Wind Utility FACTS
-
Upload
tumuluri-phani-kumar -
Category
Documents
-
view
70 -
download
2
Transcript of Wind Utility FACTS
![Page 1: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/1.jpg)
A STATIC COMPENSATION METHOD BASED SCHEME
FOR IMPROVEMENT OF POWER QUALITY IN WIND
GENERATION
Under the Guidance, Project Members V.Satyanarayana,M.Tech V.ANJITH
KUMAR(08MF1A0215)K.D PAVAN KUMAR(08MF1A0223)
V.SRINIVASA RAO(08MF1A0252)D.BRIJESH(08MF1A0220)
![Page 2: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/2.jpg)
Introduction
• Wind is a renewable Green Energy source
Load
kinetic Energy
Mechanical Energy
Electrical Energy
![Page 3: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/3.jpg)
Introduction
• Wind is also a clean Abundant Source
• No Emissions, No Pollutions
sulfur dioxide
particulates
carbon dioxide
![Page 4: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/4.jpg)
Introduction• One of the main problems in wind energy generation is the connection to the grid.
Injection of wind power into the grid affects the power quality resulting in poor performance of the system. The wind energy system faces frequently fluctuating voltage due to the nature of wind and introduction of harmonics into the system. Injection of the wind power into an electric grid affects the power quality. The performance of the wind turbine and thereby power quality are determined on the basis of measurements and the norms followed according to the guideline specified in International Electro-technical Commission standard, IEC-61400. The influence of the wind turbine in the grid system concerning the power quality measurements are-the active power, reactive power, variation of voltage, flicker, harmonics, and electrical behavior of switching operation and these are measured according to national/international guidelines. The paper study demonstrates the power quality problem due to installation of wind turbine with the grid.
![Page 5: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/5.jpg)
Introduction
0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
Germany USA Denmark CANADA
2004 (MW)2005 (MW)
Total installed wind power MW-capacity( data from World Wind Energy Association)
![Page 6: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/6.jpg)
Introduction
• Wind Energy Conversion System (WECS) Using Large Squirrel Cage/Slip ring Induction Generators– Stand alone-Village Electricity– Electric Grid Connected WECS
• Distributed/Dispersed/Farm Renewable Wind Energy Schemes– Located closer to Load Centers– Low Reliability, Utilization, Security
![Page 7: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/7.jpg)
Motivations
• Energy crisis– Shortage of conventional fossil fuel based energy
– Escalating/rising cost of fossil fuels
• Environmental/Pollution/GHG Issues – Greenhouse gas emission /Carbon Print
– Acid Rain/Smog/VOC-Micro-Particulates
– Water/Air/Soil Pollution &Health Hazards
![Page 8: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/8.jpg)
Motivations
• Large wind farm utilization is also emerging (50MW-250 MW) Sized Using Super Wind driven Turbines 1.6, 3.6, 5 MW Sizes
• Many new interface Regulations/Standards/PQ Requirements regarding full integration of large distributed/dispersed Wind Farms into Utility Grid.
![Page 9: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/9.jpg)
Motivations
• Challenges for Utility Grid–Wind Integration.– Stochastically-Highly Variable wind power injected into the Utility
Grid.
– Increased Wind MW-Power penetration Level.
– Low SCR-Weak Distribution/Sub Transmission/Transmission Networks
- Mostly of a Radial Configuration
- Large R/X ratio distribution Feeder with high Power Losses (4-10 %), Voltage Regulation Problems/Power Quality/Interference Issues.
– Required Reactive Power Compensation & Increased Burden brought by the induction generator
![Page 10: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/10.jpg)
WECS
Sample Distribution Study System
L.L.1 L.L.2
L.L.3N.L.L
I.M.
T1T3T2
Infinite Bus
![Page 11: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/11.jpg)
WECS-Decoupled Interface Scheme
Cself
WindTurbine
I.G.Lf
Cf
UncontrolledRectifier
PWMInverter
To Grid
DC LinkInterface
![Page 12: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/12.jpg)
System Description-wind turbine
• Wind turbine model based on the steady-state power characteristics of the turbine
– S -- the Total BladeArea swept by the rotor blades (m^2)
– v -- the wind velocity (m/s)– ρ--air density (kg/v^3)
31
2m pP C S V
![Page 13: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/13.jpg)
System Description
3
21 3 4 6( , ) i
c
pi
CC C C C e C
tip speed ratio λ is the quotient between the
tangential speed of the rotor blade tips
and the undisturbed wind
velocity
3
1 1 0.035
0.08 1i
C1=0.5176, C2=116,
C3=0.4, C4=5, C5=21 and C6=0.0068
![Page 14: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/14.jpg)
System Description – Wind speed
• The dynamic wind speed model consists of four basic components:– Mean wind speed-14 m/s– Wind speed ramp with a slope of ±5.6– Wind gust
• Ag: the amplitude of the gust• Tsg: the starting time of the gust • Teg: the end time of the gust• Dg = Teg - Tsg
– Turbulence components: a random Gaussian series
[1 cos(2 ( / / ))]g g sg gv A t D T D
![Page 15: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/15.jpg)
Wind Speed Dynamic Model
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
2
4
6
8
10
12
14
16
18
Time (Second)
Win
d S
peed
(m
/s)
The eventual windspeed applied to the wind turbine is the summation
of all four key components.
![Page 16: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/16.jpg)
MPFC-FACTS Scheme 1
• Complementary PWM pulses to ensure dynamic topology change between switched capacitor and tuned arm power filter
• Two IGBT solid state switches control the operation of the MPFC via a six-pulse diode bridge
![Page 17: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/17.jpg)
Tri-loop Error Driven Controller
VoltageStabilization
loop
Current Dynamic Error Tracking loop
Current HarmonicTracking Loop
ModulationIndex
![Page 18: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/18.jpg)
DVR-FACTS Scheme 2
• A combination of series capacitor and shunt capacitor compensation
• Flexible structure modulated by a Tri-loop Error Driven Controller
If S1 is high and S2 is low, both the series and
shunt capacitors are connected into the circuit, while the
resistor and inductor will be fully shorted
If S1 is low and S2 is high, the series capacitor will be removed from the system, the resistor and inductor will be connected to the
shunt capacitors as a tuned arm filter
![Page 19: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/19.jpg)
HPFC-FACTS Scheme 3
• Use of a 6-pulse VSC based APF to have faster controllability and enhanced dynamic performance
• Combination of tuned passive power filter and active power filter to reduce cost
PWM converter
DC Capacitor to provide the
energizing voltage
Passive Filter tuned
near 3rd harmonicfrequency
Coupling capacitor
Coupling transformer
![Page 20: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/20.jpg)
Novel Scheme-3 Multi-loop Error Driven Controller
![Page 21: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/21.jpg)
Novel Decoupled Multi-loop Error Driven Controller
• Using decoupled direct and quad. (d , q) voltage components
• Using The Phase Locked Loop (PLL) to get the required synchronizing signal- phase angle of the synthesized VSC-Three Phase AC output voltages with Utility-Bus
• Using Proportional plus Integral (PI) controller to regulate any tracked errors
• Using Pulse Width Modulation-PWM with a variable modulation index -m
![Page 22: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/22.jpg)
Novel Decoupled Multi-loop Error Driven Controller
• Outer-Voltage Regulator: Tri-loop Dynamic Error-Driven controller– The voltage stabilization loop
– The current dynamic error tracking loop
– The dynamic power tracking loop
• Inner-Voltage Regulator: Mainly to control the DC-Side capacitor charging and discharging voltage to ensure almost a near constant DC capacitor voltage
![Page 23: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/23.jpg)
Controller Tuning
• Control Parameter: Selection/optimization• Using a guided Off-Line Trial-and-Error Method based
on successive digital simulations – Minimize the objective function-Jo
– Find optimal Gains: kp, ki and individual loop weightings (γ) to yield a near minimum Jo under different set-selections of the controller parameters
2
1
( )N
o tk
J e k
Where settling time count N settling
sample
T
T
![Page 24: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/24.jpg)
00.5
11.5
2
05
1015
0
0.2
0.4
0.6
0.8
1
Kp
A Sample of J0-Ki-Kp 3-phase-portrait for Controller Parameter Searching
Ki
Jo
![Page 25: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/25.jpg)
Digital Simulation
• Digital Study System Validation is done by using Matlab/Simulink/Sim-Power Software Environment under a sequence of excursions:– Load switching/Excusrions
• At t = 0.2 second, the induction motor was removed from bus 5 for a duration of 0.1 seconds;
• At t = 0.4 second, linear load was removed from bus 4 for a duration of 0.1 seconds;
• At t = 0.5 second, the AC distribution system recovered to its initial state.
– Wind-Speed Gusting changes modeled by dynamic wind speed-Software model
![Page 26: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/26.jpg)
Digital Simulation
• Digital Simulation Environment: MATLAB /Simulink/Sim-Power• Using the discrete simulation mode with a
sample time of 0.1 milliseconds• The digital simulations were carried out
without and with the novel FACTS-based devices located at Bus 5 for 0.8 seconds
![Page 27: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/27.jpg)
System Dynamic Responses at Bus 2 without and with MPFC
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5
Per
uni
t
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80135
Per
uni
t
Current (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-1012
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-2-101
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.511.1
Time (Second)
Power Factor
![Page 28: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/28.jpg)
System Dynamic Responses at Bus 3 without and with MPFC
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.52
Per
uni
t
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5
Per
uin
t
Current (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.5
00.5
1
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Time (Second)
Power Factor
![Page 29: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/29.jpg)
System Dynamic Responses at Bus 5 without and with MPFC
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5
Per
uni
t
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5
Per
uni
t
Current (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-101
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Time (Second)
Power Factor
![Page 30: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/30.jpg)
The frequency variation at the WECS interface without and with MPFC
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.856
57
58
59
60
61
62
Time (Second)
Fre
quen
cy (
Hz)
with compensation
without compensation
![Page 31: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/31.jpg)
System Dynamic Responses at Bus 2 without and with DVR
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5P
er u
nit
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8013
Per
uni
t
Current (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-1012
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-2-101
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Time (Second)
Power Factor
![Page 32: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/32.jpg)
System Dynamic Responses at Bus 3 without and with DVR
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5
Per
uni
t
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5
Per
uni
t
Current (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-1012
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Time (Second)
Power Factor
![Page 33: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/33.jpg)
System Dynamic Responses at Bus 5 without and with DVR
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5P
er u
nit
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Per
uni
t
Current (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.5
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.5
00.5
1
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Time (Second)
Power Factor
![Page 34: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/34.jpg)
The frequency variation at the WECS interface without and with DVR
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.856
57
58
59
60
61
62
Time (Second)
Fre
quen
cy (
Her
z)
with compensation
without compensation
![Page 35: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/35.jpg)
System Dynamic Responses at Bus 2 without and with HPFC
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5
Per
uni
t
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8013
Per
uni
tCurrent (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-1012
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-101
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Time (second)
Power Factor
![Page 36: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/36.jpg)
System Dynamic Responses at Bus 3 without and with HPFC
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5P
er u
nit
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Per
uni
t
Current (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.2
0
0.5
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.5
0 0.5
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Time (Second)
Power Factor
![Page 37: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/37.jpg)
System Dynamic Responses at Bus 5 without and with HPFC
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5P
er u
nit
Voltage (L-L rms)
with compensation
without compensation
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
1.5
Per
uni
t
Current (rms)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Per
uni
t
Real Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.5
00.5
1
Per
uni
t
Reactive Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
0.51
Time (Second)
Power Factor
![Page 38: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/38.jpg)
The frequency variation at the WECS interface without and with HPFC
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.856
57
58
59
60
61
62
Time (Second)
Fre
quen
cy (
Her
z)
with compensation
without compensation
![Page 39: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/39.jpg)
Comparison of Voltage THD with Different Compensation Scheme
Busnumber
Withoutcompensator
WithMPFC
WithDVR
WithHPFC
1 28.39% 4.90% 11.9% 4.99%
2 32.70% 4.60% 12.2% 4.88%
3 35.95% 4.29% 12.6% 4.69%
4 35.75% 3.51% 12.2% 4.51%
5 35.77% 3.32% 13.1% 3.90%
6 36.04% 3.57% 8.57% 4.57%
![Page 40: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/40.jpg)
Comparison of Steady-state Bus Voltage with Different Compensation Scheme
Busnumber
Withoutcompensator
WithMPFC
WithDVR
WithHPFC
1 0.97 1.02 1.01 1.05
2 0.95 1.00 1.03 1.05
3 0.94 1.00 1.02 1.05
4 0.89 0.99 1.02 1.05
5 0.86 0.99 1.02 1.06
6 0.83 0.96 1.03 1.05
![Page 41: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/41.jpg)
Conclusions
• Three Novel FACTS-based Converter & Control schemes, namely the MPFC, the DVR, and the HPFC, have been Developed and validated for voltage stabilization, power factor correction and power quality improvement in the distribution network with dispersed wind energy integrated.
![Page 42: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/42.jpg)
Recommendation
• The Low-Cost MPFC-Scheme 1 is preferred for low to medium size wind energy integration schemes (from 600 to 5000 kW).
• The DVR-Scheme 2 is good for Strong AC sub-transmission and distribution systems with large X/R ratio
• The HPFC-Scheme 2 Active Power Filter & Capacitor Compensator is most suitable for Larger Wind-Farms with MW-energy penetration level (100 MW or above).
![Page 43: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/43.jpg)
Recommendation
• The schemes validated in this research need to be fully tested in the distribution network with real dispersed wind energy systems.
• This research can be extended to the grid integration of other dispersed renewable energy.
• Other Artificial Intelligence based control strategies can be investigated in future work.
![Page 44: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/44.jpg)
Conclusions
• A Validation Study of a unified sample study system Using the MATLAB/Simulink
• A dynamic wind speed software model was developed to simulate the varying Random/Stochastic and temporal wind variations in the MATLAB/Simulink
• Three Novel FACTS based Stabilization Schemes were validated using digital simulations
• Novel Control strategies using dynamic Multi-Loop Decoupled Controllers were developed & Validated
![Page 45: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/45.jpg)
Publications• [1] A. M. Sharaf and Weihua Wang, ‘A Low-cost Voltage Stabilization and Power Quality
Enhancement Scheme for a Small Renewable Wind Energy Scheme’, 2006 IEEE International Symposium on Industrial Electronics, 2006, p.1949-53, Montreal, Canada
• [2] A. M. Sharaf and Weihua Wang, ‘A Novel Voltage Stabilization Scheme for Standalone Wind Energy Using A Dynamic Sliding Mode Controller’, Proceeding- the 2nd International Green Energy Conference, 2006, Vol. 2, p.205-301, Oshawa, Canada
• [3] A. M. Sharaf, Weihua Wang, and I. H. Altas, ‘Novel STATCOM Controller for Reactive Power Compensation in Distribution Networks with Dispersed Renewable Wind Energy ’, 2007 Canadian Conference on Electrical and Computer Engineering, Vancouver, Canada, April, 2007
• [4] A. M. Sharaf, Weihua Wang, and I. H. Altas, ‘A Novel Modulated Power Filter Compensator for Renewable Dispersed Wind Energy Interface’, the International Conference on Clean Electrical Power, 2007, Capri, Italy, May, 2007
• [5] A. M. Sharaf, Weihua Wang, and I. H. Altas, ‘A Novel Modulated Power Filter Compensator for Distribution Networks with Distributed Wind Energy ’ (Accepted by International Journal of Emerging Electric Power System)
![Page 46: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/46.jpg)
![Page 47: Wind Utility FACTS](https://reader034.fdocuments.in/reader034/viewer/2022052301/5448cf0eb1af9f5f618b4b54/html5/thumbnails/47.jpg)