What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... ·...

24
Construction Products Regulation (CPR) EN50575 What do I need to know? ©2018 Structured Cable Products Inc.

Transcript of What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... ·...

Page 1: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

Construction Products Regulation (CPR)EN50575

What do I need to know?

©2018 Structured Cable Products Inc.

Page 2: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

What is CPR?1. CPR standardizes flammability ratings for

permanently installed construction products into EuroClasses.

2. CPR applies to: power, telecommunications, data, and control cables.

3. CPR designates minimum cable fire safety standards (EuroClasses) based on installation & type of building.

a) Each country sets their own minimum EuroClass requirements for installation cables.

• Excluded: interconnect cables such as HDMI and patch cords; direct burial cables.

©2018 Structured Cable Products Inc.

Page 3: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

Purpose of CPR

• Standardizes across Europe the materials used in cable construction

• Sets higher safety levels for fire and dangerous substances

• Provides greater clarity and traceability of the cables used in construction

• Remove misrepresented and “knock-off” brands from the market

©2018 Structured Cable Products Inc.

and…

Page 4: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

CPR Simplifies Cable ComparisonConsultants and Project Managers can more easily spec the right

cable most suitable for the installation

©2018 Structured Cable Products Inc.

Page 5: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

Cables are now rated by EuroClass

There are 4 EuroClasses that directly apply to low voltage cables: B2ca, Cca, Dca, Eca

©2018 Structured Cable Products Inc.

These classes refer to combustible cables in ascending order of fire growth rate and heat release.

Page 6: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

Smoke, Droplets, Acidity

©2018 Structured Cable Products Inc.

CPR Sub-Classifications

Page 7: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

B2ca-s1,d1,a1

SCP CPR Jacket Markings

Ca = Cable

B2 = EuroClass

Smoke Production

Flaming Droplets

Acidity

STRUCTURED CABLE PRODUCTS --- CAT6A-F/FTP-LSZH-BL-B2 --- CATEGORY 6A LOW SMOKE ZERO HALOGEN - 10GBASE-T 600MHZ F/FTP ISO/IEC 11801 CLASS EA 4PR 23AWG SOL BC EN50575:2014 CE B2ca-s1,d1,a1 EU RoHS EC ZONE/DEVICE A B C D E 0 1 2 3 4 5 6 7 8 9 ***M

©2018 Structured Cable Products Inc.

Page 8: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

EuroClass - Hierarchy

Highest B2ca-s1,d1,a1High Cca-s1,d1,a1Medium High Dca-s1,d1,a1Medium Dca-s3,d2,a3Low Eca

CPR EuroClasses can be substituted - Higher to Lower ONLY

©2018 Structured Cable Products Inc.

Example: If project requires Dca cable, you can substitute B2ca or Cca.

All higher rated cables are approved for lower requirements

Page 9: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

EuroClasses and Cable PricingThe higher the CPR EuroClass the higher the manufacturing costs

Your cable pricing structure should be based on EuroClass hierarchy

©2018 Structured Cable Products Inc.

B2ca and Cca also require continuous auditing of the manufacturer

Page 10: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

Decoding CPR Product Labeling

©2018 Structured Cable Products Inc.

Page 11: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

CE Label

©2018 Structured Cable Products Inc.

Page 12: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

SCP Product Labeling

©2018 Structured Cable Products Inc.

Page 13: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

DoP- Declaration of Performance

• DoP is the certificate issued by the manufacturer, referencing the notifying body’s Certification of Compliance

• Manufacturers have legal obligation to provide written Declaration of Performance (DoP) in accordance with CPR requirements.

• All SCP DoP are posted online at www.scpcat5e.com

©2018 Structured Cable Products Inc.

Page 14: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

What EuroClass cable do I need use?

©2018 Structured Cable Products Inc.

Page 15: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

CPR Cable Installation Guide

Each country in Europe has different CPR regulations. Please refer to your country specific requirements. The above guide is for visual representation only.

Residential

©2018 Structured Cable Products Inc.

Page 16: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

Know Your Country CPR Requirements

©2018 Structured Cable Products Inc.

Each member state sets their own CPR requirements

If you are the one making the installation cable decisions…. Please learn your country rules.

Page 17: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

You have liability

Installers are legally required to use the correct CPR rated cable for each installation

©2018 Structured Cable Products Inc.

Page 18: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

SCP Leads the Way in CPR Compliance

©2018 Structured Cable Products Inc.

SCP has the largest selection of CPR compliant cables in Europe for the CEDIA

and Custom Installation markets

Page 19: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

SCP EuroClass Category CablesCategory Cables

Cat7a LSZH S/FTP B2ca-s1,d1,a1Cat6a LSZH U/FTP, F/FTP B2ca-s1,d1,a1Cat6 LSZH UTP, F/UTP Dca-s1,d1,a1*Cat5e LSZH UTP, F/UTP Dca-s1,d1,a1*

HNCPROPLUS-7a-LSZH Dca-s1,d1,a1HNCPROPLUS-6a-LSZH Dca-s1,d1,a1HNCPROPLUS LSZH UTP, F/UTP Dca-s1,d1,a1*HNCPRO LSZH UTP, F/UTP Dca-s1,d1,a1*

PVC UL CMR:HNCPROPLUS UTP, F/UTP Dca-s3,d2,a3 or EcaHNCPRO UTP, F/UTP Dca-s3,d2,a3 or Eca

HDBaseT Category Cables

©2018 Structured Cable Products Inc.

PVC UL CMR:Cat6a U/FTP, F/FTP Dca-s3,d2,a3 or EcaCat6 UTP, F/UTP Dca-s3,d2,a3 or EcaCat5e UTP, F/UTP Dca-s3,d2,a3 or Eca

*Also: Dca-s2,d2,a1

Page 20: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

SCP EuroClass Speaker Cables

LSZH In-Wall Speaker Cables12 AWG OFC LSZH Dca-s1,d1,a114 AWG OFC SZH Dca-s1,d1,a116 AWG OFC LSZH Dca-s1,d1,a1

NEW Commercial Speaker Cables100V Systems

SP-2.5 LSZH Cca-s1,d1,a1SP-1.5 LSZH Cca-s1,d1,a1

In-Wall Speaker Cables – PVC UL CMR12 AWG OFC Dca-s3,d2,a3 or Eca14 AWG OFC Dca-s3,d2,a3 or Eca16 AWG OFC Dca-s3,d2,a3 or Eca

Indoor/Outdoor Speaker Cables – PVC UL CMR12 AWG OFC HD Dca-s3,d2,a3 or Eca14 AWG OFC HD Dca-s3,d2,a3 or Eca16 AWG OFC HD Dca-s3,d2,a3 or Eca

SCP is transitioning warehouse stock to the above. Please confirm EuroClass requirements with SCP at time of order.

©2018 Structured Cable Products Inc.

Page 21: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

SCP EuroClass Control Cables

22/2ESH-LSZH Dca-s2,d2,a322/4EPSH-LSZH Eca Coming: Dca-s2,d2,a322/2ESH PVC Eca

CTRL-1-LSZH Dca-s2,d2,a3CTRL-2-LSZH Dca-s2,d2,a3

CTRL-1-D PVC Dca-s3,d2,a3CTRL-2-D PVC Dca-s3,d2,a3

EIB-BUS-2x2-LSZH Dca-s2,d2,a3Coming: Dca-s1,d1,a1

Universal Control Line Level Audio

Please confirm EuroClass requirements with SCP at time of order.

©2018 Structured Cable Products Inc.

PVC UL : Eca Coming: Dca-s3,d2,a3

Crest-1, Lutron-Green, Lutron-QSLSZH: Eca Coming: Dca-s2,d2,a3

Page 22: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

SCP CPR Cable Review

1. All SCP bulk cable stock is CPR compliant

2. SCP has the largest variety of CPR compliant cables for the CEDIA market

3. EuroClass Cable Ratings include: B2ca, Cca, Dca and Eca.

SCP is transitioning all bulk cable stock to a minimum Dca EuroClass.

©2018 Structured Cable Products Inc.

Page 23: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

1

19March2018

ConstructionProductsRegulation(CPR)andcables–March2018-UKposition

Aswidelypredicted,thefull“comingintoeffect”ofCPRforcablesfrom1stJuly2017hasthrownupmanyquestions.Mostimportantamongsttheseistheoneaskedbymanyspecifiersandusers“Whatclass(es)ofreactiontofireperformancemustweuse?”

Thecorrectansweris“ThereiscurrentlynoUKlegalrequirementforanyspecificclass,thereforedesignersandspecifiersarefreetoselectanyclasssolongastheirdecisionreflectsthedemandsofotherapplicableregulations.”

ThereasonforthisisCPR,asastatutoryregulationthatautomaticallyappliesthroughouttheEU,requiresmanufacturerstoplacetheirproductsonthemarketinaspecifiedmanner.InparticulartheymustprepareaDeclarationofPerformance(DoP)andapplyCEMarking.Bothofthesemustshowtheclassofreactiontofireperformance.ForcablestheCEmarkingmustbeonthelabellingorequivalent.

Theregulationdoesnotdefinewhichclassofreactiontofireperformanceisapplicabletoaparticularinstallation.ThatisentirelytheprerogativeoftheMemberState.InUKthatresponsibilityisvestedintheMinistryofHousing,CommunitiesandLocalGovernment(MHCLG).

https://www.gov.uk/government/organisations/ministry-of-housing-communities-and-local-government

TodateMHCLGhasconsistentlysaidthatitwillnotmakeanyprescriptivelegalrequirementonreactiontofireforcablesviaamendmentstoTheBuildingRegulations2010.Ifitweretodoso,thentheobviousplaceforinclusionwouldbeinApprovedDocumentB,Volumes1and2,forwhichMHCLGisresponsible,thoughsuchApprovedDocumentsthemselvesaredescribedas“practicalguidance”andincludethestatement“thereisnoobligationtoadoptanyparticularsolutioncontainedinanApprovedDocument.”Thustheresponsibilitytomakeanappropriatechoicerestswiththemarketplace,especiallyspecifiersandendusers.

FurthervoluntaryguidancecancomefromsuchplacesasBritishStandards,someofwhichmaybeusedaswaysofdemonstratingcompliancewithpartsoftheBuildingRegulations.Inparticular,thewell-respectedandlongstandingBS7671(theIETWiringRegulations),maybeusedtodemonstratecompliancewithPartP(electricalsafety–dwellings)oftheBuildingRegulations.

(NOTE:AlthoughtheregulationofbuildingsinthedevolvedadministrationsofScotlandandWalesdifferfromthatinEngland,therelationshipwithBS7671issimilar.Fornon-dwellings,theElectricityatWorkRegulationswouldapply,withwhichasimilarrelationshipexistswithBS7671)

Thecurrent(17thedition)ofBS7671pre-datestheintroductionofCPRforcablesbutincludesrequirementsforreactiontofirebasedonthelong-establishedinternationaltestmethodscoveringflamepropagationandsmokerelease.Thenew(18th)editionisinitsfinalstagesandthetechnicalcontenthasbeen“signedoff.”Itwillretaintheexistingreactiontofirerequirementsandwillreferin a non-prescriptive way to CPR and the classes of performance. In practice, because some of the CPR test methods correspond topre-existing ones, the use of cables with a minimum class of Eca is de-facto recognised.

Page 24: What do I need to know? - Amazon Web Serviceshabitech.s3.amazonaws.com/PDFs/SCP/CPR/SCP_CPR... · What is CPR? 1. CPR standardizes flammability ratings for permanently installed construction

2

WhilstBS7671coverstheentiregeneralityofinstallationsuptoanincluding1kVAC,somespecialisedareasmayneedextraguidance.InthisrespectanotherBritishStandard,BS6701,hasrecentlybeenamended.Thisstandardrelatestotelecommunicationcablesystemsandcanthusembracesituations,e.g.verticalpathways(risers),whereverylargebundlesofcablesmaybetightlyinstalledinplacesandwherefiresafetyorevacuationiskey.ThenewamendmentgivesClassCcaforwhataredefinedas“installationcables”,andClassEcaforallothertelecommunicationcables.

ItmustagainbeemphasisedthatbothBS7671andBS6701arenotlegalrequirementsaccordingtoMHCLGandthishasbeenconfirmed.Theuserisfullyentitledtofindsafesolutionsforhisinstallationswithoutreferencetothesepublications.butmaythenneedtodemonstratecompliancewiththeBuildingRegulationsandtheElectricityatWorkRegulationsbyothermeans.

Inadvanceof1stJuly2017BCAhadissueditsGuidetoSpecifiers(Jan2017),whichgavecertainminimumrecommendations.Inthelightofthesubsequentmarketexperiencefollowingthe“comingintoeffect”,andthedevelopmentswithrelevantstandards,thisisbeingupdated.Itwillemphasisetheprincipalcontentofthispaper,namelythatnoclassofreactiontofire,beithighorlow,isinanywaymandatoryundercurrentlaw.

Forfurtherinformationpleasecontact:

PeterSmeeth:[email protected]:[email protected]

BritishCablesAssociation(BCA):Flat7,11TheGrangeWimbledonVillageLondonSW194PTTel:07973636688

Orvisitwww.bcauk.org

Disclaimer:Alltheaboveinformationreflectsourunderstandingofthecurrentpositionandis,tothebestofourknowledgeandbelief,correctandreliable.Incaseofdoubt,specifiers,usersandinstallersshouldseektheirownadviceregardingtheinterpretationoftheConstructionProductsRegulation,itbeingtheprimaryregulatorysource,andalsotheMHCLG.