New Regs – Get Ready for Containment Testing if
You Haven’t Done So Already!
Edward S. Kubinsky Jr.
CROMPCO, LLC
Director of Regulatory Affairs,
Training and Certification
NISTM Conference
10/05/2016
![Page 2: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/2.jpg)
There Are Several Important Changes That Are Coming
Quickly to Owners in MA Due To New MA DEP and
Federal UST Rules. We’re Going To Focus On
Containment Testing (Spill Buckets & Containment Sumps)
![Page 3: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/3.jpg)
Spill Bucket Testing Testing spill buckets for tightness: 1st test is required to be performed by
01/02/2017 for existing UST systems (installed prior to 01/02/2015) and every 5
years thereafter (follow manufacturer’s guidelines, PEI RP 1200 or state
standard)
New spill buckets installed on or after 01/02/2015 must be tested at installation
and every 5 years thereafter
Testing is not applicable for stage I vapor recovery spill buckets
*****Frequency of testing will need to change to at least every 3 years
to comply with the new federal UST regulations*****
![Page 4: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/4.jpg)
GET FAMILIAR WITH THE NEW
STANDARD!!!!!
![Page 5: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/5.jpg)
PEI RP1200
•Overfill Prevention Equipment
•Leak Detection Sensors
•ATGs
•Line Leak Detectors
•Spill buckets
•Containment Sumps
•Tank & Piping Interstitial Spaces
•Shear Valves
•E-Stops
PURPOSE – Provide general
procedures and guidelines for
conducting equipment testing
and inspections to meet the new
EPA regulations and covers:
![Page 6: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/6.jpg)
PEI RP1200
![Page 7: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/7.jpg)
Chapter 6: Covers Spill Bucket
and Containment Sump Testing
![Page 8: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/8.jpg)
Spill Bucket: Hydrostatic Test
![Page 9: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/9.jpg)
Spill Bucket Testing (Hydrostatic)
RP 1200: (hydrostatic)
Clean, inspect and repair defects
Fill cap and adapter seal tightly (or use plumber’s plug)
Drain valve leak tight (or permanently removed)
Fill with water to within 1.5 inches of top
Measure water depth to within 1/16 inch
Wait one hour
Water level must drop less than 1/8 inch
![Page 10: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/10.jpg)
Spill Bucket Testing: Vacuum Test
![Page 11: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/11.jpg)
Spill Bucket Vacuum (Primary)
RP 1200: (vacuum)
Clean, inspect and repair defects
Fill cap and adapter seal tightly (or use plumber’s plug)
Drain valve leak tight (or permanently removed)
Seal test cover to top of spill bucket
Apply vacuum of 30 inches water column
Hold for one minute
If ending vacuum is 26 inches or greater, test passes
![Page 12: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/12.jpg)
Spill Bucket Vacuum (Outer Wall if DW)
RP 1200: (vacuum)
Clean, inspect and repair defects
Attach to secondary access point
Apply vacuum of 15 inches water column
Hold for one minute
If ending vacuum is 12 inches or greater, test passes
![Page 13: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/13.jpg)
Containment Sump Testing TO COMPLY WITH THE NEW MA DEP UST REGULATIONS, ALL
CONTAINMENT SUMPS MUST BE TESTED BY 01/02/2017:
Currently, there is no periodic testing of sumps required after the first test is performed
However, with the new federal UST regulations, owners using interstitial monitoring
(required in MA for DW piping installed on or after 05/28/99) for release detection on their
DW piping will need to eventually test their SUMPS & UDC’S for tightness every 3 years to
comply with the new federal UST regulations (follow manufacturer’s guidelines, PEI RP
1200 or state standard); or
Use a double wall sump/UDC and monitor the interstitial space of the sump/UDC monthly
(and document)
**For UST Systems brought into use on or after 01/02/2015, this must be done at
installation.
![Page 14: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/14.jpg)
Piping Containment Sump Testing (Tank & UDC):
PEI RP 1200
![Page 15: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/15.jpg)
Containment Sump Testing:
Industry Standard PEI RP 1200
RP 1200: (hydrostatic)
Clean, inspect and repair defects
Fill with water to 4” above highest penetration or sidewall seam
Measure water depth to within 1/16 inch
Wait one hour
Water level must drop less than 1/8 inch
![Page 16: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/16.jpg)
Containment Sump Testing (per
MA DEP Regulations):
![Page 17: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/17.jpg)
What happens when MA DEP must incorporate the
new federal UST rules into their rules in order to
continue to remain a SPA state and maintain
approval for their UST program (this must happen by
10/13/18)?
Will containment sump tests that have been
performed only to the level of the sensor be
acceptable?
At what level will future containment tests need to be
performed in MA?
![Page 18: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/18.jpg)
FYI: PEI RP 1200 Committee
to Meet in December 2016 to
Begin Discussions and
Revisions to the Document
![Page 19: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/19.jpg)
What have we learned from experience in another
state when containment testing was first mandated?
![Page 20: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/20.jpg)
MD Wrote a Protocol on 4/26/05 Which is
Very Similar to PEI RP 1200
http://www.mde.state.md.us/programs/Land/OilControl/FactSheetsPublications/Documents/www.mde.
state.md.us/assets/document/OilControl/MD_Contain_System_Training_Protocol.pdf
![Page 21: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/21.jpg)
MD Spill Bucket Testing Data
![Page 22: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/22.jpg)
Containment Sump Testing Will Be Painful in the Beginning
Here’s what MD test data looked like when they first started testing
containment sumps back in 2005/2006 with their new rules.
![Page 23: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/23.jpg)
Containment Sump Testing Will Be Painful in the Beginning
Here’s what MD test data looked like when they first started testing
containment sumps back in 2005/2006 with their new rules.
![Page 24: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/24.jpg)
Containment Sump Testing Will Be Painful in the Beginning
Here’s what MD test data looked like when they first started testing
containment sumps back in 2005/2006 with their new rules.
![Page 25: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/25.jpg)
Tanknology Data (Bill Logue @ NECSEMA 3/16/16)
![Page 26: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/26.jpg)
Tanknology Data (Bill Logue @ NECSEMA 3/16/16)
![Page 27: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/27.jpg)
Containment Sump & Spill
Bucket Testing Data in MA for
2015
![Page 28: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/28.jpg)
Containment Sump & Spill
Bucket Testing Data in MA for
2016
![Page 29: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/29.jpg)
Be Prepared to Repair
![Page 30: You Haven’t Done So Already! · Industry Standard PEI RP 1200 RP 1200: (hydrostatic) Clean, inspect and repair defects Fill with water to 4” above highest penetration or sidewall](https://reader035.fdocuments.in/reader035/viewer/2022071418/611655dbca47082a6e17bbfc/html5/thumbnails/30.jpg)
QUESTIONS?