LGAI LGAI Technological Center, S.A. Campus UAB s/n Apartado de Correos 18 E - 08193 Bellaterra (Barcelona) T +34 93 567 20 00 F +34 93 567 20 01 www.applus.com This document will not be reproduced otherwise than in full. Only the reports with the original signature or collated will be legally valid This document consists of 4 pages LGAI Technological Center S.A. Inscrita en el registro Mercantil de Barcelona, Tomo 35.803, Folio1, Hoja Nº B-266.627 Inscripción 1ª C.I.F. : A-63207492 Page 1 Nº 9/LE 897 X/F Title: Title: Title: Title: Classification report of the fire resistance of a duct according to EN 13501-3:2005 + A1:2009 Standard “Fire Classification of construction products and building elements. Part 3 Classification using data from fire resistance tests on products and elements used in building service installations: fire resisting ducts and fire dampers.” (equivalent to UNE EN 13501-3:2007+A1:2010). Tested material: Tested material: Tested material: Tested material: Metallic duct protected with “Flexbifire” blankets supplied by Bifire. Test according to EN 1366-1:1999: "Fire Resistance tests for service installations. Part 1: Ducts" (equivalent to UNE EN 1366-1:2000) and EN 1363-1:1999 “Fire Resistance tests: General Requirements” (equivalent to UNE EN 1363-1:2000). Duct is tested according to duct A criterion in vertical position. File number: File number: File number: File number: 12/4725 12/4725 12/4725 12/4725-147 147 147 147 Solicitor: Solicitor: Solicitor: Solicitor: Bifire srl via Lavoratori Autobianchi 1 20832 Desio (MB) Italy Report Date: Report Date: Report Date: Report Date: 30 th January 2013 Tested on: Tested on: Tested on: Tested on: 29 th March 2012

Transcript of X/F - Bifire 12-4725-576 FLEXBIFIRE... · 66..6.-6.--- FIELD OF DIRECT APPLICATION (according to...

LGAI LGAI Technological Center, S.A. Campus UAB s/n Apartado de Correos 18 E - 08193 Bellaterra (Barcelona) T +34 93 567 20 00 F +34 93 567 20 01 www.applus.com

This document will not be reproduced otherwise than in full. Only the reports with the original signature or collated will be legally valid This document consists of 4 pages

LGAI Technological Center S.A. Inscrita en el registro Mercantil de Barcelona, Tomo 35.803, Folio1, Hoja Nº B-266.627 Inscripción 1ª C.I.F. : A-63207492

Page 1

Nº 9/LE 897

X/F

Title: Title: Title: Title: Classification report of the fire resistance of a duct according to EN 13501-3:2005 + A1:2009 Standard “Fire Classification of construction products and building elements. Part 3 Classification using data from fire resistance tests on products and elements used in building service installations: fire resisting ducts and fire dampers.” (equivalent to UNE EN 13501-3:2007+A1:2010).

Tested material:Tested material:Tested material:Tested material: Metallic duct protected with “Flexbifire” blankets supplied by Bifire. Test according to EN 1366-1:1999: "Fire Resistance tests for service installations. Part 1: Ducts" (equivalent to UNE EN 1366-1:2000) and EN 1363-1:1999 “Fire Resistance tests: General Requirements” (equivalent to UNE EN 1363-1:2000). Duct is tested according to duct A criterion in vertical position.

File number: File number: File number: File number: 12/472512/472512/472512/4725----147147147147

Solicitor: Solicitor: Solicitor: Solicitor: Bifire srl via Lavoratori Autobianchi 1 20832 Desio (MB) Italy Report Date:Report Date:Report Date:Report Date: 30th January 2013 Tested on:Tested on:Tested on:Tested on: 29th March 2012

File number: 13/4725-147 Page 2

1. 1. 1. 1. ---- INTRODUCTIONINTRODUCTIONINTRODUCTIONINTRODUCTION This fire resistance classification report defines the classification assigned to duct according to EN 13501-3:2005 + A1:2009 Standard “Fire Classification of construction products and building elements. Part 3 Classification using data from fire resistance tests on products and elements used in building service installations: fire resisting ducts and fire dampers.” (equivalent to UNE EN 13501-3:2007+A1:2010). 2. 2. 2. 2. ---- DETAILS OF THE CLASSIFIED ELEMENTDETAILS OF THE CLASSIFIED ELEMENTDETAILS OF THE CLASSIFIED ELEMENTDETAILS OF THE CLASSIFIED ELEMENT 2.1. 2.1. 2.1. 2.1. ---- Type of functionType of functionType of functionType of function The tested element, a duct of 4300 mm (length) x 1100 mm (width) x 600 mm (height), is defined as a metallic duct type A (metallic duct with inner section of 1000 mm x 500 mm according to point 6.1.3 de UNE EN 1366-1:2000) assembled in vertical position. Its function consists to distribute the air giving a fire resistance. 2.2. 2.2. 2.2. 2.2. ---- DescriptionDescriptionDescriptionDescription The test report provides an entire description of the items subjected to the test. 3. 3. 3. 3. ---- TEST REPORTTEST REPORTTEST REPORTTEST REPORT This classification report is based on the following test report: File Number: File Number: File Number: File Number: 12/472512/472512/472512/4725----576576576576 Part 1Part 1Part 1Part 1 Issued on: Issued on: Issued on: Issued on: 20202020 of of of of NovemberNovemberNovemberNovember of 201of 201of 201of 2012222 Test performed on: Test performed on: Test performed on: Test performed on: 29 of March29 of March29 of March29 of March of 201of 201of 201of 2012222 4. 4. 4. 4. ---- TEST RESULTS TEST RESULTS TEST RESULTS TEST RESULTS 4444.1. .1. .1. .1. –––– Test StandardTest StandardTest StandardTest Standard: : : : EN 1366-1:1999: "Fire Resistance tests for service installations. Part 1: Ducts"(equivalent to UNE EN 1366-1:2000). 4.2. 4.2. 4.2. 4.2. –––– EEEExposure conditionsxposure conditionsxposure conditionsxposure conditions Temperature/time curveTemperature/time curveTemperature/time curveTemperature/time curve T = 345 log10 (8t + 1) + 20 Exposure directionExposure directionExposure directionExposure direction Exposed to fire from the outside Duct orientationDuct orientationDuct orientationDuct orientation Vertical Number of exposed sidesNumber of exposed sidesNumber of exposed sidesNumber of exposed sides 4 Load appliedLoad appliedLoad appliedLoad applied Without load Support conditionsSupport conditionsSupport conditionsSupport conditions Duct placed directly on the furnace floor and fixed

at the closing slab by means of angular profiles of 75x50x5 mm, placed one at each corner.

File number: 13/4725-147 Page 3

4.3.4.3.4.3.4.3.---- RRRResults tableesults tableesults tableesults table

Minute failureMinute failureMinute failureMinute failure CauseCauseCauseCause

IntegrityIntegrityIntegrityIntegrity It is maintained the entire test, 202 minutes

-

InsulationInsulationInsulationInsulation 200’ Temperature rise of tp 25

exceeds 180ºC

Smoke leakSmoke leakSmoke leakSmoke leak It is maintained the entire test, 202 minutes

-

5.5.5.5.---- CLASSIFICATIONCLASSIFICATIONCLASSIFICATIONCLASSIFICATION According to section 7.2 of the Standard EN 13501-3:2005+A1:2009, the classification of the before-mentioned element is the following:

Vertical Vertical Vertical Vertical type A type A type A type A dddduct of uct of uct of uct of 4300430043004300 mm in length and section mm in length and section mm in length and section mm in length and section 1101101101100000 mm x mm x mm x mm x 666600000000 mmmmmmmm (metallic duct of 10(metallic duct of 10(metallic duct of 10(metallic duct of 1000 mm x 500 00 mm x 500 00 mm x 500 00 mm x 500 mm of inner section and mm of inner section and mm of inner section and mm of inner section and 1 mm in thickness)1 mm in thickness)1 mm in thickness)1 mm in thickness) protected protected protected protected with “with “with “with “FlexbifireFlexbifireFlexbifireFlexbifire”””” blanketsblanketsblanketsblankets fromfromfromfrom BIFIREBIFIREBIFIREBIFIRE....

EI EI EI EI 120120120120 ((((veveveve oooo→→→→i)i)i)i) SSSS

6.6.6.6.---- FIELD OF DIRECT APPLICATION (according to point. 13 of UNE EN 1366FIELD OF DIRECT APPLICATION (according to point. 13 of UNE EN 1366FIELD OF DIRECT APPLICATION (according to point. 13 of UNE EN 1366FIELD OF DIRECT APPLICATION (according to point. 13 of UNE EN 1366----1:2000 Standard)1:2000 Standard)1:2000 Standard)1:2000 Standard) FeatureFeatureFeatureFeature ReferencReferencReferencReference of tested sae of tested sae of tested sae of tested samplemplemplemple Modifications Modifications Modifications Modifications

General Rectangular duct - Covers only

rectangular ducts

Duct’s orientation

Duct type A vertically assembled.

- Covers type A ducts

without branches.

Size of duct Metallic duct with section 1000 x 500 mm (width x height).

- Unlimited decrease - Allowed width increase

+ 250 mm. - Allowed height

increase + 500 mm.

Duct supported at each storey

Not applicable

Applicable to any number of storeys provided that:

- Layout as tested one.

- Distance between supporting construction does not exceed 5m.

- limitations on

File number: 13/4725-147 Page 4

buckling are satisfied (see below)

Limitations on buckling

Length of exposed duct (L): 2000 mm Smallest lateral dimensions (d): 600 mm Tested L/d ratio: 3.33

Test results are only applicable to situations where the L/d ratio does not exceed 8:1 If additional supports are provided, distance between supports or between supports and supporting constructions shall be considered as L.

Support frame concrete slab 200 mm of thickness and 2100 kg/m3

Applicable to slabs with a thickness equal or major than 200 mm and density equal or major than 2100 kg/m3.

Steel duct

Duct with a class A air tightness (according to EN 1507: 2007)

Applicable to ducts with higher air tightness than class A

The validity period is the one indicated in the product certification system. This document is not neither a type approval nor a product certification.

Responsible of Fire Laboratory LGAI Technological Center, S.A.

Responsible of Fire Resistance LGAI Technological Center, S.A.

The results refer exclusively to the sample, product or material surrendered to the Laboratory, just as it is informed in the section of received material and tested under the conditions indicated in the norms mentioned in this document.

Quality Service WarrantyQuality Service WarrantyQuality Service WarrantyQuality Service Warranty Applus+Applus+Applus+Applus+, guaranties that this work has been realized following the exigencies of our Quality and Sustainable System, complying with honouring the contractual conditions and the legal standard. We would be very grateful if you would send us any comment you consider appropriate , addressing either to the signatory of this document or to the Applus+ Quality Director, to the direction [email protected]

Bifire® s.r.l. Sede Legale Via Carducci 8 – Milano - 20123 (MI) Sede Operativa Via Lavoratori dell’Autobianchi 1- Desio – 20832 (MB) Telefono +39 0362-364570 - Telefax +39 0362-334134 Internet www.bifire.it - E-mail [email protected] Partita IVA 03645510961 Capitale Sociale € 600.000,00 i.v. Registro Imprese Milano n°03645510961 -N°REA CCIAA MI 1964336

RIQUALIFICAZIONE DI CONDOTTA DI VENTILAZIONE EI120 ORIZZONTALE E

VERTICALE CON FLEXBIFIRE sp.40mm

Riqualificazione antincendio con grado di protezione EI120 di condotta di ventilazione metallica

orizzontale e verticale con feltro a base di fibre minerali ed alcaline non biopersistenti rivestito da

speciale tessuto di vetro denominato FLEXBIFIRE avente spessore nominale di sp.40mm.

PRODOTTO: FLEXBIFIRE sp.40mm singolo strato

CONDOTTA: Condotta metallica di classe A o superiore (EN 1507), in posizione verticale o

orizzontale, con o senza diramazioni laterali, superiori o inferiori

POSA:

- tratti rettilinei: Avvolgere il condotto con singolo strato di FLEXBIFIRE 40mm,

sovrapposizione trasversale di 200mm, sovrapposizione longitudinale di 200mm per tutto

lo spessore del FLEXBIFIRE. Occorrerà aiutarsi con il nastro Bifire per far aderire bene il

FLEXBIFIRE al condotto metallico, e poi fissare il tutto con il filo d’acciaio;

- tratti curvilinei: Avvolgere il condotto con singolo strato di FLEXBIFIRE 40mm partendo

dal raggio esterno della curva procedendo verso l’interno. Nella parte interna della curva

occorrerà concentrare e compattare il FLEXBIFIRE per i raggi più piccoli; se necessario, si

dovrà posare un secondo materassino al fine di non lasciare nessuna parte del condotto

metallico scoperta; si dovrà comunque garantire una sovrapposizione trasversale e

longitudinale di 200mm; Occorrerà aiutarsi con il nastro Bifire per far aderire bene il

FLEXBIFIRE al condotto metallico, e poi fissare il tutto con il filo d’acciaio.

FISSAGGIO PRODOTTO: 1 giro di filo d’acciaio, diametro 1.2mm, passo 333mm

SOSTEGNO CONDOTTA: il sostegno in orizzontale deve essere opportunamente dimensionato in

funzione del peso al metro lineare del condotto e del carico sui pendini di sospensione (EN 1366-1

punto 13.6.1). Indicativamente, per una condotta avente sezione 1000x500x1,0 utilizzare pendini

in acciaio φ10mm, barra orizzontale a “C” 40x30x2 preforata, passo 1.6mt.

In verticale vincolare il condotto nella zona dell’attraversamento a soletta con sostegno in profili

ad L 75x50x5 e barre filettate di serraggio.

CERTIFICATO DI RIFERIMENTO:APPLUS 11/2701-2802 (in conformità con UNI EN 1366-1)

APPLUS 12/4725-576 (in conformità con UNI EN 1366-1)

Bifire® s.r.l. Sede Legale Via Carducci 8 – Milano - 20123 (MI) Sede Operativa Via Lavoratori dell’Autobianchi 1- Desio – 20832 (MB) Telefono +39 0362-364570 - Telefax +39 0362-334134 Internet www.bifire.it - E-mail [email protected] Partita IVA 03645510961 Capitale Sociale € 600.000,00 i.v. Registro Imprese Milano n°03645510961 -N°REA CCIAA MI 1964336

Fig.1: riqualificazione EI120 di condotta di ventilazione: sezione longitudinale di un tratto orizzontale

Fig.2: riqualificazione EI120 di condotta di ventilazione: sezione trasversale

FLEXBIFIRE sp.40mmsu condotto principale

FLEXBIFIRE sp.40mmprotezione attraversamento

filo d'acciaio Ø1,2mmchiusura coprigiunto

filo d'acciaio Ø1,2mmchiusura attraversamento

filo d'acciaio Ø1,2mmchiusura condottoprincipale

333 333 333

10001000

condotto in acciaiomax 1250x1000mm

200

FLEXBIFIRE sp.40mmsu condotto principale

condotto in acciaiomax 1250x1000mm

Bifire® s.r.l. Sede Legale Via Carducci 8 – Milano - 20123 (MI) Sede Operativa Via Lavoratori dell’Autobianchi 1- Desio – 20832 (MB) Telefono +39 0362-364570 - Telefax +39 0362-334134 Internet www.bifire.it - E-mail [email protected] Partita IVA 03645510961 Capitale Sociale € 600.000,00 i.v. Registro Imprese Milano n°03645510961 -N°REA CCIAA MI 1964336

Fig.3: riqualificazione EI120 di condotta di ventilazione: tratto curvilineo

Fig.4: riqualificazione EI120 di condotta di ventilazione: sezione longitudinale di un tratto verticale

FLEXBIFIRE sp.40mmsu condotto principale

filo d'acciaio Ø1,2mm

filo d'acciaio Ø1,2mm

FLEXBIFIRE sp.40mmsu condotto principale

FLEXBIFIRE sp.40mmprotezione attraversamento

filo d'acciaio Ø1,2mmchiusura coprigiunto

filo d'acciaio Ø1,2mmchiusura condottoprincipale

condotto in acciaiomax 1250x1000mm

filo d'acciaio Ø1,2mmchiusura attraversamento

"L" 75x50x5mmin acciaio

tassello metallicobarra filettata di serraggio