Xenon Lighting: Technology Evaluation & TestingDue to the potential use of xenon lamps in outdoor...
Transcript of Xenon Lighting: Technology Evaluation & TestingDue to the potential use of xenon lamps in outdoor...
PG&E’s Emerging Technologies Program ET12PGE1262
Xenon Lighting:
Technology Evaluation & Testing
ET Project Number: ET12PGE1262
Project Manager: Philip Broaddus Pacific Gas and Electric Company Prepared By: California Lighting Technology Center University of California, Davis 633 Pena Drive Davis, California
Issued: June 2015
PG&E’s Emerging Technologies Program ET12PGE1262
Copyright, 2015, Pacific Gas and Electric Company. All rights reserved.
i
PG&E’s Emerging Technologies Program ET12PGE1262
ACKNOWLEDGEMENTS
Pacific Gas and Electric Company’s Emerging Technologies Program is responsible for this project. It was developed as part of Pacific Gas and Electric Company’s Emerging Technology – Technical Assessment program under internal project number ET12PGE1262. The California Lighting Technology Center conducted this technology evaluation for Pacific Gas and Electric Company with overall guidance and management from Philip Broaddus. For more information on this project, contact [email protected].
LEGAL NOTICE
This report was prepared for Pacific Gas and Electric Company for use by its employees and agents. Neither Pacific Gas and Electric Company nor any of its employees and agents:
(1) makes any written or oral warranty, expressed or implied, including, but not limited to those concerning merchantability or fitness for a particular purpose;
(2) assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, process, method, or policy contained herein; or
(3) represents that its use would not infringe any privately owned rights, including, but not limited to, patents, trademarks, or copyrights.
ii
PG&E’s Emerging Technologies Program ET12PGE1262
ABBREVIATIONS AND ACRONYMS
CCT Correlated Color Temperature
CIE International Commission on Illumination
CLTC California Lighting Technology Center
CMH Ceramic Metal Halide
CRI Color Rendering Index
DLC DesignLights Consortium
HPS High Pressure Sodium
IES Illuminating Engineering Society
LED Light Emitting Diode
LM Lighting Memorandum
LPW Lumen per Watt
MH Metal Halide
nm nanometers
PGE Pacific Gas and Electric Company
TM Technical Memorandum
SSL Solid-state Lighting
iii
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURES
Figure 1 – Two meter integrating sphere ......................................... 7
Figure 2 – CIE color space with black body locus .............................. 8
Figure 3 – Color rendering index (CRI Ra) color samples.................... 9
Figure 4 – CIE 1960 with blackbody locus and vectors indicating
positive and negative Duv. ........................................... 9
Figure 5 - CCT quadrangles for the Energy Star LED specification ..... 10
Figure 6 - Goniophotometer (Type C) ........................................... 11
Figure 7 - Xenon Testing Set Up, Side View ................................... 12
Figure 8 – Xenon Testing Set Up, Top View ................................... 12
Figure 9 – Light Sensor Location, Bare lamp .................................. 13
Figure 10 – Light Sensor Location, Fixture ..................................... 14
Figure 11 –Thermocouple Attachment Locations ............................. 14
Figure 12 – Luminous Flux for Manufacturer 2 - Bare Lamps
(Manufacturer Specifications in Dashed Lines) ............... 18
Figure 13 – Luminous Flux for Manufacturer 2 – In Fixtures
(Manufacturer Specifications in Dashed Lines) ............... 18
Figure 14 - CCT for Manufacturer 2 (Manufacturer Specifications in
Dashed Lines) ............................................................ 19
Figure 15– Duv for Manufacturer 2 ............................................... 20
Figure 16 – CRI for Manufacturer 2 (Manufacturer Specifications in
Dashed Lines) ............................................................ 20
Figure 17 - Bare Lamp Distribution Plot for Initial Light Output ........ 21
Figure 18 - Fixture Distribution Plot for Initial Light Output .............. 21
Figure 19 – Light Level during Life Testing for Manufacturer 2 -
Bare Lamps ............................................................... 23
Figure 20 – Light Level during Life Testing for Manufacturer 2 -
Fixtures .................................................................... 24
Figure 21 - Ballast Temperatures for Manufacturer 2 – Bare Lamps .. 25
Figure 22 – Ballast and Chamber Temperatures for Manufacturer 2
- Fixture .................................................................... 26
iv
PG&E’s Emerging Technologies Program ET12PGE1262
TABLES
Table 1 – Average Luminaire Efficacy for Outdoor Lighting
Technologies ............................................................... 1
Table 2 – Average Luminaire CRI for Outdoor Lighting Technologies ... 1
Table 3 – Average Luminaire CCT for Outdoor Lighting
Technologies ............................................................... 2
Table 4 – Average Lamp Life for Outdoor Lighting Technologies ......... 2
Table 5 - Manufacturer Literature Performance Claims And Tested
Performance - Manufacturer 2 ....................................... 2
Table 6 - Performance specifications for the DesignLights
Consortium benchmark ................................................. 3
Table 7 – Installed Baseline for Outdoor Lighting Technologies in
the United States ........................................................ 5
Table 8 – Chromaticity coordinates defining CCT quadrangles for
Energy Star LED specification ..................................... 10
Table 9 – Average Luminaire Efficacy for Outdoor Lighting
Technologies ............................................................. 15
Table 10 – Average Luminaire CRI for Outdoor Lighting
Technologies ............................................................. 15
Table 11 – Average Luminaire CCT for Outdoor Lighting
Technologies ............................................................. 16
Table 12 – Average Lamp Life for Outdoor Lighting Technologies ..... 16
Table 13 - Manufacturer Performance Claims ................................. 17
Table 14 - Manufacturer Literature Performance CLAIMS AND
Tested Performance - Manufacturer 2 ........................... 27
Table 15 - Performance specifications for the DesignLights
Consortium benchmark ............................................... 27
v
PG&E’s Emerging Technologies Program ET12PGE1262
CONTENTS
ABBREVIATIONS AND ACRONYMS _____________________________________________ II
FIGURES _______________________________________________________________ III
TABLES ________________________________________________________________ IV
CONTENTS _____________________________________________________________ V
EXECUTIVE SUMMARY _____________________________________________________ 1
INTRODUCTION __________________________________________________________ 5
BACKGROUND __________________________________________________________ 5
EMERGING TECHNOLOGY __________________________________________________ 6
ASSESSMENT OBJECTIVES __________________________________________________ 6
TECHNICAL APPROACH ___________________________________________________ 7
Market Characterization ........................................................... 7
Photometric Testing ................................................................. 7
Life Testing .......................................................................... 11
Data Analysis ........................................................................ 14
RESULTS_______________________________________________________________ 15
Market Characterization ......................................................... 15
Photometry Results ............................................................... 17
Colorimetric Results ............................................................... 19
Distribution Results ............................................................... 21
Run-Time Results .................................................................. 21
EVALUATIONS __________________________________________________________ 27
RECOMMENDATIONS ____________________________________________________ 29
APPENDIX 1 – EQUIPMENT SPECIFICATION SHEETS _______________________________ 30
1
PG&E’s Emerging Technologies Program ET12PGE1262
EXECUTIVE SUMMARY
PROJECT GOAL Due to the potential use of xenon lamps in outdoor applications, CLTC in collaboration with PG&E, developed an
evaluation and testing program for xenon technology used in general illumination, outdoor applications. The
research included under this project informs utilities about the performance and reliability of xenon lamps in these
applications as compared to Light Emitting Diodes (LED), induction or other appropriate parking and area lighting
solutions. This program identified available xenon products, evaluated manufacturers’ product literature to estimate
their performance against other outdoor luminaires, and quantified photometric and electrical performance of
representative xenon products in a laboratory setting using industry-accepted test methods. Information and results
may be used to determine the viability of xenon technology for current or future incentive programs.
PROJECT DESCRIPTION This evaluation project consists of a commercially available outdoor lighting product market assessment, a
comparison of manufacturer claims regarding these products, and a laboratory evaluation of representative xenon
products marketed for use in the outdoor sector. Laboratory test results characterize xenon product performance with
respect to photometric and electrical properties over the course of 11,000 hours of run-time.
PROJECT FINDINGS Manufacturer’s claimed performance data was collected for representative examples of existing outdoor
technologies to inform a recommended minimum performance specification for general illumination, outdoor
applications. For each lighting technology, products were compared based on equivalent initial delivered light
output and binned into output ranges. The average of manufacturer’s claimed performance by output range is
provided in Table 1 – Table 4.
TABLE 1 – AVERAGE LUMINAIRE EFFICACY FOR OUTDOOR LIGHTING TECHNOLOGIES
Light Output (lm) Average Luminaire Efficacy (lm/W)
HPS Induction LED MH Ceramic Xenon
0 – 5,000 - 46.4 63.7 81.1 67.7
5,001 – 10,000 57.6 47.6 74.0 74.4 69.7
10,001 – 15,000 65.5 93.1 74.4 76.0 66.7
15,001 – 20,000 64.6 - 75.6 - 66.7
20,001 – 25,000 - - 71.6 75.6 -
TABLE 2 – AVERAGE LUMINAIRE CRI FOR OUTDOOR LIGHTING TECHNOLOGIES
Light Output (lm) Average CRI
HPS Induction LED MH Ceramic Xenon
0 – 5,000 - 83 70 70 85
5,001 – 10,000 21 85 73 70 78
10,001 – 15,000 21 80 73 70 85
15,001 – 20,000 21 - - 90 85
20,001 – 25,000 - - 70 90 -
2
PG&E’s Emerging Technologies Program ET12PGE1262
TABLE 3 – AVERAGE LUMINAIRE CCT FOR OUTDOOR LIGHTING TECHNOLOGIES
Light Output (lm) Average CCT (Kelvin)
HPS Induction LED MH Ceramic xenon
0 – 5,000 - 5,000 3,900 2,800 4,500
5,001 – 10,000 2,100 5,000 4,500 2,800 4,400
10,001 – 15,000 2,100 5,000 4,500 2,800 4,300
15,001 – 20,000 2,100 - - 3,000 4,300
20,001 – 25,000 - - 5,000 3,000 -
TABLE 4 – AVERAGE LAMP LIFE FOR OUTDOOR LIGHTING TECHNOLOGIES
Light Output (lm) Average Lamp Life (hours)
HPS Induction LED MH Ceramic xenon
0 – 5,000 - 100,000 65,000 30,000 25,000
5,001 – 10,000 24,000 100,000 75,000 30,000 40,000
10,001 – 15,000 24,000 100,000 75,000 30,000 20,000
15,001 – 20,000 24,000 - - 24,000 20,000
20,001 – 25,000 - - 24,000 50,000 -
Following this work, the project team identified two, representative, xenon product manufacturers for inclusion in a
multi-year test program to evaluate their products photometric and electrical performance over time. These
manufacturers are referenced as Manufacturer 1 and Manufacturer 2. Reliability issues encountered during the lamp
burn-in with Manufacturer 1 products disqualified it from the long-term testing program. After the initial burn-in
period, testing included 16 test samples from Manufacturer 2. Seven of the samples were tested in shoe-box fixtures.
Nine samples were tested without fixtures and are referenced as ‘bare lamps’. A summary of Manufacturer 2
performance claims, initial test results and 11,000-hour test results are provided in Table 5.
TABLE 5 - MANUFACTURER LITERATURE PERFORMANCE CLAIMS AND TESTED PERFORMANCE - MANUFACTURER 2
Performance Metric
Manufacturer
Specification
Sheet
Tested Initial
Performance (Average)
Tested 11,000 Hour
Performance (Average)
Bare Lamp Bare Lamp Fixture Bare Lamp Fixture
System Power (W) 67.4 67.7 135.0 69.1 73.5
Luminous Flux – Initial (lm) 6,660 5,176.6 6,275 4,177 2,849
Luminous Flux – Mean (lm) 6,030 - - - -
Efficacy (lm/W) Up to 108 76.5 46.5 60.4 38.8
CRI >80 64.3 65.6 42.4 42.2
CCT 4,300 3,430 3,470 2,853 2,622
Lamp Life (hrs.) 30,000 - - - -
Test results were compared to manufacturer claims and industry standards available at the time of this evaluation.
One industry tool used to benchmark lighting product performance is the DesignLights Consortium (DLC). The
DLC “promotes quality, performance and energy efficient commercial sector lighting solutions through
collaboration among its federal, regional, state, utility, and energy efficiency program members, luminaire
3
PG&E’s Emerging Technologies Program ET12PGE1262
manufacturers, lighting designers, and other industry stakeholders throughout the US and Canada.” The current
DLC standard for retrofit kits intended for outdoor pole mounted area luminaire applications is included in Table 6.
TABLE 6 - PERFORMANCE SPECIFICATIONS FOR THE DESIGNLIGHTS CONSORTIUM BENCHMARK
DesignLights Consortium Technical Requirements - Retrofit Kits for Outdoor Pole Mounted Area Luminaires 1
Minimum Light Output 1,000 lumens
Zonal Lumen Density 100% light output: 0-90°, <10% light output: 80-90°
Minimum Luminaire Efficacy 70 lumens per Watt
Allowable CCT Less than or equal to 5,700 Kelvin (defined by ANSI C78.377-2011)
Minimum Color Rendering Index 65
L70 Lumen Maintenance 50,000 hours
Warranty 5 years
With respect to luminous output, the xenon product’s baseline and 11,000 hour run-time test results were lower than
manufacturer’s claims. However, the DLC technical specification for outdoor, pole mounted, retrofit kits requires a
minimum light output of 1,000 lumens and tested xenon products met this criteria.
With respect to light distribution, the DLC specification requires 100% of light output to be below 90 degrees with
less than 10% in the 80-90 degree zone. The initial light output distribution plots for representative product samples
showed that the bare lamp retrofit kit produced a non-cutoff distribution. When installed in a shoebox fixture, the
luminaire produced a cutoff distribution with 0.5% of its light output in the 80-90 degree zone. The xenon bare
lamp retrofit kit met the DLC requirements for zonal lumen density when installed in a typical shoebox fixture.
With respect to system efficacy, manufacturer literature claimed an initial system efficacy of 98.8 lumens per watt
(LPW). The average efficacy of the tested bare lamps resulted in an initial value of 76.5 LPW and 60.4 LPW at
11,000 hours of run-time. The average efficacy of products installed in fixtures resulted in an initial value of 46.5
LPW and 38.8 LPW at 11,000 hours of run-time. The DLC technical specification for outdoor, pole mounted
retrofit kits requires an efficacy of 70 LPW. The tested xenon products did not meet this criteria.
For outdoor retrofit kits, manufacturer literature claimed CCT performance of 4,300 K. Tested products did not meet
the manufacturer claims. See Table 5. DLC specifications allow a CCT less than or equal to 5,700 K. Over the
course of the evaluation, the tested products met this criteria with products trending towards warmer CCT over the
11,000 hours of run-time
With respect to color rendering index (CRI), manufacturer literature claimed a CRI of 80 or greater for tested
products. Test results show an average, initial CRI of 65 and a CRI of 42 at 11,000 hours of run-time. The tested
xenon products did not meet manufacturer claims for CRI. DLC specifications require a minimum of 65 CRI. The
tested xenon products did not meet DLC requirements.
Eleven of 18 bare lamps tested failed prior to the 11,000 hours of run-time. Leveraging industry standards for
similar lighting technologies where “average rated lamp life is defined as that time after which 50% of a large group
of lamps are still in operation”2, the tested xenon products did not meet manufacturer claims of a 30,000 hour
lifetime.
1 DesignLights Consortium. Technical Requirements Table v2.1. 2015. 2 Illuminating Engineering Society. The Lighting Handbook. Tenth Edition. Page 7.45. 2011.
4
PG&E’s Emerging Technologies Program ET12PGE1262
For xenon lamps installed and tested in fixtures, three of seven fixtures were operational at 11,000 hours. The test
product’s configuration included redundant arc tubes. Of the total arc tubes, 3 of 14 arc tubes were operational.
Leveraging industry standards for similar lighting technologies where “average rated lamp life is defined as that
time after which 50% of a large group of lamps are still in operation”, the tested xenon product did not meet
manufacturer claims of a 30,000 hour lifetime when installed in typical shoebox fixtures.
At the time of this evaluation, the tested xenon products did not meet manufacturer claims for light output, luminaire
efficacy, CCT, CRI or lifetime.
PROJECT RECOMMENDATIONS The performance testing conducted as part of this xenon evaluation provides context regarding expected product
operation. Stakeholders considering development of incentive programs for xenon products used in the commercial
outdoor lighting sector should consider this data. The representative xenon products tested did not meet
manufacturer performance claims for light output, luminaire efficacy, CCT, CRI or lifetime. For best-practice
lighting design, each product should be evaluated individually to verify its reliability and performance before
specifying its use. In addition, it is recommended that industry accepted standards be leveraged as the performance
specification for xenon moving forward. One such standard, provided by the DLC, is available for LED outdoor,
pole mounted, retrofit kits.
5
PG&E’s Emerging Technologies Program ET12PGE1262
INTRODUCTION Due to the potential use of xenon lamps in outdoor applications, CLTC in collaboration with PG&E, developed an
evaluation and testing program for xenon technology used in general illumination, outdoor applications. The
research included under this project informs utilities about the performance and reliability of xenon lamps in these
applications as compared to Light Emitting Diodes (LED), induction or other appropriate parking and area lighting
solutions. This program identified available xenon products, evaluated manufacturers’ product literature to estimate
their performance against other outdoor luminaires, and quantified photometric and electrical performance of
representative xenon products in a laboratory setting using industry-accepted test methods. Information and results
may be used to determine the viability of xenon technology for current or future incentive programs.
BACKGROUND In a properly designed lighting system, application-appropriate illumination levels are provided without producing
extraneous light or glare. Luminaire pole spacing and distribution types are chosen to optimize the coefficient of
utilization or maximize the use of light where it is needed. Light pollution and light trespass, such as street lights
shining into neighboring windows, is mitigated with use of appropriate optical designs. As of 2010, high pressure
sodium (HPS) and metal halide lamps with magnetic ballasts were identified as the most common types of
luminaires used in outdoor applications. Potential replacement technologies include induction, LED, ceramic metal
halide, and xenon.
TABLE 7 – INSTALLED BASELINE FOR OUTDOOR LIGHTING TECHNOLOGIES IN THE UNITED STATES 3
Source
Type
Installed
Base
Market
Share
Incandescent 17,814,000 10%
Halogen 4,021,000 2%
Compact fluorescent 12,053,000 7%
Linear fluorescent 29,124,000 16%
Mercury vapor 4,177,000 2%
Metal halide 29,514,000 17%
High pressure sodium 57,941,000 32%
Low pressure sodium 1,455,000 1%
LED 19,219,000 11%
Miscellaneous 3,056,000 2%
3 Navigant Consulting, Inc., Building Technologies Program, U.S. Department of Energy. 2010 U.S. lighting market characterization.
January 2012.
6
PG&E’s Emerging Technologies Program ET12PGE1262
EMERGING TECHNOLOGY Xenon products marketed for outdoor, general illumination applications consist predominantly of retrofit kits that
include a xenon lamp and ballast. Interviews with lighting distributors established that the most common xenon
retrofit kits were targeted at shoebox-style fixtures. Therefore, the shoebox-style retrofit solution was chosen as the
representative xenon product for this evaluation.
Performance characteristics of commercially available luminaires for general outdoor applications were reviewed to
characterize this market. The project team reviewed an example of each lighting solution listed in Table 7 and for a
range of light output groups. Performance metrics collected include power, light output, CCT, CRI, and lifetime.
Power (W) – The maximum amount of power required to operate the luminaire (measured in watts).
Light Output (lm) – The amount of visible light output by a light source independent of direction, and
weighted to the sensitivity of human vision (measured in lumens).
Correlated Color Temperature (CCT), Duv – CCT correlates a luminaire’s color to the color of a black
body radiator at a given temperature and is measured in degrees kelvin (K). A tight tolerance on the color
temperature and Duv of luminaires ensures that luminaires in close spatial proximity appear to be the same
color.
Color Rendering Index – CRI compares a light source’s rendering of a set of pastel colors with that of a
blackbody radiator of the same CCT. CRI (Ra) is the most widely used standard to establish the ability of a
luminaires to render colors correctly.
Lifetime – The lifetime of each lamp, expressed in hours. For metal halide and xenon this was defined as
the number of hours that on average 50% of lamps would fail by (67% for high pressure sodium). For LED
and induction lamps, this is the point at which lumen output has reduced to 70% of its initial rated output
(L70).
These performance metrics were used to compare xenon luminaires with traditional outdoor luminaires and other
potential replacement technologies. These metrics form the foundation of the minimum performance specification
recommended for xenon products used in general illumination, outdoor applications.
ASSESSMENT OBJECTIVES The assessment objective of the xenon technology evaluation program was to characterize xenon product
performance with respect to multiple performance metrics and compare that performance to other outdoor lighting
technologies. Performance metrics were collected from manufacturer’s product literature and used as part of the
initial market characterization discussed below. The project team also conducted a laboratory evaluation of selected
xenon products to verify manufacturer’s claims and document actual product performance with respect to industry
standard technical requirements for alternative replacement technologies. Recommendations based on evaluation
results may be used to determine the xenon’s viability for current or future rebate and incentive programs.
7
PG&E’s Emerging Technologies Program ET12PGE1262
TECHNICAL APPROACH This evaluation program’s technical approach included a market characterization and photometric testing of selected
xenon products conducted according to industry-standard test procedures.
MARKET CHARACTERIZATION
Manufacturer performance data was collected for representative examples of traditional and emerging technologies.
Xenon manufacturers identified during the market characterization were contacted and interviews conducted to
understand how they intended xenon products to be used in outdoor applications. Products commercially available
in the United States were determined appropriate for inclusion in the evaluation.
PHOTOMETRIC TESTING
Selected products underwent photometric testing to verify initial and long-term performance. For photometric
testing, luminaires and lamps were mounted on brackets optimized for their form factor. Integrating sphere and
goniophotometer tests were completed to characterize the product’s baseline performance. Additional integrating
sphere tests were completed after each 1,000 hours of run-time to characterize performance over time.
INTEGRATING SPHERE Metrics related to light, without respect to angle, such as light output, correlated color temperature (CCT), CRI, and
chromaticity, were measured in an integrating sphere, shown in Figure 1. The sphere’s interior coating allows for
light to be distributed diffusely and evenly over sphere’s interior surface. A shielded spectrometer on the sphere’s
surface was used to collect spectral power distribution (SPD) measurements. SPD provides radiance (power in
Watts) per wavelength (nm). The spectrometer used in this testing is capable of measuring light with wavelengths
between 360 nanometers (nm) and 1,000 nm.
FIGURE 1 – TWO METER INTEGRATING SPHERE
8
PG&E’s Emerging Technologies Program ET12PGE1262
The procedures for collecting integrating sphere measurements are detailed in the Illuminating Engineering
Society’s (IES) Lighting Memorandums (LM), LM-51 Electrical and Photometric Measurements of HID Lamps4
and LM-79 Photometric Measurements for Solid State lighting5. Spectrometer software converts the captured SPD
data into metrics of interest such as total light output (lumens), color correlated temperature (CCT), color rendering
index (CRI) and chromaticity coordinates. A source’s total light output is determined by summing the photopically
corrected SPD over the visible light spectrum.
CCT correlates a lamp’s color to the color of a black body radiator at a given temperature and is measured in Kelvin
(K). The spectrum of color visible to the human eye is defined by the International Commission on Illumination
(CIE) color space. Figure 2 illustrates the blackbody locus, a line representing the spectrum of color that is radiated
from an ideal black body radiator.
FIGURE 2 – CIE COLOR SPACE WITH BLACK BODY LOCUS
4 LM51 Electrical and Photometric Measurements of HID. Illumination Engineering Society of North America. 2000. 5 LM79 Photometric Measurements for Solid State Lighting. Illumination Engineering Society of North America. 2008.
9
PG&E’s Emerging Technologies Program ET12PGE1262
CRI compares a light source’s rendering of a set of standard colors (Figure 3) with that of a blackbody radiator of
the same CCT. Average CRI (Ra) is represented as a single number from 0-100. Ra is based on an eight standard
color samples. Six additional color pallets have been added to augment the Ra metric.
FIGURE 3 – COLOR RENDERING INDEX (CRI RA) COLOR SAMPLES
Duv is defined as the closest distance of the tested sample from the Plankian locus in the color space. Positive
signed Duv is above the Plankian locus and negative signed Duv is below the Plankian locus.6 (Figure 4)
FIGURE 4 – CIE 1960 WITH BLACKBODY LOCUS AND VECTORS INDICATING POSITIVE AND NEGATIVE DUV. 7
6 American National Standard: Specifications for the Chromaticity of Solid State Lighting Products.
ANSI C78.377-2011. 7 Thompson, M. Defining quality of Light. Voices for SSL Efficiency 2011 – DOE SSL market introduction workshop.
10
PG&E’s Emerging Technologies Program ET12PGE1262
Chromaticity quadrangle specifications are provided in Figure 5, showing the quadrangles for the 7-step MacAdam
ellipses. MacAdam ellipses represent regions on the chromaticity chart where a portion of the population cannot
differentiate color. MacAdam steps refer to the size of the tolerance range as defined by the allowable deviation
from the target CCT. Table 3 provides the color space coordinates that define the MacAdam ellipse equivalent
quadrangles in Figure 5.
FIGURE 5 - CCT QUADRANGLES FOR THE ENERGY STAR LED SPECIFICATION8
TABLE 8 – CHROMATICITY COORDINATES DEFINING CCT QUADRANGLES FOR ENERGY STAR LED SPECIFICATION 9
8 ANSI C78.377-2011. Specifications for the Chromaticity of Solid State Lighting Products. 2011.
9 ANSI C78.377-2011. Specifications for the Chromaticity of Solid State Lighting Products. 2011.
11
PG&E’s Emerging Technologies Program ET12PGE1262
GONIOPHOTOMETER – TYPE C Angular light distribution is measured using a goniophotometer such as the one shown in Figure 6. For this
evaluation, a C-type goniophotometer was used. In a C-type goniophotometer, light sources are translationally fixed
in a central location and a mirror moves around the light source. The source is rotated around its vertical axis to
collect light intensity data for a spatial characterization of its light output. The light sensor used to collect data is a
photopically corrected cosine photosensor. The procedures for taking angular distribution measurements are detailed
in IES LM-51 Electrical and Photometric Measurements of HID Lamps and LM-79 Photometric Measurements for
Solid State Lighting. The output from the goniophotometer provides luminous intensity (candelas) as a function of
user-defined angular resolution in the vertical and horizontal planes.
FIGURE 6 - GONIOPHOTOMETER (TYPE C)
LIFE TESTING
Run-time data used for life testing is collected from the lamp or luminaire mounted in a test rack that allows for the
regulation of thermal conditions. Lamps are controlled through a central switch that turns all units on or off.
Photosensors are placed next to each lamp or fixture to determine how many hours each has been on and measure
relative light depreciation over time. A data acquisition and control system records temperature and voltage data,
and controls the on/off switch. Figures 7 and 8 show the laboratory run-time test chamber including the fixture
mounting apparatus and test instrumentation used in this program.
12
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURE 7 - XENON TESTING SET UP, SIDE VIEW
FIGURE 8 – XENON TESTING SET UP, TOP VIEW
The data acquisition system was centrally located with data cables connected to sensors at each product sample. The
system consists of a desktop computer running LabVIEW software connected to a data acquisition chassis that holds
modules for communication with voltage and temperature sensors. For each light source, one voltage and two
thermocouple lead wires were connected from the chassis to the thermocouples and light sensor/amplifier. The
thermocouples were attached to the ballast at the temperature measurement point and at the base of the light source.
The light sensor was placed in a tube aimed at the lamp to restrict stray light contributions. A detailed equipment
list for the run-time testing apparatus is provided below.
13
PG&E’s Emerging Technologies Program ET12PGE1262
Data acquisition
National instruments compact DAQ chassis (cDAQ-9178)
o (32) Channel voltage module (NI9205)
o (6) 16-channel thermocouple modules (NI9940)
Desktop computer running LabVIEW software by National Instruments and Windows 7 operating
system
Sensors
Light
o (32) Photometric cosine corrected photo sensors LI-COR (LI-210SA)
o (32) Trans conductance LI-COR amplifiers EME Systems UTA
Temperature
o (67) 40-gauge, K-type thermocouples Omega 5TC-TT-K
Main line voltage
o Eagle 120 power analyzer
Control
Power
o Digital out (NI 6008)
o Digitally controlled multi-pole single throw relay
Light level and component temperature data were recorded at a one minute resolution. Light level data allowed for
verification of the number of hours run, while component temperature data allowed for safety monitoring and acted
as a diagnostic tool for system failure analysis. Figure 9 and Figure 10 show the location of the light sensors for the
bare lamps and fixtures. Figure 11 shows the thermocouple attachment locations with two on the center of the lamp
ballasts and a third on the housing to illustrate chamber temperature.
Time series data collected over the course of the evaluation allowed for the validation of manufacturer’s claims and
assisted with reliability assessments. Light level and component temperature trends for both bare lamps and lamps
operating in fixtures is provided in the results. Data was reduced to remove time periods when the lights were
intentionally turned off, including two daily, hour-long, off periods and lab maintenance periods.
FIGURE 9 – LIGHT SENSOR LOCATION, BARE LAMP
14
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURE 10 – LIGHT SENSOR LOCATION, FIXTURE
FIGURE 11 –THERMOCOUPLE ATTACHMENT LOCATIONS
DATA ANALYSIS Manufacturer’s literature, industry standards and product test results collected over the course of the program are
compiled through 11,000 hours of run-time. Trend plots for product performance are provided to compare to
industry standards and manufacturer claims.
15
PG&E’s Emerging Technologies Program ET12PGE1262
RESULTS Over the course of the xenon evaluation, product performance data was gathered according to the technical approach
outlined in this report. The results from the market characterization, photometric testing and life testing are
provided in this section.
MARKET CHARACTERIZATION Manufacturer’s claimed performance data was collected for representative examples of existing outdoor
technologies to inform a recommended minimum performance specification for general illumination, outdoor
applications. For each lighting technology, products were compared based on equivalent initial delivered light
output and binned into output ranges.
Within each light output range, the average manufacturer claimed luminaire efficacy is provided in Table 9.
TABLE 9 – AVERAGE LUMINAIRE EFFICACY FOR OUTDOOR LIGHTING TECHNOLOGIES
Light Output (lm) Average Luminaire Efficacy (lm/W)
HPS Induction LED MH Ceramic xenon
0 – 5,000 - 46.4 63.7 81.1 67.7
5,001 – 10,000 57.6 47.6 74.0 74.4 69.7
10,001 – 15,000 65.5 93.1 74.4 76.0 66.7
15,001 – 20,000 64.6 - 75.6 - 66.7
20,001 – 25,000 - - 71.6 75.6 -
Within each light output range, the average manufacturer claimed luminaire CRI is provided in Table 10.
TABLE 10 – AVERAGE LUMINAIRE CRI FOR OUTDOOR LIGHTING TECHNOLOGIES
Light Output (lm) Average CRI
HPS Induction LED MH Ceramic xenon
0 – 5,000 - 83 70 70 85
5,001 – 10,000 21 85 73 70 78
10,001 – 15,000 21 80 73 70 85
15,001 – 20,000 21 - - 90 85
20,001 – 25,000 - - 70 90 -
16
PG&E’s Emerging Technologies Program ET12PGE1262
Within each light output range, the average manufacturer claimed luminaire CCT is provided in Table 11.
TABLE 11 – AVERAGE LUMINAIRE CCT FOR OUTDOOR LIGHTING TECHNOLOGIES
Light Output (lm) Average CCT (Kelvin)
HPS Induction LED MH Ceramic xenon
0 – 5,000 - 5,000 3,900 2,800 4,500
5,001 – 10,000 2,100 5,000 4,500 2,800 4,400
10,001 – 15,000 2,100 5,000 4,500 2,800 4,300
15,001 – 20,000 2,100 - - 3,000 4,300
20,001 – 25,000 - - 5,000 3,000 -
Within each light output range, the average manufacturer claimed lamp life is provided in Table 12.
TABLE 12 – AVERAGE LAMP LIFE FOR OUTDOOR LIGHTING TECHNOLOGIES
Light Output (lm) Average Lamp Life (hours)
HPS Induction LED MH Ceramic xenon
0 – 5,000 - 100,000 65,000 30,000 25,000
5,001 – 10,000 24,000 100,000 75,000 30,000 40,000
10,001 – 15,000 24,000 100,000 75,000 30,000 20,000
15,001 – 20,000 24,000 - - 24,000 20,000
20,001 – 25,000 - - 24,000 50,000 -
Products from two US manufacturers identified at the time of product selection are included and manufacturers are
referenced as Manufacturer 1 and Manufacturer 2. All commercially available xenon products were intended as a
luminaire retrofit solution with the most common retrofit targeted at a shoebox-style fixture operating with a high
intensity discharge (HID) lamp.
The most common xenon replacement lamp identified during the market characterization was categorized as 100
Watts and operated in a horizontal orientation. Xenon retrofit offerings for lamp sizes greater than 70 Watts are
composed of arrays of smaller, standard-sized xenon lamps. Manufacturer 1 offered lamps in multiples of 35 Watts,
while Manufacturer 2 offered lamps in multiples of 60 Watts. To produce approximately a 100 Watt lamp, xenon
systems consisted of arrays of three-35 Watt lamps totaling 105 Watts, or two-60 Watt lamps totaling 120 Watts.
To account for multi-lamp arrays, and various beam distribution patterns, the array geometry was chosen by
application with options for fixture reflector modifications. Xenon product distributors were given the opportunity to
assist with the retrofit design to make the test units resemble a typical luminaire geometry found in the field. In
addition to testing 100 Watt lamp arrays installed in shoebox-style fixtures, individual bare lamps were tested to
provide performance data comparing arrays and the individual source with respect to photometric performance and
longevity.
The 100 Watt, horizontal product category was selected as the representative case for product testing. Sample size
was limited by product availability and cost. Fourteen fixtures were donated to the project allowing for a test
sample size of seven for each brand. Nine bare lamps from each distributor were included in the testing. This sample
size was selected to maximize the data acquisition channels available on the data acquisition system. The products
selected for evaluation are provided below. Detailed product performance claims are provided in Table 13.
17
PG&E’s Emerging Technologies Program ET12PGE1262
Test Set-up: Sterner Executive Square 19” shoebox fixture (type 3H reflector)
o (7) Manufacturer 1: 105 Watt xenon lamp array system
o (7) Manufacturer 2: 120 Watt xenon lamp array system
Test Set-up: Bare Lamp
o (9) Manufacturer 1: 35 Watt xenon lamp and ballast system
o (9) Manufacturer 2: 60 Watt xenon lamp and ballast system
TABLE 13 - MANUFACTURER PERFORMANCE CLAIMS
Performance Metric Manufacturer 1 Manufacturer 2
Power (W) 105 60
Luminous Flux - Initial (lm) 10,710 6,660
Luminous Flux - Mean (lm) - 6,030
Efficacy (lm/W) 102 Up to 108
CRI 90 >80
Working Temperature (°C) -40 to 85 -50 to 85
CCT 4,100 - 5,000 4,300
Lamp Life (hrs.) 16,000 - 18,000 30,000
After the initial burn-in period, testing included 16 test samples from Manufacturer 2. Reliability issues encountered
during the lamp burn-in with Manufacturer 1 lamps disqualified the product from the long-term testing program;
however disqualified lamps that survived the initial 100-hour burn in period were run in the test chamber. Light
level and temperature measurements for these products are not included in project reports. Data is available upon
request for limited performance metrics.
PHOTOMETRY RESULTS Light output, or luminous flux, is calculated by integrating a lamp’s SPD weighted for photopic vision. Figure 12
shows measured luminous flux, in lumens, for bare lamps and the manufacturer’s claimed initial and mean output.
Figure 13 shows luminous flux, in lumens, for the units tested in fixtures compared to manufacturer specifications.
Products that did not produce light at 1,000-hour interval testing are marked with an ‘x’ to indicate end of life. Light
level data provided in ‘Run-Time’ results provide specific time of failure. For bare lamps, six of the nine test
samples failed before the 11,000 hour test. For fixtures, four of the seven test samples failed before the 11,000 hour
test.
18
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURE 12 – LUMINOUS FLUX FOR MANUFACTURER 2 - BARE LAMPS (MANUFACTURER SPECIFICATIONS IN DASHED LINES)
FIGURE 13 – LUMINOUS FLUX FOR MANUFACTURER 2 – IN FIXTURES (MANUFACTURER SPECIFICATIONS IN DASHED LINES)
19
PG&E’s Emerging Technologies Program ET12PGE1262
COLORIMETRIC RESULTS The SPD data collected by the LabSphere spectrometer and processed with TOCS software is used to derive CCT,
Duv, and CRI. Results are shown in Figure 14. Duv shown in Figure 15, and CRI shown in Figure 16.
FIGURE 14 - CCT FOR MANUFACTURER 2 (MANUFACTURER SPECIFICATIONS IN DASHED LINES)
20
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURE 15– DUV FOR MANUFACTURER 2
FIGURE 16 – CRI FOR MANUFACTURER 2 (MANUFACTURER SPECIFICATIONS IN DASHED LINES)
21
PG&E’s Emerging Technologies Program ET12PGE1262
DISTRIBUTION RESULTS Initial light output distribution data is provided in Figure 17 for the bare lamp configuration and Figure 18 for the
fixture configuration. The blue line depicts the vertical plane through the horizontal angle corresponding to the
maximum candela value. The red line depicts the horizontal plane through the vertical angle corresponding to the
maximum candela value.
FIGURE 17 - BARE LAMP DISTRIBUTION PLOT FOR INITIAL LIGHT OUTPUT
FIGURE 18 - FIXTURE DISTRIBUTION PLOT FOR INITIAL LIGHT OUTPUT
RUN-TIME RESULTS Light level and component temperature data was recorded each minute during life testing for all the tested devices.
Light level data allowed for verification of the number of hours run, while component temperature data allowed for
safety monitoring and thermal analysis of the devices. Figure 19 and Figure 20 show the light level trends for the
bare lamps and fixtures, respectively, while Figure 21 and Figure 22 show the component temperature trends for the
bare lamps and fixtures, respectively. Data was reduced to remove time periods when the lights were intentionally
turned off, including the two, hour-long, off periods per day and lab maintenance periods.
22
PG&E’s Emerging Technologies Program ET12PGE1262
The reduction in component temperature as shown in Figure 21 and 22 correlates to lamp failures identified in light
level data. Specific drops in ballasts temperatures are noticeable at time of failure providing detail as to which lamp
of the two-lamp system failed.
23
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURE 19 – LIGHT LEVEL DURING LIFE TESTING FOR MANUFACTURER 2 - BARE LAMPS
24
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURE 20 – LIGHT LEVEL DURING LIFE TESTING FOR MANUFACTURER 2 - FIXTURES
25
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURE 21 - BALLAST TEMPERATURES FOR MANUFACTURER 2 – BARE LAMPS
26
PG&E’s Emerging Technologies Program ET12PGE1262
FIGURE 22 – BALLAST AND CHAMBER TEMPERATURES FOR MANUFACTURER 2 - FIXTURE
27
PG&E’s Emerging Technologies Program ET12PGE1262
EVALUATIONS
Xenon product test results were evaluated in comparison to manufacturer claims and industry standards available at
the time of the evaluation. Reliability issues encountered during the lamp burn-in with Manufacturer 1 lamps
disqualified it from the long-term testing program. After the initial burn-in period, testing includes 16 test samples
from Manufacturer 2. A summary of Manufacturer 2 performance claims, initial tested performance and 11,000-
hour tested performance are provided in Table 14.
TABLE 14 - MANUFACTURER LITERATURE PERFORMANCE CLAIMS AND TESTED PERFORMANCE - MANUFACTURER 2
Performance Metric
Manufacturer
Specification
Sheet
Tested Initial
Performance (Average)
Tested 11,000 Hour
Performance (Average)
Bare Lamp Bare Lamp Fixture Bare Lamp Fixture
System Power (W) 67.4 67.7 135.0 69.1 73.5
Luminous Flux – Initial (lm) 6,660 5,176.6 6,275 4,177 2,849
Luminous Flux – Mean (lm) 6,030 - - - -
Efficacy (lm/W) Up to 108 76.5 46.5 60.4 38.8
CRI >80 64.3 65.6 42.4 42.2
CCT 4,300 3,430 3,470 2,853 2,622
Lamp Life (hrs.) 30,000 - - - -
One industry tool used to benchmark lighting product performance is the DesignLights Consortium (DLC). The
DLC “promotes quality, performance and energy efficient commercial sector lighting solutions through
collaboration among its federal, regional, state, utility, and energy efficiency program members, luminaire
manufacturers, lighting designers, and other industry stakeholders throughout the US and Canada.”
The current DLC standard for retrofit kits intended for outdoor pole mounted area luminaire applications are
included as reference in Table 15.
TABLE 15 - PERFORMANCE SPECIFICATIONS FOR THE DESIGNLIGHTS CONSORTIUM BENCHMARK
DesignLights Consortium Technical Requirements - Retrofit Kits for Outdoor Pole Mounted Area Luminaires 10
Minimum Light Output 1,000 lumens
Zonal Lumen Density 100% light output: 0-90°, <10% light output: 80-90°
Minimum Luminaire Efficacy 70 lumens per Watt
Allowable CCT Less than or equal to 5,700 Kelvin (defined by ANSI C78.377-2011)
Minimum Color Rendering Index 65
L70 Lumen Maintenance 50,000 hours
Warranty 5 years
10 DesignLights Consortium. Technical Requirements Table v2.1. 2015.
28
PG&E’s Emerging Technologies Program ET12PGE1262
With respect to luminous output, the xenon product’s baseline and 11,000 hour run-time test results were lower than
manufacturer’s claims. However, the DLC technical specification for outdoor, pole mounted, retrofit kits requires a
minimum light output of 1,000 lumens and tested xenon products met this criteria.
With respect to light distribution, the DLC specification requires 100% of light output to be below 90 degrees with
less than 10% in the 80-90 degree zone. The initial light output distribution plots for representative product samples
showed that the bare lamp retrofit kit produced a non-cutoff distribution. When installed in a shoebox fixture, the
luminaire produced a cutoff distribution with 0.5% of its light output in the 80-90 degree zone. The xenon bare
lamp retrofit kit met the DLC requirements for zonal lumen density when installed in a typical shoebox fixture.
With respect to system efficacy, manufacturer literature claimed an initial system efficacy of 98.8 lumens per watt
(LPW). The average efficacy of the tested bare lamps resulted in an initial value of 76.5 LPW and 60.4 LPW at
11,000 hours of run-time. The average efficacy of products installed in fixtures resulted in an initial value of 46.5
LPW and 38.8 LPW at 11,000 hours of run-time. The DLC technical specification for outdoor, pole mounted
retrofit kits requires an efficacy of 70 LPW. The tested xenon products did not meet this criteria.
For outdoor retrofit kits, manufacturer literature claimed CCT performance of 4,300 K. Tested products did not meet
the manufacturer claims. See Table 5. DLC specifications allow a CCT less than or equal to 5,700 K. Over the
course of the evaluation, the tested products met this criteria with products trending towards warmer CCT over the
11,000 hours of run-time
With respect to CRI, manufacturer literature claimed a CRI of 80 or greater for tested products. Test results show an
average, initial CRI of 65 and a CRI of 42 at 11,000 hours of run-time. The tested xenon products did not meet
manufacturer claims for CRI. DLC specifications require a minimum of 65 CRI. The tested xenon products did not
meet DLC requirements.
Eleven of 18 bare lamps tested failed prior to the 11,000 hours of run-time. Leveraging industry standards for
similar lighting technologies where “average rated lamp life is defined as that time after which 50% of a large group
of lamps are still in operation”11
, the tested xenon products did not meet manufacturer claims of a 30,000 hour
lifetime.
For xenon lamps installed and tested in fixtures, three of seven fixtures were operational at 11,000 hours. The test
product’s configuration included redundant arc tubes. Of the total arc tubes, 3 of 14 arc tubes were operational.
Leveraging industry standards for similar lighting technologies where “average rated lamp life is defined as that
time after which 50% of a large group of lamps are still in operation”, the tested xenon product did not meet
manufacturer claims of a 30,000 hour lifetime when installed in typical shoebox fixtures.
At the time of this evaluation, the tested xenon products did not meet manufacturer claims for light output, luminaire
efficacy, CCT, CRI or lifetime.
11 Illuminating Engineering Society. The Lighting Handbook. Tenth Edition. Page 7.45. 2011.
29
PG&E’s Emerging Technologies Program ET12PGE1262
RECOMMENDATIONS The performance testing conducted as part of this xenon evaluation provides context regarding expected product
operation. Stakeholders considering development of incentive programs for xenon products used in the commercial
outdoor lighting sector should consider this data. The representative xenon products tested did not meet
manufacturer performance claims for light output, luminaire efficacy, CCT, CRI or lifetime. For best-practice
lighting design, each product should be evaluated individually to verify its reliability and performance before
specifying its use. In addition, it is recommended that industry accepted standards be leveraged as the performance
specification for xenon moving forward. One such standard, provided by the DLC, is available for LED outdoor,
pole mounted, retrofit kits.
30
PG&E’s Emerging Technologies Program ET12PGE1262
APPENDIX 1 – EQUIPMENT SPECIFICATION SHEETS