Wind Analysis (CP3 British Standard) Updated
description
Transcript of Wind Analysis (CP3 British Standard) Updated
12.52 m
12.00 m
10.35 m
45.00 m/s
A from Section 5.4 0r Table 2 of CP 3: Chapter V Part 2
1.00 from Section 5.5.1 of CP 3: Chapter V Part 2
A from Section 5.5.2 of CP 3: Chapter V Part 2
1.00 from Figure 2 of CP 3: Chapter V Part 2
0.95 Force Coefficient from Table 10
Topographic Location
Ground Roughness
Cladding & Building Size Class
S3 - Multiplying Factor Relating to Life of Structure
Cf
PROJECT INFORMATION
Building Analysis Data
Length of Building
Width of Building
Height of Building
Basic Wind Speed (V)
Table 2 or Section 5.4
Table 3
Section 5.5.1
Section 5.5.2
Tabe 10 force coefficient
Calculate and View Result
from Section 5.4 0r Table 2 of CP 3: Chapter V Part 2
from Section 5.5.1 of CP 3: Chapter V Part 2
from Section 5.5.2 of CP 3: Chapter V Part 2
PROJECT INFORMATION
Wind Analysis Data for CP3 Chapter V Part 2
12.5200 m
12.000 m
10.350 m
45.00 m/s
A from Section 5.4 0r Table 2 of CP 3: Chapter V Part 2
1.00 from Section 5.5.1 of CP 3: Chapter V Part 2
A from Section 5.5.2 of CP 3: Chapter V Part 2
= Characteristic Wind Pressure (N/m2)
= Design Wind Speed (m/s)
( from Section 4.3 of CP 3: Chapter V Part 2 )
= Multiplying Factor Relating to topology
( from Table 2 of CP 3: Chapter V Part 2 )
= Multiplying Factor Relating to Height above Ground & Wind Breaking
( from Table 3 of CP 3: Chapter V Part 2 )
= Multiplying Factor Relating to Life of Structure
( from Figure 2 of CP 3: Chapter V Part 2 )
= m/s
= N/m2
= kN/m2
= Force Coefficient
= kN/m2
Design Wind Pressure Cf.Wk
= kN/m2
Length of Building
Vs
Cladding & Building Size Class
Cf.Wk 1.251
Wind Load Calculation
Ground Roughness
Cf
Cf • Wk 1.251
1.317
1.00
1316.922
0.950
Wind Pressure Calculation
Vs
Wk
Wk
Wk
V • S1 • S2 • S3
46.35
S1
WIND LOAD CALCULATION
Width of Building
Height of Building
S2
0.613 • Vs2
S3
1.03
1.00
Basic Wind Speed (V)
Topographic Location
Design Wind Pressure Cf.Wk
= kN/m2
DIRECTION 1 +
Height Width Area Force Total Force Location
0.2 12.52 2.504 3.133
1.65 12.52 20.658 25.845
1.65 12.52 20.658 25.845
1.65 8.514 14.0481 17.575
1.65 8.514 14.0481 17.575
1.5 7.35 11.025 13.793
1.5 7.35 11.025 13.793
0.25 7.35 1.8375 2.299
DIRECTION 1 -
Height Width Area Force Total Force Location
0.2 12.52 2.504 3.133
1.65 12.52 20.658 25.845
1.65 12.52 20.658 25.845
1.65 8.514 14.0481 17.575
1.65 8.514 14.0481 17.575
1.5 7.35 11.025 13.793
1.5 7.35 11.025 13.793
0.25 7.35 1.8375 2.299
DIRECTION 2 +
Height Width Area Force Total Force Location
0.2 12 2.4 3.003
1.65 12 19.8 24.771
1.65 12 19.8 24.771
1.65 12 19.8 24.771
1.65 12 19.8 24.771
1.5 6 9 11.260
1.5 6 9 11.260
0.25 6 1.5 1.877
DIRECTION 2 -
Height Width Area Force Total Force Location
0.2 12 2.4 3.003
1.65 12 19.8 24.771
1.65 12 19.8 24.771
1.65 12 19.8 24.771
1.65 12 19.8 24.771
1.5 6 9 11.260
1.5 6 9 11.260
0.25 6 1.5 1.877
31.368UPPER
STOREY 4LOWER
16.092UPPER
UPPER
STOREY 3
Cf.Wk 1.251
28.977LOWER
UPPERSTOREY 1
STOREY 2LOWER
43.420
49.543
36.031
13.136
28.977
43.420
31.368
16.092
STOREY 1LOWER
27.774UPPER
STOREY 2LOWER
49.543UPPER
LOWER
STOREY 3LOWER
36.031UPPER
WIND LOAD CALCULATION
5.449
4.001
3.675
6.000
STOREY 4LOWER
13.136UPPER
27.774
6.260
5.449
4.001
3.675
6.260
6.000
5.063
3.000
6.000
6.000
5.063
3.000
STOREY 1
STOREY 2
STOREY 3
STOREY 4
STOREY 1
STOREY 2
STOREY 3
STOREY 4
LOWER
UPPER
LOWER
UPPER
LOWER
UPPER
LOWER
UPPER
LOWER
UPPER
UPPER
LOWER
UPPER
LOWER
UPPER
LOWER
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
= 1 & 2
+ + 3 4
Wind Analysis Data for CP3 Chapter V Part 2
OPTION 1: CONCENTRATED LOAD ON BEAM-COLUMN JOINT
Dir1 Dir2
A or B A or B
4.563 m2 3.269 m
2
1.258 m2 0.958 m
2
5.821 m2 4.227 m
2
cf.wk x Area(A) cf.wk x Area(A)
7.300 kN 5.300 kN
C or D C or D
3.637 m2 2.606 m
2
0.000 m2 0.000 m
2
3.637 m2 2.606 m
2
4.600 kN 3.300 kN
OPTION 2: UNIFORMLY DISTRIBUTED LOAD ON COLUMN
Dir1 Dir2
A or B (Parapet) A or B (Parapet)
1.258 m2 0.958 m
2
cf.wk x Area(A) cf.wk x Area(A)
1.600 kN 1.200 kN
A or B A or B
2.645 m 1.895 m
cf.wk x width(A) cf.wk x width(A)
3.400 kN/m 2.400 kN/m
OPTION 3: CONCENTRATED LOAD ON THE CENTER OF BUILDING WIDTH PER FLOOR
Dir1 Dir2
A A
9.125 m2 6.538 m
2
2.516 m2 1.916 m
2
11.641 m2 8.454 m
2
cf.wk x Area(A) cf.wk x Area(A)
14.600 kN 10.600 kN
B B
7.274 m2 5.211 m
2
0.000 m2 0.000 m
2
7.274 m2 5.211 m
2
cf.wk x Area(A) cf.wk x Area(A)
9.200 kN 6.600 kN
WIND LOAD CALCULATION
0.5
0
0.4
0
2.4
5
0.1
5
2.1
25
1
.37
5
A B
C D
0.5
0
0.4
0
2.4
5
0.1
5
A B
0.5
0
0.4
0
2.4
5
0.1
5
2.1
25
1
.37
5
A
B
a All cases except those in b and c
b Very exposed hill slopes and crests where
acceleration of the wind is known to occur
c steep sided, enclosed valleys sheltered fromm all winds
Topographic Location
b
c
1.1
0.9
Topography Factor
Topography Value of S1
a 1
GO TO DATA INPUTS
Height A B C Height A B C Height A B C Height A B C
1 0.83 0.78 0.73 1 0.72 0.67 0.63 1 0.64 0.6 0.55 1 0.56 0.52 0.47
2 0.83 0.78 0.73 2 0.72 0.67 0.63 2 0.64 0.6 0.55 2 0.56 0.52 0.47
3 0.83 0.78 0.73 3 0.72 0.67 0.63 3 0.64 0.6 0.55 3 0.56 0.52 0.47
5 0.88 0.83 0.78 5 0.79 0.74 0.7 5 0.7 0.65 0.6 5 0.6 0.55 0.5
10 1 0.95 0.9 10 0.93 0.88 0.83 10 0.78 0.74 0.69 10 0.67 0.62 0.58
15 1.03 0.99 0.94 15 1 0.95 0.91 15 0.88 0.83 0.78 15 0.74 0.69 0.64
20 1.06 1.01 0.96 20 1.03 0.98 0.94 20 0.95 0.9 0.85 20 0.79 0.75 0.7
30 1.09 1.05 1 30 1.07 1.03 0.98 30 1.01 0.97 0.92 30 0.9 0.85 0.79
40 1.12 1.08 1.03 40 1.1 1.06 1.01 40 1.05 1.01 0.96 40 0.97 0.93 0.89
50 1.14 1.1 1.06 50 1.12 1.08 1.04 50 1.08 1.04 1 50 1.02 0.98 0.94
60 1.15 1.12 1.08 60 1.14 1.1 1.06 60 1.1 1.06 1.02 60 1.05 1.02 0.98
80 1.18 1.15 1.11 80 1.17 1.13 1.09 80 1.13 1.1 1.06 80 1.1 1.07 1.03
100 1.2 1.17 1.13 100 1.19 1.16 1.12 100 1.16 1.12 1.09 100 1.13 1.1 1.07
120 1.22 1.19 1.15 120 1.21 1.18 1.14 120 1.18 1.15 1.11 120 1.15 1.13 1.1
140 1.24 1.2 1.17 140 1.22 1.19 1.16 140 1.2 1.17 1.13 140 1.17 1.15 1.12
160 1.25 1.22 1.19 160 1.24 1.21 1,18 160 1.21 1.18 1.15 160 1.19 1.17 1.14
180 1.26 1.23 1.2 180 1.25 1.22 1.19 180 1.23 1.2 1.17 180 1.2 1.19 1.16
200 1.27 1.24 1.21 200 1.26 1.24 1.21 200 1.24 1.21 1.18 200 1.22 1.21 1.18
Ground Roughness
Height of Building = 10.35 1 1.03
Height of Building = 15 2 1
Cladding & Building Size Class = A 3 0.88
Ground Roughness = 1.00 4 0.74
s2 = 1.03
(1) Open Country with No Obstructions(4) Surface with large and frequent
obstructions, e.g. city centes
(2) Open Country with
Scattered Windbreaks
(3) Country with many windbreaks;
Small towns; outskirts of large cities
GO TO DATA INPUTS
Ground Roughness 1 Long fetches of open, level or nearly level country with no shelter.
Examples are flat coastal fringes, fens, airfields and grasslands,
moorland or farmland without hedges or walls around the fields.
Ground Roughness 2 Flat or undulating country with obstructions such as hedges or walls
around fields, scattered windbreaks of tress and occasional buildings.
Examples are most farmland and country estates with the exception
of those parts that are well wooded.
Ground Roughness 3 Surfaces covered by numerous large obstructions.
Examples are well-wooded parkland and forest areas, towns and their
shrubs, and their suburbs, and the outskirts of large cities. The general
level of rooftops and obstructions is assumed at about 10m, but the
category will include built-up areas generaaly apart from those that
qualify for category 4.
Ground Roughness 4 Surfaces covered by numerous large obstructions with a general
roof height of about 25 m, or more. This category covers onty the
centres of large towns and cities where the buildings are not only
high, but are also bot too widely spaced,
GROUND ROUGHNESS CATEGORY
GO TO DATA INPUTS
CLASS A All units of cladding, glazing and roofing and their immediate
fixings and individual members of unclad structures
CLASS B All buildings and structures where neither the greatest horizontal
dimension nor the greatest vertical dimension exceeds 50 m (165ft).
CLASS C All buildings and structures whose greatest horizontal dimension
and greatest vertical dimension exceeds 50 m (165ft).
CLADDING AND BUILDING SIZE CATEGORY
GO TO DATA INPUTS
0.5 1 2 4 6 10 20
>4 1.2 1.3 1.4 1.5 1.6 1.6 1.6
<1/4 0.7 0.7 0.75 0.75 0.75 0.75 0.75
3 1.1 1.2 1.25 1.35 1.4 1.4 1.4
1/3 0.7 0.75 0.75 0.75 0.8 0.8 0.8
2 1 1.05 1.1 1.15 1.2 1.2 1.2
1/2 0.75 0.75 0.8 0.85 0.9 0.9 0.9
1.5 0.95 1 1.05 1.1 1.15 1.15 1.15
2/3 0.8 0.85 0.9 0.95 1 1 1
1 1 0.9 0.95 1 1.05 1.1 1.2 1.4
cf = 0.95
h/b HEIGHT OVER BREADTH RATIO
cf FORCE COEFFICIENT
4
3
2
1.5
L/W b/d
GO TO DATA INPUTS
12.52 m
12.00 m
10.35 m
45.00 m/s
A from Section 5.4 0r Table 2 of CP 3: Chapter V Part 2
1.00 from Section 5.5.1 of CP 3: Chapter V Part 2
A from Section 5.5.2 of CP 3: Chapter V Part 2
1.00 from Figure 2 of CP 3: Chapter V Part 2
0.95 Force Coefficient from Table 10
PROJECT INFORMATION
Cf
Basic Wind Speed (V)
Building Analysis Data
Topographic Location
Width of Building
S3 - Multiplying Factor Relating to Life of Structure
Cladding & Building Size Class
Ground Roughness
Length of Building
Height of Building
Calculate and View Result
Table 3
Table 2 or Section 5.4
Section 5.5.1
Section 5.5.2
Table 10 force coefficient