30 550
Indicative prices and availability are to be confirmed before the order.
(1) Rated time to heat domestic water 10÷60°C(2) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)(3) Exchanger head loss.
LITRES DIMENSIONS mm ø CONNS. ANODES
TYPEA B C ø D E H e1-u1 e2-u2
300 350 375 505 550 1240 1500 1”1/4 1”1/4 TT
500 385 410 540 650 1525 1800 1”1/4 1”1/4 TT
750 405 420 550 800 1545 1870 1”1/4 1”1/2 TT
1000 405 420 550 800 1795 2120 1”1/4 1”1/2 TT
1500 480 530 710 950 2100 2480 1”1/4 1”1/2 TT1
2000 510 560 740 1100 2130 2540 1”1/2 2” TT1
2500 560 610 790 1250 2130 2590 1”1/2 2” TT1
3000 560 610 790 1250 2430 2890 1”1/2 2” TT2
4000 570 625 845 1400 2440 2870 2” 2”1/2 TT2
5000 580 635 855 1600 2450 2920 2” 2”1/2 TT2
USE
Water heater for production and storageof Domestic Hot Water (DHW).Working temperature: max 80°C.Working pressure: max 8 bar.
MATERIAL
Austenitic stainless steel AISI 316L1,4404 EN 10088-2 suitable forcontact with potable water.
EXCHANGER
U-tube bundle expanded on platesuitable for contact with potable water.-Stainless Steel tubes and plate inAISI 316L.Working temperature: max 99°C.Working pressure: max 12 bar.
GASKETS
EPDM food-grade dielectric rubbergaskets code GGE.
INSULATION
VERTICAL VERSION ) 1000 lHard polyurethane, thickness 30mm(PUR30).VERTICAL VERSION * 1500 lSoft polyurethane, thickness 50mm(PUF50).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Electronic impressed-current anodeof titanium for permanent cathodic
protection; not subject to consumption,CORREX is part icular ly ideal forprotection of storage tanks and waterheaters (also if already installed)that must operate under particularlyaggressive physical and chemicalwater conditions.
PACKING
Polythen bubble sheet.
80 °C 8 bar 120 °C 3 years Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS GASKETS WARRANTY PED
ANTICORROSION WARRANTY
3 years.
e1 primary inletu1 primary outlete2 secondary inletu2 secondary outlet
r circulation (ø 3/4” up to 1000 l, ø 1” 1/4 > 1000 l)
sc drain (ø 1” 1/4 up to 2000 l, ø 2” > 2000 l)
a CorrexS exchanger support with teflon
slide (*4000 l)t thermometer ø 1/2”
ts thermostat ø 1/2”
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 7/36
Catalogue 20085
USE
Water heater for production and storageof Domestic Hot Water (DHW).Working temperature: max 60°C.Working pressure: max 6 bar.
ANTICORROSIVE COATING
HOT GALVANIZATION suitable forcontact with potable water accordingto UNI EN ISO 1461 standards.
EXCHANGER
U-tube bundle expanded on plate,suitable for contact with potable water.-Copper tubes Cu-DHP (99,9%).-Galvanized tubes.Working temperature: max 99°C.Working pressure: max 12 bar.
GASKETS
EPDM food-grade dielectric rubbergaskets code GGE.
INSULATION
Soft polyurethane, thickness 50mm(PUF50) .
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ 63, to be periodicallyreplaced.
ACCESSORIES ON REQUEST (page 28)
Electronic impressed-current anode oftitanium for PERMANENT CATHODICPROTECTION.
PACKING
Polythen bubble sheet.
BVZ-CWATER HEATERS WITH REMOVABLE EXCHANGER
GALVANIZED // FLEXIBLE INSULATION
HEAT UP TIME(1) 1 HOUR
LITRES COPPER GALVANIZED HEAT OUTPUT DHW PRODUCTION (2) 6p(3) WEIGHT
CODE CODE kW l/h l/10’ l/60’ m H2O kg
300 BVZR 0300 C BVZZ 0300 C 18 450 418 793 0,48 70
500 BVZR 0500 C BVZZ 0500 C 24 600 671 1171 0,64 105
750 BVZR 0750 C BVZZ 0750 C 36 900 1007 1757 1,80 135
1000 BVZR 1000 C BVZZ 1000 C 48 1200 1343 2343 2,60 160
1500 BVZR 1500 C BVZZ 1500 C 73 1800 2014 3514 4,50 250
2000 BVZR 2000 C BVZZ 2000 C 97 2400 2686 4686 6,30 295
2500 BVZR 2500 C BVZZ 2500 C 122 3000 3357 5857 8,30 330
3000 BVZR 3000 C BVZZ 3000 C 146 3600 4029 7029 10,00 370
4000 BVZR 4000 C BVZZ 4000 C 195 4800 5371 9371 5,50 510
5000 BVZR 5000 C BVZZ 5000 C 244 6000 6714 11714 9,30 595
HORIZONTAL version: codes BOZR-C BOZX-C
(1) Rated time to heat domestic water 10÷60°C(2) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)(3) Exchanger head loss.
LITRES DIMENSIONS mm ø CONNS. ANODES
A B B1 C C1 ø D E ø F H H1 L M N e1 -u1 e2-u 2 TYPE
300 325 350 225 480 355 550 1215 300 1410 715 1450 350 205 1” 1/4 1” 1/4 AMS 1
500 345 370 235 500 365 650 1485 300 1710 825 1760 385 240 1” 1/4 1” 1/4 AMS 4
750 370 395 220 525 350 750 1610 300 1855 910 1900 405 260 1” 1/4 1” 1/2 AMS 4
1000 375 438 218 562 342 800 1915 300 2170 955 2205 420 270 1” 1/4 1” 1/2 AMS 4
1500 435 484 274 666 456 950 2055 380 2400 1155 2380 465 315 1” 1/2 2” 2 x AMS 4
2000 450 500 254 682 436 1100 2070 380 2450 1285 2450 500 350 1” 1/2 2” 2 x AMS 4
2500 510 560 244 742 426 1200 2180 380 2540 1375 2560 530 380 1” 1/2 2” 2 x AMS 4
3000 520 570 229 752 411 1300 2190 380 2570 1460 2600 550 400 1” 1/2 2” 2 x AMS 8
4000 570 625 295 845 515 1400 2440 430 2870 1565 2910 625 440 2” 2” 1/2 2 x AMS 8
5000 580 635 330 855 550 1600 2450 430 2920 1780 2970 655 470 2” 2” 1/2 2 x AMS 8
ANTICORROSION WARRANTY
3 years.
60 °C 6 bar 120 °C 3 years Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS GASKETS WARRANTY PED
BVZ-C BOZ-C
AMSMS
AMSMS*1500500
sc1c1
AMSMS
AMSMS*1500500
r11
ø1” 1/4
ø1” 1/4
e1 primary inletu1 primary outlete2 secondary inletu2 secondary outlet
r circulation (ø 3/4” up to 1000l, ø 1” 1/4 > 1000 L)
sc drain (ø 1” 1/4 up to 2000 l, ø 2” > 2” )
sc1 drain ø 1” 1/4
r1 circulation ø 1” 1/4 AMS Magnesium Anode
S exchanger support withteflon slide (*4000 l)
t thermometer ø 1/2”ts thermostat ø 1/2”
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 8/36
Catalogue 20086
USE
Water heater for production andstorage of Domestic Hot Water (DHW)by means of solar systems, heatpumps, condensate recovery systemsand thermal output integration fromtraditional fuel.Working temperature: max 80°C.Working pressure: max 6 bar.
ANTICORROSIVE COATING
SmaltoPLAST®: thermoplastic coatingsuitable for contact with potable water;grey colour RAL 7038.
EXCHANGER
U-tube bundle expanded on plate,suitable for contact with potable water.-Copper tubes Cu-DHP (99,9%).-Stainless Steel tubes AISI316L.Working temperature: max 99°C.Working pressure: max 12 bar.
GASKETS
EPDM food-grade dielectric rubbergaskets code GGE.
INSULATION
Soft polyurethane, thickness 50mm(PUF50).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ 63, to be periodicallyreplaced.
ACCESSORIES ON REQUEST (page 28)
Electronic impressed-current anode oftitanium for PERMANENT CATHODICPROTECTION.
PACKING
Polythen bubble sheet.
SOLAR INTEGRATED WATER HEATERS
WITH REMOVABLE EXCHANGER
(1) Power with solar circuit 75÷65°C and domestic circuit 10÷45°C(2) Power with solar circuit 60÷50°C and domestic circuit 10÷40°C(3) Power with solar circuit 45÷35°C and domestic circuit 10÷30°C(4) Power with integration circuit 80÷70°C and domestic circuit 10÷45°C
ei integration inletui integration outletes solar inletus solar outlete2 secondary inletu2 secondary outlet
r circulation (ø 3/4” up to 1000 l, ø 1” 1/4 > 1000 l)
sc drain (ø 1” 1/4 up to 2000 l, ø 2” > 2000 l)
AMS Magnesium AnodeI Integration exchanger
S Exchanger support (4000l)S1-S2 Solar exchanger
sd probe ø 1/2”t thermometer ø 1/2”
tm thermostat of minimum ø 1/2”
LITRES DIMENSIONS mm ø CONNS. ANODES
A B B1 B2 C C1 C2 ø D E ø F ø FI H es-us ei-ui e2-u2 TYPE
300 325 328 - 948 510 - 1083 550 1215 380 300 1410 1” 1/2 1” 1/4 1” 1/4 AMS 1
500 345 363 - 1218 545 - 1353 650 1485 380 300 1710 1” 1/2 1” 1/4 1” 1/4 AMS 4
750 370 420 - 1343 640 - 1478 750 1610 430 300 1855 2” 1” 1/4 1” 1/2 AMS 4
1000 375 425 - 1598 645 - 1730 800 1915 430 300 2170 2” 1” 1/4 1” 1/2 AMS 4
1500 435 465 - 1878 685 - 2013 950 2055 430 300 2400 2” 1” 1/4 2” 2 x AMS 4
2000 450 500 950 1818 682 1132 1942 1100 2070 380 300 2450 1” 1/2 1” 1/4 2” 2 x AMS 4
3000 520 570 1010 2050 752 1192 2232 1300 2190 380 380 2570 1” 1/2 1” 1/2 2” 2 x AMS 8
4000 570 633 1138 2073 838 1343 2278 1400 2440 430 380 2870 2” 1” 1/2 2” 1/2 2 x AMS 8
5000 580 643 1148 2083 848 1353 2288 1600 2450 430 380 2920 2” 1” 1/2 2” 1/2 2 x AMS 8
LITRES COPPER STAINLESS STEEL EXCHANGER HEAT OUTPUT kW WEIGHT
CODE CODICE S1 S2 I
(1) (2) (3) (1) (2) (3) (4) kg
300 BSIR 0300 BSIX 0300 48 32 16 - - - 12 95
500 BSIR 0500 BSIX 0500 72 48 24 - - - 18 130
750 BSIR 0750 BSIX 0750 96 64 32 - - - 18 175
1000 BSIR 1000 BSIX 1000 120 80 40 - - - 24 200
1500 BSIR 1500 BSIX 1500 168 112 56 - - - 36 285
2000 BSIR 2000 BSIX 2000 96 64 32 96 64 32 48 330
3000 BSIR 3000 BSIX 3000 144 96 48 144 96 48 73 420
4000 BSIR 4000 BSIX 4000 192 128 64 192 128 64 97 575
5000 BSIR 5000 BSIX 5000 240 160 80 240 160 80 122 665
BSI
ANTICORROSION WARRANTY
3 years.
80 °C 6 bar 120 °C 5 yearsL. 296/2006
Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS GASKETS WARRANTY PED
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 9/36
Catalogue 20087
Ø F
BVS-VA BOS-VA
AMS
AMS*1500
AMS
AMS*1500
r1
sc1
BVS-VAOVERHEATED WATER / STEAM WATER HEATERS
LITRES COPPER STAINLESS STEEL HEAT OUTPUT kW (1) WEIGHT
CODE CODE 0,5 bar
111,6°C
1 bar
120,4°C
2 bar
133,7°C
4 bar
152°C
6 bar
165°C
8 bar
175,4°C
10 bar
184,1°C
12 bar
191,7°C kg
300 (3) BVSR 0300 VA BVSX 0300 VA 35 38 44 52 57 62 65 68 65
500 (3) BVSR 0500 VA BVSX 0500 VA 47 52 59 70 77 83 88 91 100
750 BVSR 0750 VA BVSX 0750 VA 70 77 89 104 115 124 131 137 125
1000 BVSR 1000 VA BVSX 1000 VA 94 103 118 139 154 165 175 182 150
1500 BVSR 1500 VA BVSX 1500 VA 140 155 177 208 230 248 262 274 230
2000 BVSR 2000 VA BVSX 2000 VA 187 206 237 277 307 330 350 365 270
3000 BVSR 3000 VA BVSX 3000 VA 285 314 360 422 467 502 532 555 345
4000 BVSR 4000 VA BVSX 4000 VA 378 417 478 561 621 667 * * 475
5000 BVSR 5000 VA BVSX 5000 VA 476 525 601 705 781 839 * * 550
4000 (2) BVSR 4000 D VA BVSX 4000 D VA 756 834 956 1122 1242 1334 * * 545
5000 (2) BVSR 5000 D VA BVSX 5000 D VA 952 1050 1202 1410 1562 1678 * * 630
HORIZONTAL version codes BOSR-VA BOSX-VA
(1) - The reported power is valid f or steam water heaters; for overheated water heaters decrease by 10%. For intermediate pressures and temperatures, power can beobtained by linear interpolation.
-DHW production 10÷45°C with storage at 60°C: continuous (l/h)=kW•24; first 10 minutes peak (l/10’) =kW•4+V•1,14; first hour peak (l/60’)=kW•24+V•1,14, V= tank volume (litres)
- Heating up 10÷60°C in minutes = V·2,8/kW(2) D= Split exchanger
LITRES DIMENSIONS mm ø CONNS. ANODES
A B B1 C C1 ø D ø De E ø F H H1 L M N e 1-u 1 e 2-u2 TYPE
300 325 350 225 480 355 550 620 1215 300 1410 715 1450 350 205 1” 1/4 1” 1/4 AMS 1500 345 370 235 500 365 650 720 1485 300 1710 825 1760 385 240 1” 1/4 1” 1/4 AMS 4
750 370 395 220 525 350 750 820 1610 300 1855 910 1900 405 260 1” 1/4 1” 1/2 AMS 4
1000 375 438 218 562 342 800 870 1915 300 2170 955 2205 420 270 1” 1/4 1” 1/2 AMS 4
1500 435 484 274 666 456 950 1050 2055 380 2400 1155 2380 465 315 1” 1/2 2” 2 x AMS 4
2000 450 500 254 682 436 1100 1200 2070 380 2450 1285 2450 500 350 1” 1/2 2” 2 x AMS 4
3000 520 570 229 752 411 1300 1400 2190 380 2570 1460 2600 550 400 1” 1/2 2” 2 x AMS 8
4000 570 625 295 845 515 1400 1500 2440 430 2870 1565 2910 625 440 2” 2” 1/2 2 x AMS 8
5000 580 635 330 855 550 1600 1700 2450 430 2920 1780 2970 655 470 2” 2” 1/2 2 x AMS 8
e1 primary inletu1 primary outlete2 secondary inlet
u2 secondary outletr circulation (ø 3/4” up to 1000l,
ø 1” 1/4 > 1000 l)sc drain (ø 1” 1/4 up tp 2000 l,
ø 2” > 2000 l)sc1 drain ø 1” 1/4
r1 circulation ø 1” 1/4AMS Magnesium Anode
S Teflon exchanger support
(4000l)t thermometer ø 1/2”
tr thermocontrollerts thermostat ø 1/2”
USE
Water heater for production and storageof Domestic Hot Water (DHW).Design temperature: 99°C.Working temperature for validity ofanticorrosion warranty: max 80°C.Working pressure: max 6 bar.
ANTICORROSIVE COATINGSmaltoPLAST®: thermoplastic coatingsuitable for contact with potable water;grey colour RAL 7038.
EXCHANGER
U-tube bundle expanded on plate,suitable for contact with potable water.-Copper tubes Cu-DHP (99,9%).-Stainless Steel tubes AISI 316L.Working temperature: max see table.Working pressure: max see table.
GASKETS
Silicon food-grade dielectric rubbergaskets code GGS.
INSULATION
VERTICAL VERSION ) 1000 l:Hard polyurethane, thickness 30mm(PUR30).VERTICAL VERSION * 1500 l andHORIZONTAL VERSION:Soft polyurethane, thickness 50mm(PUF50).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ 63, to be periodicallyreplaced.
ACCESSORIES ON REQUEST (page 28)
Electronic impressed-current anode oftitanium for PERMANENT CATHODICPROTECTION.
PACKING
Polythen bubble sheet.
ANTICORROSION WARRANTY
3 years.
S T E A M W A
T E R
H E A T E R
S
80 °C 6 bar 200 °C 3 years PED Art. 3.3Dir. n. 97/23/EEC
CECat. 1ª form A
Dir. n. 97/23/EEC
WATER HEATERS GASKETS WARRANTY STORAGE TANK HEAT EXCHANGER
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 10/36
Catalogue 20088
BRVRAPID WATER HEATERS WITH FIXED COIL
GLASS LINED FLOOR STANDING
LITRES CODE EXCHANGER
m2
HEAT OUTPUT
kW
HEAT UP TIME(1)min
DHW PRODUCTION (2) 6p(3) WEIGHT
l/h l/10’ l/60’ m H2O kg
110 BRV 110 0,8 25 15 614 243 755 0,50 45
150 BRV 150 0,8 25 20 614 295 807 0,50 50
200 BRV 200 1,3 42 16 1032 429 1289 1,50 65
300 BRV 300 1,3 56 18 1376 615 1762 0,60 85
500 BRV 500 2,2 74 23 1818 946 2461 1,60 130
800 BRVF 0800 2,3 95 28 2334 1417 3362 2,60 190
1000 BRVF 1000 2,7 130 26 3194 1817 4479 5,40 215
(1) Time to heat domestic water 10÷60°C(2) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)(3) Exchanger head loss.
LITRES DIMENSIONS mm ø CONNS. ANODESTYPEA B C ø De E H e1-u1 e2-u2
110 140 265 645 520 740 950 1” 1/4 1” 1/4 2 x AMS 5
150 140 265 645 520 775 1120 1” 1/4 1” 1/4 2 x AMS 5200 150 290 830 570 920 1220 1” 1/4 1” 1/4 2 x AMS 5
300 155 295 835 670 930 1230 1” 1/4 1” 1/4 2 x AMS 5
500 175 345 1085 720 1205 1680 1” 1/4 1” 1/4 2 x AMS 5
800 245 375 1225 870 1370 1830 1” 1/2 1” 1/2 2 x AMS 1
1000 245 375 1430 870 1600 2080 1” 1/2 1” 1/2 2 x AMS 1
e1 primary inletu1 primary outlete2 secondary inletu2 secondary outlet
r circulation ø 1”sc drain
AMS Magnesium Anodewith welded plug
F Blind flange F 280 Bt thermometer ø 1/2”
ts thermostat ø 1/2”
USE
Water heater for rapid production andstorage of Domestic Hot Water (DHW).Working temperature: max 90°C.Working pressure: max 8 bar.
ANTIOCORROSIVE COATING
GLASS-LINING: inorganic coating(VITREOUS ENAMEL) heated at950°C, suitable for potable wateraccording to DIN 4753.3 standards.
EXCHANGER
Fixed spiral coil.Working temperature: max 99°C.Working pressure: max 12 bar.
INSULATION
It is completely insulated with hardpolyurethane thickness 30mm.(PUR30)
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ63, complete withwelded plug.
Smaltiflon steel flange.
PACKING
110÷200l carton box.300÷1000l pallet + Polythen bubblesheet.
ø D
BRV BRVF
BRVF
F 280 B
ANTICORROSION WARRANTY
5 years.
90 °C 8 bar 120 °C 5 years Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS GASKETS WARRANTY PED P
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 11/36
Catalogue 20089
R A P I D W A T E R
H E A T E R S
DRVSOLAR WATER HEATERS WITH FIXED DOUBLE COIL
GLASS LINED FLOOR STANDING
LITRES DIMENSIONS mm ø CONNS. ANODES
A B C ø De E G H L es-us ei-ui e2-u2 TYPE
300 225 300 740 620 840 970 1360 1100 1” 1” 1” 1/4 AMS 5
500 240 315 865 720 980 1175 1640 1365 1” 1” 1” 1/4 AMS 5
800 345 445 995 870 1115 1290 1850 1465 1” 1/2 1” 1/2 1” 1/2 AMS 1
1000 345 445 1145 870 1265 1440 2100 1615 1” 1/2 1” 1/2 1” 1/2 AMS 1
ei integration inletui integration outletes solar inletus solar outlete2 secondary inletu2 secondary outlet
r circulation ø 3/4”sc drai n
AMS Magnesium Anodewith welded plug
I Integration exchangerS Solar exchanger
sd probe ø 1/2”t thermometer ø 1/2”
tm thermostat ø 1/2”
(1) Time to heat the whole content of domestic water from 10 to 60°C(2) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)(3) Time to heat from 10 to 60°C the 40% of domestic water, i.e. the volume heated by the integration exchanger.
USE
Water heater for rapid productionand storage of Domestic Hot Water(DHW) through solar energy and heatintegration from traditional fuel.Working temperature: max 90°C.Working pressure: max 8 bar.
ANTICORROSIVE COATING:
GLASS-LINING: inorganic coating(VITREOUS ENAMEL) heated at950°C, suitable for potable wateraccording to DIN 4753.3 standards.
EXCHANGER
Fixed spiral coil.Working temperature: max 99°C.Working pressure: max 12 bar.
INSULATION
It is completely insulated with hardpolyurethane thickness 30mm (PUR30).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ63, complete withwelded plug.
PACKING
Pallet+Polythen bubble sheet.
ø D
DRV
ANTICORROSION WARRANTY
5 years.
LITRES CODE SOLAR COIL INTEGRATION COIL WEIGHT
kg
EXCHANGER
m2
HEATOUTPUT
kW
HEAT UP(1)mi n
DHW PRODUCTION (2) EXCHANGER
m2
HEATOUTPUT
kW
HEAT UP(3)
mi n
DHW PRODUCTION (2)
l/h l/10’ l/60’ l/h l/10’ l/60’
300 DRV 0300 1,1 37 21 909 537 1295 0,6 22 19 540 261 711 80
500 DRV 0500 1,6 57 23 1400 876 2043 1,1 37 19 909 436 1194 125
800 DRV 0800 2,2 71 30 1744 1318 2772 1,2 44 25 1081 637 1538 185
1000 DRV 1000 2,7 95 28 2334 1674 3619 1,2 44 32 1081 751 1652 200
AMS
90 °C 6 bar 5 yearsL. 296/2006
Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS WARRANTY PED
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 12/36
Catalogue 200810
BRMVRAPID WATER HEATERS WITH FIXED COIL
GLASS LINED WALL MOUNTED
LITRES CODE EXCHANGER HEAT OUTPUT HEAT UP TIME(1)min
DHW PRODUCTION (2) 6p(3) WEIGHT
m2 kW l/h l/10’ l/60’ m H2O kg
100 BRMV 100 0,6 18 16 442 202 571 0,25 37
150 BRMV 150 0,8 25 20 614 295 807 0,50 47
200 BRMV 200 0,9 31 19 761 383 1018 0,95 57
300 BRMV 300 1,2 41 22 1007 553 1393 2,2 70
LITRES DIMENSIONS mm ø CONNS. ANODES
A B C ø De E G H e1-u1 e2-u2 TYPE
100 170 275 260 470 380 250 900 1” 1” AMS 5
150 170 275 260 520 530 275 1050 1” 1” AMS 5200 170 275 260 520 820 275 1340 1” 1” AMS 5
300 175 275 260 570 840 300 1360 1” 1/4 1” 1/4 AMS 1
(1) Time to heat domestic water 10÷60°C(2) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)(3) Exchanger head loss.
USE
Water heater for rapid production andstorage of Domestic Hot Water (DHW).Working temperature: max 90°C.Working pressure: max 8 bar.
ANTICORROSIVE COATING
GLASS-LINING: inorganic coating(VITREOUS ENAMEL) heated at 950°C,suitable for potable water according toDIN 4753.3 standards.
EXCHANGER
Fixed spiral coil.Working temperature: max 99°C.Working pressure: max 12 bar.
INSULATION
It is completely insulated with hardpolyurethane thickness 30mm (PUR30).
EXTERNAL JACKET
SCAI white colour RAL 9010.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ63, complete withwelded plug.
STIRRUP BRACKETS
PACKING
Carton box.
ts
ts
t
t
ø D
ANTICORROSION WARRANTY
5 years.
CM
AMS
90 °C 6 bar 5 years Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS WARRANTY PED
e1 primary inletu1 primary outlete2 secondary inletu2 secondary outlet
AMS Magnesium Anodewith welded plug
CM Brackets for wall installationt thermometer ø 1/2”
ts thermostat ø 1/2”
VERTICAL installation: at wall or on basement HORIZONTAL installation: at wall only
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 13/36
Catalogue 200811
BISSOLAR INTEGRATED WATER HEATERS
WITH REMOVABLE EXCHANGER
LITRES CODE HEAT OUTPUT
kW
HEAT UP TIME(1)min
DHW PRODUCTION (2) WEIGHT
kgl/h l/10’ l/60’
100 BIS 100 11,6 26 285 190 428 35
150 BIS 150 16,2 28 399 280 613 46
200 BIS 200 20,1 30 494 367 779 60
300 BIS 300 24,0 37 589 526 1017 75
(1) Time to heat domestic water 10÷60°C(2) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)
LITRES DIMENSIONS mm ø CONNS. ANODES
A B C ø De E G H e1-u1 e2-u2 TYPE
100 170 275 260 470 380 250 900 1” 1” AMS 5
150 170 275 260 520 530 275 1050 1” 1” AMS 5
200 170 275 260 520 820 275 1340 1” 1” AMS 5
300 175 275 260 610 840 320 1360 1” 1/4 1” 1/4 AMS 1
USE
Water heater for production and storageof Domestic Hot Water (DHW).Working temperature: max 60°C.Working pressure: max 6 bar.
ANTICORROSIVE COATING
SMALTIFLON: organic powder coatingsuitable for potable water; green colourRAL 6003.
EXCHANGER
External double wall can also be usedfor natural circulation.Working temperature: max 99°C.Working pressure: max 3 bar*.
*only with sanitary circuit previouslyfilled up with water at 6 bar.
INSULATION
It is completely insulated with hardpolyurethane thickness 30mm (PUR30).
EXTERNAL JACKET
SCAI white colour RAL 9010
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ63, complete withwelded plug.
STIRRUP BRACKETS
PACKING
Carton box.
BIS
installazione VERTICALE: a parete o pavimento installazione ORIZZONTALE: solo a pareteANTICORROSION WARRANTY
3 years.
CM
AMS
60 °C 6 bar 3 years Art. 3.3Dir. n. 97/23/EEC
WATER HEATERS WARRANTY PED
e1 primary inletu1 primary outlete2 secondary inletu2 secondary outlet
AMS Magnesium Anodewith welded plug
CM Brackets for wall installation
VERTICAL installation: at wall or on basement HORIZONTAL installation: at wall only
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 14/36
Catalogue 200812
s c u p
ACS-P ACSO-P
ts
moveble supports
ACSDOMESTIC HOT WATER STORAGE TANKS
SmaltoPLAST ®
// RIGID INSULATION
LITRES CODE DIMENSIONS mm ø CONNS. ANODES WEIGHT
A B C ø De H H1 L N ac-af TYPE kg
200 ACS 0200 P 275 665 1165 520 1380 655 1270 185 1” 1/4 AMS 1 40
300 ACS 0300 P 295 685 1185 620 1410 755 1320 205 1” 1/4 AMS 1 50
500 ACS 0500 P 325 715 1465 720 1710 850 1600 240 1” 1/4 AMS 4 85
750 ACS 0750 P 345 835 1585 820 1855 945 1740 260 1” 1/2 AMS 4 110
1000 ACS 1000 P 355 895 1895 870 2170 990 2060 270 1” 1/2 AMS 4 135
1500 ACS 1500 P 435 955 2055 1020 2400 1155 2285 320 2” 2xAMS 4 210
2000 ACS 2000 P 450 1040 2070 1170 2450 1285 2355 350 2” 2xAMS 4 250
HORIZONTAL version: code AC SO-P.
USE
Storage of Domestic Hot Water (DHW).Working temperature: max 80°C.Working pressure: max 8 bar.
ANTICORROSIVE COATING
SmaltoPLAST®: thermoplastic coating
suitable for contact with potable water;grey colour RAL 7038.
INSULATION
Hard polyurethane thickness 30mm(PUR30).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ63, complete withwelded plug
ACCESSORIES ON REQUEST (page 28)
Electronic impressed-current anode oftitanium for PERMANENT CATHODICPROTECTION.
PACKING
Polythen bubble sheet.
ac hot wateraf cold waterep preparatory inlet ø 1”1/4up preparatory outlet ø 1”1/4
r circulation (ø 3/4” up to 1000 l, ø 1”1/4 >1000l)
sc drain
AMS Magnesium Anode with welded plugt thermometer ø 1/2”
ts thermostat ø 1/2”
ANTICORROSION WARRANTY
3 years.
80 °C 8 bar 3 years Art. 3.3Dir. n. 97/23/EEC
STORAGE TANKS WARRANTY PED
ACS F
ACSFwith inspection flange and blind plate not suitablefor exchanger installation.
øF=300 200÷1000 litres øF=380 1500÷5000 litres
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 15/36
Catalogue 200813ACSOACS
r1
sc1
ACSDOMESTIC HOT WATER STORAGE TANKS
SmaltoPLAST ®
/ / FLEXIBLE INSULATION
AMS Magnesium Anode with welded plugt thermometer ø 1/2”
ts thermostat ø 1/2”sc1 drain ø 1” 1/4
LITRES CODE DIMENSIONS mm ø CONNS. ANODES WEIGHT
A B C ø D H H1 L N ac-af TYPE kg
1500 ACS 1500 435 955 2055 950 2400 1155 2285 315 2” 2 x AMS 4 200
2000 ACS 2000 450 1040 2070 1100 2450 1285 2355 350 2” 2 x AMS 4 235
2500 ACS 2500 510 1100 2180 1200 2540 1375 2410 380 2” 2 x AMS 4 270
3000 ACS 3000 520 1110 2190 1300 2570 1460 2450 400 2” 2 x AMS 8 300
4000 ACS 4000 570 1240 2440 1400 2870 1565 2720 440 2” 1/2 2 x AMS 8 400
5000 ACS 5000 580 1250 2450 1600 2920 1780 2780 470 2” 1/2 2 x AMS 8 470
HORIZONTAL version: code ACSO
USE
Storage of Domestic Hot Water (DHW).Working temperature: max 80°C.Working pressure: max 6//8 bar.
ANTICORROSIVE COATING
SmaltoPLAST®: thermoplastic coa-
ting suitable for contact with potablewater; grey colour RAL 7038.
INSULATION
Soft polyurethane thickness 50mm(PUF50).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ63, complete withwelded plug.
ACCESSORIES ON REQUEST (page 28)
Electronic impressed-current anode oftitanium for PERMANENT CATHODICPROTECTION,
PACKING
Polythen bubble sheet.
ANTICORROSION WARRANTY
3 years.
H O T W A T E R
S T O R A G E T A
N K S
ac hot wateraf cold water
ep preparatory inlet ø 1”1/4up preparatory outlet ø 1”1/4
r circulation (ø 3/4” up to 1000 l, ø 1”1/4 > 1000l)
sc drain (ø 1” 1/4 up to 2000 l,
ø 2” > 2000l)r1 circulation ø 1” 1/4
80 °C 6//8 bar 3 years Art. 3.3Dir. n. 97/23/EEC
STORAGE TANKS WARRANTY PED
ACS F
ACSFwith inspection flange and blind plate not suitablefor exchanger installation.
øF=380
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 16/36
Catalogue 200814
USE
Storage of Domestic Hot Water (DHW).Working temperature: max 90°C.Working pressure: max 6//8 bar.
ANTICORROSIVE COATING
GLASS-LINING: inorganic coating(VITREOUS ENAMEL) heated at 950°C,suitable for potable water according toDIN 4753.3 standards.
INSULATION
Hard polyurethane thickness 30mm(PUR30).
EXTERNAL JACKET
SCAI yellow colour RAL 1007.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ63, complete withwelded plug.
CORREX ON REQUEST (PAGE 28)
Electronic impressed-current anode oftitanium for PERMANENT CATHODICPROTECTION.
PACKING
Polythen bubble sheet.
ACV
s c u p
ACS-P ACSO-P
ts
moveble supports
LITRES CODE DIMENSIONS mm ø CONNS ANODES WEIGHT
A B C ø De H H1 L N ac-af TYPE kg
200 ACV 0200 275 665 1165 520 1380 655 1270 185 1” 1/4 AMS 1 40
300 ACV 0300 295 685 1185 620 1410 755 1320 205 1” 1/4 AMS 1 55
500 ACV 0500 325 715 1465 720 1710 850 1600 240 1” 1/4 AMS 4 95
750 ACV 0750 345 835 1585 820 1855 945 1740 260 1” 1/2 AMS 4 115
1000 ACV 1000 355 895 1895 870 2170 990 2060 320 1” 1/2 AMS 4 140
HORIZONTAL version: code ACVO
ac hot wateraf cold waterep preparatory inlet ø 1”1/4up preparatory outlet ø 1”1/4
r circulation (ø 3/4” up to 1000 l)sc drain ø1”1/4
AMS Magnesium Anode with welded plugt thermometer ø 1/2”
ts thermostat ø 1/2”
DOMESTIC HOT WATER STORAGE TANKS
GLASS LINED // RIGID INSULATION
ACV ACVO
90 °C 6//8 bar 5 years Art. 3.3Dir. n. 97/23/EEC
STORAGE TANKS WARRANTY PED
ANTICORROSION WARRANTY
5 years.
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 17/36
Catalogue 200815ACX
a3000
ACXDOMESTIC HOT WATER STORAGE TANKS
STAINLESS STEEL // RIGID INSULATION
r1 circulation ø 1” 1/4a Corrext thermometer ø 1/2”
ts thermostat ø 1/2”sc1 drain ø 1” 1/4
LITRES CODE DIMENSIONS mm ø CONNS. ANODES WEIGHT
A B C ø D H ac-af TYPE kg
300 ACX 0300 350 730 1240 550 1500 1” 1/4 TT 45
500 ACX 0500 385 755 1525 650 1800 1” 1/4 TT 80
750 ACX 0750 405 895 1545 800 1870 1” 1/2 TT 95
1000 ACX 1000 405 895 1795 800 2120 1” 1/2 TT 110
1500 ACX 1500 480 1000 2100 950 2480 1” 1/2 TT1 180
2000 ACX 2000 510 1040 2130 1100 2540 2” TT1 210
2500 ACX 2500 560 1100 2130 1250 2590 2” TT1 250
3000 ACX 3000 560 1100 2430 1250 2890 2” TT2 268
4000 ACX 4000 570 1240 2440 1400 2870 2” 1/2 TT2 400
5000 ACX 5000 580 1250 2450 1600 2920 2” 1/2 TT2 470
Indicative prices and availability are to be confermed before the order.
USE
Storage of Domestic Hot Water (DHW).Working temperature: max 80°C.Working pressure: max 8 bar.
ANTICORROSIVE COATING
Austenitic stainless steel AISI316L1.4404 EN 10088-2 suitable forcontact with potable water.
INSULATION
VERTICAL VERSION ) 1000 lHard polyurethane, thickness 30mm(PUR30).VERTICAL VERSION * 1500 lSoft polyurethane, thickness 50mm(PUF50).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Electronic impressed-current anode forPERMANENT CATHODIC PROTECTION;not subject to consumption, CORREXis particularly ideal for protection ofstorage tanks and water heaters (alsoif already installed) that must operateunder particularly aggressive physicaland chemical water conditions.
PACKING
Polythen bubble sheet.
ANTICORROSION WARRANTY
3 years.
ac hot wateraf cold water
ep preparatory inlet ø 1”1/4up preparatory outlet ø 1”1/4
r circulation (ø 3/4” up to 1000 l, ø 1”1/4 >1000l)
sc drain (ø 1” 1/4 up to 2000 l, ø 2” >2000l)
80 °C 8 bar 3 years Art. 3.3Dir. n. 97/23/EEC
STORAGE TANKS WARRANTY PED
ACX F
AISI 316L
ACXFwith inspection flange and blind plate not suitablefor exchanger installation.
øF=300 200÷1000 litres øF=380 1500÷5000 litres
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 18/36
Catalogue 200816
ANTICORROSION WARRANTY
2 years.
ACZ-E
USE
Storage of Domestic Hot Water (DHW).Working temperature: max 60°C.Working pressure: max 6 bar.
ANTICORROSIVE COATING
HOT-DEEP GALVANIZATION accordingto UNI EN ISO 1461 standards suitablefor contact with potable water.
INSULATION
Soft polyurethane thickness 50mm(PUF50).
EXTERNAL JACKET
SCAI grey colour RAL 7038.
CATHODIC PROTECTION
Magnesium Anodes (AMS) made ofspecial alloy AZ63, complete withwelded plug.
PACKING
Polythen bubble sheet.
Without insulation ACZ.This tank, even if supplied withoutinsulation, must be thermal insulatedbefore use.
ACZ
DOMESTIC HOT WATER STORAGE TANKS
GALVANIZED // FLEXIBLE INSULATION
ACZ-E ACZO-E
sc1
r1
LITRES 200÷1000 LITRES 1500÷5000
ac hot wateraf cold water
ep preparatory inlet ø 1”1/4up preparatory outlet ø 1”1/4
r circulation (ø3/4” up to 1000 l)sc drain (ø 1” 1/4 up to 2000 l,
ø 2” > 2000 l)
r1 circulation ø 1” 1/4sc1 drain ø 1” 1/4
AMS Magnesium Anode ø 1” 1/4t thermometer ø 1/2”
ts thermostat ø 1/2”sc1 drain ø 1” 1/4
LITRES CODE DIMENSIONS mm ø CONNS.
ac-af
ANODES
TYPE
WEIGHT
kgB C ø D ø De H1 L N
200 ACZ 0200 685 1195 450 550 655 1270 185 1” 1/4 AMS 1 35
300 ACZ 0300 700 1215 550 650 755 1320 205 1” 1/4 AMS 1 45
500 ACZ 0500 735 1485 650 750 850 1600 240 1” 1/4 AMS 4 80
750 ACZ 0750 860 1610 750 850 945 1740 260 1” 1/2 AMS 4 100
1000 ACZ 1000 915 1915 800 900 990 2060 270 1” 1/2 AMS 4 125
1500 ACZ 1500 955 2055 950 1050 1155 2235 315 2” 2xAMS 4 200
2000 ACZ 2000 1040 2070 1100 1200 1285 2305 350 2” 2xAMS 4 235
2500 ACZ 2500 1100 2180 1200 1300 1375 2410 380 2” 2xAMS 4 285
3000 ACZ 3000 1110 2190 1300 1400 1460 2450 400 2” 2xAMS 8 300
4000 ACZ 4000 1240 2440 1400 1500 1565 2720 440 2” 1/2 2xAMS 8 475
5000 ACZ 5000 1250 2450 1600 1700 1780 2780 470 2” 1/2 2xAMS 8 565
HORIZONTAL version: code ACZO.
60 °C 6 bar 2 years Art. 3.3Dir. n. 97/23/EEC
STORAGE TANKS WARRANTY PED
LITRES CODE DIMENSIONS mm ø CONNS.
ac-af
ANODES
TYPE
WEIGHT
kgA B C ø D ø De H
200 ACZ 0200 E 295 685 1195 450 550 1480 1” 1/4 AMS 1 40
300 ACZ 0300 E 310 700 1215 550 650 1510 1” 1/4 AMS 1 50
500 ACZ 0500 E 345 735 1485 650 750 1810 1” 1/4 AMS 4 85
750 ACZ 0750 E 370 860 1610 750 850 1955 1” 1/2 AMS 4 110
1000 ACZ 1000 E 375 915 1915 800 900 2270 1” 1/2 AMS 4 140
1500 ACZ 1500 E 435 955 2055 950 1050 2500 2” 2xAMS 4 210
2000 ACZ 2000 E 450 1040 2070 1100 1200 2550 2” 2xAMS 4 260
2500 ACZ 2500 E 510 1100 2180 1200 1300 2640 2” 2xAMS 4 295
3000 ACZ 3000 E 520 1110 2190 1300 1400 2670 2” 2xAMS 8 330
4000 ACZ 4000 E 570 1240 2440 1400 1500 2870 2” 1/2 2xAMS 8 440
5000 ACZ 5000 E 580 1250 2450 1600 1700 2920 2” 1/2 2xAMS 8 515
HORIZONTAL version: code ACZO-E.
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 19/36
Catalogue 200817
PUW
USEStorage and production of heatingwater.Used to exploit discontinuousfunctioning of heating units such assolid-fuel boilers stoves or furnaces,or in low water-content systemsto limit burner operation or for theadditional exploitation of solar system
or heat pumps.Working temperature: max 90°CWorking pressure: max 3 bar
EXCHANGERFixed spiral coil in carbon steel.Working temperature: max 99°C.Working pressure: max 12 bar.
PACKING
Polythen bubble sheet.
PUHEAT ACCUMULATORS
PUWPU
ACCESSORY ON REQUEST (1)
CODE TECHNICAL DATA
PUF Blind flange F280B provided with gaskets and screws (see page 8)
Can be supplied during construction only.
USE
Storage of heating water.Used to exploit discontinuous functioningof heating units such as solid-fuel boilersstoves or furnaces, or in low water-contentsystems to limit burner operation.Working temperature: max 90°C.Working pressure: max 3 bar
ANTICORROSIVE COATING
- Inside: untreated steel- Outside: anti-rust paint black colour.
INSULATION
Soft polyurethane thickness 100 mm(PUF100).
EXTERNAL JACKET
SCAI orange colour RAL 2002.
F Blind flange (on request)sa a ir ven tsd probe ø 1/2”
t thermometer ø 1/2”es solar inlet ø 1”us solar outlet ø 1”
mc boiler flowrc boiler returnmi heating system flowri heating system return
rp floor heating system returnsc drain
90 °C 3 bar 1 year Art. 3.3Dir. n. 97/23/EEC
HEAT ACCUMULATOR WARRANTY PED
LITRES HEAT ACCUMULATOR HEAT ACCUMULATOR WITH COIL
CODE WEIGHT kg CODESOLAR COIL
m2WEIGHT kg
300 PU 0300 55
500 PU 0500 85 PUW 0500 1,5 110
800 PU 0800 120 PUW 0800 2,4 155
1000 PU 1000 135 PUW 1000 2,4 170
1500 PU 1500 210 PUW 1500 2,4 250
2000 PU 2000 235
3000 PU 3000 300
LITRES DIMENSIONS mm ø CONNS.
A B C ø D E H L mc-rc mi-ri-rp
300 310 600 1200 550 - 1500 900 1” 1/4 1” 1/4
500 340 620 1470 650 740 1800 1270 1” 1/4 1” 1/4
800 370 750 1750 750 970 2080 1310 1” 1/2 1” 1/21000 375 760 1900 800 975 2250 1590 1” 1/2 1” 1/2
1500 420 880 2040 950 1020 2430 1760 1” 1/2 1” 1/2
2000 435 900 2035 1100 - 2470 1930 1” 1/2 1” 1/2
3000 510 1040 2170 1300 - 2640 2400 1” 1/2 1” 1/2
C O M B I N E D
ANTICORROSION WARRANTY1 year.
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 20/36
Catalogue 200818
KMB
ei
ui
A
C 1
L
M
KMB
COMBINED SOLAR HEAT ACCUMULATORS WITH GLASS LINED
DOMESTIC STORAGE TANK AND DOUB LE EXCHAN GER
LITRES (1) CODE INTEGRATION
COIL
m2
SOLAR
COIL
m2
HOT WATER HEATER PERFORMANCES WEIGHT
kg
HEAT OUTPUT
kW
HEAT UP TIME(2)min
DHW PRODUCTION (3)
l/h l/10’ l/60’
500/110 KMB 0500 110 1,5 1,5 36 15 885 340 1078 170
800/150 KMB 0800 150 2,4 2,4 36 15 885 340 1078 250
1000/200 KMB 1000 200 2,4 2,4 45 16 1106 441 1363 270
1500/300 KMB 1500 300 2,4 2,4 50 21 1229 590 1614 360
(1) Total capacity / domestic storage t ank capacity(2) Time to heat domestic water 10 ÷ 60°C(3) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10’); first hour peak (l/60’)
es solar in letus solar outle tei integration inletui integration outlete2 entrata secondariou2 uscita secondario
r circulation ø 3/4”mc boiler flowrc boiler returnmi heating system flowri heating system return
rp floor heating system returnsc drain
AMS 1 Magnesium Anode with welded plugsa air vent ø 1/2”sd probe ø 1/2”
t thermometer ø 1/2”
USE
− Storage and production of heatingwater− Production and storage of DomesticHot Water (DHW)This equipment is used to benefit bydiscontinuous functioning of heating
units such as solid-fuel boilers, stovesor furnaces, or in low water-contentsystems to limit burner operationand for the additional exploit of solarsystems and heat pumps.Working temperature:− Heat accumulator: max 90°C.− Domestic storage tank: max 90°C.Working pressure:− Heat accumulator: max 3 bar.− Domestic storage tank: max 6 bar.
EXCHANGER
Fixed spiral coil.Working temperature: max 99°C.Working pressure: max 12 bar.
ANTICORROSIVE COATING
− Heat accumulator:INSIDE: untreated carbon steel.OUTSIDE: anti-rust paint black colourRAL 9011.− Domestic storage tank:GLASS LINING: inorganic coating(VITREOUS ENAMEL) heated at 950°C,suitable for potable water accord toDIN 4753.3 standards.
INSULATION
Soft polyurethane thickness 100mm(PUF100).
EXTERNAL JACKET
SCAI orange colour RAL 2002.
CATHODIC PROTECTION
Magnesium Anode (AMS) made ofspecial alloy AZ63, complete withwelded plug.
PACKING
Pallet+Polythen bubble sheet.
ANTICORROSION WARRANTY
− Heat accumulator: 1 year.− Domestic storage tank: 5 years.
LITRES DIMENSIONS mm ø CONNS. PACKINGH x L x P
cmA B C C1 ø D E G H L M mc-rc-mi-ri-rp ei-ui-es-us e2-u2
500/110 260 540 820 660 650 1070 1390 1700 990 1390 1” 1” 3/4” 185 x 85 x 85
800/150 270 540 820 870 750 1100 1650 1980 1050 1650 1” 1” 3/4” 213 x 100 x 100
1000/200 300 580 850 900 800 1130 1830 2180 1230 1830 1” 1” 3/4” 233 x 100 x 100
1500/300 320 600 870 920 950 1400 1940 2330 1340 1940 1” 1” 3/4” 248 x 120 x 120
90 °C 3 bar 5 yearsL. 296/2006
Art. 3.3Dir. n. 97/23/EEC
ACCUMULATOR WARRANTY PED
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 21/36
Catalogue 200819KOMBI
KOMBICOMBINED SOLAR HEAT ACCUMULATORS
GLASS LI NED DOME STIC STORAGE TANK
LITRES (1) CODE SOLAR
COIL
m2
HOT WATER HEATER PERFORMANCES WEIGHT
kg
HEAT OUTPUT
kW
HEAT UP TIME(2)min
DHW PRODUCTION (3)
l/h l/10’ l/60’
500/150 KOMBI 0500 150 1,5 36 15 885 340 1078 146
800/150 KOMBI 0800 150 2,4 36 15 885 340 1078 191
1000/200 KOMBI 1000 200 2,4 45 16 1106 441 1363 214
1500/300 KOMBI 1500 300 2,4 50 21 1229 590 1614 284
(1) Total capacity / domestic storage tank capacity(2) Time to heat domestic water 10 ÷ 60°C(3) DHW production 10÷45°C with primary 80÷70°C and storage at 60°C: continuous (l/h); first 10 minutes peak (l/10 ’) ; first hour peak (l/60 ’) ’) .
LITRES DIMENSIONS mm ø CONNS. PACKINGH x L x P
cmA B C C1 ø D E G H mc-rc-mi-ri-rp es-us e2-u2
500/150 260 540 820 660 650 1070 1390 1700 1” 1” 3/4” 185 x 85 x 85
800/150 270 540 820 870 750 1100 1650 1980 1” 1” 3/4” 213 x 100 x 100
1000/200 300 580 850 900 800 1130 1830 2180 1” 1” 3/4” 233 x 100 x 100
1500/300 320 600 870 920 950 1400 1940 2330 1” 1” 3/4” 248 x 120 x 120
es solar in letus solar outle te2 secondary inletu2 secondary outlet
r circulation ø 3/4”mc boiler flowrc boiler returnmi heating system flowri heating system returnrp floor heating system returnsc drai n
USE
− Storage and production of heatingwater.− Production and storage of DomesticHot Water (DHW).This equipment is used to benefit bydiscontinuous functioning of heating
units such as solid-fuel boilers, stovesor furnaces, or in low water-contentsystems to limit burner operat ionand for the additional exploit of solarsystems and heat pumps.Working temperature:− Heat accumulator: max 90°C.− Domestic storage tank: max 90°C.Working pressure:− Heat accumulator: max 3 bar.− Domestic storage tank: max 6 bar.
EXCHANGER
Fixed spiral coil.Working temperature: max 99°C.Working pressure: max 12 bar.
ANTICORROSIVE COATING
− Heat accumulator:INSIDE: untreated carbon steel.OUTSIDE: anti-rust paint black colourRAL 9011.− Domestic storage tank: GLASSLINING: inorganic coating (VITREOUSENAMEL) heated at 950°C, suitable forpotable water according to DIN 4753.3standards.
INSULATION
Soft polyurethane thickness 100mm(PUF100)
EXTERNAL JACKET
SCAI orange colour RAL 2002.
CATHODIC PROTECTION
Magnesium Anode (AMS) made ofspecial alloy AZ63, complete withwelded plug.
PACKING
Pallet+Polythen bubble sheet.
ANTICORROSION WARRANTY
− Heat accumulator: 1 year.− Domestic storage tank: 5 years.
AMS 1 Magnesium Anode with welded plugsa air vent ø 1/2”sd probe ø 1/2”
t thermometer ø 1/2”
90 °C 3 bar 5 yearsL. 296/2006
Art. 3.3Dir. n. 97/23/EEC
ACCUMULATOR WARRANTY PED
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 22/36
Catalogue 200820
ARSTORAGE TANKS FOR CHILLED WATER
EXTERNAL ALUMINIUM JACKET
USE
These units are used connectedto FAN COIL for storage of chilledwater in summer and hot waterfrom heat pump or low temperatureheat generators (max.50°C) in theintermediate seasons and winter.
They ensure even average temperaturesand limit the action of the chillercompressor.Working temperature:− Refrigeration: 7÷12°C− Heating: max 70°C-AR− Heating: max 90°C- ACRWith outdoor temperature lower than-2°C we suggest to add ethyleneglycol in a 15% solution, in any casecomplying with instructions given bythe manufacturer of the chiller or heatpump.Working pressure: max 6 bar.
ANTICORROSIVE COATING
AR galvanized: HOT-DEEP GALVANIZATIONaccording to UNI EN ISO 1461 standards.
ACR untreated steel: the tank functionsexclusively as primary circuit; therefore itdoes not need any cathodic protection.A special protection is applied on thefitting threads to maintain them wellpreserved and easy to be connectedduring installation.
INSULATION
CFC-free hard polyurethane, thickness30mm (PUR30), density 40kg/m³.It ensures heat insulation and anti-condensate protection.
EXTERNAL JACKET
Embossed aluminium, thickness 0,4 mm.
PACKING
Polythen bubble sheet.
AR-ACR ARO-ACRO
moveble supports
e inletu outlet
sc drain ø 1”1/4s1 drain
t thermometer ø 1/2”ts thermostat ø 1/2”
ANTICORROSION WARRANTY
3 years - AR.1 year - ACR.
ACCESSORY ON REQUEST (1)
CODE TECHNICAL DATA
AFZ 032 Flanged connection DN 32 PN 16 UNI EN 1092-1 welded and electrolytically galvanized for connection ø 1” 1/4
AFZ 040 Flanged connection DN 40 PN 16 UNI EN 1092-1 welded and electrolytically galvanized for connection ø 1” 1/2
AFZ 050 Flanged connection DN 50 PN 16 UNI EN 1092-1 welded and electrolytically galvanized for connection ø 2”
AFZ 080 Flanged connection DN 80 PN 16 UNI EN 1092-1 welded and electrolytically galvanized for connection ø 3”
(1) Separate supplied, NOT INSTALLED.
LITRES AR GALVANIZED ACR UNTREATED STEEL
CODE WEIGHT kg CODE WEIGHT kg
100 AR 0100 22 ACR 0100 20
200 AR 0200 35 ACR 0200 31
300 AR 0300 45 ACR 0300 41
500 AR 0500 75 ACR 0500 70
750 AR 0750 105 ACR 0750 95
1000 AR 1000 120 ACR 1000 110
1500 AR 1500 A 220 ACR 1500 205
2000 AR 2000 A 265 ACR 2000 245
HORIZONTAL version: code ARO, ACRO.
LITRES DIMENSIONS mm ø CONNS.
A B C ø De H H1 L e-s1-u100 265 790 175 460 995 610 900 1” 1/4
200 285 1145 210 510 1360 660 1270 1” 1/2
300 305 1165 215 610 1395 760 1310 2”
500 335 1415 245 710 1670 860 1590 3”
750 385 1535 295 810 1840 960 1760 3”
1000 400 1690 310 860 2020 1010 1930 3”
1500 450 2010 335 1010 2400 1165 2400 3”
2000 465 2025 370 1160 2450 1295 2450 3”
7÷70 °C 6 bar 1 - 3 years Art. 3.3Dir. n. 97/23/EEC
STORAGE TANKS WARRANTY PED
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 23/36
Catalogue 200821
ARSTORAGE TANKS FOR CHILLED WATER
EXTERNAL SCAI JACKET
USE
These units are used in air conditioningsystems with low-water-content toensure even average temperaturesand limit the action of the chillercompressor.
Working temperature:− Refrigeration : 7÷12°C.− Heating: max 70°C.With outdoor temperature lower than-2°C we suggest to add ethyleneglycol in a 15% solution, in any casecomplying with instructions given bythe manufacturer of the chiller or heatpump.Working pressure: max 6 bar.
ANTICORROSIVE COATING
AR galvanized: HOT-DEEP GALVANIZATIONaccording to UNI EN ISO 1461 standards.ARN untreated steel: the tank functionsexclusively as primary circuit; thereforeit does not need any cathodic protection.A special protection is applied on the
fitting threads to maintain them wellpreserved and easy to be connectedduring installation.
INSULATION
Reticular polyethylene, thickness19mm (PE19), ensures heat insulationand anti-condensate protection.
EXTERNAL JACKET
SCAI green colour RAL 6018.
PACKING
Polythen bubble sheet.
ANTICORROSION WARRANTY
3 years - AR.1 year - ARN.
LITRES AR GALVANIZED ARN UNTEATRED STEEL
CODE WEIGHT kg CODE WEIGHT kg
1500 AR 1500 215 ARN 1500 200
2000 AR 2000 255 ARN 2000 235
2500 AR 2500 300 ARN 2500 280
3000 AR 3000 330 ARN 3000 305
4000 AR 4000 510 ARN 4000 465
5000 AR 5000 600 ARN 5000 550
HORIZONTAL version: code ARO, ARNO.
LITRES DIMENSIONS mm ø CONNS.
A B C ø De H H1 L e-s1-u1500 450 2010 335 990 2400 1165 2285 3”
2000 465 2025 370 1140 2450 1295 2355 3”
2500 510 2070 425 1240 2540 1375 2410 3”
3000 560 2120 445 1340 2570 1460 2450 4”
4000 610 2370 475 1440 2845 1550 2710 4”
5000 620 2380 510 1640 2895 1785 2780 4”
AR-ARN ARO-ARNO
e inlet
u outletsc drain ø 1”1/4s1 drain
t thermometer ø 1/2”ts thermostat ø 1/2”
ACCESSORY ON REQUEST (1)
CODE TECHNICAL DATA
AFZ 080 Flanged connection DN 80 PN 16 UNI EN 1092-1 welded and electrolitically galvanized for connection ø 3”.
AFZ 100 Flanged connection DN 100 PN 16 UNI EN 1092-1 welded and electrolitically galvanized for connection ø 4”.
(1) Separate supplied, NOT INSTALLED.
C O L D W A T E R
S T O R A G E T A
N K S
7÷70 °C 6 bar 1 - 3 years Art. 3.3Dir. n. 97/23/EEC
STORAGE TANKS WARRANTY PED
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 24/36
Catalogue 200822
USE
− AUTOCLAVES: used in watersystems to ensure even pressurewater supply to the higher floors ofbuildings.− PRE-AUTOCLAVES: can be used asair-bearing pre-autoclaves with double
function of anti- water hammer andwater storage tank.Working temperature: - 10÷ + 50°C.
PED TEST
They are tested at 1,5 the workingpressure and supplied with conformitycertificate in accordance with Directive97/23/ EEC.
ANTICORROSIVE COATING
HOT-DEEP GALVANIZED according toUNI EN ISO1461 standards, suitablefor potable water.
ACCESSORIES ON REQUEST (page28)
INSULATION
Reticular polyethylene, thickness 19mm(PE19), ensures thermal insulation andanti-condensate protection.
EXTERNAL JACKET
SCAI green colour RAL 6018.
PACKING
Polythen bubble sheet.
AZ AZO
AZ AUTOCLAVES AND PRE-AUTOCLAVES GALVANIZED
LITRES TEST PRESSURE 8 bar TEST PRESSURE 11 bar
CODE WEIGHT kg CODE WEIGHT kg
100 AZ 08 0100 CE 23 - -
200 AZ 08 0200 CE 36 - -
300 AZ 08 0300 CE 48 - -
500 AZ 08 0500 CE 72 - -
750 AZ 08 0750 CE 106 - -
1000 AZ 08 1000 CE 122 AZ 11 01000 173
1500 AZ 08 01500 213 AZ 11 01500 263
2000 AZ 08 02000 306 AZ 11 02000 318
2500 AZ 08 02500 358 AZ 11 02500 460
3000 AZ 08 03000 422 AZ 11 03000 496
4000 AZ 08 04000 638 AZ 11 04000 760
5000 AZ 08 05000 732 AZ 11 05000 881
6000 AZ 08 06000 840 AZ 11 06000 1004
8000 AZ 08 08000 1204 AZ 11 08000 1395
10000 AZ 08 10000 1476 AZ 11 10000 1715
HORIZONTAL version (code AZ0 08, AZ0 11).
Internal coating treatment SmaltoPLAST® on request.
LITRES DESIGNPRESSURE
bar
DIMENSIONS mm ø CONNS.
A B øD H H1 L a1 e-s1-u-v1 z
100 8 325 210 400 1050 615 915 1/2” 1” -
200 8 340 230 450 1460 660 1330 1/2” 1” -
300 8 380 260 550 1520 770 1380 1” 1/2 1” 1/2 -
500 8 400 295 650 1805 860 1680 1” 1/2 2” -
750 8 430 355 750 1970 955 1840 1” 1/2 2” -
1000 8/11 445/460 355/365 800 2140/2285 1000 2010/2170 1” 1/2 2” -
1500 8/11 540/550 395/410 950 2560/2410 1195 2390/2250 1” 1/2 2” 1” 1/2
2000 8/11 570 450/445 1100/1000 2620/2800 1330/1230 2480/2670 1” 1/2 2” 1” 1/2
2500 8/11 580/665 460/550 1100/1200 2810/2730 1330/1420 2680/2620 1” 1/2 3” 2”
3000 8/11 625/665 510/550 1250/1200 2890/2930 1460/1420 2770/2820 1” 1/2 3” 2”
4000 8/11 740/760 595/600 1450 3080 1730 2890 1” 1/2 3” 2”
5000 8/11 740/760 605/610 1450 3580 1730 3390 1” 1/2 3” 2” 1/2
6000 8/11 750/770 605/610 1450 4080 1730 3890 1” 1/2 4” 2” 1/2
8000 8/11 815 680/690 1650 4150 1890 4000 1” 1/2 4” 2” 1/2
10000 8/11 815 680/690 1650 5150 1890 5000 1” 1/2 4” 2” 1/2
e inletu outlet
sc drain ø 1” 1/4(ø 2” l 2500 ÷ 4000)
s1 draina1 ai r feeda2 air feed ø1” 1/4
i level gauge ø 1/2”m pressure gauge ø 1/2”p pressure switch ø 1/2”T platev safety valve ø1” 1/4
v1 safety valvez vent for galvanization
VS MR
PU PM
ANTICONDENSATE PROTECTION
room 8 //11 bar 1 year Directiven. 97/23/EEC
TEMPERATURE PRESSURE WARRANTY PED - CE
ANTICORROSION WARRANTY1 year.
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 25/36
Catalogue 200823
SACCOMPRESSED AIR VESSELS
LITRES PAINTED GALVANIZED
CODE WEIGHT kg CODE WEIGHT kg
1000 SAC 11 01000 V 165 SAC 11 01000 Z 180
1500 SAC 11 01500 V 235 SAC 11 01500 Z 260
2000 SAC 11 02000 V (1) 290 SAC 11 02000 Z 320
3000 SAC 11 03000 V 470 SAC 11 03000 Z 515
4000 SAC 11 04000 V 700 SAC 11 04000 Z 770
5000 SAC 11 05000 V 810 SAC 11 05000 Z 890
6000 SAC 11 06000 V 920 SAC 11 06000 Z 1015
8000 SAC 11 08000 V 1280 SAC 11 08000 Z 1410
10000 SAC 11 10000 V 1560 SAC 11 10000 Z 1715
HORIZONTAL version code SAC0 11-V, SAC0 11-Z.
LITRES DIMENSIONS mm ø CONNS.
A B C ø D H H1 L z e-s1-u
1000 700 1000 455 800 2370 1110 2160 - 2”
1500 700 1000 495 950 2445 1250 2240 1” 1/4 2”
2000 700 1000 525 1000 2895 1320 2650 1” 1/4 2”
3000 800 1000 605 1200 3030 1495 2810 2” 3”
4000 800 1000 635 1450 3100 1785 2870 2” 3”
5000 800 1500 635 1450 3610 1785 3370 2” 3”
6000 800 2150 635 1450 4100 1785 3870 2” 3”
8000 1000 2150 715 1650 4220 1950 3990 2” 4”
10000 1000 3150 715 1650 5220 1950 4990 2” 4”
USE
Storage and distribution of compressedair at room temperature (10÷50°C).
Test pressure: 11 bar
PED TEST
The vessels are manufactured andtes ted according to the EuropeanDirective 97/23/EEC.Supplied with installation, use andmaintenance manual and Declarationof Conformity in accordance with theDirective.
ANTICORROSIVE COATING
− PAINTED: anti-rust paint blue colourRAL 5015.− HOT-DEEP GALVANIZED accordingto UNI EN ISO 1461 standards.
ACCESSORIES ON REQUEST (page 28)
PACKING
Polythen bubble sheet.
ANTICORROSION WARRANTY
1 year.
SAC SACO
cc
VS 11 A MR 11
PU PM
(1) Test pressure: 10,8 bar.
ACCESSORIES ON REQUEST
TYPE CODE TECHNICAL DATA
VS 11 A VS 11 A Certified safety valve ø 1” discharge rate 31167l/min.
MR 11 MR 11 Bourdon gauge ø 63x1/4”
PU PU Man hole 300 x 400
PM PM Hand hole 100 x 150
e inletu outletm pressure gauge ø 3/8”p pressure switch ø 1/2”
sc drain ø 1” 1/4s1 drainT platev safety valve ø 1” 1/4z vent for galvanizing
room 10,8 bar 1 year Directiven. 97/23/EEC
TEMPERATURE PRESSURE WARRANTY PED - CE
V E S S E L S
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 26/36
Catalogue 200824 VGF
VGFGLASS LINED BALANCED FLUE INDUSTRIAL GAS WATER HEATERS
SEALED AND FORCED-DRAUGHT COMBUSTION
LITRES CODE FAN INTPUT OUTPUT METHANE GAS GPL HEAT UP DHW PRODUCTION (4) WEIGHT
TERMICA CONSUMPTION (1) CONSUMPTION (2) (3)
Pa kW kW m3 /h kg/h min l/h l/10’ l/60’ kg
220 VGF 2 90 26 23,4 2,76 2,05 26 592 358 851 165
300 VGF 3 65 31 27,9 3,12 2,31 32 666 464 1019 195
400 VGF 4 64 31 27,9 3,12 2,31 42 666 582 1137 235
(1) Standard equipment(2) Spare parts kit included as standard accessory.(3) Time of heating water from 15° to 65°C(4) Production of DHW from 15° to 50° C with storage at 65°C: continuous (l/h); first 10 min peak (l/10’), first hour peak (l/60’).
TYPE CODE VERSION
KSO C 12 horizontal coaxial exhaust
KSV C 32 vertical coaxial exhaust
KSD C 52 split horizontal exhaust
LITRES DIMENSIONS mm ø CONNS.
ac-af-r-sc
ANODES
TYPE
PACKING mm
l w hA B C ø De E ø F H
220 370 570 770 680 1130 100/60 1710 1” AM 4 183x79x79
300 370 570 770 680 1360 100/60 1950 1” AM 4 200x79x79
400 370 570 770 730 1520 100/60 2130 1” AM 4 220x83x83
ac hot wateraf cold waterr circulation
sc drain
AM Magnesium AnodeB Stainless Steel multigas
burner with air draughtEV Electric fanned fluePS Instrument panel with:
- Anoden Tester- Weekly timer- Push- button panel- Operation thermostat- Safety thermostat
T ThermometerTF Flue tubes
USE
Water heater for production andstorage of Domestic Hot Water
(DHW).Working temperature: max 65°C.Working pressure: max 6 bar.
ANTICORROSIVE COATING
GLASS-LINING: inorganic coating(VITREOUS ENAMEL) heatedto 950°C, suitable for potablewater according to DIN 4753.3standards.
INSULATION
Glass wool , thickness 25 mm;category 0.
EXTERNAL JACKET
Galvanized and plastic coatedsteel; grey colour RAL 7035.
CATHODIC PROTECTION
Magnesium Anodes (AM) made ofspecial alloy AZ63, complete withAnoden Tester (AT 1) for fast andreliable check of anode operationand consumption.
SAFETY
Sealed combustion environ-mentally safe; safety thermostatto avoid any overheating andexhaust fume control device (DCF)against abnormal exhaust.
ELECTRIC POWER
230 V AC/50 Hz.
The weekly timer and the AnodenTester are standard accessories.
PACKING: Wood crate.
ANTICORROSION WARRANTY
2 years.
• Sealed combustion
• Force-draught (EN 89 type C)
These sealed-combustion water heaters can be installed virtually anywhere because the fuel circuit is sealed and separated fromthe room where they are located. The fan-forced-draught enables the simultaneous suctioning of the combustion air with exhaustof the by-products of combustion outside the room, even without a flue or a chimney.The equipment is fitted with an electrical gas valve and electronic ignition with ionisation flame control. The various functionsare controlled and handled by an electronic switchboard. This system is designed to “clean” the fuel combustion chamber withfresh air before every burner ignition. This process prevents any gas residue (especially in the event of liquefied gas) from causingpotentially hazardous situations.A differential pressure switch guarantees the immediate blockage of the gas flow and shuts off the burner in case of a badworking operation of the exhaust fume fan or of any other anomalous exhaust operation. Ignition can be programmed by using
the weekly timer.The equipment is fitted with a double thermostat (operation and safety).
IMPORTANT: EXTRACTION AND EXHAUST KIT TO BE ORDERED WITH THE WATER HEATER
Fumes are exhausted and air is vented by through a kit, which has been especially designed andtested for our equipment. Available in coaxial version (horizontal or vertical) or in split horizontalversion. On request are also available 90° curves and 1 meter extensions that allow to fit the kitaccording to every kind of installation .
* Standard length of the hose included in the kit** Maximum length required for safe and efficient operation; this length has to be reduced by 1 meter for any eventual additional curve.
KSOhorizontal coaxial exhaust
(EN 89 type C12)
KSDsplit horizontal exhaust
(EN 89 type C52)
KSVvertical coaxial exhaust
(EN 89 type C32)
Air
Fumes
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 27/36
Catalogue 200825VG ZG
GENERGY ECONOMY INDUSTRIAL GAS WATER HEATERS
ELECTRONIC IGNITION
LITRES DIMENSIONS mm ø CONNS. ANODES PACKING cm
A B C ø De E ø F G H ac-af-r TYPE l w h
150 300 500 - 580 1200 100 160 1315 3/4” 3/4” x 400 145x65x65
200 300 500 - 580 1450 100 160 1565 3/4” 3/4” x 800 170x65x65
300 300 510 - 680 1540 140 160 1715 3/4” 1” 1/2 x 500 183x78x78
400 310 510 - 730 1560 140 160 1725 1” 1” 1/2 x 500 183x82x82
500 310 510 - 730 1810 140 160 1975 1” 1” 1/2 x 1000 212x82x82
600 310 1010 1730 780 2045 140 - 2170 1” 1” 1/2 x 900 220x89x89
800 340 910 1470 980 1775 160 - 1980 1” 1/4 1” 1/2 x 900 203x110x110
1000 340 910 1470 1080 1845 160 - 2030 1” 1/4 1” 1/2 x 900 203x120x120
1500 340 960 2000 1180 2085 160 - 2250 1” 1/42” x 5002” x 900
227x130x130
2000 340 960 2150 1280 2325 160 - 2490 1” 1/42” x 5002” x 900
255x140x140
GLASS- LINED
LITRES CODE INPUT OUTPUT METHANE GAS GPL HEAT UP DHW PRODUCTION (4) WEIGHT
CONSUMPTION (1) CONSUMPTION (2) (3)
kW kW m3 /h kg/h min l/h l/10’ l/60’ kg
150 VG 1 10,6 9,1 1,16 0,863 44 219 216 414 80
200 VG 2 10,6 9,1 1,16 0,863 59 219 276 474 90
300 VG 3 26,7 22,9 2,68 1,99 38 563 447 916 155
400 VG 4 26,7 22,9 2,68 1,99 50 563 565 1034 165
500 VG 5 26,7 22,9 2,68 1,99 63 563 682 1151 185
GALVANIZED
600 ZG 6 26,7 22,9 2,68 1,99 75 563 801 1270 235
800 ZG 8 34,8 29,6 3,49 2,59 77 727 1063 1669 290
1000 ZG 10 34,8 29,6 3,49 2,59 97 727 1298 1904 335
1500 ZG 15 34,8 29,6 3,49 2,59 146 727 1887 2493 455
2000 ZG 20 34,8 29,6 3,49 2,59 194 727 2476 3082 550
(1) Standard equipment(2) Spare parts kit included as standard accessory.(3) Time of heating water from 15° to 65°C(4) Production of DHW from 15° to 50° C with storage at 65°C: continuous (l/h); first 10 min peak (l/10’), first hour peak (l/60’).
ac hot wateraf cold waterr circulation
AMS Magnesium Anode with welded plugB Stainless Steel multigas burner
CF Fume HoodDCF Fume Control Device
PS Instrument panel with:- Anoden Tester- Weekly timer- Push- button panel- Operation thermostat- Safety thermostat- Electronic ignition gas valve ø 1/2”
T ThermometerTF Flue tubes (150-200l only one central tube)
USE
Water heater for production and storageof Domestic Hot Water (DHW).Working temperature: max 65°C.Working pressure: max 6 bar.
ANTICORROSIVE COATING
-GLASS-LINING: inorganic coating(VITREOUS ENAMEL) heated to950°C, suitable for potable wateraccording to DIN 4753.3 standards.- GALVANIZED: HOT-GALVANIZEDaccording to UNI EN ISO 1461standards.
INSULATION
Glass wool, 25 mm thickness;category 0.
EXTERNAL JACKET
Galvanized and plast ic coated
steel; grey colour RAL 7035.
CATHODIC PROTECTION
Magnesium Anodes (AM) made ofspecial alloy AZ63, complete withAnoden Tester (AT 1) for fast andreliable check of anode operationand consumption.
SAFETY
Gas valve with safety thermostat andexhaust fume control device (DCF).
ELECTRONIC IGNITION
the equipment are fitted with aspecial gas valve, the 830 TANDEM,that enables ELECTRONICIGNITION and automatic re-ignition without a pilot flame. Sincethe equipment has no pilot flame, itoffers significant gas fuel savings.
ELECTRIC POWER
230 V AC/50 Hz.
PACKING: Wood crate
ANTICORROSION WARRANTY
2 years.
• Unsealed combustion• Natural draught• Break-in-the-draught/wind protection• Fume control device (DCF)
(EN 89 type B 11 BS)
G A S W A T E R
H E A T E R S
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 28/36
Catalogue 200826
SR SX SZ HOT WATER HEAT EXCHANGERS
kW COPPER STAINLESS STEEL SCAMBIATORE ZINCATO DIMENSIONS mm HOLES WEIGHT
CODE CODE CODE ø F ø I L n° kg
12 SR 012 A SX 012 A SZ 012 A
300 262
505
16
7,5
18 SR 018 A SX 018 A SZ 018 A 505 8
24 SR 024 A SX 024 A SZ 024 A 550 9
36 SR 036 A SX 036 A SZ 036 A 795 10,5
48 SR 048 A SX 048 A SZ 048 A 845 12
36 SR 036 B SX 036 B SZ 036 B
380 346
795
19
15
48 SR 048 B SX 048 B SZ 048 B 845 16,5
73 SR 073 B SX 073 B SZ 073 B 948 20
60 SR060 B SX 060B SZ 060B 595 20
97 SR 097 B SX 097 B SZ 097 B 1005 23
122 SR 122 B SX 122 B SZ 122 B 1035 26
146 SR 146 B SX 146 B SZ 146 B 1065 29
120 SR 0400 A SX 0400 A SZ 0400 A
430 396
681
22
36
97 SR 097 C SX 097 C SZ 097 C 1218 25
168 SR 0500 A SX 0500 A SZ 0500 A 850 43
122 SR 122 C SX 122 C SZ 122 C 1518 29
195 SR 195 C SX 195 C SZ 195 C 1260 38
244 SR 244 C SX 244 C SZ 244 C 1560 45
TZ HEADS
GGE-K/GGS-KHOT WATER GASKET KIT
STEAM OR OVERHEATED WATER GASKETS KIT
TYPE WATER STEAM DIMENSIONS mm HOLES WEIGHT
CODE CODE ø F ø I n° kg
300 GGE 300 K 4 V GGS 300 K 300 262 16 2
380 GGE 380 K 4 V GGS 380 K 380 346 19 2
430 GGE 430 K GGS 430 K 430 396 22 2
TYPE CODE DIMENSIONS mm CONNS. HOLES WEIGHT
A B ø F ø I ø n° kg
300 TZA 300 ST 123 70 300 262 1” 1/4 16 4
380 TZB 380 ST 182 75 380 346 1” 1/2 19 7
430 TZ 430 220 78 430 396 2” 22 9
U-tube bundle expanded on plate.Copper tubes of Cu-DHP (99,9%),suitable for potable water according toUNI EN 1057 standards.
U-tube bundle expanded onplate. AISI 316L tubes suitablefor potable water.
Return head of painted carbon steel.
Pair of gaskets of food-gradedielectric EPDM rubber fortemperature max 120°C.
holes ø 16,5
SR
SX
SZ
Suitable for contact with potablewater according to Regulat ion1935/04/EEC.Working temperature: max 99°C.Working pressure: max 12 bar.
U-tube bundle expanded on plate.Carbon steel tubes, hot deepgalvanized according to UNI EN ISO1461 standards.
Pair of gaskets in silicon, food-
grade and dielectr ic rubber fortemperature max 200°C.
GGE-K
GGS-K
holes ø 15
holes ø 12
WITHOUT CROSS PIECE WITH CROSS PIECE
holes ø 12
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 29/36
Catalogue 200827
S-VASTEAM OR OVERHEATED WATER HEAT EXCHANGERS
m2 TESTPRESSURE
barKw
COPPER STAINLESS STEEL DIMENSIONS mm CONNS. HOLES WEIGHT
CODE CODE A ø F ø I L ø n° kg
0,37 12 68 SR 0037 12 VA (1) SX 0037 12 VA (1)
123 300 262
577
1” 1/4 16
13
0,5 12 91 SR 0050 12 VA (1) SX 0050 12 VA (1) 622 14
0,75 12 137 SR 0075 12 VA SX 0075 12 VA 556 15
1 12 182 SR 0100 12 VA SX 0100 12 VA 556 16
1,5 12 274 SR 0150 A 12 VA SX 0150 A 12 VA
182 380 346
777
1” 1/2 19
28
2 12 365 SR 0200 B 12 VA SX 0200 B 12 VA 925 31
3 12 555 SR 0300 C 12 VA SX 0300 C 12 VA 1337 38
2 8 334 SR 0200 C 8 VA SX 0200 C 8 VA
220 430 396
1298
2” 22
38
2,5 8 420 SR 0250 8 VA SX 0250 8 VA 1598 41
4 8 667 SR 0400 B 8 VA SX 0400 B 8 VA 1340 52
5 8 839 SR 0500 B 8 VA SX 0500 B 8 VA 1640 58
(1) According to Art. 3.3 of Directive 97/23/EEC.
Expanded U-tube copper bundle Cu-DHP (99,90%) UNI EN 1057.U-tube carbon steel plate.Return head of painted carbon steel.
Expanded U-tube ASI316L bundle.U-tube carbon steel plate.Return head of painted carbon steel.
Suitable for potable water.
These exchangers and return heads,even if provided unassembled, cannot be supplied separately because, inaccordance with Directive 97/23/EEC,they constitute a “single set”.
SX-VA
SR-VA
ACCESSORIE S AND SPARE PARTS FOR PRESSU RE VESSELS
TYPE CODE TECHNICAL DATA
SAFETY VALVE
VS 8 Certified safety valve ø 3/8” discharge rate 6028 l/min.
VS 11 Certified safety valve ø 3/8” discharge rate 7504 l/min.
VS 11 A Certified safety valve ø 3/8” discharge rate 31167 l/min.
MANOMETERMR 8 Bourdon gauge ø 63x1/4” 8 bar.
MR 11 Bourdon gauge ø 63x1/4” 11 ba r.
INSPECTION
OPENING (1)
PU Man hole 300x400 (capacity * 1000 l).
PM Hand hole 100x150 (capacity * 300 l).
(1) Avaible only in course of the vessel construction.
VS MR
PU PM
175,4 // 191,7°C 8 // 12 bar 200 °C Cat. 1ª Form A Dir. n. 97/23/EEC
TEMPERATURE PRESSURE GASKETS PED - CE
ACCESSORIES
A C C E S S O R I E S
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 30/36
Catalogue 200828
AM MAGNESIUM ANODES
Magnesium Anodes, in AZ63 alloy,mounted on an insulated plug: whenconnected to the Anoden Tester enableremote control without interruptingthe water heater operation.
Magnesium anodes, in AZ63 alloy,mounted on a welded plug.
INSULATED PLUG
TYPE CODE DIMENSIONS WEIGHT
ø T ø D mm L mm kg
AM 1 AM 1 1” 1/4 33 320 0,75
AM 2 AM 2 1” 1/4 33 520 1,10
AM 3 AM 3 1” 1/4 33 700 1,35
AM 4 AM 4 1” 26 320 0,45
WELDED PLUG
AMS 1 AMS 1 1” 1/4 32 320 0,70
AMS 4 AMS 4 1” 1/4 32 520 1,00
AMS 5 AMS 5 1” 26 320 0,45
AMS 8 AMS 8 1”1/4 32 700 1,25
AM
AMS
TT CORREX
Electric power: 230 V AC/50 Hz.In accordance with 95/2005/EEC,96/2002/EEC, 108/2003/EEC.
TYPE CODE COMBINING DIMENSIONS mm ELECTRODES
H L P n° CONNS. ø L mm
MP 23S TT Storage tanks/Water heaters 200÷1000 l 80 50 45 1 1” 1/4 200
UP 19H TT 1 Storage tanks/Water heaters 1500÷2500l 100 50 40 1 1” 1/4 400
UP 19H TT 2 Storage tanks/Water heaters 3000÷5000 l 100 50 40 2 1” 1/4 832
Electronic impressed-current anode for permanent cathodic protection; not subject to consumption, CORREX is particularly ideal for protection of storage tanks andwater heaters (if also already installed) that must operate under particularly aggressive physical and chemical water conditions.
AT 1 ANODEN TESTER
Electromagnetic control device tocheck operation and consumptionof the magnesium anodes withinsulated plug (AM). It is mountedon self-extinguishing plastic box.
TYPE CODE DIMENSIONS mm
H L P
AT 1 AT 1 82 66 55
$ 4
$ 4
The equipment includes: General switch, Thermometer with sleeve, Thermostat with sleeve, Summer-Winter Switch.
TYPE CODE DIMENSIONS mm WEIGHT
H L P kg
PR PR 235 95 95 1,1
CONTROL PANEL PR
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 31/36
Catalogue 200829
Safety valve: Since water is incompressible and at high temperature it in-
creases its volume, it is necessary to provide a suitable expansion system,
in order to avoid irreparable damages to the tank. We recommend provi-
de for an expansion system with a safety valve, whose diameter should be
calculated according to the following formula:
NOTE: Setting pressure of the safety valve must not be higher than wor-
king pressure of the water heater.
Expansion tank : In order to avoid frequent drains from the safety valve,
as well as continuous and dangerous stresses to the water heater, it is use-
ful to install an expansion tank, fitted with a non toxic bladder (alimentary).
As far as dimensioning is concerned, we recommend an expansion tank,
whose capacity is at least equal to the 10% of the water heater capacity.
Water hammering: Any brusque or sudden stops in the water flow could
cause “PRESSURE WAVES” which may cause serious damage and /or
breakage; therefore all cold and hot water systems must have mechanical
(spring) shock-absorbers against water hammering, or better hydro pneu-
matic ones.
Electrical protectionIn order to guarantee the user’s safety and to avoid possible wrong currents, CORRECT GROUNDING of electric Masses and of foreign Masses is to be
performed.
Electronic impressed-current anode for permanent cathodic protection;
not subject to consumption, CORREX is particularly ideal for protection
of storage tanks and water heaters (also if already installed) that must
operate under particularly aggressive physical and chemical water con-
ditions.
Correx
Protection against overpressure
V 5
v = volume of the tank in litres
d= valve opening diameter (15mm minimum)
Cathodic protectionagainst corrosion
Modern research has proved that CORROSION is an electrical, or more exactly,
an electrochemical phenomenon. This phenomenon concerns particularly
water heaters since they are containers of continuously renewed water, whose
aggressivenesses increases with correspondent increase of temperature(especially
when it rises over 55÷60°C). CATHODIC PROTECTION is based on principle that
corrosion takes place only in the ANODIC AREAS and not in the CATHODIC
ones.
In order to have a cathodic protection even in the minimum COATING
IMPERFECTIONS of the water heater, one or more sacrificial MAGNESIUM
ANODES are installed. Through the consumption of the anode and the production
of a low-tension current, the tank and the heat exchanger are efficaciously
protected against corrosion.
Our anodes are made of a special AZ 63 Magnesium alloy, which guarantees
PHYSIOLOGICAL INNOCUOUSNESS, ELECTRODE POTENTIAL ()-0,9V) and
MASS LOSS RATE ()30 • m-2 • d-1) according to DIN 4753-6.
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 32/36
//SmaltoPLAST®
ASPECT QUALITY REQUIREMENTS
Treatment on the insideof tank
SmaltoPLAST® is approved incompliance with EuropeanDirective 2002/72/EEC andRegulation 1935/04/EEC
on the use of drinking water intended to come into contact with food
Working temperature 80° C continuous
Characteristics of the water used
Total minimum hardnessrequired 15°FpH 6.5 - 9.5chlorides and sulphates 250 mg/l
Storage temperature The standard allows for storage temperatures up to65°C (UNI 9182). However,it is recommended to notexceed 60°C in order to ensure
energy savings, limit lime-scale deposits and corrosion.The standard (Appendix U) inany case prohibits water fromcirculating at temperaturesabove 60°C when galvanisedsteel pipework is used
Cathodic protection - Magnesium anodes (sacrificial)- Correx impressed current anodes
Coverage (100% effectiveness) 5,5 m2/kg a 200μ
Granulometry 95% < 212μ
Mass density (at rest) 0,40 g/cm3
Fluidisation characteristics excellent
TYPICAL PROPERTIES OF THE COATING
Thickness 200-220μ
Appearance smooth - shiny
Colour Grey
Maximum temperature 100° C
The data provided below refer to a 200μ thick coating applied
in normal conditions to 3 mm thick steel plate.The surface has been treated following degreasing and sandblasting, unless otherwise specified.
SmaltoPLAST® is a thermoplastic material specifically designedto provide a long-lasting corrosion-proof coating on steel.The use of SmaltoPLAST®, in addition to water with suitablephysical-chemical characteristics (i.e. does not cause scaling
and is not aggressive) and the installation of magnesium or Correx anodes, guarantees the protection of the water heater against corrosion.It is recommended to not exceed a temperature of 60°C so as toensure the correct operation of the appliance and its efficiency over time.
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 33/36
Catalogue 200831
The warranties contained in this catalogue are offered according to
the terms described for each item and cover only PERFORATION
FROM ELECTROCHEMICAL CORROSION and are valid only for
properly coated surfaces with particular reference to those in con-
tact with Domestic Hot Water. Nevertheless, the above mentioned
warranties fail in the following cases:
a) The equipment is not provided with efficient and permanent ca-
thodic protection, with which it is normally endowed.
b) Quality requisites of potable water supply do not comply with
DLgs 31/01 in accordance with Directive n.98/83/EEC, and in
particular are are not in conformity with the following parame-
ters:
c) When disassembling the heat exchanger (copper or stainless ste-
el) for cleaning or periodical servicing, it is reassembled without
checking that the exchanger and the tank are ELECTRICALLY
INSULATED, as per original arrangement and checking in our
factory. We remind that electrochemical corrosion is quite ag-
gressive in case of contact between metals with different nobility
degree when deepened in the same electrolyte.
d) The maximum working temperature allowed for each water hea-
ter is not respected. We remind that water aggressiveness highly
increases with correspondent increase of temperature, in parti-
cular when temperature rises over 60°C.
(*) Maximum admissible value for stainless steel products.
(**) In addition to fulfilment of sanitary measures, water must be balanced (neither hard, nor corrosive) according to TILLMANN’s diagram.
However, prescribed water treatments cannot prevent its alimentary use and must be effected with proper equipments; in case of water
softening or desalination total hardness cannot be lower than 15°F.
PARAMETERSHYDROGEN IONICCONCENTRATION
pH
ELECTRICALCONDUCTIVITY μs cm-1 (a 20°C)
CHLORIDESmg/l Cl
SULPHATESmg/l SO4
TOTAL HARDNESS°F (**)
PARAMETERS VALUES 6,5÷9,5 2500 250 (*) 250minimun requiredconcentration 15
Glass-lining GalvanizationStainless steel
The solution that offers the best guaran-
tee against corrosion is vitreous enamel.
The enamel, fired in large furnaces at
over 800 °C, differs from paints due to
its strictly inorganic chemical composi-
tion (no carbon) and its chemical bonds.
Hot-dip galvanisation is performed by
deepping the tank into a bath of molten
zinc at a temperature of around 450°C.
Galvanization offers dual protection,
thanks to the barrier effect of the surface
layer of Zn and its alloys, around 80-100
microns thick, which also isolates the
steel against external elements.
The general factors that lead to corrosion
are negligible in water heaters made from
stainless steel, however in certain condi-
tions the presence of chlorides is the main
cause of pitting corrosion. To prevent this
risk, our water heaters are manufactured
using special types of low carbon stainless
steel, such as AISI 316L and, for very cor-
rosive water, AISI 316 Ti (with Titanim).
Inorganic coating DIN 4753.3, suitable for
contact with potable water in accordance
with Regulation 1935/04/EEC.
Hot deep galvanized UNI EN ISO 1461,
suitable for contact with potable water in
accordance with Regulation 1935/04/EEC.
AISI316L 1.4404 EN 10088-2 suitable
for contact with potable water in
accordance with Directive 98/83/EEC.
WARRANTIES
W A R R A N T I E
S
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 34/36
PRICE1. This catalogue replaces and cancels all previous editions.
ORDER2. All orders are subject to approval by our Company.3. By placing an order the Customer acknowledges having
read and accepted our “General Conditions of Sale”, aswell as knowing and approving all the technical data andcharacteristics of our products as shown in the correspon-ding illustrations. Furthermore our Company reserves theright to improve its products without prior notice; such
changes shall not oblige the company to modify contractsand/or orders.
4. A placed order binds the Customer and cannot be changedor cancelled without the consent of our Company.
5. All orders, even if confirmed, are considered as acceptedwith the right to total or partial cancellation depending onthe supply of raw materials or due to force majeure or otherunforeseen causes.
DELIVERY 6. Delivery time is indicative, and not binding for our Com-
pany. Delays or partial deliveries do not give the Customerthe right to cancel the order, to claim for damages and/orto suspend payments.
7. The delivery date is the date on which the goods leave ourpremises.
8. All our products are sold ex works and with our standard
packing: consequently transport and different type of pa-cking costs are borne by the Customer.
COMPLAINTS9. Complaints shall not be accepted if not made upon receipt
of the goods and must in any case be made within and notlater than the terms specified by law.
10. Any damage caused by transport must be notified directly to the carrier and to us in copy within eight days from thedelivery by means of registered letter.
11. Returned goods shall not be accepted without our prior appro-val; in any case transport costs will be borne by the customer.
12. Complaints in progress do not give the right to suspendpayments.
13. In the event of certified defects of the product, our Company shall replace or repair, at its own indisputable discretion,the faulty product or elements of the product itself; besidefrom this, the Customer cannot lay further claims.
WARRANTY 14. The warranties contained in this catalogue are offered by our
Company according to the terms described for each productand only cover perforation from electrochemical corrosion;for any other warranty (of manufacturing, defects) the provi-sions of the Italian Civil Code shall be applied.All warranties shall be invalidated if all the instructions re-ported in our drawings, servicing manuals and technicalsheets, are not strictly observed or if relevant provisions ofthe law or specific technical standards are not met.Furthermore, evidence of un-authorised repairs, tamperingwith the product, use of non-original parts or accessories,shall automatically invalidate the warranty.
INSPECTIONS15. Inspections by our technical personnel can be corried out
only if express demanded by the Customer; in any case theservice shall be invoiced.
PAYMENTS16. Payment of invoices shall be made to our Head Office in
Rovigo according to the terms reported in the invoice.17. Non-payments give us the right to suspend further deliveries
of material.18. Delayed payments shall be debited with the current rate of
bank interest.
DISPUTES19. For all legal purposes Rovigo shall be the place of jurisdiction.
GENERAL CONDITIONS
OF SALE
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 35/36
Northvale Heating Products Zani Storage Tanks & Calorifiers
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
7/16/2019 zani-catalog.pdf
http://slidepdf.com/reader/full/zani-catalogpdf 36/36
p h o t o
G . D
e S a n d r e
C A T - U
K 0 9 0 8_
1 5 0 0
ZANI SPA GROUP
Plant V.le del Lavoro, 18/A 45100 Rovigo (Italia)Tel. +39 0425 474815
Fax +39 0425 474319id i
Plant Via Monte Grappa, 7120061 Carugate (MI - Italia)Tel. +39 02 9254934 - 35
Fax +39 02 9252415ffi i i i
Head office and plant ZANI SPA V.le del Lavoro, 1845100 Rovigo (Italia)Tel. +39 0425 474815
Fax +39 0425 474319i i
Plant Via Grandi, 15 Z. I. Nord45100 Rovigo (Italia)Tel. +39 0425 30666
Fax +39 0425 34054i ll i i
Northvale Heating Products Zani Storage Tanks & Calorifiers
Auckland (Head Office) Christchurch (Branch Office)31 Station Road, Penrose, Auckland, NZ 39 Leslie Hills Dr, Riccarton, Christchurch, NZPO Box 12021, Penrose, Auckland 1642 PO Box 13516, Armagh, Christchurch 8141Ph: +64-9-579 2185 Fax: +64-9-579 2181 Ph: +64-3-379 7884 Fax: +64-3-379 7874
Web: www.cookeindustries.co.nz Email: sales@cooke industries .co.nz