XDD DFFFF2 5HY˛˝ ; $ 1ipcmty.com/wp-content/uploads/2015/07/94311-3A.pdf · 2015. 7. 30. · XDD...
Transcript of XDD DFFFF2 5HY˛˝ ; $ 1ipcmty.com/wp-content/uploads/2015/07/94311-3A.pdf · 2015. 7. 30. · XDD...
5911 Butterfield Road Hillside, IL 60162 • tel: (708) 236-6000 • fax: (708) [email protected] • www.ljtechnologies.com • ISO 9001 Registered Rev: 9431X-3A
1
94311/94312/94313/94314Detonation Flame Arresters
Features • Withstands instantaneouspressure
attheFlamefrontinexcessof500psig
• Tubebankdesignensuresconsistentfunctioning
• Carbon steel or 316 S.S. housingconstruction,316S.S.tubebank
• Optionalfittingsforpressuretapsortemperatureprobes
• Designed&testedinaccordancewithappendixA, 33U.S.CodeofFederalRegulationspart154
• Standarddrainplug
• Pressure and temperature tapsoptional
TheShand&JursDetonationFlameArrestersprovideprotectionagainstflamepropagationthroughpipingruns and vapor recovery systems,while allowingmaximumflowefficiencies. Thisdesignquenchesaflamefrontapproachingfromeitherdirection,evenifithastransitionedtoadetonation.TheArresterscontainadetonationwhileretainingtheintegrityofboththearrestingelementandthehousing.Thisisensuredbythedesignofthepassagesinthetubebankandthedetonationresistantconstruction.
Standardconstructionof thehousing isavailable inCarbon Steelor 316 Stainless Steel. The tubebankis Stainless Steel throughout. Special constructionmaterialstowithstandthecorrosiveactionsofsomevapors andatmospheric conditionsareavailableuponrequest.
Becauseof the severe serviceconditions that theDetonationFlameArresterencounters,allconstructionweldingisperformedinaccordancewithASMEBoilerandPressureVesselCodeSectionVllland IX.Class150lb.hydrostaticallytestedat425psig.Class300lb.hydrostaticallytestedat750psig.
Thesemodelsareavailableinarangeofsizesfrom2”through24”.Additionalsizesavailableuponrequest.StandardconnectionsareANSI150lb.or300lb.Classraisedfaceflanges.
9431X Detonation Flame Arresters
Model Number Service / Approval* Size
94311 NECGroupD/FactoryMutual 2”-12”
94312 NECGroupDMarine/FactoryMutual,U.S.CoastGuard 2”-12”
94313 NECGroupC&D/FactoryMutual 2”-6”
94314 NECGroupC&DMarine/FactoryMutual 2”-6”
*STEEL,316,DUPLEXStainlessSteel
5911 Butterfield Road Hillside, IL 60162 • tel: (708) 236-6000 • fax: (708) [email protected] • www.ljtechnologies.com • ISO 9001 Registered Rev: 9431X-3A
Detonation Flame Arresters
2
94311/94312/94313/94314
Class 300 lb.
Class 150 lb.
Dimensions
Size 2” 3” 4” 6” 8” 10” 12” 18”“A” 305/16 351/16 379/16 451/16 605/16 749/16 761/16 6913/16“B” 61/2 81/4 10 121/2 15 171/2 201/2 28“C” 10 121/2 15 201/2 251/2 301/2 36 471/2
Size 2” 3” 4” 6” 8” 10” 12” 14” 16” 18”“A” 291/16 339/16 361/16 431/16 581/16 7115/16 739/16 595/16 595/16 6113/16“B” 6 71/2 9 11 131/2 16 19 21 231/2 25“C” 9 11 131/2 19 231/2 271/2 32 383/4 383/4 433/4
Alldesignssubjecttochange.Certifieddimensionsandspecificationsavailableuponrequest.
Specifications
Materials of Construction
Sizes:2”,3”,4”,6”,8”,10”,12”,14”,16”,18”,20”,22”,24”DINSizesAvailable
CarbonSteel,316StainlessSteel,Carpenter20,Hastelloy-C,orDuplexStainlessSteel.(OtherMaterialAvailable)
150/300 lb.
Flange Rating:ANSI150lb.or300lb.