Z-MAX 45 Termination Instructions 1A Tools 1B 1C Remove center spline Flush Cutters Jacket Stripper ZMAX45 Termination tool (p/n: Z-TOOL-45) ! F/UTP shown here See back page for other cable types. Drain wire & foil Invert Foil Wrap Drain wire Remove Mylar Wrap 2 Remove Jacket ~ 2.5 in. (64 mm) 3 UTP (skip to step 1C) Termination Module Outlet Body Hybrid Version Rear cover Zip Tie Flat Screwdriver Outlet Body Keystone Version Mount lacing module in tool handle facing front Optional: For large O.D. cables, pliers may be helpful when lacing Back Front OR Cable Jacket stop Lace all four pairs with lacing module supported in tool handle. Pin#s: 12 36 54 78

Transcript of Z-MAX 45 Termination Instructions - The Siemon...

Page 1: Z-MAX 45 Termination Instructions - The Siemon Companyfiles.siemon.com/int-download-installation-instructions/wa_z-max-45_ii.pdfZ-MAX 45 Termination Instructions 13 14 12 1 2 Tip:

Z-MAX 45 Termination Instructions

1A

Tools

1B 1C Remove center spline

Flush Cutters

JacketStripper

ZMAX45Termination tool(p/n: Z-TOOL-45)

!

F/UTP shown here

See back page for othercable types.

Drain wire& foil

InvertFoil

WrapDrainwire

RemoveMylar Wrap

2

RemoveJacket

~ 2.5 in. (64 mm)

3

UTP (skip to step 1C)

TerminationModule Outlet Body

Hybrid Version

Rearcover

Zip Tie

FlatScrewdriver

Outlet BodyKeystone Version

Mount lacing module in toolhandle facing front

Optional:For large O.D.cables, pliersmay be helpfulwhen lacing

Back

Front

OR

Cable Jacketstop

Lace all four pairswith lacing modulesupported in toolhandle.Pin#s:

1 2 3 6 5 4 7 8

Page 2: Z-MAX 45 Termination Instructions - The Siemon Companyfiles.siemon.com/int-download-installation-instructions/wa_z-max-45_ii.pdfZ-MAX 45 Termination Instructions 13 14 12 1 2 Tip:

Z-MAX 45 Termination Instructions

4

87

10

FlushCuttersonly

OR

Ensure outlet is fully seatedonto base of tool duringtermination.

!

Front view

Remove

1

Cut flush

2

5

+90◦

6

Keying features for properorientation

9

1

2

3

-90◦

OR

OR

Drain wireTie-wrap

12

Page 3: Z-MAX 45 Termination Instructions - The Siemon Companyfiles.siemon.com/int-download-installation-instructions/wa_z-max-45_ii.pdfZ-MAX 45 Termination Instructions 13 14 12 1 2 Tip:

Z-MAX 45 Termination Instructions

13

14

12

1

2

Tip: Squeeze outletagainst lip on toolto secure whenpulling apart

Pull apart by hand or use tool

1

1

2

11

Faceplate mountfrom rear asshown:

Faceplate Mounting:

3

Disassembly:

Page 4: Z-MAX 45 Termination Instructions - The Siemon Companyfiles.siemon.com/int-download-installation-instructions/wa_z-max-45_ii.pdfZ-MAX 45 Termination Instructions 13 14 12 1 2 Tip:

©2

01

8S

iem

on

Re

v.B

12

/18

10

0.2

5197

.00

To assist safe installations, comply with the following:A. Use caution when installing or modifying telecommunications circuits.B. Never touch uninsulated wire terminals unless the circuit has been disconnected.C. Never install this device in a wet location.D. Never install wiring during a lightning storm.

Lors de l'installation, respectez les consignes de sécurité suivantes:A. Utiliser avec prudence lors de l'installation ou de la modification circuits detélécommunications.B. Ne jamais toucher les bornes de fil métallique non isolés sauf si le circuit a été débranché.C. Ne jamais installer cet appareil dans un endroit humide.D. Ne jamais installer pendant un orage.

To ensure you have the latestrevision to this document, please visit:

Z-MAX 45 Termination – Alternate Cable types

S/FTPStranded(26 AWG)

Co

ntin

ue

To

Ste

p2

!

4X (Foil)1A 1B 1C 1D 1E

~38 mm(1.5 in)

~13 mm(0.5 in)

~13 mm(0.5 in)

Co

ntin

ue

To

Ste

p2

!

U/FTPSolid

1A 1B

~70 mm(2.75 in)

≤ 6.35 mm(.25 in)

1X(foil)

DrainWire

3X

(foil)

360°2X

*Note for OSP Category 6A shielded cable w/double jacket:Please refer to the supplemental cable preparation instructionsavailable at: www.siemon.com/us/download/installation.aspxand click on WORK AREA.

www.siemon.com

S/FTPandF/FTPSolid(23 AWG)

Co

ntin

ue

To

Ste

p2

!

1A 1B 1C

~64 mm(2.5 in)

F/FTP & S/FTP

F/FTP S/FTP

6.35 mm(.25 in)

6.35 mm(.25 in)

4X(Foil)

F/FTP & S/FTP

S/FTPSolid(22 AWG)

4X (Foil)

~51 mm(2 in)

1A 1B 1C 1D

360°

Note braidwrap direction

Co

ntin

ue

To

Ste

p2

!

~10-12 mm(.4-.5 in)

~13 mm(~.5 in)

~13 mm(~.5 in)

~13 mm(~.5 in)