Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
-
Upload
adil-rasheed-khan -
Category
Documents
-
view
8 -
download
0
description
Transcript of Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
1/11
Footings Example 1Design of a square spread footing of a seven-story building
Design and detail a typical square spread footing of a six bay by five bay seven-story building,
founded on stiff soil, supporting a 24 in. square column. The building has a 10 ft high basement.
The bottom of the footing is 13 ft below finished grade. The building is assigned to Seismic
Design Category (SDC) B.
Given:
Column load
Service dead loadD = 541 kipService live loadL = 194 kip
Seismic load E= 18 kip
(Column force due to the building frame
resisting the seismic load)
Material propertiesConcrete compressive strengthf
c= 4 ksi
Steel yield strengthfy= 60 ksi
Normalweight concrete = 1Density of concrete = 150 lb/ft3
Allowable soil-bearing pressures
Donly: qall.D= 4000 p
sf
D +L: qall,D+L= 5600 psfD +L + E: qall.Lat= 6000 psf
Fig. 1.1Rectangular foundation plan.
ACI 318-14 Procedure Computation
Step 1: Foundation type
13.1.1 This bottom footing is 3 ft belowbasement slab. Therefore, it is
considered a shallow foundation.
Step 2: Material requirements
13.2.1.1 The mixture proportion mustsatisfy the durability requirements
of Chapter 19 (318) and structural
strength requirements. The
designer determines the durabilityclasses. Please see Chapter 2 of
SP-17 for an in-depth discussion
of the categories and classes.
ACI 301 is a referencespecification that is in sync with
ACI 318. ACI encourages
By specifying that the concrete mixture shallbe in accordance with ACI 301 and providing
the exposure classes, Chapter 19 requirements
are satisfied.
Based on durability and strengthrequirements, and experience with localmixtures, the compressive strength of concrete
is specified at 28 days to be at least 4000 psi.
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
2/11
referencing 301 into job
specifications.
There are several mixture optionswithin ACI 301, such as
admixtures and pozzolans, which
the designer can require, permit,or review if suggested by the
contractor.
Example 1 provides a more
detailed breakdown ondetermining the concrete
compressive strength and
exposure categories and classes.
Step 3: Determine footing dimensions
13.3.1.1 To calculate the footing base area,
divide the service load by theallowable soil pressure.
Area of footing =
total service load ( )
allowable soil pressure, qa
P
Assuming a square footing.
The footing thickness is
calculated in Step 5, footing
design.
The unit weights of concrete and soil are 150
pcf and 120 pcf; close. Therefore, footingself-weight will be ignored:
2
.,
135 ft4
541 k
ksfall D
D
q (controls)
,
2541 k+ 194 k 131 ft5.6 ksf
all D L
D L
q
2
.,
D + L +E 541 k + 194 k + 18 k126 ft
6 ksfall Latq
2 135 ft 11.6 ftl
Therefore, provide 12 x 12 ft square footing.
Step 4: Soil pressure
Footing stability
Because there is no overturningmoment, overall footing stability
is assumed.
Calculate factored soil pressure
uPq
Areau
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
3/11
5.3.1(a)
5.3.1(b)
5.3.1(d)
5.3.1(e)
Calculate the soil pressuresresulting from the applied
factored loads.
Load Case I: U= 1.4D
Load Case II: U= 1.2D+ 1.6L
Load Case IV: U= 1.2D+ E +L
Load Case IV: U= 0.9D+ E
The load combinations includesthe seismic uplift force. In this
example, uplift does not occur.
U = 1.4D = 1.4(541 kip) = 757 kip
2
757 kipq = 5.3 ksf
144 ftu
U = 1.2D + 1.6L = 1.2(541 kip) + 1.6(194 kip)
= 960kip
2
960 kipq = 6.7 ksf
144 ftu (controls)
U = 1.2D + 1.0E+ 1.0L
= 1.2(541 kip) + 18 kip + 1.0(194 kip) = 861 kip
2
861 kipq = 6.0 ksf
144 ftu
U = 0.9D + 1.0E= 0.9(541 kip)+ 18 kip = 505 kip
2
505 kipq = 3.5 ksf
144 ftu
13.3.2.1 Because the footing has equal dimension in plan, it will be designed in onedirection and symmetry is assumed.
Step 5: One-way shear design
Fig. 1.2One-way shear in longitudinal
direction.
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
4/11
21.2.1(b)
7.5.1.1
7.5.3.122.5.1.1
22.5.5.1
7.4.3.2
20.6.1.3.1
Shear reduction factor:
Vn Vu
n c sV V V
Therefore:
'2c c wV f b d
And satisfying: u cV V
The critical section for one-wayshear is at a distance dfrom the
face of the column (Fig. 1.2).
The engineer could either assume
a value for dthat satisfies thestrength Eq. (22.5.5.1) by iteration
or solve Eq. (7.5.1.1).
In this example, the first approach
is followed:
Assume that the footing is 30 in.thick.
The cover requirement is 3 in. to
bottom of reinforcement. Assume
that No. 8 bars are used in theboth directions and design for themore critical case (upper layer).
Therefore, the effective depth d:
d= 30 in.3 in.1 in.1 in./2
= 25.5 in.
( )2 2
n u ul c
V V d bq
shear= 0.75
Assume Vs= 0 (no shear reinforcement)
Vn= V
c
(12 ft) 24 in. 25.5 in.( )
in. in.22(12 ) 12
ft ft
(12 ft)(6.7 ksf) = 231 kip
uV
0.75(2) 4000 psi (12 ft)(25.5 in.)
(12 in./ft) = 348 kip
cV
Vc= 348 kip > Vu= 231 kip OK
Therefore, assumed depth is adequate:
h= 30 in.
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
5/11
Step 6: Two-way shear design
22.6.1.2
22.6.1.422.6.4.1
22.6.2.1
22.6.5.1
22.6.5.2
The foundation will not be
reinforced with shear
reinforcement for two-way action.Therefore, the nominal shear
strength for two-way foundation
without shear reinforcement isequal to the concrete shear
strength:
vn= vc
Under punching shear theory,
inclined cracks are assumed to
originate and propagate at 45degrees away and down from the
column corners. The punch area is
calculated at an average distanceof d/2 from column face on all
sides (Fig. 1.3).
bo= 4(c+ d)
ACI 318 permits the engineer to
take the average of the effective
depth in the two orthogonal
directions when designing thefooting, but in this example the
smaller effective depth will beused.
The two-way shear strength
equations for nonprestressed
members must be satisfied and theleast calculated value of (a), (b),
and (c) controls:
'
'
4 (a)
4(2 ) (b)
c c
c c
v f
v f
where is ratio of the long side to
short side of column; = 1
'( 2) (c)sc co
dv f
b
Fig. 1.3Two-way shear.
bo= 4(24 + 25.5) = 198 in.
4(1.0)( 4000 psi) = 253 psicv
4
(2 )(1.0)( 4000 psi) = 379.5 psi1cv
(40)(25.5 in.)( 2)( 4000 psi) = 452 psi
198 in.cv
Equation (a) controls; vc= 253 psi
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
6/11
22.6.5.3
21.2.1(b)
8.5.1.1
s= 40, considered interior
column
'4 b dc c o
V f
Use a reduction factor of 0.75:
'(0.75)4 b dc c oV f
2 2[(a) ( ) ]u uV q c d
Check if design strength exceeds
required strength:VcVu?
(253 psi)(198 in.)(25.5 in.)= 1277 kip
1000 lb/kipcV
= 0.75
Vc= 0.75(1277 kip) = 958 kip
224 in.+25.5 in.[(12 ft)(12 ft) ( ) ](6.7 ksf)
12 in./ft
851 kip
uV
Vc= 958 kip> Vu= 851 kip OK
Two-way shear strength is adequate.
Step 7: Flexure design
13.2.71 The critical section is permitted to
be at the face of the column (Fig.
1.4).
2( ) ( ) / 22
u ul c
M q b
Fig. 1.4Flexure in the longitudinal
direction.
2
24 in.12 ft
12 in./ft(6.7 ksf)( ) (12 ft) / 22
uM
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
7/11
22.2.1.1
22.3.1.1
22.2.2.1
22.2.2.2
21.2.1(a)
8.5.1.1(a)
8.6.1.1
13.3.3.3(a)
21.2.1(a)
21.2.2
22.2.2.4.122.2.2.4.3
Set compression force equal to
tension force at the column face:
C= T
C = 0.85fcbaand T = Asfy
'0.85
s y
c
A fa
f b and
( )2
n s ya
M A f d
Substitute for ain the equation
above.
Use reduction factor from Table
21.2.1.
Setting Mn
Mu= 1005 ft-k andsolving for As:
Check the minimum
reinforcement ratio: l= 0.0018
Check if the tension controlled
assumption and the use of = 0.9 is correct.
To answer the question, the
calculated tensile strain inreinforcement is compared to the
values in Table 21.2.2. The strain
in reinforcement is calculatedfrom similar triangles (refer to
Fig. 1.5):
c= ( )
c
t d c
where:1
a=
c
and a= 0.28As
Mu= 1005 ft-kip
ss
A (60 ksi)0.1A
0.85(5 ksi)(12 ft)a
= 0.9
s(0.1)A
(0.9) (60 ksi)(25.5 in. )2n sM A
As= 8.91 in.2
As,min= 0.0018(12 ft)(12 in./ft)(30 in.)
= 7.8 in.2 0.005
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
8/11
Section is tension controlled and = 0.9
Fig. 1.5Strain distribution across footing.
Step 8: Transfer of column forces to the base
16.3.1.1
22.8.3.2
22.8.3.2(a)
22.8.3.2(b)
Factored forces are transferred tothe foundation at the base of the
column by bearing on concrete
and the reinforcement dowels.
The foundation is wider on allsides than the loaded area.
Therefore, the nominal bearing
strength,Bn, is the smaller of the
two equations.
'21
1
(0.85 )n cA
B f AA
and
'12(0.85 )n cB f A
Check if 2
1
2.0A
A where
A1is the bearing area of thecolumn andA2is the area of thepart of the supporting footing that
is geometrically similar to and
concentric with the loaded area.
22
21
[(12 ft)(12 in./ft)]6 2
(24 in.)
A
A
Therefore, Eq. (22.8.3.2(b)) controls.
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
9/11
21.2.1(d)
16.3.4.1
16.3.5.4
25.4.9.2
25.3.1
The reduction factor for bearing is
0.65:
Column factored forces aretransferred to the foundation by
bearing and throughreinforcement dowels. Providedowel reinforcement area of at
least 0.005Agand at least four
bars.
Bars are in compression for all
load combinations. Therefore, the
bars must extend into the footinga compression development
length, ldc, the larger of the two:
'50
(0.0003 )
y rb
dc c
y r b
fd
l f
f d
The footing depth must satisfy the
following inequality so that thevertical reinforcement can be
developed within the provided
depth:
, ,2 3 in.dc b dwl b barsh l r d d
where
r= radius of No. 6 bent = 6db
bearing= 0.65
2nB (0.65)(2)(0.85)(4000 psi)(24 in.)
Bn= 2546 kip > 960 kip (Step 4) OK
As,dowel= 0.005(24 in.)2= 2.88 in.2
Use eight No. 6 bars
0.02(60,000 psi)(0.75 in.) 14.3 in.
4000 psidcl
0.0003(60,000 psi)(0.75 in.) 13.5 in.dcl
ldc= 14.3 in. (controls)
hreqd= 14.3 in. + 6(0.75 in.) + 0.75 in.
+ 2(0.75 in.) + 3 in. = 24.05 in.
hreqd= 24.1 in. < hprov.= 30 in. OK
Step 9: Footing details
13.2.8.3
13.2.7.1
Development length
Reinforcement development is
calculated at the maximumfactored moment, which occurs atthe column face. Bars must extend
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
10/11
25.4.2.2
25.4.2.4
a tension development length
beyond the critical section.
'
3{ }
40
y t e sd b
trc
b
fl d
c Kf
d
where
tbar location; not more than12 in. of fresh concrete belowhorizontal reinforcement
e coating factor; uncoated
sbar size factor; No. 8 andlarger
cb= spacing or cover dimension
to center of bar, whichever is
smaller
tr= transverse reinforcementindex
It is permitted to useKtr= 0.
But the expression:b tr
b
c K
d
must
not be taken greater than 2.5.
3 60, 000 (1.0)(1.0)(1.0){ }
40 2.5(1.0) 4000
= 28.5d
d b
b
psil d
psi
No. 6:b tr
b
c K
d
=
3.5 in. 03.5 2.5
1.0 in.
No.8 bars: 28.5(1.0 in.) = 28.5 in. > 12 in. OK
ldin the longitudinal direction:
ld,prov. = ((12 ft)(12 in./ft)24 in.)/23 in.
ld,prov. = 57 in. > ld,reqd= 28.5 in. OK
use straight No. 8 bars in both directions.
-
5/19/2018 Www.concrete.org Portals 0 Files PDF 318-Example-1 RF R1
11/11
Step 10: Detailing