Xtralis Training 2

download Xtralis Training 2

of 45

Transcript of Xtralis Training 2

  • 8/10/2019 Xtralis Training 2

    1/45

    Xtralis AG. All rights reserved.

    xtralis.com

    Powerful Early Warning Safetyand Security Solutions

  • 8/10/2019 Xtralis Training 2

    2/45

    Topic 3

    Site Assessment

  • 8/10/2019 Xtralis Training 2

    3/45

  • 8/10/2019 Xtralis Training 2

    4/45

    - Give careful consideration to environmental conditions that may affect the ability of thesampling network to obtain an air sample. Factors such as:

    - high air velocities

    - frequent air changes

    - air pressure variations

    - air temperature.

    - Variations within the area to be protected will all affect system performance, and mayrequire the use of at least one other VESDA sampling method to effectively monitor thefire zone

    - To ensure a satisfactory airflow through the air sampling network and the Detector , theaspirator should exhaust to an equal or lower atmospheric pressure than that of theprotected area.

    Environmental Conditions

  • 8/10/2019 Xtralis Training 2

    5/45

    Topic 4

    Pipe Network Design

  • 8/10/2019 Xtralis Training 2

    6/45

    Regulatory Requirements

    The optimum detector sensitivity takes the following into

    consideration: Level of protection needed, room environment,

    nature of work done.

    In designing an air sampling network, due consideration must be

    given to relevant Fire Codes, Standards and Regulations that may

    govern such issues as

    maximum permissible response time;

    maximum allowable area coveragefor a single sampling

    point;

    distanceof sampling points from bordering walls; Maximum spacingbetween sampling points

  • 8/10/2019 Xtralis Training 2

    7/45

    General Design Guidelines

    A maximum of four sampling pipe runs connectedto each VESDA Detector is recommended althoughsome systems can have up to eight pipes, witheach pair of pipes branched at the Detector inlet.

    The combined length of pipe runs from a singleVESDA Detector should not exceed 650 ft.

    Individual pipe lengths should not exceed 325ft.

    However, where response times in excess of 60seconds are acceptable, the combined length of allpipe runs can be extended beyond the 650 ft. limit.

  • 8/10/2019 Xtralis Training 2

    8/45

    The ASPIRE modeling system should be used todetermine the maximum number of sampling points per

    pipe run.

    The designer should use national codes for PointDetector spacingas the criteria for determining theminimum number of sampling points.

    The default sampling hole size is 5/64

    Sample Point Spacing Guidelines

  • 8/10/2019 Xtralis Training 2

    9/45

    A Grid Overlaid on Construction Plans

    Location of

    sampling point

    or smoke

    detector.

    This layout is

    using a grid

    overlay concept.

    Grid overlay

  • 8/10/2019 Xtralis Training 2

    10/45

    Sampling Points Arranged with a Grid Layout

    Maximum

    zone size20,000 sq

    ft

    Sampling pipes Sampling points

    VESDA

    Detector

    5ft 10ft

    10ft

    10ft10ft10ft

    10ft

    10ft

    5ft

    5ft

    5ft

  • 8/10/2019 Xtralis Training 2

    11/45

    Grid Overlay

    10m

    5.0m

    7.0m

    5.0m

    10m grid

  • 8/10/2019 Xtralis Training 2

    12/45

    Grid Overlay

    Sampling pipes Sampling points

    VESDA

    Detector

  • 8/10/2019 Xtralis Training 2

    13/45

    Regulatory Requirements

    More details:

    You must comply with the local standards that are applicable for

    your area and application.

    Australia

    U.K. and Europe

    North

    America

    http://localhost/Template/VESDA%20Codes%20ANZ.ppthttp://localhost/var/www/xtralis/New%20Corporate%20Marketing%20Materials/Module%202%20-%20Codes%20v1.2.ppthttp://localhost/var/www/xtralis/New%20Corporate%20Marketing%20Materials/Module%202%20-%20Codes%20v1.2.ppthttp://localhost/var/www/xtralis/New%20Corporate%20Marketing%20Materials/Module%202%20-%20Codes%20v1.2.ppthttp://localhost/Template/VESDA%20Codes%20ANZ.ppt
  • 8/10/2019 Xtralis Training 2

    14/45

    Codes & StandardsVESDA detectors are UL268

    listed for primary detection

  • 8/10/2019 Xtralis Training 2

    15/45

    Over 300,000 VESDA units have been installed around the world

    in a diverse range of environments and has gained global

    approvals:

    FM (USA)

    UL (USA)

    ULC (Canada)

    CSFM (California)

    LPC (UK)

    AFNOR (France)VdS (Germany)

    SSL (Australia)

    NC (China)

  • 8/10/2019 Xtralis Training 2

    16/45

    NFPA STANDARDS

    NFPA 72 - NATIONAL FIRE ALARM CODE

    NFPA 75 - COMPUTER / DATA PROCESSING EQUIPMENT

    NFPA 76TELECOMMUNICATIONS

    NFPA 318 - PROTECTION OF CLEAN ROOMS

    NFPA 850PROTECTION FOR ELECTRIC GENERATING PLANTS

    NFPA 909 -PROTECTION OF CULTURAL RESOURCES

    NFPA 914PROTECTION OF HISTORIC STRUCTURES

    NFPA 2001 - CLEAN AGENT EXTINGUISHING SYSTEMS

  • 8/10/2019 Xtralis Training 2

    17/45

    CODES Relative to Extinguishing

    NFPA 2 Hydrogen Technologies Code

    NFPA 11 Standard for lo, med, hi expansion foam

    NFPA 12 Carbon Dioxide Extinguishing Systems

    NFPA 12a Halon 1301 Fire Extinguishing Systems

  • 8/10/2019 Xtralis Training 2

    18/45

    5.7.3.3 Air Sampling-Type Smoke Detector.

    5.7.3.3.1: Each sampling port of an air sampling-type smoke detector shall be treated as a spot-type

    detector for the purpose of location and spacing.

    5.7.3.3.2:

    Maximum air sample transport time from the farthest sampling point shall not exceed 120seconds.

    NFPA 72 - 2002 EDITION

  • 8/10/2019 Xtralis Training 2

    19/45

    NFPA 72 - 2002 EDITION

    5.7.3.3.7 Air sampling network piping and fittings shall be airtight and permanently fixed. **

    5.7.3.3.8 Sampling system piping shall be conspicuously identified as SMOKE DETECTOR

    SAMPLING TUBE.DO NOT DISTURB, as follows:

    (A) At changes in direction or branches of piping;(B) At each side of penetrations of walls, floors, or other barriers;

    (C) At intervals on piping that provide visibility within the space, but no greater than 20ft.

    * *EXCEPT AT THE INLET MANIFOLD OF THE DETECTOR!!!

  • 8/10/2019 Xtralis Training 2

    20/45

    TABLE 10.4.2.2 TEST METHODS

    DEVICE

    3. Air Sampling

    METHOD

    Per manufacturers recommended test methods,

    detector alarm responseshall be verified through the end samplingport on each pipe run;

    airflowthrough all other ports shall be verified as well.

  • 8/10/2019 Xtralis Training 2

    21/45

    Alarm Response:

    Take off alarm delays.

    Spray smoke into the farthest sample hole (End Vent) from

    the detector.

    Using a stop watch, time the time taken for the detector to

    respond to the increase of smoke.

    Airflow:

    Using a digital manometer, measure the pressure readings

    at the sample holes & compare to the initial readings.

  • 8/10/2019 Xtralis Training 2

    22/45

    Air Sampling methods

    When designing a pipe network, the key area for protection to consider are:

    1. Does the room need protection?

    2. Does the air handling unit need protection?

    3. Does the object need protection?

    The three basic air sampling methodsused to protect a room are:

    Standard Pipe SamplingSystems

    (below ceiling or floor void or above cabinet)

    Capillary tube sampling

    (concealed, above-ceiling, or within cabinets). Return air sampling

    (within duct or return air grille)

    Inter-beam sampling

    (more details in separate application course)

  • 8/10/2019 Xtralis Training 2

    23/45

    Air Sampling - Introduction

    The most basic and widely used sampling method involves suspending

    lengths of CPVC/PVC pipe of internal diameter (ID is 0.87,

    normal) over the area to be protected.

    The pipes can be arranged in a variety of ways so that they cover the

    whole area of the monitored fire zone.

    These lengths of pipe are then connected to the Detector inlet manifold

    (normally up to four for each Detector).

    Each of the pipe lengths has a number of small holes spaced along its

    length that act as sampling points.

    The far end of each sampling pipe is terminated by a vented endcapdesigned to balance the smoke sensitivity of each of the sampling

    points.

  • 8/10/2019 Xtralis Training 2

    24/45

    Designing a pipe network - basics

    Is there moving air in the

    environment requiring fire

    protection?

    Is there objects in the

    environment requiring fireprotection?

    A simple environment requiring

    fire protection

  • 8/10/2019 Xtralis Training 2

    25/45

    Below Ceiling Sampling example 1

    Below-ceiling

    sampling

  • 8/10/2019 Xtralis Training 2

    26/45

    For ceiling mounted applications, sampling pointsshould be atleast 1 inch, but not more than 4 inchesbelow the ceiling and should be oriented downinto theroom space.

    This arrangement places the sampling points beneaththe small boundary layer of warm air that causessmoke stratification and is common in heatedenvironments or in actual fire conditions.

    Standard Sampling Pipe Network Guidelines

  • 8/10/2019 Xtralis Training 2

    27/45

    Capillary sampling - Introduction

    Capillary sampling is a means of locating sampling points

    away from the main sampling pipe without creating

    extremely complex networks.

    Typically, this method uses short 3 ft12 ft lengths of 3/16inch1/2 inch ID flexible tubing that branches off from the

    trunk pipe and then penetrates a given surface.

    Capillary sampling is useful where there is a localized

    monitoring of equipment cabinets is required.

    The sample hole location is marked with a printed decalaround the sample hole.

  • 8/10/2019 Xtralis Training 2

    28/45

    Sampling trunkpipe

    Capillary tube

    Trunk adaptor

    (any orientation

    Miniaturesampling pointfitting

    Ceiling panelor tile

    typical concealed sampling installation. The sampling point fitting places the sampling hole more than 25 mm (1

    nch) below the ceiling panel or tile.

    Ceiling capillary sampling

  • 8/10/2019 Xtralis Training 2

    29/45

    With concealed sampling, the trunk pipe network runs through a ceiling

    void and capillary tubes branch off at regular intervals to penetrate the

    ceiling panels or tiles

    The end of each capillary tube is terminated in a sampling point fitting

    The end vent of each pipe run should penetrate the protected area

    In some circumstances, an even more discreet means of sampling is

    needed.

    This is usually the case in historical buildings or in decorated interiors.

    A capillary tube branches from the trunk pipe and penetrates into thefire zone.

    Concealed Sampling Pipework

  • 8/10/2019 Xtralis Training 2

    30/45

    Mansion in Brazil

  • 8/10/2019 Xtralis Training 2

    31/45

    Sample hole

    Historic registered Liberty Theater 65 dome Astoria OR.

  • 8/10/2019 Xtralis Training 2

    32/45

    The minimum capillary tube ID is 0.2 inch.

    Although capillary tubes can be any length up to 26 ft it will benecessary to increase the capillary tube ID as the length of thetube increases.

    Concealed Sampling Guidelines

  • 8/10/2019 Xtralis Training 2

    33/45

    Inter-beam Sampling

    Walking Sticks

    are typically used

    between inter

    beam areas and

    difficult to get toplaces

  • 8/10/2019 Xtralis Training 2

    34/45

  • 8/10/2019 Xtralis Training 2

    35/45

    AHU# 1 AHU# 2

    VESDADetector

    Sampling pipes

    Standoffs StandoffsSealedendcap

    Sealedendca

    Esc

    1.0VESDA

    LaserPLUS

    FAULTS

    System

    Zone

    UrgentPo wer

    NetworkAirflowFilter

    ModeTest

    SilenceScan

    Reset Isolate

    OKIsolated

    Sensitivity

    Smoke Level

    ZoneNumber

    FirstAlarmSector

    Return Air Grille Sampling

  • 8/10/2019 Xtralis Training 2

    36/45

    Return Air Sampling

    Sampling

    point

    angled

    (between

    20 to 45

    deg) to

    obtain bestair sampleAHU

    Path of return air stream

    AHU vent

  • 8/10/2019 Xtralis Training 2

    37/45

    In areas of high assessed risk only two AHUs should be monitored by a

    single Detector.

    Additionally, only one AHU should be monitored by each sampling pipe.

    Return Air Grille Sampling

    Standoff p ost100 to 200 mm long(4 in to 8 in)

    Samplingpipe

    Self tapp ingscrews

    AHU

    Sampling pointangled to obtaibest air sample

    AHUvent

    Path ofreturn

    airstream

  • 8/10/2019 Xtralis Training 2

    38/45

    In-Duct Sampling

    Exhaust probe from detector

    Intake probe to detector

    AIR

    FLOW

  • 8/10/2019 Xtralis Training 2

    39/45

    AIRFLOW

    A pressure curve forms

    around the pipe as the

    airflow passes around it(20 to 45 deg angle)

    In-Duct Sampling

  • 8/10/2019 Xtralis Training 2

    40/45

    Reference Sampling

    Air Sampling External Source (Reference Zone)Reference Detector

    VESDAnet

    VESDAnet

    Sampling Pipes sampling Zone 1

    VESDA Zone 5

    (Reference Zone)

    Sampling Pipes sampling Zone 2

    Sampling Pipes sampling Zone 4Sampling Pipes sampling Zone 3

    Detector

    monitoring

    internal area

    VESDA Zone 1

    (Reference

    reading is

    subtracted)

    Detector

    monitoring

    internal area

    VESDA Zone 2

    (Reference

    reading is

    subtracted)

    Detector

    monitoring

    internal area

    VESDA Zone 4

    (Reference

    reading is

    subtracted)

    Detector

    monitoring

    internal area

    VESDA Zone 3

    (Reference

    reading is

    subtracted)

  • 8/10/2019 Xtralis Training 2

    41/45

    Effects of using multiple pipes

    Smoke diluted by air

    samples closer to the

    detector (low

    concentration)

    Smoke picked up

    here (high

    concentration)

    VESDALaserPLUS 88

    14 3 2 xWorst

    Option

    14 3 2

    VESDALaserPLUS 88

    Shorter pipe runs mean

    that dilution from smokefree air is less of a

    problem

    Best

    Option

  • 8/10/2019 Xtralis Training 2

    42/45

    ASPIRE2 - One Pipe

    6

    11

    16

  • 8/10/2019 Xtralis Training 2

    43/45

  • 8/10/2019 Xtralis Training 2

    44/45

  • 8/10/2019 Xtralis Training 2

    45/45

    ASPIRE2 Summary

    When using APIRE2, all parameter changes must be

    followed by the compute (calculate) command.