www.hsl.gov.ukAn Agency of the Health and Safety Executive
www.hsl.gov.ukAn Agency of the Health and Safety Executive
UKELG 50th ANNIVERSARY MEETINGRECENT DELOPMENTS IN AREA
CLASSIFICATION FOR GASES
ROGER SANTON, HEALTH & SAFETY LABORATORY, BUXTON
An Agency of the Health and Safety Executive
CONTENTS
• Current standards
• Previous work on gases
• QUADVENT
• Natural ventilation estimation
• Constraints
• Examples
• Demonstration
• Future developments
• References
An Agency of the Health and Safety Executive
CURRENT STANDARDS
• BS EN 60079-10-1:2009, Electrical apparatus for explosive gas atmospheres – Part 10: Classification of hazardous areas.
• Area classification code for installations handling flammable fluids, Model Code of safe practice, IP 15 3rd edition, The Energy Institute, 2005.
• IGEM/SR/25, Edition 2, Hazardous area classification of natural gas installations, Institution of Gas Engineers and Managers, 2010.
An Agency of the Health and Safety Executive
CURRENT STANDARDS
• BS EN 60079-10-1:2009, Electrical apparatus for explosive gas atmospheres – Part 10: Classification of hazardous areas. – Zone definitions– Source terms
– Vz
An Agency of the Health and Safety Executive
CURRENT STANDARDS
• Vz
– Hypothetical gas cloud volume– Mean concentration of 50% LEL (for secondary
releases)– Determines level of ventilation
– If Vz is less than 0.1m3, ventilation is regarded as high and zone is classified Negligible Extent (NE) and no precautions against ignition are required.
– Equations for the calculation of Vz are included in BS EN 60079-10-1:2009
An Agency of the Health and Safety Executive
GASES
An Agency of the Health and Safety Executive
Gases
• Vz estimated from BS EN 60079-10-1 found to be 100 to 3000 times larger than values obtained from CFD
• Reported at Hazards XIX (Gant et al)
An Agency of the Health and Safety Executive
GASES
Vz from BS EN is 2 – 3 orders of magnitude larger
In every case Vz from CFD is less than 0.1m3
An Agency of the Health and Safety Executive
GASES
• BS EN 60079-10-1 calculation is based on premise that ratios:
Actual ventilation rate / Ventilation rate required to dilute gas escape to specified
level
And
Enclosure volume / Vz
Are equal.
This has no scientific basis.
An Agency of the Health and Safety Executive
GASES
• 2006
• Steel works sorted
• Natural gas industry subject to DSEAR– Unable to comply with their own code IGEM/SR/25– No lower pressure limit for zone 2
• Unable to justify application of NE zoning
• Unable to reach agreement with HSE on threshold for zoning low pressure installations
• BS EN 60079-10-1 methodology in doubt
An Agency of the Health and Safety Executive
GASES
• Natural Gas - Joint Industry Project 2006-2007– HSL report RR630 and Hazards XXI paper
• IGEM/SR/25 revised to include Zone 2 NE, published 2010
An Agency of the Health and Safety Executive
OTHER GASES
An Agency of the Health and Safety Executive
OTHER GASES
• “QUADVENT”
• Based on an integral gas jet model
• Well established scientific credibility
• Full mathematical derivation published 2011, (Webber et al)
An Agency of the Health and Safety Executive
QUADVENT
• Unchoked flow will result if:
aP
P1.9
where P is the gas storage pressure and Pa is atmospheric pressure.
An Agency of the Health and Safety Executive
QUADVENT
• When the flow is choked (sonic) it is necessary to define a pseudo source hole radius rs, where ro is the orifice radius
9.15.010
as P
Prr
An Agency of the Health and Safety Executive
QUADVENT
Vz =
• ρb (kg/m3) is the density of the background (which normally approximates to that of air)
• ρs (kg/m3) is the density of the source gas
• α is the entrainment coefficient (recommended value 0.05)
• xb (v/v) is the background concentration
• xcrit (v/v) is the concentration of interest (50% LEL for secondary releases)
32/33 1
16
9
bcrit
b
s
bs
xx
xr
An Agency of the Health and Safety Executive
QUADVENT
The background concentration of flammable gas xb in the enclosure is
q1 (m3/s) is the ventilation rate
qs (m3/s) is the source gas volume flowrate
ε is the efficiency of background mixing (see below).
The leak rate qs can be derived from standard methods for the estimation of leak flowrates. Appropriate methods are included in BS EN 60079-10-1:2009, Annex A.
1q
qx sb
An Agency of the Health and Safety Executive
QUADVENT
Outdoors there is zero background concentration, xb=0, and the background density is that of pure air
32/33 1
16
9
crits
asZ x
rV
An Agency of the Health and Safety Executive
QUADVENT
• The axial distance z to a concentration xzone may be derived as an approximation to the zone extent. An appropriate value of xzone should be chosen. BS EN 60079-10-1 uses 100% LEL for example.
bzone
zones
xx
xrz
1
b
s
2
An Agency of the Health and Safety Executive
VALIDATION
• Quadvent has been validated against detailed CFD simulations which themselves have been validated against experimental data.
• The validation data includes simulations of a range of flammable gas release rates in enclosures of various sizes at a range of different ventilation rates.
• All of the simulations are for unobstructed releases of methane in a ventilation controlled chamber.
• The agreement between the QUADVENT model and the CFD simulations is surprisingly good considering how simple the QUADVENT calculation is.
An Agency of the Health and Safety Executive
VALIDATION
Figure 1 Predictions from CFD (filled symbols) and the integral model QUADVENT (hollow symbols) for Vz plotted against the concentration at the
ventilation outlet.
An Agency of the Health and Safety Executive
ENCLOSURE VENTILATION
• The ventilation rate of an enclosure is a key input to an area classification assessment.
• Forced ventilation rates can be established from design or equipment specifications.
• The natural ventilation rate will vary through time as it is strongly influenced by the weather conditions. Simple approaches for the estimation of ventilation rates, suitable for use as part of HAC methodologies, are therefore required.
An Agency of the Health and Safety Executive
ENCLOSURE VENTILATION
• BS5925:1991 contains methods for very simple enclosures
• A spreadsheet containing a simple model of wind and buoyancy driven ventilation is available from the Chartered Institution of Building Services Engineers (CIBSE)
• COMIS or CONTAM multizone models
• Experimental measurements, or CFD simulations
• Quadvent contains an estimation method
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Hole size
• Local congestion and confinement– Ventilation efficiency factor ε
• Safety factor
• Sub-chambers
• Pressure
• Vz value for small enclosures
• Availability of ventilation
• Background concentration
• Validation limited to methane
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Hole size– Vz is a function of the cube of the hole
radius
– Vz must not be under-estimated
– Minimum of 0.25mm2 is recommended (except under specified circumstances)
– Further guidance in Cox Lees and Ang
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Congestion and confinement– Guidance in IGEM/SR/25 Appendix 6– Efficiency of mixing ε
• ε = 1 represents an unobstructed release • ε = ½ represents a moderate degree of
obstruction • ε = ⅓ represents a significant obstruction to the
ventilation flow
– Over 100 m3 verify local ventilation effectiveness with smoke tests etc.
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Safety factor– To allow for uncertainty– Apply a factor of 2 to estimated ventilation rate
or– Ensure hole size is conservative
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Sub chambers– Compute Vz for the volume of the sub-chamber with
reduced ventilation rate
or
– Set Vz to sub-chamber volume
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Pressure– Limit NE zones to systems at less than 10 barg– Limit to 20 barg based on risk assessment taking
the consequences of ignition, i.e. the risk of injury, into account
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Vz size criterion
– For enclosure volumes of less than 10m3 the criterion of 0.1 m3 for Vz should be reduced to 1% of the enclosure volume. This constraint is taken from BS EN 60079-10-1:2009
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Ventilation availability– The guidance in BS EN 60079-10-1:2009
should be observed • NE zones not allowed if availability is poor
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Background concentration– Suggested limit 25% LEL– Under consideration for inclusion in
software– Manual check
An Agency of the Health and Safety Executive
QUADVENT CONSTRAINTS
• Validation– Whilst this methodology is valid for all
gases, it should be noted that the validation of the criterion of 0.1 m3 for the value of Vz leading to an NE classification has only been carried out for natural gas.
An Agency of the Health and Safety Executive
QUADVENT EXAMPLES
• Outdoor butane gas pipework, secondary releases
• P = 4.5 bara
• Hole size = 0.25mm2
Vz, m3 Zone
BS EN 60079-10-1:2009
0.63 Zone 2
QUADVENT 0.0021 Zone 2 NE
An Agency of the Health and Safety Executive
QUADVENT EXAMPLES
• Natural gas plant room• P = 76 mbarg• Hole size = 2.5mm2
Vz m3 Zone
BS EN 60079-10-1:2009
183 Zone 2
IGEM/SR/25 N/A Zone 2 NE
QUADVENT 0.025 Zone 2 NE
EI 15 N/A Zone 1
An Agency of the Health and Safety Executive
DEMONSTRATION
An Agency of the Health and Safety Executive
CONCLUSIONS
• BS EN 60079-10-1:2009– Arbitrary results– No scientific foundation
– Vz up to 3 orders of magnitude too high
• QUADVENT– Scientific basis– Often reduces zoning requirements– Capital and maintenance costs of protected
equipment can be restricted to genuine risks
An Agency of the Health and Safety Executive
FUTURE DEVELOPMENTS UNDER CONSIDERATION
• Software – now available for gases (See leaflet)
• Flashing liquids (LPG, Ammonia) (Project in progress)
• Plumes
• Impingement
• Liquid pools
• Gas mixtures
• Mist (JIP in progress)
An Agency of the Health and Safety Executive
REFERENCES
• BS EN 60079-10-1:2009, Electrical apparatus for explosive gas atmospheres – Part 10: Classification of hazardous areas.
• Area classification code for installations handling flammable fluids, Model Code of safe practice, IP 15 3rd edition, The Energy Institute, 2005.
• Cox, A.W., Lees, F. P. and Ang, M. L., Classification of Hazardous Locations, I Chem E, 1990.
• Area classification for secondary releases from low pressure natural gas systems, HSL Research Report RR630.
An Agency of the Health and Safety Executive
REFERENCES 2
• Ventilation theory and dispersion modelling applied to hazardous area classification, D.M. Webber, M.J. Ivings and R.C. Santon, Journal of Loss Prevention in the Process Industries 24 (5) September 2011, 612-621 http://dx.doi.org/10.1016/j/jlp.2011.04.002
• Gant, S.E., Ivings, M.J., Jones, A., and Santon, R., Hazardous Area Classification of Low Pressure Natural Gas Systems using CFD Predictions. Hazards XIX, Manchester, 2006
• New Methods for Hazardous Area Classification for Explosive Gas Atmospheres, R.C. Santon, M.J.Ivings, D.M. Webber and A Kelsey, Hazards XXIII, Southport 2012
An Agency of the Health and Safety Executive