Wireless Stairwell Fixture Solution

4
® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Wireless Stairwell Fixture 369338b 1 06.04.12 ® Wireless Stairwell Fixture Solution The stairwell fixture works with a Lutron Radio Powr Savr TM wireless occupancy sensor (sold separately) to save energy and lower energy costs. The easy-to-install fixture includes a preprogrammed dimming ballast and RF receiver that adjusts light levels based on stairwell occupancy. Features • Universal input voltage 120/277 V • Ballast has occupied and unoccupied levels that can be preset to a specific location's code requirements for lighted stairwells • Integral wireless control device with RF receiver • Integral failsafe defaults to occupied light level if sensor is missing or malfunctioning • Rotary locking lampholders • Also available: Emergency ballast battery backup • Fully assembled fixture comes ready to install • Power factor greater than 0.9 • Total harmonic distortion <10% • Class A sound rating • No visible lamp flicker • Approved to UL and CSA standards Environment • 10 to 40 °C (50 to 104 °F) • Relative humidity less than 90% non-condensing • For indoor use only RF Range (occupancy sensor to wireless control) • 60 foot (18 m) line of sight • 30 foot (9 m) through normal construction Fixture Specifications • Ceiling or wall surface mount • Housing and switch box: 20 gauge white high- reflective powder coat steel End caps: 18 gauge white high-reflective powder coat steel • Lutron ballast with adjustable high-end occupied level and low-end unoccupied level with 2 available factory default settings: 10% unoccupied; 50% occupied 20% unoccupied; 80% occupied • Prismatic acrylic lens • 120/277 V universal input voltage • Compatible with all Lutron Radio Powr Savr TM wireless occupancy sensors Lamps • Use only with lamps conforming to the IEC 60081/60901 specification; Lutron recommends Sylvania, GE, or Philips lamps for proper dimming performance • Refer to lamp manufacturer for lamp burn-in requirements • Lamps are not included with fixture • 2-foot, 3-foot, and 4-foot fixtures available; 1 or 2 lamps Lamp options: T8, T5HE, T5HO, reduced wattage T8 • 8-foot fixture available in 2-lamp or 4-lamp T8 only Wireless control device

Transcript of Wireless Stairwell Fixture Solution

Page 1: Wireless Stairwell Fixture Solution

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Wireless Stairwell Fixture

369338b 1 06.04.12

®

Wireless Stairwell Fixture Solution

The stairwell fixture works with a Lutron Radio Powr SavrTM wireless occupancy sensor (sold separately) to save energy and lower energy costs. The easy-to-install fixture includes a preprogrammed dimming ballast and RF receiver that adjusts light levels based on stairwell occupancy.

Features

•Universalinputvoltage120/277V•Ballasthasoccupiedandunoccupiedlevelsthatcan

be preset to a specific location's code requirements for lighted stairwells

• IntegralwirelesscontroldevicewithRFreceiver• Integralfailsafedefaultstooccupiedlightlevelifsensoris

missing or malfunctioning•Rotarylockinglampholders•Alsoavailable:Emergencyballastbatterybackup•Fullyassembledfixturecomesreadytoinstall•Powerfactorgreaterthan0.9•Totalharmonicdistortion<10%•ClassAsoundrating•Novisiblelampflicker•ApprovedtoULandCSAstandards

Environment

•10to40°C(50to104°F)•Relativehumiditylessthan90%non-condensing•Forindooruseonly

RF Range (occupancy sensor to wireless control)

•60foot(18m)lineofsight•30foot(9m)throughnormalconstruction

Fixture Specifications

•Ceilingorwallsurfacemount•Housingandswitchbox:20gaugewhitehigh-

reflective powder coat steel Endcaps:18gaugewhitehigh-reflectivepowdercoat steel

•Lutronballastwithadjustablehigh-endoccupiedlevelandlow-endunoccupiedlevelwith2availablefactorydefaultsettings: 10%unoccupied;50%occupied

20%unoccupied;80%occupied•Prismaticacryliclens•120/277V universal input voltage•CompatiblewithallLutronRadioPowrSavrTM

wireless occupancy sensors

Lamps

•UseonlywithlampsconformingtotheIEC60081/60901specification;LutronrecommendsSylvania,GE,orPhilipslampsforproperdimmingperformance

•Refertolampmanufacturerforlampburn-in requirements

•Lampsarenotincludedwithfixture•2-foot,3-foot,and4-footfixturesavailable;1or2lamps Lampoptions:T8,T5HE,T5HO,reducedwattageT8

•8-footfixtureavailablein2-lampor4-lampT8only

Wireless control device

Page 2: Wireless Stairwell Fixture Solution

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Wireless Stairwell Fixture

369338b 2 06.04.12

®

· Press the tapswitch once to continue to the unoccupiedlightlevelsetting;seethetablebelowfor the approximate light levels as displayed by the LEDs.

· Press the tapswitch to save your light level settings and return the wireless control device to normal operation mode.

Note:Programmingmodewilltimeoutafter30seconds if no buttons are pressed on the wireless control device.

Programming and Functionality

The wireless control device can be programmed to performfourfunctions:

1.Burn-in. Pull out the air gap switch at the bottom of the wirelesscontroldevice.Thelightswillgotofullon(100%).Consultlampmanufacturerforrecommendedburn-inperiod.

2.Return to factory settings. To reset the occupied and unoccupied light levels to their factory settings, perform thefollowingsequenceusingthetapswitch: Tap3times,holdingthetapswitchdownonthethird

tap. The lights will cycle up and down. Releasethetapswitch,thenimmediatelytap3times. Thelightswillcycleupanddown3timestoverifyyouhave returned to factory settings.

Note: Returning the wireless control device to factory settings will disassociate the wireless control device from any associated sensors.

3.Associate with sensor. Press and hold the tapswitch onthewirelesscontroldevicefor6seconds,untiltheLEDsflash.Thenpressandholdthe"Off"or"LightsOn/Off"buttononthesensorfor6seconds,untilthelenson the sensor flashes orange. The sensor and lights will flash to confirm association.

4.Set desired occupied and unoccupied light levels. Press and hold the tapswitch and the up rocker at the sametimefor3secondstoenterprogrammingmode. · To set the desired occupied light level, use the up and

down rockers to raise or lower the light level. The table below shows the approximate light levels, as displayed bytheLEDs.

LED Display

= on = off

Occupied Setting

40% 50% 60% 70% 80% 90% 100%

Unoccupied Setting

1% 5% 10% 20% 30% 40% 50%

Tapswitch

UpRocker

DownRocker

Airgapswitch

LEDs

Note: To set reduced wattage T8lampstotheir10%lowendlight level, program the unoccupied light level of the wirelesscontroldeviceto1%.

Wireless control device

Page 3: Wireless Stairwell Fixture Solution

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Wireless Stairwell Fixture

369338b 3 06.04.12

®

Photometric Data

For detailed photometric data, see www.lutron.com

Candela Plot Candela Table

0 15 30

45

60

75

90

105

120 135 150 165 180

15 30

45

60

75

90

105

120 135 150 165

250

500

750

1000

4100 K Data Zonal Lumen Summary

4 foot 2-lamp 32 W T8 stairwell fixture Tested with clear prismatic lensLightOutput 4406Lumens

Wattage 58.84

Lumens/Watt 74.88

ColorTemperature 4100K

Zone Lumens % of Luminaire0-30 779 17.7

0-40 1301 29.5

0-60 2312 52.5

0-90 3403 77.2

90-180 1003 22.8

0-180 4406 100.0

0 90

0 937 937

5 929 946

15 900 981

25 841 979

35 748 883

45 619 750

55 429 614

65 195 588

75 79 575

85 23 497

90 1 426

Dimensions

513in(1299mm)

47^in(1218mm)

396in(1013mm)47 in (103mm)

73 in (181mm)

6in(22mm)KOprovided at end opposite the switch

1in(6mm)dia.mountinghole(4x)

(4-footfixtureshown)

44 in (111mm)

36 in (98mm)

6in(22mm)KOtyp.

Page 4: Wireless Stairwell Fixture Solution

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Wireless Stairwell Fixture

369338b 4 06.04.12

®

Ordering Guide

Select appropriate code in each column to complete model number. Example:FXSWXX12CP114U51XXXXWH

PRODUCT FAMILY TYPE SIZE LENS LAMPSLAMP TYPE/WATTAGE

REGION CONTROLS MOUNTING OPTIONS COLOR/FINISH

FXFixture

SWStairwell

XXStandard

121 x 2 ft

CPClear prismatic

11 lamp

1414 W T5HE, 2 ft

UUL—North America

5150% high end, 10% low end

XXStandard

XXNone

WHMatte white

131 x 3 ft

OAOpal acrylic

22 lamps

1717 W T8, 2 ft

8280% high end, 20% low end

E1T8 emergency ballast (not available for 2 ft fixture)

141 x 4 ft

44 lamps (1 x 8 ft only)

2424 W T5HO, 2 ft

E3T5HE emergency ballast (not available for 2 ft fixture)

181 x 8 ft

2121 W T5HE, 3 ft

E5T5HO emergency ballast (not available for 2 ft fixture)

2525 W T8, 3 ft

2828 W T5HE, 4 ft

3232 W T8, 4 ft

3939 W T5HO, 3 ft

5454 W T5HO, 4 ft

RW 25,28,30WT8reduced wattage, 4ft