Yccd Chillers 46 152 Kw

26
YCCD AIR COOLED LIQUID CHILLER R407C REFRIGERANT COOLING CAPACITIES 46 kW to 152 kW YORK YCCD twin refrigerant circuit air cooled liquid chillers are a compact design suitable for chilled water or glycol cooling. YCCD units are available in three versions: YCCD (standard); YCCD LN (low noise operation) and YCCD HT (high temperature operation). YCCD models 60 - 150 of all three versions are available with either user friendly standard control or optional YORK Integrated System Network (ISN) control. YCCD models 170 - 210 are fitted with YORK ISN control as standard. YCCD units are designed to be located outside on the roof of a building or at ground level. The units can be converted into total cooling plants with the field mounted Hydro Kit option. CONTENTS Specification Accessories and Options Controls Operating Limitations Refrigeration Flow Diagram Selection Guide Water Pressure Drops Cooling Capacities Glycol Selection Guide Glycol Cooling Capacities Sound Power Spectrum Physical Data Electrical Data Electrical Connections Dimensions Space Requirements AVAILABLE MODELS & NOMINAL COOLING CAPACITIES TABLE 1 FEATURES BENEFITS Two refrigerant circuits. System stand-by security. Minimum base area/maximum capacity. Minimum installation space. Low weight , single power and control supplies. Easy to install. Full factory run test. Operating quality control. Accessible components. Ideal for maintenance operations Residual current circuit breaker. Operator safety. Microprocessor control with visual display of temperatures and alarms. Simple operation. Manufactured to ISO 9001/EN 29001. High standard of quality control. SPECIFICATION The chillers shall be completely factory assembled with all interconnecting refrigerant piping and wiring ready for field installation. After assembly the YCCD shall have a full test run with water flowing through the evaporator. The YCCD shall be pressure tested, evacuated and fully charged with refrigerant and include an initial oil charge. YCCD LN (Low Noise Version) Very low noise levels are achieved on YCCD LN units without any impact on unit performance or operating limits. The noise reduction is obtained using greater surface area condenser coils and special fan configuration. In addition, on models 60 - 150, the compressor compartment is completely acoustically insulated. Mufflers are mounted on the compressor discharge lines of all models and each compressor is also separately enclosed in an acoustic sound blanket. YCCD HT (High Temperature Version) YCCD HT units are suitable for operation at higher ambient temperatures. The higher ambient limit is obtained using greater surface area condenser coils and high efficiency fans. Page G.1 Doc. No. PC150/01.04/GB 60 75 90 105 120 150 170 190 210 Cooling Capacity (kW) 46.2 53.0 62.9 72.6 88.2 100.5 122.2 135.3 148.6 60 75 90 105 120 150 170 190 210 Cooling Capacity (kW) 47.9 53.4 64.3 70.1 89.8 102.3 118.9 135.6 143.5 60 75 90 105 120 150 170 190 210 Cooling Capacity (kW) 49.6 57.1 67.8 77.6 95.6 109.0 124.0 142.9 151.7 Cooling capacities at 7°C leaving chilled liquid temperature and 35°C condenser air entering temperature. Model Model Model YCCD (Standard) YCCD LN (Low Noise) YCCD HT (High Temperature)

description

xx

Transcript of Yccd Chillers 46 152 Kw

Page 1: Yccd Chillers 46 152 Kw

YCCD

AIR COOLEDLIQUID CHILLERR407C REFRIGERANT

COOLING CAPACITIES46 kW to 152 kW

YORK YCCD twin refrigerant circuit aircooled liquid chillers are a compact designsuitable for chilled water or glycol cooling.

YCCD units are available in threeversions: YCCD (standard); YCCD LN(low noise operation) and YCCD HT (hightemperature operation). YCCD models 60- 150 of all three versions are availablewith either user friendly standard control oroptional YORK Integrated SystemNetwork (ISN) control. YCCD models 170- 210 are fitted with YORK ISN control asstandard.

YCCD units are designed to be locatedoutside on the roof of a building or atground level. The units can be convertedinto total cooling plants with the fieldmounted Hydro Kit option.

CONTENTSSpecification

Accessories and Options

Controls

Operating Limitations

Refrigeration Flow Diagram

Selection Guide

Water Pressure Drops

Cooling Capacities

Glycol Selection Guide

Glycol Cooling Capacities

Sound Power Spectrum

Physical Data

Electrical Data

Electrical Connections

Dimensions

Space Requirements

AVAILABLE MODELS & NOMINAL COOLING CAPACITIES TABLE 1

FEATURES BENEFITSTwo refrigerant circuits. System stand-by security.

Minimum base area/maximum capacity. Minimum installation space.

Low weight , single power and control supplies. Easy to install.

Full factory run test. Operating quality control.

Accessible components. Ideal for maintenance operations

Residual current circuit breaker. Operator safety.

Microprocessor control with visual display of temperaturesand alarms.

Simple operation.

Manufactured to ISO 9001/EN 29001. High standard of quality control.

SPECIFICATIONThe chillers shall be completely factory assembled with all interconnectingrefrigerant piping and wiring ready for field installation. After assembly the YCCDshall have a full test run with water flowing through the evaporator. The YCCD shallbe pressure tested, evacuated and fully charged with refrigerant and include aninitial oil charge.

YCCD LN (Low Noise Version)Very low noise levels are achieved on YCCD LN units without any impact on unitperformance or operating limits. The noise reduction is obtained using greatersurface area condenser coils and special fan configuration. In addition, on models60 - 150, the compressor compartment is completely acoustically insulated. Mufflersare mounted on the compressor discharge lines of all models and each compressoris also separately enclosed in an acoustic sound blanket.

YCCD HT (High Temperature Version)YCCD HT units are suitable for operation at higher ambient temperatures. Thehigher ambient limit is obtained using greater surface area condenser coils and highefficiency fans.

Page G.1Doc. No. PC150/01.04/GB

60 75 90 105 120 150 170 190 210Cooling Capacity (kW) 46.2 53.0 62.9 72.6 88.2 100.5 122.2 135.3 148.6

60 75 90 105 120 150 170 190 210Cooling Capacity (kW) 47.9 53.4 64.3 70.1 89.8 102.3 118.9 135.6 143.5

60 75 90 105 120 150 170 190 210Cooling Capacity (kW) 49.6 57.1 67.8 77.6 95.6 109.0 124.0 142.9 151.7

Cooling capacities at 7°C leaving chilled liquid temperature and 35°C condenser

air entering temperature.

Model

Model

Model

YCCD (Standard)

YCCD LN (Low Noise)

YCCD HT (High Temperature)

Page 2: Yccd Chillers 46 152 Kw

The unit structure shall be of heavy gauge galvanised steelfastened with stainless steel screws and bolts. Galvanised steelparts shall be painted with baked-on powder paint (Desert Sand(RAL1019)). The unit base is riveted and all internal sheet metalpanels are not painted (60 to 150 only).

CompressorsYCCD models 60-75-120-150 shall have two hermeticreciprocating compressors with internal motor protectionhoused in a separate acoustically lined enclosure.

YCCD models 90-105-170-190-210 shall have scrollcompressors.

Compressors on all models shall be mounted on rubberanti-vibration pads and have direct on line starting.

The compressor motors shall be refrigerant gas cooled, withintegral thermistor protection against overloads. The overloadprotection is automatically reset after approximately 8 seconds.

The motor terminal boxes shall have IP-54 weather protection.

The compressors shall be switched On and Off by the unitmicroprocessor to provide capacity control.

EvaporatorThe evaporator shall be a stainless steel plate type heatexchangers thermally insulated with flexible closed cell material.Design working pressure shall be 10 bar g on the water side and30 bar g on the refrigerant side. An electric heater mat andevaporator differential pressure switch shall be provided forfreeze protection.

Water connection to the evaporator is via 2 inch gasconnections. A bleed valve is provided on the evaporatorpipework.

Refrigerant CircuitsTwo refrigerant circuits shall be provided and each circuit shallinclude: service valves for refrigerant charging, discharge andliquid line isolating valves, a sight glass with moisture indicator, afilter dryer and a thermostatic expansion valve.

On models 60 - 150 high and low pressure switches shall also beprovided.

On models 170 - 210 transducers and switches shall be includedon the high pressure circuits and transducers shall be providedon the low pressure circuits.

Air Cooled CondensersThe condenser coils shall be seamless copper tubes, arrangedin staggered rows, mechanically expanded into corrugatedaluminium fins. Design working pressure of the coils shall be28 bar g.

All YCCD models shall have a stepless fan speed controllerfitted as standard. When standard control is fitted, the controlleroperates on the basis of ambient air temperature allowingoperation down to -5°C ambient air temperature. When ISNcontrol is fitted, the controller operates on the basis ofcondensing pressure with operation possible down to -18°Cambient air temperature.

The condenser fans shall be direct drive with aluminium aerofoilblades. Each fan will have a painted galvanised steel protectionguard. The totally enclosed fan motors shall have IP-54 weatherprotection and thermocontact protection embedded in theirwindings.

Power and Control PanelAll controls and motor starting equipment necessary for full unitoperation shall be factory wired and tested.

Power and control components are accessed via individualdoors on YCCD models 60 to150.

The control compartment shall contain an electronic circuitboard and a soft touch key control panel with display ofoperating functions, alarms and stops.

The power compartment shall have a door interlocked isolatorand shall contain compressor and fan contactors, fuses andsupply protection.

Page G.2Doc. No. PC150/01.04/GB

ACCESSORIES AND OPTIONSIntegrated System Network (ISN) ControlA YORK Integrated System Network (ISN) control is fitted as standardon YCCD models 170 - 210 and is available as an option on models 60 -150. The ISN control offers Building Management System (BMS)communication, leaving chilled liquid temperature or entering chilledliquid temperature control, sequence control, double setpoint, displayand print of unit operational and history data alarm history.

ISN Control - EMS Offset Card (Temperature Reset/Offset)Additional PCB allowing alternative signals to be used from customerEMS to unit controls to perform remote liquid leaving temperaturesetpoint reset/offset function. Suitable for water and glycol controlranges (cannot be fitted when a sequence control is fitted).

ISN Control - Sequence and Automatic Lead/Lag ControlSequencing control centre to manage sequencing control of up to eightunits in parallel based on mixed liquid temperature, interconnectingwiring by others (cannot be fitted when an EMS offset card is fitted).

Remote On/Off Kit (YCCD 60 - 150 Standard Control only)The kit allows remote activation of the cooling mode when the YCCD unitis in stand-by.

The kit contains a remote control with 3 metre cable for wall mounting,additional PCB for LED control and full installation instructions.

Hydro KitThe field installed YORK Hydro Kit is a hydraulic package complete withall components required for the correct operation of a liquid distributioncircuit. The Hydro Kit can be combined directly on YCCD models 60 -150 or remotely on all models.

The Hydro Kit is fully enclosed and comprises: a buffer tank, pump(s),expansion tank(s), filter, pressure gauge, shut-off valves, safety valve,automatic vent valve, drain valve, charge valve, safety valve for systemdischarge and electrical panel (if selected, optional water filter is notavailable).

Flow SwitchSupplied loose for field installation by contractor.

Water filterA field mounted water filter for fitting in the customers water circuit (notavailable if Hydro Kit is selected).

Anti-vibration MountsOpen spring isolator mounts with fixing down holes, for field installation.

High Pressure Fans (only available on Standard Units withISN Control)Alternative fans suitable for external static pressures up to 80 Pa.

Condenser Coil ProtectionCopper Fin Condenser Coils - Condenser coils are constructed withcopper fins (ASTM 287 Test, after 1500 hours 17% weight loss).

Gold Epoxy Coated Aluminium Condenser Fins - Offers corrosionresistance in mild seashore locations (Acetic acid spray test ASTM, after1500 hours 7% weight loss).

Condenser Coil GuardsPainted galvanised steel wire guards mounted on the unit exterior.

Gauge Kit (YCCD 60 - 150 Standard Control only)Factory fitted mechanical dial gauges for suction and dischargepressure indication of each refrigerant circuit.

Page 3: Yccd Chillers 46 152 Kw

ISN CONTROL (Standard YCCD 170 - 210, optional YCCD 60 - 150)

The panel shall contain:

• A 40 character Liquid Crystal Display (LCD) with LightEmitting Diode (LED) back lighting for outdoor viewing.

• A Colour coded 12-button keypad.• Customer terminal block for control inputs and liquid flow

switch.The microprocessor control will include:

Status Key for display of:• Status of the unit and each refrigerant circuit• System and unit safety fault messages

Display/Print Keys for display of:• Chilled liquid and ambient air temperatures• System pressures (each circuit)• Operating hours and starts (each compressor)• Load and unload timers and cooling demand• Liquid pump, evaporator heater and condenser fan status

Print calls up to the liquid crystal display:

• Operating data for the systems• History of fault shutdown data for up to the last six fault

shutdown conditions

An RS-232 port, in conjunction with this press-to-print button, isprovided to allow hard copy print-outs via a separate printer.

Entry Keys• To program and modify system values

Setpoints Keys for programming:• Chilled liquid temperature setpoint and range• Remote reset temperature range• Set daily schedule/holiday for start/stop• Manual override for servicing• Cut-outs for low ambient temperature, low liquid temperature,

high discharge pressure and low suction pressure• Number of compressors and anti-recycle timer (compressor

start cycle time)

Unit Keys• To set time and unit options

Unit ON/OFF switch• To activate or deactivate the unit

Page G.3Doc. No. PC150/01.04/GB

+

-

IN

OUT

SET

P

P

-P

-P

H 02

H 02

Circuit 1 System

Setpoints Display

Circuit 2

®

1 2 3 5 6

789101112131415

4

STANDARD CONTROL (YCCD 60 - 150 only)

Standard Control Panel

1 Setpoint selection and display key and LED 10 External interlock alarm LED.2 Setpoint change key (-). Decreases desired water temperature. 11 Antifreeze alarm.3 Setpoint change key (+). Increases desired water temperature. 12 Low pressure alarm LED.4 Display 13 High pressure alarm LED.5 Inlet water display and LED. 14 Compressor ON LED.6 Outlet water display and LED. 15 Start-up key and LED.7 Start key and LED - Cooling. 16 Voltage ON LED.8 Not used. 17 Unit alarm activated LED.9 Voltage ON LED. 18 Start key and LED - Cooling.

®®

1617

18

Remote On/Off Panel (Optional)

OPER DATA

Control CenterTM

COOLINGSETPOINTS

PRINT SCHEDULE/ADVANCE DAY

HISTORY PROGRAM

ON OFF

UnitSetpoints

Millennium

EntryDisplay/Print

ENTER/ADV

OPTIONS

CLOCK

STATUSS Y S 1 COMP RUNNI NG

S Y S 2 COMP RUNNI NG

ISN Millennium™ Control Center Panel

Page 4: Yccd Chillers 46 152 Kw

The microprocessor control system is capable of displaying thefollowing:

• Return and leaving liquid temperature• Low leaving liquid temperature cutout setting• Low ambient temperature cutout setting• Ambient air temperature• Metric or Imperial data• Discharge and suction pressure cutout settings• System suction pressures• System discharge pressures• Anti-recycle timer status• Anti-coincident system start timer condition• Compressor run status• No cooling load condition• Day, date and time• Daily start/stop times• Holiday status• Automatic or manual system lead/lag control• Lead system definition

• Compressor starts & operating hours (each compressor)• Status of evaporator heater and fan operation• Run permissive status• Number of compressors running• Load & unload timer status• Water pump status• Liquid Temperature Reset via a YORK ISN DDC or Building

Automation System (by others)Provision shall be included for optional remote chilled liquidtemperature reset.

The operating program will be stored in non-volatile memory(EPROM) to eliminate chiller failure due to AC powerfailure/battery discharge. Programmed setpoints shall beretained in lithium battery backed RTC memory.

Page G.4Doc. No. PC150/01.04/GB

60 75 90 105Min. Max. Min. Max. Min. Max. Min. Max.

Chilled Liquid outlet Water outlet °CLiquid temperature Brine outlet °C

Temperature spread °K

Flow rate (1) l/s 1.38 3.68 1.58 4.22 1.79 4.77 2.13 5.67

Pressure drop (1) kPa 8.4 54.6 9.5 62.6 8.9 58.4 9.9 65.8Maximum operating pressure bar 10 (6 bar with Hydro Kit)

Ambient Air entering Standard control °CAir temperature ISN control °C

External static Standard fans Pa 0pressure High pressure fans (4) Pa 80

Recommended system chilled water volume (2) l 420 480 510 560

Minimum capacity step % 50%Power supply voltage (5) V

Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.Chilled Liquid outlet Water outlet °C +6 to +15Liquid temperature Brine outlet °C -8 to +15

Temperature spread °K 3 to 8

Flow rate (1) l/s 2.63 7.02 3.00 8.00 3.64 9.69 4.00 10.67 4.45 11.86

Pressure drop (1) kPa 7.9 72.0 19.9 155.4 14.8 105.8 16.1 114.1 19.9 141.7Maximum operating pressure bar 10 (6 bar with Hydro Kit)

Ambient Air entering Standard control °CAir temperature ISN control °C

External static Standard fans Pa 0pressure High pressure fans (4) Pa 80

Recommended system chilled water volume (2) lMinimum capacity step %

Power supply voltage (5) V(1) Total unit flow rate and pressure drop are givenCaution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.(2) Table shows minimum water / brine volume of system(3) Maximum ambient air temperature depends on coding:

Standard/Low Noise Units: 43°CHigh Temperature units: 45°C

(4) Optional high pressure fans only available on standard YCCD units with ISN control(5) Voltage 400V +/- 10%

400 V, 3 Ø, 50 Hz (nominal)

YCCD

YCCD170 190120 150

915800 55050%

+6 to +15-8 to +15

3 to 8

400 V, 3 Ø, 50 Hz (nominal)

-5 to + see note (3)-18 to + see note (3)

210

Not available-18 to + see note (3)

-5 to + see note (3)-18 to + see note (3)

57525%25%20%

475

TABLE 2 OPERATING LIMITATIONS

Page 5: Yccd Chillers 46 152 Kw

SELECTION GUIDEDATA REQUIREDTo select a YORK YCCD chiller the following information isrequired:

1. Required cooling capacity.2. Design chilled liquid entering and leaving temperatures.3. Design chilled liquid flow rate.4. Design condenser entering air temperature. This will normally

be the design summer ambient air temperature unlesslocation or other factors have an influence.

5. Altitude above sea level.6. Design Cooler fouling factor.

Note: Items 1, 2 and 3 must be linked by the following formulae:

Cooling capacity (kW) = Flow Rate (l/h) x Range (°C)860

Where:Range = Entering chilled liquid temperature - leaving chilledliquid temperature.

YCCD SAMPLE SELECTIONA R407C chiller is required to cool water from 13°C to 7°Chaving a cooling capacity of 60 kW.

Other design conditions applying are:

Ambient air entering condenser: 35°CFouling factor: 0.044 m² °C/kWAltitude: Sea level

From a cursory examination of capacity Table 5 a model YCCD90 gives approximately the required capacity of 60.0 kW.

No correction factors, for fouling factor or altitude, applytherefore the conditions will be as follows:

Cooling capacity: 60.0 kWTotal unit input power: 26.3 kWWater temperature: 13 °C to 7 °CWater flow rate 60.0 = 2.38 l/s

4.187 x 6Cooler pressure drop = 16 kPa (see Figure 2).

Notes:

The optional strainer limits the unit maximum flow rate to10.4 litres per second.

The pressure drops given are for the strainer component only.They do not include the pressure drop of any other piping orfittings required to mount the strainer. The strainer is to beinstalled by others.

For glycol operation, the pressure drop correction factors foreither ethylene or propylene glycol solutions need to be appliedas shown in the pressure drop correction graphs.

Page G.5Doc. No. PC150/01.04/GB

YCCD Models 60 -150

REFRIGERANT FLOW DIAGRAM FIGURE 1

YCCD Cooling ModeLow pressure liquid refrigerant enters the cooler (Evaporator) and is evaporated and superheated by the heat energy absorbed fromthe chilled water passing through the cooler plates. Low pressure vapour enters the compressor where pressure and superheat areincreased. Heat is rejected via the air cooled condenser coil and fans. The fully condensed and subcooled liquid refrigerant thenenters the expansion valve where pressure reduction and further cooling takes place before returning to the cooler.

COOLERFouling Factor m² °C/kW Capacity Factor Comp. Input Factor

0.044 1.000 1.0000.088 0.987 0.9950.176 0.964 0.9850.352 0.926 0.962

FOULING FACTOR TABLE 3

Altitude (m) Capacity Factor Comp. Input Factor0 1.000 1.000

600 0.987 1.0101200 0.973 1.0201800 0.958 1.0292400 0.943 1.038

ALTITUDE FACTORS TABLE 4

YCCD Models 170 -210

Note: Only one refrigerant circuit shown.

Model Pressure Drop Calculation60 Pressure Drop [kPa] = 4.5429 x (Flow Rate [l/s]1.9084)

75 Pressure Drop [kPa] = 3.9487 x (Flow Rate [l/s]1.9192)

90 Pressure Drop [kPa] = 2.9111 x (Flow Rate [l/s]1.9194)

105 Pressure Drop [kPa] = 2.2928 x (Flow Rate [l/s]1.9346)

120 Pressure Drop [kPa] = 0.8962 x (Flow Rate [l/s]2.2508)

150 Pressure Drop [kPa] = 1.9910 x (Flow Rate [l/s]2.0955)

170 Pressure Drop [kPa] = 1.1043 x (Flow Rate [l/s]2.0089)

190 Pressure Drop [kPa] = 1.0120 x (Flow Rate [l/s]1.9959)

210 Pressure Drop [kPa] = 1.0012 x (Flow Rate [l/s]2.0025)

PRESSURE DROP CALCULATIONS

Item Pressure Drop Calculation2"/50 mm strainer Pressure Drop [kPa] = 1.0568 x Flow Rate [l/s]1.9334

Page 6: Yccd Chillers 46 152 Kw

Page G.6Doc. No. PC150/01.04/GB

1

FLOW RATE (l/s)

PR

ES

SU

RE

DR

OP

(kP

a)

27

10

20

30

40

50

60

70

8090

100

120

140

160

3 4 5 6 7 8 9 10 11 12

60

75 90105

120

150

170190

210

210

190

FIGURE 2 YCCD MODELS 60 TO 210

YCCD WATER PRESSURE DROPS

1

FLOW RATE (l/s)

2 3 4 5 6 7 8 9 10 11 12

PR

ES

SU

RE

DR

OP

(kP

a)

7

10

20

30

40

50

60

70

8090

100

120

140

160180200220

60

7590

150

105

120

170210190

190

210

FIGURE 2A YCCD MODELS 60 TO 210 WITH OPTIONAL STRAINER FITTED

Page 7: Yccd Chillers 46 152 Kw

Page G.7Doc. No. PC150/01.04/GB

LCLT Cool Power Cool Power Cool Power Cool Power Cool Power Cool Power

°C kW kW kW kW kW kW kW kW kW kW kW kW

6 53.4 18.5 48.9 19.0 47.1 19.2 44.4 19.4 39.8 19.7 37.1 20.07 55.3 18.9 50.9 19.4 49.0 19.5 46.2 19.8 41.5 20.0 38.9 20.4

8 57.3 19.2 52.7 19.8 50.9 19.9 48.1 20.1 43.3 20.4 40.6 20.710 61.1 19.8 56.4 20.4 54.5 20.6 51.6 20.8 46.8 21.1 44.0 23.3

12 64.7 20.3 59.9 21.0 57.9 21.5 55.0 21.5 50.0 21.8 47.1 22.215 70.5 21.4 65.4 22.1 63.4 22.5 60.4 22.6 55.2 22.8 0.0 0.0

6 61.2 21.6 56.1 22.2 54.0 22.4 50.9 22.6 45.6 23.0 42.5 23.47 63.4 22.0 58.3 22.6 56.2 22.8 53.0 23.1 47.6 23.4 44.6 23.8

8 65.7 22.4 60.4 23.1 58.3 23.3 55.1 23.5 49.6 23.8 46.5 24.110 70.1 23.2 64.7 23.8 62.5 24.1 59.2 24.3 53.6 24.6 50.4 27.2

12 74.2 23.7 68.7 24.5 66.4 25.1 63.1 25.1 57.3 25.2 0.0 0.015 80.8 25.0 75.0 25.8 72.7 26.3 69.2 26.4 0.0 0.0 0.0 0.0

6 66.8 21.6 64.1 23.5 62.9 24.3 61.1 25.5 54.6 27.7 50.8 29.17 68.8 21.9 66.0 23.8 64.7 24.6 62.9 25.8 56.2 28.0 52.3 29.3

8 70.7 22.2 67.9 24.1 66.6 24.9 64.7 26.2 57.8 28.3 53.9 29.710 74.7 22.9 71.8 24.8 70.4 25.6 68.4 26.9 61.2 29.1 0.0 0.0

12 78.8 23.6 75.6 25.5 74.2 26.4 72.2 27.6 64.5 29.8 0.0 0.0

15 85.1 24.6 81.6 26.7 80.1 27.5 77.9 28.8 0.0 0.0 0.0 0.0

6 75.7 25.2 73.3 27.5 72.2 28.5 70.5 30.0 64.8 32.6 61.3 34.47 77.9 25.4 75.3 27.8 74.2 28.8 72.6 30.3 66.6 33.0 63.0 34.7

8 79.9 26.0 77.3 28.4 76.1 29.4 74.4 30.9 68.3 33.7 64.6 35.410 83.7 27.2 81.1 29.6 79.9 30.7 78.0 32.2 71.6 35.0 0.0 0.0

12 87.6 28.4 84.9 30.9 83.6 32.0 81.6 33.6 75.0 36.5 0.0 0.015 93.4 30.3 90.5 33.0 89.1 34.1 87.1 35.8 0.0 0.0 0.0 0.0

6 101.9 35.6 93.3 36.6 89.9 36.9 84.6 37.4 75.8 38.0 70.7 38.67 105.5 36.3 97.0 37.3 93.4 37.7 88.2 38.1 79.2 38.6 74.2 39.2

8 109.3 37.0 100.5 38.1 97.0 38.4 91.6 38.8 82.6 39.3 77.4 39.810 116.6 38.2 107.6 39.4 103.9 39.7 98.4 40.1 89.2 40.6 0.0 0.0

12 123.4 39.2 114.2 40.5 110.5 41.4 104.9 41.4 0.0 0.0 0.0 0.015 134.4 41.2 124.8 42.6 121.0 43.4 115.1 43.5 0.0 0.0 0.0 0.0

6 116.1 43.7 106.3 45.0 102.4 45.4 96.5 45.9 86.4 46.6 80.5 47.47 120.3 44.6 110.5 45.9 106.5 46.3 100.5 46.8 90.2 47.5 84.5 48.2

8 124.6 45.5 114.6 46.8 110.5 47.2 104.4 47.7 94.1 48.2 88.2 48.910 132.8 46.9 122.6 48.3 118.4 48.8 112.2 49.3 101.6 49.9 0.0 0.0

12 140.6 48.1 130.2 49.7 125.9 50.8 119.5 50.8 0.0 0.0 0.0 0.015 153.1 50.6 142.2 52.3 137.8 53.3 131.2 53.5 0.0 0.0 0.0 0.0

6 133.1 41.7 126.0 45.5 123.0 47.2 118.4 49.7 108.5 54.6 102.6 57.77 137.2 42.1 129.9 46.0 126.8 47.6 122.2 50.2 112.0 55.1 105.9 58.1

8 140.1 43.0 132.9 47.1 129.5 48.5 124.7 51.1 114.4 56.1 108.0 59.210 145.7 44.7 137.9 48.8 134.7 50.4 129.8 53.2 119.0 58.2 112.5 61.3

12 151.1 46.5 143.1 50.6 139.7 52.4 134.7 55.2 123.5 60.4 116.7 63.515 158.8 49.3 150.4 53.6 147.0 55.5 141.7 58.4 130.2 63.9 123.2 67.1

6 146.6 48.5 139.0 52.8 135.9 54.6 131.2 57.3 120.3 62.2 113.7 65.27 151.0 49.2 143.4 53.4 140.1 55.2 135.3 57.9 124.0 62.8 117.2 65.9

8 155.1 50.3 147.2 54.6 143.9 56.4 139.0 59.2 127.4 64.0 120.4 67.210 163.3 52.5 155.1 56.9 151.6 58.8 146.4 61.7 134.2 66.6 126.9 69.8

12 171.7 54.9 162.9 59.4 159.3 61.4 153.8 64.2 141.1 69.3 116.7 63.515 184.2 58.7 174.9 63.3 171.0 65.3 165.2 68.3 151.5 73.5 123.2 67.1

6 162.0 50.4 153.3 54.9 149.7 56.8 144.2 59.7 132.2 65.3 125.1 68.77 167.1 51.1 158.0 55.6 154.3 57.4 148.6 60.4 136.3 66.0 128.9 69.4

8 170.2 52.2 161.1 56.7 157.4 58.7 151.6 61.7 139.1 67.4 131.5 70.810 176.7 54.5 167.2 59.2 163.5 61.1 157.5 64.2 144.4 70.1 136.6 73.6

12 183.0 56.8 173.2 61.7 169.1 63.7 163.1 66.8 149.7 72.9 141.6 76.515 191.9 60.7 181.8 65.6 177.5 67.7 171.2 71.0 157.1 77.4 148.8 81.0

0.0 Data out of the operating limits

LCLT: Leaving chilled liquid temperature Cool kW: Cooling capacityPower kW: Unit power input, including the power input of the compressors, fans, control circuit

and power input of the liquid pump to overcome unit pressure drop.

YCCD 210

Model

YCCD 150

YCCD 60

YCCD 75

YCCD 90

YCCD 120

YCCD 105

YCCD 190

YCCD 170

40 43Condenser Entering Air Temperature °C

25 30 32 35

YCCD COOLING CAPACITIES (Standard Units) TABLE 5

Page 8: Yccd Chillers 46 152 Kw

Page G.8Doc. No. PC150/01.04/GB

LCLT Cool Power Cool Power Cool Power Cool Power Cool Power Cool Power

°C kW kW kW kW kW kW kW kW kW kW kW kW

6 55.3 18.6 50.7 19.2 48.8 19.3 46.0 19.6 41.2 19.9 38.4 20.27 57.3 19.0 52.7 19.5 50.8 19.7 47.9 19.9 43.0 20.2 40.3 20.5

8 59.4 19.4 54.6 19.9 52.7 20.1 49.8 20.3 44.9 20.6 42.0 20.910 63.3 20.0 58.5 20.6 56.5 20.8 53.5 21.0 48.5 21.3 45.6 23.5

12 67.1 20.5 62.1 21.2 60.0 21.7 57.0 21.7 51.8 22.0 48.8 22.415 73.0 21.6 67.8 22.3 65.7 22.7 62.6 22.8 57.2 23.0 54.1 21.7

6 61.8 21.8 56.6 22.5 54.5 22.7 51.3 22.9 46.0 23.3 42.8 23.67 64.0 22.3 58.8 22.9 56.7 23.1 53.4 23.4 48.0 23.7 45.0 24.1

8 66.3 22.7 60.9 23.3 58.8 23.5 55.6 23.8 50.1 24.1 46.9 24.410 70.7 23.4 65.2 24.1 63.0 24.4 59.7 24.6 54.1 24.9 50.8 27.512 74.8 24.0 69.3 24.8 67.0 25.4 63.6 25.4 57.8 25.7 54.5 26.215 81.5 25.3 75.7 26.1 73.3 26.6 69.8 26.7 63.8 26.9 60.3 25.4

6 68.5 22.2 65.7 24.1 64.5 24.9 62.7 26.2 56.0 28.4 52.1 29.87 70.4 22.4 67.5 24.3 66.2 25.2 64.3 26.4 57.5 28.6 53.6 30.0

8 72.5 22.8 69.6 24.8 68.3 25.6 66.3 26.8 59.3 29.0 55.2 30.510 76.7 23.5 73.6 25.4 72.2 26.3 70.1 27.6 62.8 29.8 60.2 29.412 80.8 24.2 77.5 26.2 76.1 27.1 73.9 28.3 66.1 30.6 60.2 29.415 87.2 25.3 83.6 27.4 82.1 28.2 79.8 29.6 71.4 31.8 66.7 28.5

6 73.2 26.9 70.9 29.4 69.8 30.5 68.2 32.1 62.6 34.9 59.2 36.87 75.3 27.2 72.7 29.7 71.7 30.8 70.1 32.5 64.3 35.3 65.3 37.3

8 77.0 27.9 74.6 30.4 73.4 31.5 71.7 33.2 65.8 36.1 70.0 35.510 80.5 29.2 78.0 31.8 76.8 33.0 75.0 34.7 74.3 34.9 65.3 37.3

12 84.0 30.6 81.4 33.3 80.2 34.5 78.3 36.2 74.3 34.9 70.0 35.515 89.2 32.7 86.4 35.6 85.1 36.8 83.2 38.6 82.0 36.5 77.5 34.4

6 103.7 35.4 95.0 36.4 91.5 36.7 86.2 37.2 77.2 37.8 72.0 38.37 107.5 36.1 98.7 37.1 95.2 37.5 89.8 37.9 80.6 38.4 75.5 39.0

8 111.3 36.8 102.4 37.8 98.8 38.2 93.3 38.6 84.1 39.0 78.8 39.610 118.7 38.0 109.5 39.1 105.8 39.5 100.2 39.9 90.8 40.4 85.4 44.6

12 125.7 39.0 116.3 40.3 112.5 41.2 106.8 41.2 97.1 41.7 91.5 42.515 136.8 41.0 127.1 42.4 123.2 43.2 117.2 43.3 107.2 43.7 101.3 41.1

6 118.2 43.0 108.3 44.2 104.3 44.6 98.2 45.2 88.0 45.9 82.0 46.67 122.5 43.9 112.5 45.1 108.4 45.5 102.3 46.0 91.9 46.7 86.1 47.4

8 126.8 44.7 116.6 46.0 112.5 46.4 106.3 46.9 95.8 47.4 89.8 48.110 135.2 46.2 124.8 47.6 120.6 48.0 114.2 48.5 103.5 49.1 97.3 54.2

12 143.2 47.3 132.5 48.9 128.2 50.0 121.7 50.0 110.7 50.7 104.2 51.615 155.9 49.8 144.8 51.5 140.3 52.4 133.6 52.6 122.2 53.1 115.4 50.0

6 129.6 43.9 122.6 47.9 119.7 49.6 115.2 52.4 105.6 57.2 99.9 60.47 133.6 44.3 126.4 48.4 123.4 50.2 118.9 52.9 109.0 57.8 103.0 60.8

8 136.4 44.8 129.1 48.9 126.0 50.6 121.4 53.3 111.3 58.2 105.2 61.410 141.7 45.6 134.2 49.8 131.1 51.6 126.3 54.4 115.8 59.2 109.5 62.4

12 147.0 46.6 139.2 50.8 136.0 52.6 131.1 55.3 120.2 60.3 113.7 63.515 154.5 48.1 146.4 52.3 143.1 54.0 137.8 56.9 126.7 62.0 119.9 65.1

6 146.8 48.2 139.3 52.5 136.2 54.3 131.5 57.0 120.5 61.7 113.9 64.87 151.3 48.9 143.6 53.1 140.4 54.9 135.6 57.6 124.3 62.3 117.4 65.4

8 155.4 49.9 147.5 54.2 144.1 56.0 139.2 58.8 127.6 63.6 120.6 66.710 163.5 52.2 155.3 56.6 151.8 58.4 146.5 61.3 134.4 66.2 127.1 69.4

12 171.8 54.6 163.1 59.1 159.4 61.0 154.0 63.8 141.2 68.9 113.7 62.915 184.3 58.3 174.9 63.0 171.1 64.9 165.3 67.9 151.6 73.0 119.9 64.4

6 156.4 52.4 148.1 57.2 144.5 59.1 139.2 62.2 127.7 68.1 120.8 71.77 161.2 53.2 152.5 57.9 148.9 59.8 143.5 62.9 131.7 68.9 124.5 72.4

8 164.4 54.2 155.6 59.1 152.0 61.1 146.4 64.2 134.3 70.2 127.0 73.810 170.6 56.6 161.4 61.5 157.8 63.6 152.1 66.8 139.4 73.0 131.9 76.7

12 176.7 59.1 167.3 64.2 163.3 66.2 157.5 69.5 144.5 75.9 136.7 78.915 185.3 63.0 175.5 68.1 171.4 70.4 165.3 73.8 151.7 80.6 143.7 83.4

0.0 Data out of the operating limits

LCLT: Leaving chilled liquid temperature Cool kW: Cooling capacityPower kW: Unit power input, including the power input of the compressors, fans, control circuit

and power input of the liquid pump to overcome unit pressure drop.

YCCD 150 LN

YCCD 170 LN

YCCD 210 LN

YCCD 60 LN

YCCD 75 LN

YCCD 90 LN

YCCD 105 LN

YCCD 120 LN

YCCD 190 LN

Model

Condenser Entering Air Temperature °C25 30 32 35 40 43

TABLE 6 YCCD LN COOLING CAPACITIES (Low Noise Units)

Page 9: Yccd Chillers 46 152 Kw

Page G.9Doc. No. PC150/01.04/GB

LCLT Cool Power Cool Power Cool Power Cool Power Cool Power Cool Power

°C kW kW kW kW kW kW kW kW kW kW kW kW

6 54.1 18.3 50.5 18.8 49.1 19.0 47.2 19.2 42.7 19.5 37.8 20.37 56.8 18.7 53.1 19.2 51.6 19.4 49.6 19.6 44.6 19.9 39.8 20.3

8 59.6 19.0 55.7 19.6 54.1 19.7 51.6 20.0 46.5 20.2 41.6 20.610 65.1 19.7 60.6 20.2 58.5 20.4 55.4 20.6 50.2 20.9 45.2 21.4

12 69.5 20.2 64.3 20.8 62.2 21.3 59.1 21.3 53.7 21.6 48.5 22.215 75.7 21.2 70.3 21.9 68.1 22.3 64.8 22.4 59.3 22.6 53.8 23.3

6 62.2 21.0 58.2 21.6 56.5 21.8 54.3 22.0 49.1 22.4 43.5 23.37 65.4 21.4 61.1 22.0 59.4 22.2 57.1 22.4 51.3 22.8 45.8 23.3

8 68.6 21.8 64.1 22.4 62.3 22.6 59.4 22.9 53.5 23.1 47.8 23.610 74.9 22.5 69.7 23.2 67.3 23.4 63.8 23.6 57.8 23.9 52.0 24.5

12 80.0 23.1 74.0 23.8 71.6 24.4 68.0 24.4 61.8 24.7 55.8 25.415 87.1 24.3 80.9 25.1 78.4 25.6 74.6 25.6 68.2 25.9 61.9 26.6

6 71.9 20.9 68.9 22.7 67.7 23.5 65.8 24.6 58.7 26.7 52.0 28.97 74.1 21.1 71.1 22.9 69.8 23.7 67.8 24.8 60.6 26.9 53.6 29.1

8 76.3 21.4 73.3 23.2 71.9 24.0 69.9 25.1 62.4 27.2 55.3 29.410 81.0 21.9 77.8 23.7 76.3 24.5 74.1 25.7 66.3 27.7 58.7 30.0

12 85.7 22.5 82.2 24.4 80.7 25.1 78.5 26.3 70.2 28.4 62.2 30.615 93.0 23.4 89.3 25.3 87.6 26.1 85.2 27.3 76.2 29.3 67.4 31.6

6 81.0 23.8 78.5 26.0 77.3 26.9 75.5 28.4 69.3 30.8 63.0 33.47 83.3 23.9 80.5 26.1 79.4 27.0 77.6 28.4 71.2 30.9 64.9 33.5

8 85.7 24.4 83.0 26.6 81.7 27.6 79.8 29.0 73.2 31.5 66.7 34.110 90.1 25.4 87.3 27.7 86.0 28.7 84.0 30.1 77.1 32.7 70.2 35.3

12 94.7 26.4 91.7 28.8 90.3 29.8 88.2 31.3 81.1 33.9 73.8 36.515 101.4 28.1 98.2 30.5 96.7 31.5 94.5 33.1 86.8 35.8 83.6 37.8

6 104.2 35.9 97.4 36.9 94.6 37.2 91.0 37.6 82.3 38.2 72.9 39.87 109.5 36.6 102.3 37.6 99.5 37.9 95.6 38.4 85.9 38.9 76.7 39.8

8 114.8 37.3 107.3 38.3 104.3 38.7 99.4 39.1 89.6 39.5 80.1 40.410 125.4 38.5 116.7 39.6 112.7 40.0 106.8 40.4 96.7 40.9 87.0 42.0

12 133.9 39.4 123.9 40.8 119.9 41.7 113.8 41.7 103.5 42.2 93.4 43.415 145.8 41.5 135.4 42.9 131.2 43.7 124.9 43.8 114.2 44.2 103.7 45.5

6 118.7 44.4 110.9 44.4 107.8 46.1 103.7 46.6 93.7 47.4 83.0 49.37 124.8 45.3 116.6 45.3 113.3 47.0 109.0 47.5 97.9 48.2 87.4 49.3

8 130.8 46.1 122.2 46.1 118.8 47.9 113.3 48.4 102.1 49.0 91.3 50.010 142.9 47.7 133.0 47.7 128.5 49.5 121.7 50.1 110.2 50.6 99.1 52.0

12 152.5 48.9 141.2 48.9 136.6 51.6 129.6 51.6 117.9 52.3 106.4 53.715 166.1 51.4 154.3 51.4 149.5 54.1 142.3 54.3 130.2 54.8 118.2 56.4

6 135.2 41.6 127.9 45.2 124.9 46.9 120.2 49.4 110.2 54.4 104.2 57.37 139.3 41.9 131.5 45.7 128.7 47.4 124.0 49.9 113.7 54.8 107.5 57.7

8 142.3 42.8 134.6 46.7 131.4 48.2 126.6 50.9 116.1 55.7 109.7 58.910 147.9 44.5 140.0 48.5 136.8 50.2 131.7 52.9 120.8 57.9 114.2 61.0

12 153.3 46.3 145.2 50.3 141.8 52.1 136.7 54.8 125.4 60.0 118.6 63.315 161.2 49.1 152.7 53.4 149.2 55.1 143.8 58.1 132.2 63.5 125.1 66.7

6 154.5 45.3 146.5 49.2 143.2 50.9 138.3 53.4 126.8 57.8 115.2 62.07 159.4 45.8 151.4 49.7 148.0 51.3 142.9 53.9 130.9 58.3 119.0 62.4

8 164.0 46.8 155.7 50.7 152.2 52.4 146.9 54.9 134.7 59.3 122.4 63.510 173.2 48.8 164.5 52.7 160.8 54.4 155.2 57.0 142.4 61.5 129.4 65.6

12 182.6 50.8 173.3 54.9 169.4 56.6 163.6 59.2 150.1 63.8 136.5 67.915 196.7 54.2 186.8 58.3 182.7 60.1 176.5 62.7 161.9 67.4 147.2 71.4

6 165.3 49.0 156.5 53.3 152.7 55.2 147.2 57.9 135.0 63.4 127.7 66.87 170.4 49.7 161.2 54.1 157.5 55.8 151.7 58.7 139.2 64.0 131.6 67.3

8 173.8 50.8 164.5 55.2 160.6 57.0 154.7 59.9 142.0 65.3 134.2 68.710 180.3 53.0 170.6 57.4 166.8 59.4 160.8 62.3 147.4 68.0 139.5 71.4

12 186.8 55.3 176.8 60.0 172.6 61.9 166.5 64.9 152.7 70.7 144.5 74.215 195.9 59.0 185.6 63.7 181.2 65.8 174.7 69.0 160.4 75.1 151.9 78.7

0.0 Data out of the operating limits

LCLT: Leaving chilled liquid temperature Cool kW: Cooling capacityPower kW: Unit power input, including the power input of the compressors, fans, control circuit

and power input of the liquid pump to overcome unit pressure drop.

YCCD 170 HT

YCCD 210 HT

Model

YCCD 120 HT

YCCD 150 HT

YCCD 60 HT

YCCD 75 HT

YCCD 90 HT

YCCD 105 HT

YCCD 190 HT

Condenser Entering Air Temperature °C25 30 32 35 40 45

YCCD HT COOLING CAPACITIES (High Temperature Units) TABLE 7

Page 10: Yccd Chillers 46 152 Kw

GLYCOL SELECTION GUIDEDATA REQUIREDTo select a YORK YCCD glycol chiller, the following informationis required.

1. Required cooling capacity.

2. Design chilled liquid entering and leaving temperatures.

3. Design chilled liquid flow rate.

4. Design condenser entering air temperature. This will normallybe the design summer ambient air temperature unlesslocation or other factors have an influence.

5. Altitude above sea level.

6. Design cooler fouling factor.

7. Static pressure resistance against condenser entering andleaving airflow where ducts, louvres, attenuators, etc., areused, at full unit air flow.

Note: Items 1, 2 and 3 must be linked by the following formulae:

Cooling capacity (kW) = Range (°C) x Flow (l/s)Glycol Factor

Where:Range = Entering chilled liquid temperature - leaving chilledliquid temperature.

To determine Glycol Factor refer to Figure 3 for ethylene glycolor Figure 5 for propylene glycol. For the design leavingtemperature look up the recommended concentration of glycoland the Glycol Factor at this concentration. This is the minimumconcentration which should be used for the design leavingtemperature. If a higher concentration is desired the GlycolFactor can be determined from Figure 4 for the ethylene glycolor Figure 6 for propylene glycol.

SELECTION METHOD1. Determine the correct model of chiller by selecting the model

which most closely matches the required capacity at thedesign conditions of leaving chilled liquid temperature andentering air temperature.

2. Apply the relevant correction factors for fouling factor andaltitude (Tables 3 and 4) and glycol concentration (Figures 3or 5), to the capacity and power values from the capacitytables. Ensure the corrected capacity is still sufficient forrequirements.

3. Using the corrected capacity of the selected chiller, adjust thedesign temperature range, or flow rate, to balance theformulae shown in “Data Required”.

4. Physical and electrical data can now be determined fromTables 12 and 13.

5. Always re-check that selections fall within the designlimitations specified (Table 2).

SAMPLE SELECTIONA chiller is required for cooling propylene glycol from 4°C to -1°Chaving a required duty of 48 kW.

The following design conditions apply:

Fouling Factor: 0.088m °C/kWAltitude: 1200mAmbient air: 30°CGlycol Strength: 27% w/w

For propylene glycol leaving at - 1°C the recommendedconcentration from Figure 5 is 27%. The specified strength istherefore suitable.

From ratings using an "Ethylene Glycol" temperature of "-2°C"leaving temperature (Propylene Glycol capacity = EthyleneGlycol capacity at 1°C lower temperature) at 30°C air aYCCD 105 gives 49,6 kW capacity and 20,4 kW power (table 9).

From the design fouling factor, corrections of Capacity x 0.987and power x 0.995 apply (Table 3).

From the design altitude, corrections of Capacity x 0.973 andpower x 1.020 apply (Table 4).

From the design glycol strength, corrections of Capacity x 1.040and power x 1.010 apply, (Interpolation from Table 9).

Applying these factors to the selection: YCCD 105

Capacity = 49.6 x 0.987 x 0.973 x 1.040 = 49.5 kW

Compressor Power = 20.4 x 0.995 x 1.020 x 1.010 = 20.9 kW

For the glycol concentration specified and a leaving chilled liquidtemperature of - 1°C, Figure 6 shows a Glycol Factor of 0.243.The flow rate can be determined, therefore, from the formulashown in "Data Required".

49.6 kW = (4 - (-1)) x Flow (l/s)0.243

Flow rate = 49.6 x 0.243 = 2.4 (l/s)5

This satisfies the Operating Limits.

Cooler pressure drop can be found by taking the value of waterpressure drop Figure 2, for a YCCD 105 and multiplying by thecorrection factor (Figure 8), for 27% strength and a meantemperature of 1.5°C,

i.e. (4 + (-1))/2°C:

12.5 kPa x 1.25 = 15.6 kPa

Page G.10Doc. No. PC150/01.04/GB

Page 11: Yccd Chillers 46 152 Kw

Page G.11Doc. No. PC150/01.04/GB

GLY

CO

LFA

CTO

R (

l/s)

°C /

kW

LEAVING LIQUID TEMPERATURE °C

CO

NC

EN

TR

ATIO

N B

YW

EI G

HT

%

FACTORS AT OTHER FIGURE 4CONCENTRATIONS FORETHYLENE GLYCOL SOLUTIONS

CO

NC

EN

TR

ATIO

N B

YW

EIG

HT

%

LEAVING LIQUID TEMPERATURE °C

GLY

CO

LFA

CTO

R (

l/s)

°C /

kWAT

RE

CO

MM

EN

DE

D C

ON

CE

NT

RAT

ION

FREEZINGTEMPERATURE

RECOMMENDEDCONCENTRATION

GLYCOL FACTOR ATRECOMMENDEDCONCENTRATION

0.28

0.27

0.26

0.25

0.24

0.23

RECOMMENDED CONCENTRATIONS FIGURE 3FOR ETHYLENE GLYCOL SOLUTIONS

GLY

CO

LFA

CTO

R (

l/s)

°C /

kW

LEAVING LIQUID TEMPERATURE °C

CO

NC

EN

TR

ATIO

N B

YW

EIG

HT

%

FACTORS AT OTHER FIGURE 6CONCENTRATIONS FORPROPYLENE GLYCOL SOLUTIONS

CO

NC

EN

TR

ATIO

N B

YW

EIG

HT

%

LEAVING LIQUID TEMPERATURE °C

FREEZINGTEMPERATURE

RECOMMENDEDCONCENTRATION

GLYCOL FACTOR ATRECOMMENDEDCONCENTRATION

GLY

CO

LFA

CTO

R (

l/s)

°C /

kWAT

RE

CO

MM

EN

DE

D C

ON

CE

NT

RAT

ION0.26

0.25

0.24

0.23

RECOMMENDED CONCENTRATIONS FIGURE 5FOR PROPYLENE GLYCOL SOLUTIONS

CO

RR

EC

TIO

N F

AC

TOR

MEAN LIQUID TEMPERATURE °C

%C

ON

CE

NT

RAT

ION

PRESSURE DROP FIGURE 8CORRECTION FACTORS FORPROPYLENE GLYCOL SOLUTIONS

CO

RR

EC

TIO

N F

AC

TOR

MEAN LIQUID TEMPERATURE °C

%C

ON

CE

NT

RAT

ION

1.50

PRESSURE DROP FIGURE 7CORRECTION FACTORS FORETHYLENE GLYCOL SOLUTIONS

Page 12: Yccd Chillers 46 152 Kw

Page G.12Doc. No. PC150/01.04/GB

Cool Power Cool Power Cool Power Cool Power Cool Power Cool Power°C kW kW kW kW kW kW kW kW kW kW kW kW-8 27.3 13.3 25.1 13.7 24.2 13.8 22.8 13.9 20.5 14.1 19.2 14.4-6 30.2 13.9 27.7 14.3 26.7 14.5 25.2 14.6 22.7 14.8 21.2 15.1

-4 33.3 14.6 30.6 15.0 29.4 15.2 27.8 15.3 25.0 15.5 23.4 15.8-2 36.5 15.3 33.5 15.7 32.3 15.9 30.5 16.0 27.4 16.3 25.6 16.5

0 39.9 16.0 36.7 16.4 35.3 16.6 33.3 16.8 29.9 17.0 28.0 17.34 47.2 17.4 43.4 17.9 41.8 18.1 39.5 18.3 35.5 18.5 33.2 18.8

-8 31.3 15.5 28.8 15.9 27.7 16.1 26.2 16.3 23.5 16.5 22.0 16.8-6 34.6 16.3 31.8 16.7 30.6 16.9 28.9 17.1 26.0 17.3 24.3 17.6

-4 38.1 17.1 35.0 17.5 33.8 17.7 31.8 17.9 28.6 18.1 26.8 18.4-2 41.8 17.9 38.4 18.4 37.0 18.5 34.9 18.7 31.4 19.0 29.4 19.3

0 45.7 18.7 42.0 19.2 40.5 19.4 38.2 19.6 34.3 19.9 32.1 20.24 54.2 20.3 49.8 20.9 48.0 21.1 45.2 21.3 40.6 21.6 38.1 22.0

-8 33.9 15.4 32.6 16.8 31.9 17.3 31.0 18.2 27.7 19.7 25.8 20.7-6 37.5 16.2 36.0 17.6 35.3 18.2 34.3 19.1 30.7 20.7 28.6 21.7

-4 41.3 17.0 39.6 18.4 38.9 19.1 37.8 20.0 33.8 21.7 31.4 22.7-2 45.3 17.8 43.5 19.3 42.7 19.9 41.4 20.9 37.0 22.7 34.5 23.8

0 49.6 18.6 47.5 20.2 46.7 20.9 45.3 21.9 40.5 23.7 37.7 24.94 58.7 20.2 56.3 22.0 55.2 22.7 53.7 23.8 48.0 25.8 44.7 27.1

-8 38.5 17.9 37.2 19.6 36.6 20.3 35.8 21.4 32.9 23.2 31.1 24.5-6 42.5 18.8 41.1 20.5 40.5 21.3 39.6 22.4 36.3 24.4 34.4 25.7

-4 46.8 19.7 45.3 21.5 44.6 22.3 43.6 23.5 40.0 25.6 37.9 26.9-2 51.4 20.6 49.6 22.5 48.9 23.3 47.8 24.6 43.9 26.7 41.6 28.2

0 56.2 21.6 54.3 23.5 53.5 24.4 52.3 25.7 48.0 28.0 45.4 29.44 66.5 23.5 64.3 25.6 63.4 26.6 61.9 28.0 56.9 30.5 53.8 32.1

-8 52.1 25.6 47.9 26.3 46.1 26.6 43.5 26.9 39.1 27.2 36.6 27.7-6 57.6 26.9 52.9 27.6 51.0 27.9 48.1 28.2 43.2 28.6 40.5 29.0

-4 63.4 28.2 58.3 28.9 56.1 29.2 53.0 29.5 47.6 29.9 44.6 30.4-2 69.6 29.5 63.9 30.3 61.6 30.6 58.1 30.9 52.2 31.3 48.9 31.8

0 76.1 30.8 69.9 31.7 67.4 31.9 63.5 32.3 57.1 32.8 53.5 33.34 90.1 33.6 82.8 34.5 79.8 34.8 75.2 35.2 67.6 35.7 63.3 36.2

-8 59.4 31.5 54.5 32.3 52.6 32.6 49.6 33.0 44.5 33.5 41.7 34.0-6 65.6 33.0 60.3 33.9 58.1 34.2 54.8 34.6 49.2 35.1 46.1 35.6

-4 72.3 34.6 66.4 35.5 64.0 35.9 60.4 36.3 54.2 36.8 50.8 37.3-2 79.3 36.2 72.8 37.2 70.2 37.5 66.2 38.0 59.5 38.5 55.7 39.1

0 86.7 37.9 79.6 38.9 76.8 39.2 72.4 39.7 65.0 40.2 60.9 40.94 102.7 41.2 94.3 42.4 90.9 42.8 85.7 43.2 77.0 43.8 72.2 44.5

-8 67.7 29.7 64.1 32.4 62.6 33.6 60.3 35.4 55.3 38.8 52.3 41.0-6 74.9 31.1 70.9 34.0 69.2 35.2 66.7 37.1 61.1 40.7 57.8 43.0

-4 82.5 32.6 78.0 35.6 76.2 36.9 73.4 38.9 67.3 42.7 63.6 45.1-2 90.5 34.2 85.6 37.3 83.6 38.6 80.5 40.7 73.9 44.7 69.8 47.2

0 98.9 35.7 93.6 39.0 91.4 40.4 88.1 42.6 80.8 46.7 76.3 49.34 117.2 38.9 110.9 42.5 108.2 44.0 104.3 46.4 95.6 50.9 90.4 53.7

-8 74.5 34.7 70.8 37.7 69.2 38.9 66.8 40.8 61.2 44.3 57.9 46.5-6 82.4 36.4 78.2 39.5 76.5 40.9 73.8 42.8 67.7 46.4 64.0 48.7

-4 90.7 38.1 86.1 41.4 84.2 42.8 81.3 44.9 74.5 48.7 70.4 51.1-2 99.5 39.9 94.5 43.3 92.4 44.8 89.2 47.0 81.8 50.9 77.3 53.5

0 108.9 41.7 103.3 45.3 101.0 46.8 97.5 49.1 89.4 53.2 84.5 55.94 128.9 45.4 122.4 49.4 119.6 51.0 115.5 53.5 105.9 58.0 100.1 60.9

-8 82.5 36.0 78.0 39.2 76.1 40.5 73.4 42.6 67.3 46.5 63.6 48.9-6 91.2 37.8 86.2 41.1 84.2 42.5 81.1 44.7 74.4 48.8 70.4 51.3

-4 100.4 39.6 94.9 43.1 92.7 44.5 89.3 46.8 81.9 51.2 77.5 53.8-2 110.1 41.4 104.1 45.1 101.7 46.6 98.0 49.0 89.9 53.5 85.0 56.3

0 120.4 43.3 113.9 47.1 111.2 48.7 107.1 51.2 98.3 56.0 92.9 58.94 142.6 47.2 134.8 51.3 131.7 53.0 126.9 55.8 116.4 61.0 110.1 64.1

LCLT: Leaving chilled liquid temperature Cool kW: Cooling capacity

Power kW: Unit power input, including the power input of the compressors, fans, control circuit

YCCD 60

YCCD 75

YCCD 90

YCCD 105

35 40 43Model LCLTCondenser Entering Air Temperature °C

25 30 32

and power input of the liquid pump to overcome unit pressure drop.

YCCD 120

YCCD 150

YCCD 170

YCCD 210

YCCD 190

TABLE 8 YCCD COOLING CAPACITIES (35% ETHYLENE GLYCOL)

Capacity Compressor Capacity CompressorFactor Input Factor Factor Input Factor

10 1.061 1.025 1.097 1.03320 1.036 1.015 1.067 1.02330 1.015 1.005 1.026 1.00835 1.000 1.000 1.000 1.00040 0.985 0.995 0.974 0.99250 0.954 0.985 0.923 0.977

If a selection at different glycol percentage is required, multiply the capacity and input power valuestable 8 (35% ethylene glycol) by the capacity and input factors for the new glycol percentages.

Ethylene Glycol Propylene Glycol% By Weight

TABLE 9 COOLING CAPACITY CORRECTION FACTORSFOR OTHER GLYCOL CONCENTRATIONS

Page 13: Yccd Chillers 46 152 Kw

Page G.13Doc. No. PC150/01.04/GB

Cool Power Cool Power Cool Power Cool Power Cool Power Cool Power°C kW kW kW kW kW kW kW kW kW kW kW kW-8 28.3 13.4 26.0 13.8 25.1 13.9 23.6 14.1 21.2 14.3 19.9 14.5-6 31.3 14.1 28.7 14.5 27.7 14.6 26.1 14.8 23.5 15.0 22.0 15.2

-4 34.5 14.7 31.7 15.2 30.5 15.3 28.8 15.5 25.9 15.7 24.2 15.9-2 37.8 15.4 34.7 15.9 33.5 16.0 31.6 16.2 28.4 16.4 26.6 16.7

0 41.3 16.1 38.0 16.6 36.6 16.7 34.5 16.9 31.0 17.2 29.1 17.44 49.0 17.6 45.0 18.1 43.3 18.2 40.9 18.4 36.7 18.7 34.4 19.0

-8 31.6 15.7 29.0 16.1 28.0 16.3 26.4 16.5 23.7 16.7 22.2 17.0-6 34.9 16.5 32.1 16.9 30.9 17.1 29.2 17.3 26.2 17.5 24.5 17.8

-4 38.4 17.3 35.3 17.7 34.0 17.9 32.1 18.1 28.8 18.4 27.0 18.6-2 42.2 18.1 38.8 18.6 37.3 18.7 35.2 19.0 31.7 19.2 29.6 19.5

0 46.1 18.9 42.4 19.4 40.8 19.6 38.5 19.8 34.6 20.1 32.4 20.44 54.6 20.6 50.2 21.2 48.4 21.3 45.6 21.6 41.0 21.9 38.4 22.2

-8 34.7 15.8 33.3 17.2 32.7 17.7 31.8 18.6 28.4 20.2 26.4 21.2-6 38.4 16.6 36.8 18.0 36.1 18.6 35.1 19.5 31.4 21.2 29.2 22.2

-4 42.3 17.4 40.6 18.9 39.8 19.5 38.7 20.5 34.6 22.2 32.2 23.3-2 46.4 18.2 44.5 19.7 43.7 20.4 42.4 21.4 37.9 23.2 35.3 24.4

0 50.7 19.0 48.7 20.6 47.7 21.3 46.4 22.4 41.5 24.3 38.6 25.54 60.1 20.7 57.6 22.5 56.5 23.3 54.9 24.4 49.1 26.4 45.7 27.7

-8 37.1 19.2 35.9 21.0 35.4 21.7 34.6 22.9 31.7 24.9 29.3 26.2-6 41.1 20.2 39.7 22.0 39.1 22.8 38.2 24.0 35.1 26.1 32.4 27.5

-4 45.2 21.1 43.7 23.0 43.1 23.9 42.1 25.2 38.6 27.4 35.7 28.8-2 49.6 22.1 47.9 24.1 47.2 25.0 46.2 26.3 42.4 28.7 39.1 30.2

0 54.2 23.1 52.4 25.2 51.6 26.1 50.5 27.5 46.4 30.0 42.8 31.64 64.2 25.2 62.1 27.5 61.2 28.5 59.8 30.0 54.9 32.7 50.7 34.4

-8 53.1 25.5 48.7 26.2 47.0 26.4 44.3 26.7 39.8 27.1 37.3 27.5-6 58.6 26.7 53.9 27.5 51.9 27.7 49.0 28.0 44.0 28.4 41.2 28.9

-4 64.6 28.0 59.3 28.8 57.2 29.0 53.9 29.4 48.5 29.8 45.4 30.2-2 70.9 29.3 65.1 30.1 62.7 30.4 59.2 30.7 53.2 31.2 49.8 31.6

0 77.5 30.6 71.2 31.5 68.6 31.8 64.7 32.1 58.1 32.6 54.4 33.14 91.7 33.4 84.3 34.3 81.2 34.6 76.6 35.0 68.8 35.5 64.5 36.0

-8 60.4 31.0 55.5 31.8 53.5 32.1 50.5 32.5 45.4 32.9 42.5 33.4-6 66.8 32.5 61.4 33.4 59.2 33.7 55.8 34.1 50.1 34.5 47.0 35.1

-4 73.6 34.0 67.6 35.0 65.1 35.3 61.4 35.7 55.2 36.2 51.7 36.7-2 80.7 35.6 74.2 36.6 71.5 36.9 67.4 37.4 60.6 37.9 56.7 38.4

0 88.3 37.2 81.1 38.3 78.1 38.6 73.7 39.1 66.2 39.6 62.0 40.24 104.5 40.6 96.0 41.7 92.5 42.1 87.3 42.5 78.4 43.1 73.5 43.8

-8 65.9 30.5 62.4 33.6 60.9 34.9 58.7 36.8 53.8 40.4 50.9 42.6-6 72.9 32.1 69.0 35.3 67.3 36.6 64.9 38.6 59.5 42.4 56.2 44.7

-4 80.2 33.6 75.9 37.0 74.1 38.4 71.4 40.5 65.5 44.4 61.9 46.8-2 88.0 35.2 83.3 38.7 81.3 40.1 78.4 42.4 71.9 46.5 67.9 49.0

0 96.3 36.7 91.1 40.4 88.9 42.0 85.7 44.3 78.6 48.6 74.3 51.24 114.0 40.0 107.9 44.0 105.3 45.7 101.5 48.2 93.1 52.9 88.0 55.8

-8 74.7 34.4 70.9 37.4 69.3 38.7 66.9 40.6 61.3 44.0 58.0 46.1-6 82.6 36.1 78.4 39.2 76.6 40.6 74.0 42.6 67.8 46.1 64.1 48.4

-4 90.9 37.9 86.3 41.1 84.4 42.5 81.4 44.6 74.7 48.3 70.6 50.7-2 99.7 39.6 94.7 43.0 92.6 44.5 89.4 46.7 81.9 50.6 77.4 53.1

0 109.1 41.4 103.5 45.0 101.2 46.5 97.7 48.8 89.6 52.9 84.7 55.54 129.2 45.1 122.6 49.0 119.9 50.7 115.7 53.2 106.1 57.6 100.3 60.5

-8 79.6 36.5 75.3 39.9 73.5 41.4 70.8 43.7 65.0 48.0 61.5 50.6-6 88.0 38.3 83.2 41.9 81.3 43.4 78.3 45.8 71.8 50.4 67.9 53.0

-4 96.9 40.1 91.6 43.9 89.5 45.5 86.2 48.0 79.1 52.8 74.8 55.6-2 106.3 42.0 100.5 46.0 98.2 47.6 94.6 50.2 86.8 55.2 82.1 58.2

0 116.2 43.9 109.9 48.1 107.4 49.8 103.4 52.5 94.9 57.7 89.7 60.84 137.6 47.8 130.2 52.4 127.1 54.2 122.5 57.2 112.4 62.9 106.3 66.3

LCLT: Leaving chilled liquid temperature Cool kW: Cooling capacityPower kW: Unit power input, including the power input of the compressors, fans and control circuit

and power input of the liquid pump to overcome unit pressure drop.

Codenser entering Air Temperature °C25 30 32 35 40 43

YCCD 150 LN

YCCD 170 LN

YCCD 210 LN

YCCD 105 LN

YCCD 190 LN

YCCD 75 LN

YCCD 90 LN

LCLT

YCCD 120 LN

Model

YCCD 60 LN

YCCD LN COOLING CAPACITIES (35% ETHYLENE GLYCOL) TABLE 10

Page 14: Yccd Chillers 46 152 Kw

TABLE 11 SOUND POWER LEVELS (FREQUENCY ANALYSIS (SPECTRUM))

Page G.14Doc. No. PC150/01.04/GB

dB(A)Model 125 250 500 1000 2000 4000 8000

60 86 84 83 82 80 70 59 8775 86 84 83 82 80 70 59 8790 87 85 84 83 81 71 60 88

105 88 86 85 84 82 72 61 89120 89 87 86 85 83 73 62 90150 89 87 86 85 83 73 62 90170 86 90 87 87 85 81 72 93190 87 91 88 88 86 82 73 94210 87 91 88 88 86 82 73 94

dB(A)Model 125 250 500 1000 2000 4000 8000

60 77 75 74 73 71 61 50 7875 77 75 74 73 71 61 50 7890 77 75 74 73 71 61 50 78

105 80 78 77 76 74 64 53 81120 78 76 75 74 72 62 51 79150 81 79 78 77 75 65 54 82170 76 80 77 77 75 71 62 83190 78 82 79 79 77 73 64 85210 78 82 79 79 77 73 64 85

dB(A)Model 125 250 500 1000 2000 4000 8000

60 87 85 84 83 81 71 60 8875 87 85 84 83 81 71 60 8890 90 88 87 86 84 74 63 91

105 90 88 87 86 84 74 63 91120 92 90 89 88 86 76 65 93150 92 90 89 88 86 76 65 93170 87 91 88 88 86 82 73 94190 88 92 89 89 87 83 74 95210 88 92 89 89 87 83 74 95

YCCD HTFREQUENCY (Hz)

YCCD LNFREQUENCY (Hz)

FREQUENCY (Hz)YCCD STD

Page 15: Yccd Chillers 46 152 Kw

PHYSICAL DATA (Standard Units) TABLE 12

Page G.15Doc. No. PC150/01.04/GB

60 75 90 105Number of refrigerant circuits 2 2 2 2Total capacity steps 2 2 2 2Compressor Number 2 2 2 2

Theoretical displacement m³/h 36.16 43.16 37.7 43.5No. of cylinders 3 3 SCROLL SCROLLNominal speed rpm 2950 2950 2950 2950Oil charge (per compressor) l 2.8 2.8 4 6.6Oil type 098L00637-000No. of loading stages % 50-100 50-100 50-100 50-100

Evaporator Number 1 1 1 1Type Plate Plate Plate PlateWater volume l 5.5 6 6.5 7.9

Air Total coil face area m² 4.3 4.3 4.3 4.3cooled Number of coils 2 2 2 2Condenser Number of rows 2 2 3 3Fans Number of fans 2 2 2 2

Nominal speed rpm 910 910 910 910Total airflow m³/s 5.3 5.3 6.1 6.1Total power (standard fans) kW 0.96 0.96 0.96 0.96Total power (high pressure fans) kW 1.96 1.96 1.96 1.96

Refrigerant Circuit 1 kg 6.0 6.5 8.5 12.0Charge Circuit 2 kg 6.0 6.5 8.5 12.0

Operating kg 719 744 912 957Shipping kg 698 725 891 935

Additional weight for copper fin coils kg 61 64 80 85Sound power level (2) dB(A) 87 87 88 89Sound pressure level at 10 m (3) dB(A) 56 56 57 58Dimensions Length mm 2110 2110 2110 2110

Width mm 1110 1110 1110 1110Height mm 1810 1810 1810 1810

120 150 170 190 210Number of refrigerant circuits 2 2 2 2 2Total capacity steps 2 2 4 4 4Compressor Number 2 2 4 4 4

Theoretical displacement m³/h 76.85 88.94 72.5 81.2 87No. of cylinders 6 6 SCROLL SCROLL SCROLLNominal speed rpm 2950 2950 2950 2950 2950Oil charge (per compressor) l 6.6 6.6 10.4 10.6 13.2Oil type 098L00637-000No. of loading stages % 50-100 50-100 20-50-70-100 25-50-75-100 25-50-75-100

Evaporator Number 1 1 1 1 1Type Plate Plate Plate Plate PlateWater volume l 9.4 11.3 12.4 14.6 14.6

Air Total coil face area m² 6.1 6.1 8.7 8.7 8.7cooled Number of coils 2 2 4 4 4Condenser Number of rows 3 4 3 3 4Fans Number of fans 3 3 3 3 3

Nominal speed rpm 910 910 910 910 910Total airflow m³/s 7.5 7.2 12.3 12.3 11.7Total power (standard fans) kW 1.44 1.44 2.94 2.94 2.94Total power (high pressure fans) kW 2.94 2.94 4.2 4.2 4.2

Refrigerant Circuit 1 kg 10.5 11.5 18.5 19.5 25.0Charge Circuit 2 kg 10.5 11.5 18.5 19.5 25.0

Operating kg 1021 1099 1434 1473 1578Shipping kg 992 1067 1422 1458 1563

Additional weight for copper fin coils kg 90 98 133 137 147Sound power level (1) dB(A) 90 90 93 94 94Sound pressure level at 10 m (2) dB(A) 59 59 62 63 63Dimensions Length mm 2760 2760 3450 3450 3450

Width mm 1110 1110 1110 1110 1110Height mm 1810 1810 2170 2170 2170

(1) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1(2) Sound pressure level values refer to ISO standard 3744

Weight(aluminum fins)

YCCD

YCCD

098L00565-000

098L00565-000

Weight(aluminum fins)

Page 16: Yccd Chillers 46 152 Kw

TABLE 12 PHYSICAL DATA (Low Noise Units)

Page G.16Doc. No. PC150/01.04/GB

60 75 90 105Number of refrigerant circuits 2 2 2 2Total capacity steps 2 2 2 2Compressor Number 2 2 2 2

Theoretical displacement m³/h 36.16 43.16 37.7 43.5No. of cylinders 3 3 SCROLL SCROLLNominal speed rpm 2950 2950 2950 2950Oil charge (per compressor) l 2.8 2.8 4 6.6Oil type 098L00637-000No. of loading stages % 50-100 50-100 50-100 50-100

Evaporator Number 1 1 1 1Type Plate Plate Plate PlateWater volume l 5.5 6 6.5 7.9

Air Total coil face area m² 4.3 4.3 4.3 4.3cooled Number of coils 2 2 2 2Condenser Number of rows 2 2 3 3Fans Number of fans 2 2 2 2

Nominal speed rpm 580 580 580 680Total airflow m³/s 4.2 4.2 4.1 4.2Total power kW 1.4 1.4 1.4 1.4

Refrigerant Circuit 1 kg 6.0 6.5 8.5 12.0Charge Circuit 2 kg 6.0 6.5 8.5 12.0

Operating kg 763 790 956 968Shipping kg 743 770 935 945

Additional weight for copper fin coils kg 65 68 85 85Sound power level (1) dB(A) 78 78 78 81Sound pressure level at 10 m (2) dB(A) 47 47 47 50Dimensions Length mm 2110 2110 2110 2110

Width mm 1110 1110 1110 1110Height mm 1890 1890 1890 1890

120 150 170 190 210Number of refrigerant circuits 2 2 2 2 2Total capacity steps 2 2 4 4 4Compressor Number 2 2 4 4 4

Theoretical displacement m³/h 76.85 88.94 72.5 81.2 87No. of cylinders 6 6 SCROLL SCROLL SCROLLNominal speed rpm 2950 2950 2950 2950 2950Oil charge (per compressor) l 6.6 6.6 10.4 10.6 13.2Oil type 098L00637-000No. of loading stages % 50-100 50-100 20-50-70-100 25-50-70-100 25-50-75-100

Evaporator Number 1 1 1 1 1Type Plate Plate Plate Plate PlateWater volume l 9.4 11.3 12.4 12.4 14.6

Air Total coil face area m² 6.1 6.1 8.7 8.7 8.7cooled Number of coils 2 2 4 4 4Condenser Number of rows 3 4 4 4 4Fans Number of fans 3 3 3 3 3

Nominal speed rpm 580 680 500 500 700Total airflow m³/s 5.6 7.0 7.9 9.6 9.6Total power kW 2.1 2.1 4.2 4.2 4.2

Refrigerant Circuit 1 kg 11.0 11.5 21.0 22.0 25.0Charge Circuit 2 kg 11.0 11.5 21.0 22.0 25.0

Operating kg 1086 1111 1524 1563 1596Shipping kg 1056 1080 1512 1548 1581

Additional weight for copper fin coils kg 97 99 142 146 149Sound power level (1) dB(A) 79 82 83 85 85Sound pressure level at 10 m (2) dB(A) 48 51 52 54 54Dimensions Length mm 2760 2760 3450 3450 3450

Width mm 1110 1110 1110 1110 1110Height mm 1890 1890 2170 2170 2170

(1) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1(2) Sound pressure level values refer to ISO standard 3744

Weight(aluminum fins)

YCCD LN

YCCD LN

098L00565-000

098L00565-000

Weight(aluminum fins)

Page 17: Yccd Chillers 46 152 Kw

PHYSICAL DATA (High Temperature Units) TABLE 12

Page G.17Doc. No. PC150/01.04/GB

60 75 90 105Number of refrigerant circuits 2 2 2 2Total capacity steps 2 2 2 2Compressor Number 2 2 2 2

Theoretical displacement m³/h 36.16 43.16 37.7 43.5No. of cylinders 3 3 SCROLL SCROLLNominal speed rpm 2950 2950 2950 2950Oil charge (per compressor) l 2.8 2.8 4 6.6Oil type 098L00637-000No. of loading stages % 50-100 50-100 50-100 50-100

Evaporator Number 1 1 1 1Type Plate Plate Plate PlateWater volume l 5.5 6 6.5 7.9

Air Total coil face area m² 4.3 4.3 4.3 4.3cooled Number of coils 2 2 2 2Condenser Number of rows 2 2 3 3Fans Number of fans 2 2 2 2

Nominal speed rpm 910 910 910 910Total airflow m³/s 5.2 5.2 7.2 6.9Total power kW 0.96 0.96 1.96 1.96

Refrigerant Circuit 1 kg 6.5 7.5 8.5 12.0Charge Circuit 2 kg 6.5 7.5 8.5 12.0

Operating kg 755 784 923 968Shipping kg 735 763 901 946

Additional weight for copper fin coils kg 64 67 81 86Sound power level (1) dB(A) 88 88 91 91Sound pressure level at 10 m (2) dB(A) 57 57 60 60Dimensions Length mm 2110 2110 2110 2110

Width mm 1110 1110 1110 1110Height mm 1810 1810 1890 1890

120 150 170 190 210Number of refrigerant circuits 2 2 2 2 2Total capacity steps 2 2 4 4 4Compressor Number 2 2 4 4 4

Theoretical displacement m³/h 76.85 88.94 72.5 72.5 87No. of cylinders 6 6 SCROLL SCROLL SCROLLNominal speed rpm 2950 2950 2950 2950 2950Oil charge (per compressor) l 6.6 6.6 10.4 10.6 13.2Oil type 098L00637-000No. of loading stages % 50-100 50-100 20-50-70-100 25-50-70-100 25-50-75-100

Evaporator Number 1 1 1 1 1Type Plate Plate Plate Plate PlateWater volume l 9.4 11.3 12.4 12.4 14.6

Air Total coil face area m² 6.1 6.1 8.7 8.7 8.7cooled Number of coils 2 2 4 4 4Condenser Number of rows 3 4 4 3 4Fans Number of fans 3 3 3 3 3

Nominal speed rpm 910 910 900 900 900Total airflow m³/s 10.0 9.4 15.2 15.2 14.4Total power kW 2.94 2.94 4.2 4.2 4.2

Refrigerant Circuit 1 kg 12.5 14.0 18.5 19.5 25.0Charge Circuit 2 kg 12.5 14.0 18.5 19.5 25.0

Operating kg 1040 1115 1458 1497 1596Shipping kg 1011 1085 1443 1482 1581

Additional weight for copper fin coils kg 92 100 135 139 149Sound power level (1) dB(A) 93 93 94 95 95Sound pressure level at 10 m (2) dB(A) 62 62 63 64 64Dimensions Length mm 2760 2760 3450 3450 3450

Width mm 1110 1110 1110 1110 1110Height mm 1890 1890 2170 2170 2170

(1) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1(2) Sound pressure level values refer to ISO standard 3744

Weight(aluminum fins)

YCCD HT

YCCD HT

098L00565-000

098L00565-000

Weight(aluminum fins)

Page 18: Yccd Chillers 46 152 Kw

ELECTRICAL DATA TABLE 13

Page G.18Doc. No. PC150/01.04/GB

60 Sys. 1+ 275 Sys. 1+ 290 Sys. 1+ 2105 Sys. 1+ 2120 Sys. 1+ 2150 Sys. 1+ 2170 Sys. 1+ 2 9.6 15.0 11.1 16.8 16.9 26.5 18.8 29.0 120 175190 Sys. 1+ 2 12.7 15.0 13.8 16.8 21.5 26.5 23.0 29.0 135 175210 Sys. 1+ 2 15.0 15.0 16.8 16.8 26.5 26.5 29.0 29.0 175 175

(1) Nominal conditions taken at 7oC leaving chilled water temperature and 35oC ambient temperature(2) Maximum conditions for the compressor taken at 15oC leaving chilled water temperature and 43oC ambient temperature

19022.4 29.0 37.8 47.5 21518.1 24.0 31.4 39.8

13515.0 16.8 26.5 29.0 17512.7 13.8 21.5 23.0

8011.0 14.0 18.2 22.5 1269.3 11.0 14.9 17.8

Power Input at

Maximum(2) percomp (kW)

Current perComp.

Nominal(1) (A)

Current perComp.

Maximum(2) (A)

DOL StartingCurrent perComp. (A)

@400 V

YCCD System

@400 V @400 V @400 V @400 V

Operating Condition LRAPower Input at

Nominal(1) percomp (kW)

Compressor Data

60 75 90 105 120 150 170 190 2102 2 2 2 3 3 3 3 3

0.48 0.48 0.48 0.48 0.48 0.48 0.98 0.98 0.980.93 0.93 0.93 0.93 0.93 0.93 1.75 1.75 1.75

0.98 0.98 0.98 0.98 0.98 0.98 1.4 1.4 1.41.75 1.75 1.75 1.75 1.75 1.75 2.9 2.9 2.9

60 75 90 105 120 150 170 190 2102 2 2 2 3 3 3 3 3

0.70 0.70 0.70 0.70 0.70 0.70 0.81 0.81 0.811.15 1.15 1.15 1.15 1.15 1.15 1.70 1.70 1.70

60 75 90 105 120 150 170 190 2102 2 2 2 3 3 3 3 3

0.48 0.48 0.98 0.98 0.98 0.98 1.40 1.40 1.400.93 0.93 1.75 1.75 1.75 1.75 2.90 2.90 2.90

Number of fansPower input per fan (kW)

Full load Amps per fan (A)

YCCD HTNumber of fans

Power input per fan (kW)Full load Amps per fan (A)

YCCDNumber of fans

Power input per fan (kW)

YCCD LN

Full load Amps per fan (A)Power input per fan (kW)

Standard Fans

High Pressure FansFull load Amps per fan (A)

Fan Data

Page 19: Yccd Chillers 46 152 Kw

ELECTRICAL CONNECTIONS (YCCD Models 60 -150 Standard Control)

Page G.19Doc. No. PC150/01.04/GB

1

3

35

10

5

37

103

104

106

108

110

39

2

4

36

11

6

38

8

105

107

109

111

40

14

(COMMON)

(NO)

COOL

YCCD TERMINAL BOARD EXTERNAL TERMINAL BOARD

LINE400-3+PE-50Hz

L1

MAIN SWITCH

L2

L3

FLOW SWITCH OREXTERNAL INTERLOCK

INTERLOCK(OPTIONAL)CIRC PUMP ETC

REMOTE INDICATIONVOLTAGE ON

REMOTEON/OFF CONTROL

REMOTE INDICATIONGENERAL ALARM

COMPRESSOR '1' ON

REMOTEINDICATION

REMOTEINDICATION

PUMP RELAYMAX 0.5 AMP 230V

PUMP 1 ON

PUMP 2 ON

ANTIFREEZEHEATER ON

PUMP MOTOR 1 OR 2THERMAL OVERLOAD

CUTOUT

COMPRESSOR '2' ON

ANTIFREEZE RELAYMAX 0.5 AMP 230V

KEY

UNIT ELECTRICAL TERMINALS

VOLTAGE FREE CONTACT

EXTERNAL EQUIPMENT TERMINALS

CUSTOMER WIRING

The following connections are required:

• One 400-3-50 Hz supply plus earth.• Control interlocks if required.

The power connections and interlocks can be made to a single terminal strip. Supply cables should enter the unit via a holeprovided.Mains isolator switches should be located adjacent to the unit and should incorporate provision for locking in the off position.Installation of differential safety cut-outs is recommended to prevent damage due to phase failure.

Page 20: Yccd Chillers 46 152 Kw

ELECTRICAL CONNECTIONS (YCCD Models 60 -150 Optional ISN Control)

Page G.20Doc. No. PC150/01.04/GB

1

3

7

5

36

20

40

8

38

2

4

35

19

6

37

103

39

14

COMMON

N.O. SYSTEM 1 GENERAL ALARM

N.O. SYSTEM 2 GENERAL ALARM

YCCD TERMINAL BOARD EXTERNAL TERMINAL BOARD

L1

MAIN SWITCH

L2

L3

FLOW SWITCH OREXTERNAL INTERLOCK

INTERLOCK(OPTIONAL)CIRC PUMP ETC

REMOTE INDICATIONVOLTAGE ON

PWM TEMP RESET

COMPRESSOR '1' ON

REMOTEINDICATION

PUMP RELAYMAX 0.5 AMP 230V

COMPRESSOR '2' ON

ANTIFREEZE RELAYMAX 0.5 AMP 230V

LINE400-3+PE-50Hz

KEY

UNIT ELECTRICAL TERMINALS

VOLTAGE FREE CONTACT

EXTERNAL EQUIPMENT TERMINALS

CUSTOMER WIRING

104

106

108

110

105

107

109

111

REMOTEINDICATION

PUMP 1 ON

PUMP 2 ON

ANTIFREEZEHEATER ON

PUMP MOTOR 1 OR 2THERMAL OVERLOAD

CUTOUT

10

11

18COOL

ICEBUILDING

REMOTEMODESELECTION

The following connections are required:

• One 400-3-50 Hz supply plus earth.• Control interlocks if required.

The power connections and interlocks can be made to a single terminal strip. Supply cables should enter the unit via a holeprovided.Mains isolator switches should be located adjacent to the unit and should incorporate provision for locking in the off position.Installation of differential safety cut-outs is recommended to prevent damage due to phase failure.

Page 21: Yccd Chillers 46 152 Kw

ELECTRICAL CONNECTIONS (YCCD Models 170 -210 Standard ISN Control)

Page G.21Doc. No. PC150/01.04/GB

1

01

3

7

5

36

20

40

44

8

38

42

2

02

4

35

19

6

37

41

103

39

43

14

COMMON

N.O. SYSTEM 1 GENERAL ALARM

N.O. SYSTEM 2 GENERAL ALARM

YCCD TERMINAL BOARD EXTERNAL TERMINAL BOARD

L1

MAIN SWITCH

L2

L3

FLOW SWITCH OREXTERNAL INTERLOCK

REMOTE START/STOP

INTERLOCK(OPTIONAL)CIRC PUMP ETC

REMOTE INDICATIONVOLTAGE ON

PWM TEMP RESET

SYS. 1COMPRESSOR '1' ON

SYS. 2COMPRESSOR '1' ON

REMOTEINDICATION

REMOTEINDICATION

PUMP RELAYMAX 0.5 AMP 230V

SYS. 1COMPRESSOR '2' ON

SYS. 2COMPRESSOR '2' ON

ANTIFREEZE RELAYMAX 0.5 AMP 230V

LINE400-3+PE-50Hz

KEY

UNIT ELECTRICAL TERMINALS

VOLTAGE FREE CONTACT

EXTERNAL EQUIPMENT TERMINALS

CUSTOMER WIRING

8

104

106

108

110

14

105

107

109

111

103

L1MAIN SWITCH

L2

L3

REMOTEINDICATION

COMMONPUMP MOTOR RELAY

ANTIFREEZE RELAY

PUMP 1 ON

PUMP 2 ON

ANTIFREEZEHEATER ON

PUMP MOTOR 1 OR 2THERMAL OVERLOADCUTOUT

HYDRO KIT TERMINAL BOARD (OPTIONAL)

LINE400-3+PE-50Hz

10

11

18COOL

ICEBUILDING

REMOTEMODESELECTION

The following connections are required:

• One 400-3-50 Hz supply plus earth.• Control interlocks if required.

The power connections and interlocks can be made to a single terminal strip. Supply cables should enter the unit via a holeprovided.Mains isolator switches should be located adjacent to the unit and should incorporate provision for locking in the off position.Installation of differential safety cut-outs is recommended to prevent damage due to phase failure.

Page 22: Yccd Chillers 46 152 Kw

DIMENSIONS

Page G.22Doc. No. PC150/01.04/GB

VIEW C~378

~77

8~

456

2" Female

VIEW A

36,5 36,510371110

A C

B

A

C

177 177

Lifti

ngP

oint

Lifti

ngP

oint

Cable Entry

VIEW B

B

(+35 mm ONLY FOR TRANSPORT)

35 mmONLY FOR

TRANSPORT

1100

YCCD Models 60, 75, 90 and 105

MODEL VERSIONDIMENSION 'A'

(mm)DIMENSION 'B'

(mm)DIMENSION 'C'

(mm)NUMBEROF FANS

YCCD 60 STANDARD 1756 2110 1810 2

LOW NOISE 1756 2110 1890 2

HIGH TEMPERATURE 1756 2110 1810 2

YCCD 75 STANDARD 1756 2110 1810 2

LOW NOISE 1756 2110 1890 2

HIGH TEMPERATURE 1756 2110 1810 2

YCCD 90 STANDARD 1756 2110 1810 2

LOW NOISE 1756 2110 1890 2

HIGH TEMPERATURE 1756 2110 1890 2

YCCD 105 STANDARD 1756 2110 1810 2

LOW NOISE 1756 2110 1890 2

HIGH TEMPERATURE 1756 2110 1890 2

Page 23: Yccd Chillers 46 152 Kw

DIMENSIONS

Page G.23Doc. No. PC150/01.04/GB

A C

VIEW B VIEW C

B

177 177

Lifti

ngP

oint

Cab

leE

ntry

Lifti

ngP

oint

1100

~378

~77

8~

456

2" Female

VIEW A

36,5 36,510371110

A

C

B

(+35 mm ONLY FOR TRANSPORT)

35 mmONLY FOR

TRANSPORT

YCCD Models 120 and 150

MODEL VERSIONDIMENSION 'A'

(mm)DIMENSION 'B'

(mm)DIMENSION 'C'

(mm)NUMBEROF FANS

YCCD 120 STANDARD 2406 2760 1810 3

LOW NOISE 2406 2760 1890 3

HIGH TEMPERATURE 2406 2760 1890 3

YCCD 150 STANDARD 2406 2760 1810 3

LOW NOISE 2406 2760 1890 3

HIGH TEMPERATURE 2406 2760 1890 3

Page 24: Yccd Chillers 46 152 Kw

DIMENSIONS (continued)

Page G.24Doc. No. PC150/01.04/GB

A

3450 1110

1017

2170

1498

173

519

1558

VIEW A

2"Female

2"Female

YCCD Models 170, 190 and 210

Page 25: Yccd Chillers 46 152 Kw

SPACE REQUIREMENTS

Page G.25Doc. No. PC150/01.04/GB

1000 mm

1000 mm (1500 mm (Models 170 - 210)

Models 60 - 150)

VIEW A

A

1300 mm

3000 mm

1000 mm (1500 mm (Models 170 - 210)

Models 60 - 150)

Single Unit Applications

1300 mm

1300 mm

A

A AB

A

1300 mm

1000 mm1000 mm

1000 mm (1500 mm (Models 170 - 210)

Models 60 - 150)

1500 mm (00 mm (Models 170 - 210)

Models 60 - 150)20

A =

B =

Multi Unit Applications

Page 26: Yccd Chillers 46 152 Kw

NOTES

Page G.26Doc. No. PC150/01.04/GB