Wet Areas Using Plasterboard Australian Standard AS 3740 - Waterproofing of Wet Areas within Residential Buildings defines a wet area as an area within a building supplied with water from a water supply system and includes bathrooms, showers, laundries and sanitary compartments. Waterproofing of wet areas may be achieved by systems using water resistant plasterboards such as WaterShield or TruRock. This section contains: Installation instructions for wet area walls. Waterproofing treatment methods for WaterShield and TruRock walls. Construction details for wet areas. Some elements of wet area installation will be carried out by a plasterer, and other elements will be completed by trades such as plumbers and tilers. All waterproofing must be carried out by an approved applicator [Refer to Section 2.3 for more information on wet areas]. INSTALLATION 168 DEFINITIONS 168 WET AREA REQUIREMENTS 168 WATERPROOFING REQUIREMENTS BY AREA 169 GENERAL REQUIREMENTS 171 FRAMING 171 PLASTERBOARD LAYOUT 171 PLASTERBOARD FIXING 171 CONSTRUCTION DETAILS 173 167

Transcript of Wet Areas Using Plasterboard - siniat.com.au

Page 1: Wet Areas Using Plasterboard - siniat.com.au

Wet Areas Using PlasterboardAustralian Standard AS 3740 - Waterproofing of Wet Areas within Residential Buildings defines a wet area as an area within a building supplied with water from a water supply system and includes bathrooms, showers, laundries and sanitary compartments.

Waterproofing of wet areas may be achieved by systems using water resistant plasterboards such as WaterShield or TruRock.

This section contains: Installation instructions for wet area walls. Waterproofing treatment methods for WaterShield and

TruRock walls. Construction details for wet areas.

Some elements of wet area installation will be carried out by a plasterer, and other elements will be completed by trades such as plumbers and tilers. All waterproofing must be carried out by an approved applicator [Refer to Section 2.3 for more information on wet areas].

INSTALLATION 168

DEFINITIONS 168

WET AREA REQUIREMENTS 168

WATERPROOFING REQUIREMENTS BY AREA 169

GENERAL REQUIREMENTS 171

FRAMING 171

PLASTERBOARD LAYOUT 171

PLASTERBOARD FIXING 171

CONSTRUCTION DETAILS 173

167

Page 2: Wet Areas Using Plasterboard - siniat.com.au

Technical Advice 1300 724 505 knaufmetal.com.au168

3.1.4 WET AREAS USING PLASTERBOARDDefinitions and Wet Area Requirements Installation

WATERPROOF MEMBRANE

Waterproof membranes are a layer of material impervious to water that are usually liquid applied. They must comply with AS/NZS 4858:2004, Wet Area Membranes and be applied according to the manufacturer’s instructions.

FLASHING

Flashing is a strip or sleeve of impervious material such as metal angle, or a liquid applied product such as a waterproof membrane. It must provide a barrier to moisture movement.

SHOWER AREA

Shower areas consist of enclosed and unenclosed areas:

Unenclosed shower areas extend 1500mm horizontally from the shower connection on the wall, up to a height of 1800mm from the finished floor.

Enclosed shower areas are bounded by walls or screens up to a height of 1800mm from the finished floor. Walls or screens include hinged or sliding doors that control the spread of water to within the enclosure

A shower fitted with a frameless glass shower screen or screen over a bath less than 1500mm long is not an enclosed shower.

Wet Area RequirementsDifferent wet areas require different levels of treatment to protect them from moisture.

WET AREA INSTALLATION REQUIREMENTS

Area Level of Risk Walls Junctions Penetrations+

Shower area High Water Resistant Waterproof Waterproof

Bathrooms Medium – Waterproof^ –

Areas adjacent to baths and spas Medium Water Resistant Waterproof Waterproof*

Walls adjoining other vessels Low Water Resistant Waterproof Waterproof*

Laundries and WCs Low – Waterproof^ –

Bathrooms and laundries requiring a floor waste High – Waterproof^ Waterproof

+ Including mechanical fixings or fasteners. ^ Applies to wall/floor junctions only. * Horizontal surface waterproof, vertical surface water resistant.

Waterproof membrane to 150mm high behind tiles

WaterShield or TruRock

Flexible wet area sealant

FIGURE 1 Basin

Definitions

Page 3: Wet Areas Using Plasterboard - siniat.com.au

Technical Advice 1300 724 505 knaufplasterboard.com.au 169

WET AREAS USING PLASTERBOARDWaterproofing Requirements

3.1.4Installation

Water Resistant Walls

Use WaterShield or TruRock covered with a waterproof membrane and tiles.

For all plasterboard joints, corners and fastener heads use MastaBase or MastaLongset.

[Refer to waterproof membrane manufacturer for application instructions]

Walls Adjoining Other Vessels

Ensure walls within 75mm of a vessel such as a sink, basin or laundry tub are water resistant to a height of 150mm minimum above the vessel.

Seal all edges where the vessel is fixed to the wall.

Waterproof Penetrations

Use a waterproof sealant or a proprietary flange system to waterproof penetrations.

Waterproof Vertical Junctions (where required)

Use a waterproof membrane as vertical flashing that has a minimum overlap of 40mm to the wall sheeting for each leg.

Wall/Floor Junctions in Shower Areas and Adjacent to Baths and Spas

Use a waterproof membrane on walls to: 150mm minimum above the finished shower floor level or lip of bath And 25mm minimum above the maximum retained water level And with the horizontal leg width a minimum of 50mm.

Wall/Floor Junctions Outside Shower Areas

Use a waterproof membrane or metal angle as flashing with a vertical leg a minimum of 25mm above the finished floor level with the horizontal leg width a minimum of 50mm.

Tiles

Waterproof membrane to 150mm high behind tiles

Waterproof membrane to walls of bath

Waterproof membrane as flashing 25mm min. above finished floor level

Flexible wet area sealant

WaterShield or TruRock

FIGURE 2 Bath (without shower) installation on timber flooring

Waterproofing Requirements by Area

Page 4: Wet Areas Using Plasterboard - siniat.com.au

Technical Advice 1300 724 505 knaufmetal.com.au170

3.1.4 WET AREAS USING PLASTERBOARDWaterproofing Requirements Installation

WWWWWWWWWWWWWWaaaaaaaaaaaaaatttttttttteeeeeeeeeeeeerrrrrrrppppppppppprrrrrrrrrrrroooooooooooooooooooooooooofffffffffffff mmmmmmmmmmmmeeeeeeeeeeeemmmmmmmmmmmbbbbbbbbbbbbbbbrrrrrrrrrraaaaaaaaaaaaaannnnnnnnneeeeeeeeeeee ttttttttttttttooooooooooo 1111111118888888888888000000000000000000000000000000mmmmmmmmmmmmmmmmmmmmmmmmm hhhhhhhhhhhhiiiiiiiiiigggggggggggggghhhhhhhhhhh

WaterShield or TruRock

Waterprooooooooooooooooooooooooooooooooooooooofffffffffff mmmmmmmmmmmmmmmeeeeeeeeeemmmmmmmmmmmmbbbbbbbbbbbbbrrrrrrrrrraaaaaaaaaaannnnnnnnnnneeeeeeeee aaaaaaaaaassssssssssss flashing wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwiiiiiiitttttttttttthhhhhhhhhhh hhhhhhhhhhhhhoooooooooooorrrrrrrrrrriiiiiiiizzzzzzzzzzzzooooooooooooonnnnnnnnnnnttttttttttaaaaaaaaaaaaallllllll lllllllllllllleeeeeeeeeeeeggggggggggggg width of 555555555555555555555555555000000000000mmmmmmmmmmmmmmmmmmmmmmmmmmmmm aaaaaaaaaaaannnnnnnnddddddddddd 22222222222555555555555555mmmmmmmmmmmmmmmmmmmmmmmmm above finiiissssssssssssssssssssssssssssssssssshhhhhhhhhheeeeeeeeeeddddddddddddd flflflflflflflflflflflfloooooooooooooooooooooooorrrrrrrrrr llllllllleeeeeeeeeeevvvvvvvvvvvvvveeeeeeeeeelllllllll

WWWWWWWWWWWWWWWWWWWWWWWWWaaaaaaaaaaaaaaaaaatttttttttttttttttteeeeeeeeeeeeeeeerrrrrrrrrrrrrrrrppppppppppppppppppppprrrrrrrrrrrrrrrroooooooooooooooooooooooooooooooooofffffffffffffffff mmmmmmmmmmmmmmmmmmmmeeeeeeeeeeeeeeeemmmmmmmmmmmmmmmmbbbbbbbbbbbbbbbbbrrrrrrrrrrrrraaaaaaaaaaaaaaaaaannnnnnnnnnnnnnnneeeeeeeeeeeeeeeee 111111111111111111111111111111111111111111111111111111111555555555555555555555555555555555555555555555555555555555555555555555555555555555555500000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000mmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmm mmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmiiiiiiiiiiiiiiiiiiinnnnnnnnnnnnnffffffffffffffffrrrrrrrrrrrrrrrrroooooooooooooooooooooommmmmmmmmmmmmmmmm sssssssssssssssshhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooowwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwweeeeeeeeeeeeeeeeerrrrrrrrrrrrrrrrrrrrrrrrrrr oooooooooooooooooooooooooooooooooooooooouuuuuuuuuuuuuuuuuuutttttttttttttttttttttttttttttttttttttttttttttttllllllllllllllllllllllllllllleeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeettttttttttttttttttttttttttttttttttttttttttttttttttttttttttttttttttt................. TTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTiiiiiiiiiiiiiiiimmmmmmmmmmmmmbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeerrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrr flflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflflooooooooooooooooooooooooooooooooooooooooooooooooooooooooooooorrrrrrrrrrrrrrrrrrrrrrrrrrrrsssssssssssssssssssss iiiiiiiiiiiinnnnnnnnnnnnnnnnnnnnnnnnnnn wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwweeeeeeeeeeeeeeeeeeeeeeeeeeeettttttttttttaaaaaaaaaaaaaaaaaaaaarrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrreeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaasssssssssssssssss mmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmuuuuuuuuuuuuuuuuuuuuuuuuuuuussssssssssssssssssssssssssssssssssssssssssssssssttttttttttttttttttttttttttttttttttttttttt bbbbbbbbbbbbbbbbbbbbbbbbbbbeeeeeeeeeeeeeee ccccccccccccccccccccccooooooooooooooooooooooooooooooooooooooooooooooooooooommmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmppppppppppppppppppppppppppppppppplllllllllllllllllllleeeeeeeeeeeeeeeeeeeeetttttttttttttttttttttttttttttttttttteeeeeeeeeeeeeeeeeeeeeeeeeeeellllllllllllllllllllllllllyyyyyyyyyyyyyyyyyyyy cccccccccccccccccccccccccccccccccccccccccooooooooooooooooooooooooooooovvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvvveeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeerrrrrrrrrrrrrrrrrreeeeeeeeeeddddddddddddddddddddddddd wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwiiiiiiiiiiiiiiiiiiiiiiiiittttttttttttttttttttthhhhhhhhhhhhhhhhhhhhhhhhaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa wwwwwwwwwwwwwwwwwwwwwwwwwwwaaaaaaaaaaaaaaaaattttttttttttttttttttttttteeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeerrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrppppppppppppppppppppppppppppppppppppppprrrrrrrrrrrrrrrrrrrrrrrrrrrrroooooooooooooooooooooooooooooooooooofffffffffffffffffffffffffffffffffffff mmmmmmmmmmmmmmmmmmmmmmmmmmmeeeeeeeeeeeeeeeeeeeeeeeeeemmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrraaaaaaaaaaaaaaannnnnnnnnnnneeeeeeeeeeeeeeeee........

TTTTTTTTTTTTTTTTTTTTTTTiiiiiiiiiiilllllllllllleeeeeeeeeeeeeeeessssssssssssssss

FFFFFFFFFFFllllllllleeeeeeeeeeexxxxxxxxxiiiiiiiiiiibbbbbbbbbbblllllllllleeeeeeeeeeee wwwwwwwwwwweeeeeeeeeeettttttttttt aaaaaaaaaaaarrrrrrrrreeeeeeeeeaaaaaaaaaaaaaaa ssssssssseeeeeeeeeeaaaaaaaaaaalllllllllaaaaaaaaaaaannnnnnnnnnntttttttttt

Use only MastaBase or MastaLongset in shower area

Finishing or all-purpose compounds are only permitted outside of tiled areas

Tiles

Flexible wet area sealant

Waterproof membrane as flashing 25mm min. above finished floor level

Waterproof membrane to 1800mm high

External shower tray(installed before wall lining)

Optional reinforcing angle behind plasterboard

WaterShield or TruRock

Use only MastaBase or MastaLongset in shower area

Finishing or all-purpose compounds are only permitted outside of tiled areas

FIGURE 3 Internal in situ tray for unenclosed shower on concrete or compressed fibre cement floor

FIGURE 4 External tray for enclosed shower on timber flooring

Page 5: Wet Areas Using Plasterboard - siniat.com.au

Technical Advice 1300 724 505 knaufplasterboard.com.au 171

WET AREAS USING PLASTERBOARDGeneral Requirements, Framing, Plasterboard Layout and Fixing

3.1.4Installation

General Requirements

For WaterShield [Refer to Section 3.1.1 non-fire rated requirements]

For TruRock [Refer to Section 3.1.1 fire rated requirements]

Waterproof all cut edges of WaterShield or TruRock that may be affected by moisture, including all penetrations and the bottom edge over a preformed shower base.

Only use paper tape and MastaBase or MastaLongset for jointing in tiled areas to strengthen the joint and provide a continuous surface for the waterproof membrane.

Recess pre-formed shower bases, baths and spas sufficiently into the wall to allow the tiles to pass down the inside perimeter rebate of the shower base [Refer to Construction Details]

After the installation of tiles, apply a waterproof sealant to all wall/floor junctions and vertical corner joints.

Masonry adhesive and stud adhesive are not permitted in tiled areas.

Frame movement should be limited at junctions in high risk areas such as showers. For this purpose use a min. 35 x 35 x 0.7mm BMT metal angle fixed to the frame in internal corners.

Framing

For internal steel walls [Refer to Section 3.1.1].

Masonry walls lined with tiles on WaterShield or TruRock must use the furring channel method. For masonry walls with plasterboard [Refer to Section 3.1.3]

Plasterboard Layout

For WaterShield [Refer to Section 3.1.1 non-fire rated requirements]

For TruRock [Refer to Section 3.1.1 fire rated requirements]

Plasterboard Fixing

Use the ‘Fastener Only Method’ in tiled or fire rated areas. Masonry or stud adhesives are not permitted.

Drive fasteners to just below the sheet surface, taking care not to break the paper linerboard.

Laminating screws can be used to fix butt joints in the second and third layer.

Tiles weighing up to 22 kg/m² (porcelain 9mm thick) may be installed when fasteners are spaced at 200mm maximum centres.

Tiles weighing from 22 to 32 kg/m² may be installed when fasteners are spaced at 200mm maximum centres on studs at 450mm centres, or fasteners spaced at 100mm centres on studs at 600mm maximum centres.

Page 6: Wet Areas Using Plasterboard - siniat.com.au

Technical Advice 1300 724 505 knaufmetal.com.au172

3.1.4 WET AREAS USING PLASTERBOARDPlasterboard Fixing Installation

Field200mm max

200mm max

200mm max

10 - 50mm

Sheet EdgesFix screws 10 - 50mm from sheet edges except at head and base tracks

Sealant If required, use sealant to maintain acoustic integrity

Recessed Edges Fix on each stud

Corners 200mm max

Plasterboard must not be fixed to head track

FIGURE 5 WaterShield in Tiled Areas 1 Layer - HorizontalScrew Only Method

FIGURE 6 WaterShield in Untiled Areas 1 Layer - HorizontalScrew and Adhesive Method

Plasterboard must not be fixed to head track

Sealant If required, use sealant to maintain acoustic integrity

Butt Joints Stagger by 600mm min on adjoining sheets and an

opposite sides of the wall

300mm max

Openings 200mm maxvertical screw spacing

Fix on each stud 50mm

Butt Joints Float between framing for Level 4 and Level 5 finishes

Temporary holding block, if required

200mm min

Adhesive daubs 200mm min from screw points and plasterboard edges

Sheet Edges Fix screws 10 - 50mm from sheet edges except at head and base tracks

Field Adhesive daubs 25mm diameter, 15mm high and 300mm max spacing

Recessed Edges Fix on each stud

Fix on each stud 60 - 100mm

300mm max

Corners 300mm max

Openings 300mm maxvertical screw spacing

10 - 50mm

200mm min

Fix on each stud 50mm

200mm max

Butt Joints Fix at 200mm max centres. Stagger by 300mm min

on adjoining sheets and on opposite sides of the wall

Fix on each stud 60 - 100mm

Tile WeightsTiles weighting up to 22 kg/m2 (porcelain 9mm thick) use,screws at 200mm maximum centres when studs are at 600mm centresTiles weighing from 22 to 32 kg/m2 use,screws at 200mm maximum centres when studs are at 450mm centres, orscrews at 100mm maximum centres when studs are at 600mm centres.

Sheet Width Fixing Pattern900mm S A A A S1200mm S A A A A S1350mm S A A A A A S

Field200mm max

200mm max

200mm max

10 - 50mm

Sheet EdgesFix screws 10 - 50mm from sheet edges except at head and base tracks

Sealant If required, use sealant to maintain acoustic integrity

Recessed Edges Fix on each stud

Corners 200mm max

Plasterboard must not be fixed to head track

FIGURE 5 WaterShield in Tiled Areas 1 Layer - HorizontalScrew Only Method

FIGURE 6 WaterShield in Untiled Areas 1 Layer - HorizontalScrew and Adhesive Method

Plasterboard must not be fixed to head track

Sealant If required, use sealant to maintain acoustic integrity

Butt Joints Stagger by 600mm min on adjoining sheets and an

opposite sides of the wall

300mm max

Openings 200mm maxvertical screw spacing

Fix on each stud 50mm

Butt Joints Float between framing for Level 4 and Level 5 finishes

Temporary holding block, if required

200mm min

Adhesive daubs 200mm min from screw points and plasterboard edges

Sheet Edges Fix screws 10 - 50mm from sheet edges except at head and base tracks

Field Adhesive daubs 25mm diameter, 15mm high and 300mm max spacing

Recessed Edges Fix on each stud

Fix on each stud 60 - 100mm

300mm max

Corners 300mm max

Openings 300mm maxvertical screw spacing

10 - 50mm

200mm min

Fix on each stud 50mm

200mm max

Butt Joints Fix at 200mm max centres. Stagger by 300mm min

on adjoining sheets and on opposite sides of the wall

Fix on each stud 60 - 100mm

Tile WeightsTiles weighting up to 22 kg/m2 (porcelain 9mm thick) use,screws at 200mm maximum centres when studs are at 600mm centresTiles weighing from 22 to 32 kg/m2 use,screws at 200mm maximum centres when studs are at 450mm centres, orscrews at 100mm maximum centres when studs are at 600mm centres.

Sheet Width Fixing Pattern900mm S A A A S

1200mm S A A A A S1350mm S A A A A A S

FIGURE 6 WaterShield in Untiled Areas 1 Layer – HorizontalScrew and Adhesive Method

FIGURE 5 WaterShield in Tiled Areas 1 Layer – HorizontalScrew Only Method

Page 7: Wet Areas Using Plasterboard - siniat.com.au

WET AREAS USING PLASTERBOARDConstruction Details

3.1.4

173Technical Advice 1300 724 505 knaufplasterboard.com.au

Details

FIGURE 7 Shower BaseInternal in-situ shower trayClass 2 membrane shown - Section

NON-FIRE RATEDSHOWER WALL DETAILS

Sealant, if required to maintain acoustic integrity

Furring channel

Additional horizontal furring channel along shower base

Bond breaker

Additional nogging to support shower base

Tiles and tile adhesive (compatible with waterproof membrane)

Flexible wet area sealant

Knauf WaterShield Knauf WaterShield

Waterproof membrane

Waterproof membrane

6mm gap and flexible wet area sealant

FIGURE 11 Shower CornerPlan

Mortar bed

FIGURE 8 Shower BaseInternal in-situ shower trayClass 3 membrane shown - Section

Sealant, if required to maintain acoustic integrity

Additional nogging to support shower base

Tiles and tile adhesive (compatible with waterproof membrane)

Flexible wet area sealant

Waterproof membrane

Mortar bed

Mortar bed Mortar bed

Tiles and tile adhesive (compatible with waterproof membrane)

Flexible wet area sealant

Waterproof membrane

FIGURE 9 Shower BasePre-formed shower tray - Section

Sealant, if required to maintain acoustic integrity

Additional nogging to support shower base

2 layers of Knauf Watershield used to prevent recessing pre-formed shower base into stud work

FIGURE 10 Shower Base over Masonry WallInternal in-situ shower tray Class 3 membrane shown - Section

Knauf WaterShield

5-10mm clearance to plasterboard

Fix 50mm from sheet bottom

Fix 50mm from sheet bottom

Fix 50mm from sheet bottom

5-10mm clearance to plasterboard

5-10mm clearance to plasterboard

Flexible wet area sealant

Optional vertical reinforcing angle in shower area

Refer to proprietry waterproof membrane manufacturer for

specific application instructions.

NON-FIRE RATEDSHOWER WALL DETAILS

Page 8: Wet Areas Using Plasterboard - siniat.com.au

3.1.4 WET AREAS USING PLASTERBOARDConstruction DetailsDetails

174 Technical Advice 1300 724 505 knaufmetal.com.au

FIGURE 12 BathtubSection

NON-FIRE RATEDBATH DETAILS

NON-FIRE RATEDGENERAL WET AREA DETAILS

Sealant, if required to maintain acoustic integrity

Waterproof membrane

Waterproof membrane

Tiles and tile adhesive (compatible with waterproof membrane)

Knauf WaterShield

Flexible wet area sealant

Flexible wet area sealant

Notch stud 35mm max and insert minimum 50x25, 1.15mm BMT top hat

400mm long 35x35, 0.7mm BMT steel angle for stud support

Steel stud frame to support bath

Bathtub

Mortar bed

5-10mm clearance to plasterboard

Fix angle to stud at 100mm max centres and 50mm max from ends

Waterproof membrane

Flexible wet area sealant

Sealant, if required to maintain acoustic integrity

Mortar bed

Tiles and tile adhesive (compatible with waterproof membrane)

Knauf WaterShield

FIGURE 13 Wall Base in General Wet AreaOutside shower - Class 3 membrane shownSection

Refer to proprietry waterproof membrane manufacturer for

specific application instructions.

Fix 50mm from sheet bottom

FIGURE 12 BathtubSection

NON-FIRE RATEDBATH DETAILS

NON-FIRE RATEDGENERAL WET AREA DETAILS

Sealant, if required to maintain acoustic integrity

Waterproof membrane

Waterproof membrane

Tiles and tile adhesive (compatible with waterproof membrane)

Knauf WaterShield

Flexible wet area sealant

Flexible wet area sealant

Notch stud 35mm max and insert minimum 50x25, 1.15mm BMT top hat

400mm long 35x35, 0.7mm BMT steel angle for stud support

Steel stud frame to support bath

Bathtub

Mortar bed

5-10mm clearance to plasterboard

Fix angle to stud at 100mm max centres and 50mm max from ends

Waterproof membrane

Flexible wet area sealant

Sealant, if required to maintain acoustic integrity

Mortar bed

Tiles and tile adhesive (compatible with waterproof membrane)

Knauf WaterShield

FIGURE 13 Wall Base in General Wet AreaOutside shower - Class 3 membrane shownSection

Refer to proprietry waterproof membrane manufacturer for

specific application instructions.

Fix 50mm from sheet bottom

NON-FIRE RATEDBATH DETAILS

NON-FIRE RATEDGENERAL WET AREA DETAILS

Page 9: Wet Areas Using Plasterboard - siniat.com.au

WET AREAS USING PLASTERBOARDConstruction Details

3.1.4

175Technical Advice 1300 724 505 knaufplasterboard.com.au

Details

FIRE RATEDSHOWER WALL DETAILS

Waterproof membrane

Flexible wet area sealant

Support framing for bath

Mortar bed

5-10mm clearance to plasterboard

Refer to proprietry waterproof membrane manufacturer for

specific application instructions.For fire rated penetration details, refer to Section 3.1.1

FIGURE 14 Shower BaseInternal in-situ shower trayClass 2 membrane shown - Section

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Bond breaker

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Additional nogging to support shower base

Tiles and tile adhesive (compatible with waterproof membrane)

Flexible wet area sealant

Knauf fire rated and moisture resistant plasterboard

Knauf fire rated and moisture resistant plasterboard

Knauf fire rated and moisture resistant plasterboard

Knauf fire rated plasterboard

Waterproof membrane

5-10mm clearance to plasterboard

Knauf fire rated plasterboard

Knauf fire rated plasterboard

Mortar bed

FIGURE 15 Shower BaseInternal in-situ shower trayClass 2 membrane shown - Section

Knauf Bindex Fire and Acoustic Sealant required to maintain integrity

Bond breaker

Additional nogging to support shower base

Tiles and tile adhesive (compatible with waterproof membrane)

Flexible wet area sealant

Knauf fire rated and moisture resistant plasterboard

Knauf fire rated plasterboard

Waterproof membrane

5-10mm clearance to plasterboard

Mortar bed

Waterproof membrane

Mortar bed

FIGURE 16 Shower BasePre-formed shower tray with upstandSection

FIGURE 17 BathtubSection

Additional nogging to support shower base

Knauf Watershield Knauf Watershield

5-10mm clearance to plasterboard

Flexible wet area sealant

Fix 50mm from sheet bottom

Fix 50mm from sheet bottom

Fix 50mm from sheet bottom

Fix 50mm from sheet bottom

FIRE RATEDSHOWER WALL DETAILS