Weishaupt dual fuel burners 1/2003 CA Sizes 30 to 70...

20
Weishaupt dual fuel burners Sizes 30 to 70 Version 1LN (NO X -reduction on gas operation) 1/2003 CA

Transcript of Weishaupt dual fuel burners 1/2003 CA Sizes 30 to 70...

  • Weishaupt dual fuel burners Sizes 30 to 70Version 1LN (NOX-reduction on gas operation)

    1/2003 CA

  • 2

    ControlControl of air and fuel is performed ac-cording to the fuel type, burner size andrequirement:

    • Two and three stageThe oil part of the dual fuel burner has a nozzle head with two or three nozzles. The capacity regulation is achieved by opening or closing the oil solenoid valves 2 and 3 with corres-ponding changes in air amount.

    • Sliding two stageOn sliding two stage regulation, the low fire and high fire points are as-signed within the control range. The burner slides depending on heat requirement between both operating points. There is no sudden increase or decrease of supplied fuel amount.

    • ModulatingModulating burners operate according to the heat requirement at any operat-ing point within the control range.

    Reduced starting capacityThe burner starts at ignition position viaseparated pilot line. This way only asmall amount of gas flows into the com-bustion chamber. After a certain delaytime the burner operates in low fire.

    Controlled shutdown from low fireControlled shutdown of the burner isperformed only at low fire. Sudden pres-sure surge in the gas supply line can beavoided.

    Gas trainAs standard, Weishaupt gas and dualfuel burners are always equipped withtwo main gas valves.Gas train can be built according to mostapplicable North American codes andstandards.

    Digital combustion managerW-FM100 and W-FM200 combustionmanager control all essential burnerfunctions, e.g. fuel and air supply andmonitor the flame with digital precision.The target is optimization of operatingconditions, maximization of economicalaspect and minimizing the emissions.Thanks to the digital combustion tech-nology, such optimization is availabletoday at reasonable cost. Expenses forinstallation and maintenance are evenclearly lower than with conventionaltechnologies. For example, a separateremote panel is no longer required forburner control. Furthermore, remoteoperation, remote diagnostic and remotemonitoring of the appliances are nowrealizable. This increases the safety andcomfort for operator.

    ApplicationsThe burners can be used with heatexchanger such as heating boiler, steamboiler, air heater and for certain processapplications. Due to the fact that theburner is capable of overcoming highcombustion chamber pressure, they aremost compatible with modern high per-formance boilers.

    FuelsOil sectionLight oil (#2 oil), viscosity 6mm2/s at68F (20°C)

    Gas sectionNatural gasPropane (LPG)

    Installation locationThe burners are designed for indooroperation with temperature of 5F(–15°C) up to 100F (+40°C) and rela-tive humidity of max. 80%

    CertificationThe burners are in compliance with mostapplicable European and NorthAmerican standards

    Excellent serviceWeishaupt has a high density sales andservice network all over the world. Thecustomer service is available every dayaround the clock. Optimum in housetraining conditions ensure high quality ofservice personnel.

    Description

    Weishaupt burners of sizes 30 to 70 were specially designed and developed forindustrial applications. The Monoblock-Burners are characterized with multipleexcellent features such as:

    • Big firing range and wide area of applications• Stable air fan performance – excellent combustion characteristics• Burner casing can be swung opened• Easy to install, setup and maintenance• Air damper closed off during burner stop• Oil pump and electric oil heater is standard for heavy oil burners

    Typical gas side Low NOx flame pattern

  • 3

    Capacity regulation

    Two stage (ZM)Oil side G

    K

    Ein Aus

    Three stage (TM)Oil side G

    ZW

    T

    Ein Aus

    Modulating (ZM) G

    K

    Z

    Ein Aus

    HF = High FireINT = Intermediate

    loadLF = Low FireIP = Ignition Position

    Burner designation

    LowNOx

    ZM = Gas/Oil: Sliding two stageor modulating

    Index for mixing head

    Code for capacity range

    Size

    Fuel: Light Oil

    Fuel: Gas

    Regulating burner

    RGL 40/1 – B, Vers. ZM-1LN

    Sliding two stage(ZM) G

    K

    Z

    Ein Aus

    Variants

    Standard

    Special version

    Digital combustion manager(W-FM 100)

    Electronic ratio controller (RVW)with O2 trim

    Electronic ratio controller (RVW)with speed control

    Electronic ratio controller (RVW)with O2 trim and speed control

    Mechanical linkage

    Digital combustion manager(W-FM 100)

    with modulating controller

    Digital combustion manager(W-FM 100)

    with modulating controllerand speed control

    Digital combustion manager(W-FM 200)

    with modulating controllerO2 trim and speed control

    LowNOx

    ZM =Gas: Sliding two stage ormodulating

    Oil: Two stage

    TM = Gas: Sliding two stage ormodulating

    Oil: Three stage

    Index for mixing head

    Code for capacity range

    Size

    Fuel: Light Oil

    Fuel: Gas

    GL 40/1 – B, Vers. TM-1LN

    HF

    LF

    LF

    LFIP

    IP

    INTLF

    HF

    HF

    ON

    ON

    ON

    ON

    OFF

    OFF OFF

    OFF

    HF

  • 4

    The advantages of digital combustion management

    Digital combustion managementmeans optimum combustion figures,continuous repeatability of settingvalues and ease of use.

    Weishaupt burners are equipped withelectronic ratio controller and digitalcombustion management to satisfy therequirements of modern combustiontechnology, which demand a precise andcontinuously reproducible supply of fueland combustion air. Only in this wayoptimal combustion figures can beensured over extended periods of time.

    If required, the burners can also beequipped with O2 trim* and variablespeed control.

    Error free operation via AZL displayand control unitSetting and control of the burner func-tions is achieved using a control and dis-play unit, the AZL, which is equippedwith an LCD display. The AZL is con-nected to the combustion manager via asafety bus system and can be posi-tioned anywhere according to the user’spreferences within 325 ft. (100 m) dis-tance from the burner.

    Flexible communication possibilitiesThe integrated communication interfaceenables all necessary information andfunctions to be transmitted to a BMSsystem. If required, remote operation andremote diagnosis functions, which areaccessible via modem, can be installed(e.g. oil/gas change-over, adjustment ofsetting values).

    Communication with external systemsvia BUSIf data has to be exchanged betweenburners and other heating systems withPLC devices, the information can beaccessible via eBUS or MODBUScommunication system.

    * In conjunction with W-FM 200 combustion manager

    Integration with building managementFor control and management functions,Weishaupt offers ProGraf NT - asoftware product that provides a realtime solution to meet all requirements.

    The price advantage of the newtechnologyWith improved technology and ease ofuse, combustion plant is becoming evenmore economical than ever before.

    • No additional burner controls arerequired, since this function is alreadygoverned by the combustion manager.Fuses and burner motor starter are theonly additional items required.

    • Less installation work means lesserrors: the burners are tested as acomplete unit at the factory.

    • If required, the W-FM 100 is availablewith an integrated modulating con-troller and variable speed module. Noseparate equipment is required. Themodulating controller and variablespeed module are included as stan-dard with the W-FM 200.

    • Commissioning and service worktakes less time. The initial presettingof the burner is carried out at the fac-tory. On site, only the site specificoperating points have to be adjusted.

    • To facilitate O2 trim, only an O2 probeand O2 module have to be installedand connected with the W-FM 200via the internal safety BUS.

    Control and Display Unit

  • 5

    Gas butterfly

    Oil regulator

    Air damper

    O2 probe*

    O2 module*

    Control andDisplay Unit

    BMSvisualizationProGraf NT

    Impulse sender

    Steppingmotors

    CAN-Bus

    CAN-Bus

    eBus/MODBUS

    W-FM 200 combustion manager

    Frequencyconverter

    Example of O2 trim and speed control with W-FM 200

  • 6

    Increased safety via shut offassembly with solenoidvalve

    The electromagnetically actuated safetyshut off device isolates the oil supply andreturn on burner models RGL40 to 70when the burner shuts down. Oil shut offdirectly at the nozzle ensures a drip freeburner shut down. (Burner modelRGL30 uses a system without nozzleshut off).

    Considerable noisereduction due to soundabsorbing air inlet

    By utilizing sound absorbing materials onthe fan suction side it has been possibleto reduce operational noise considerably.

    Cut-away of the fan housing

    Cut-away of a nozzle shut of assembly

    Proven quality in detail

    Emission figures for 1LNversion

    Excellent emission results are achievabledepending on the geometry of thecombustion chamber, volume load andfiring system (3 pass or reverse flame).

    When stating information relating toguaranteed values, certain conditions formeasurement and evaluation must betaken into account, such as combustionchamber loading, test tolerances,temperature, pressure, humidity.

    The designation 1LN is used on the newWeishaupt Low NOx burner series.

    [ppm] Example for Natural Gas operation

    60

    50

    40

    30

    20

    10

    0

    NOx CO

    NOx limit* with medium temperature < 230F (110°C)

    * According to German TA-Luft regulation

  • 7

    Burner with integrated Control and Display Unit

  • 8

    Burner model Version

    GL30/2-A ZM-1LN

    GL30/2-A TM-1LN

    RGL30/2-A ZM-1LN

    The ratings given are based on fuel with low calorific valueand an installation altitude of 0 ft. (0 m). Depending on thealtitude of the installation, a reduction in capacity ofapproximately 1% for every 328 ft. (100 m) above sea levelshould be taken into account.

    The stated oil throughputs are based on a calorific value of140,000 BTU/Gal for light oil

    Voltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent available with various voltages from 208 - 600V, 60Hz.Different voltages and frequency are available on request.

    Standard burner motor:Isolation class F, IP 54 protection

    Dual fuel burner selectionModels GL and RGL30, 1LN version

    [“WC ] Burner model GL30/2-A, vers. ZM-1LNGL30/2-A, vers. TM-1LNRGL30/2-A, vers. ZM-1LN

    Combustion head G30/2-LN 190x35MBH Nat. Gas/Propane 1,000 – 6,400GPH Light oil #2 9 – 45

    Combustion head “open”

    Combustion head “closed”

    Nat

    gas

    /LP

    G

    Ligh

    t oil

    Ligh

    t oil

    [MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000

    [GPH] 0 10 20 30 40 50

    5

    4

    3

    2

    1

    0

    -1

  • 9

    The ratings given are based on fuel with low calorific valueand an installation altitude of 0 ft. (0 m). Depending on thealtitude of the installation, a reduction in capacity ofapproximately 1% for every 328 ft. (100 m) above sea levelshould be taken into account.

    The stated oil throughputs are based on a calorific value of140,000 BTU/Gal for light oil

    Voltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent available with various voltages from 208 - 600V, 60Hz.Different voltages and frequency are available on request.

    Standard burner motor:Isolation class F, IP 54 protection

    Burner model Version

    GL40/1-B TM-1LN

    RGL40/1-B ZM-1LN

    GL40/2-A TM-1LN

    RGL40/2-A ZM-1LN

    Dual fuel burner selectionModels GL and RGL40, 1LN version

    Combustion head “open”

    Combustion head “closed”

    Combustion head “open”

    Combustion head “closed”

    [“WC ] Burner model GL40/1-B, vers. TM-1LNRGL40/1-B, vers. ZM-1LN

    Combustion head G30/2-LN 190x35KMBH Natural gas 1,530 – 7,500

    Propane 1,530 – 7,500GPH Light oil #2 11 – 53

    Nat

    gas

    /LP

    G

    Ligh

    t oil

    [MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000

    [GPH] 0 10 20 30 40 50 60

    7

    6

    5

    4

    3

    2

    1

    0

    -1

    [“WC ] Burner model GL40/2-A, vers. TM-1LNRGL40/2-A, vers. ZM-1LN

    Combustion head G40/2-LN 217x35KMBH Natural gas 1,700 – 10,500

    Propane 1,700 – 10,500GPH Light oil #2 13 – 75

    Nat

    gas

    /LP

    G

    Ligh

    t oil

    [MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000

    [GPH] 0 10 20 30 40 50 60 70 80

    7

    6

    5

    4

    3

    2

    1

    0

    -1

  • 10

    Burner model Version

    RGL50/1-B ZM-1LN

    RGL50/2-A ZM-1LN

    Combustion head “open”

    Combustion head “closed”

    Combustion head “open”

    Combustion head “closed”

    Dual fuel burner selectionModel RGL50, 1LN version

    The ratings given are based on fuel with low calorific valueand an installation altitude of 0 ft. (0 m). Depending on thealtitude of the installation, a reduction in capacity ofapproximately 1% for every 328 ft. (100 m) above sea levelshould be taken into account.

    The stated oil throughputs are based on a calorific value of140,000 BTU/Gal for light oil

    Voltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent available with various voltages from 208 - 600V, 60Hz.Different voltages and frequency are available on request.

    Standard burner motor:Isolation class F, IP 54 protection

    [“WC] Burner model RGL50/1-B, vers. ZM-1LNCombustion head G40/2-LN 217x35KMBH Natural gas 1,700 – 11,600

    Propane 1,700 – 11,600GPH Light oil #2 20 – 82

    Nat

    gas

    /LP

    G

    [MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000

    [GPH] 0 10 20 30 40 50 60 70 80 90

    8

    7

    6

    5

    4

    3

    2

    1

    0

    -1

    Ligh

    t oil

    [“WC ] Burner model RGL50/2-A, vers. ZM-1LNCombustion head G50/2-LN 260x40MBH Natural Gas 2,050 – 16,730

    Propane 2,730 – 16,730GPH Light oil #2 21 – 120

    Nat

    gas

    Ligh

    t oil

    [MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000

    [GPH] 0 20 40 60 80 100 120

    8

    7

    6

    5

    4

    3

    2

    1

    0

    -1

    Pro

    pane

    Ligh

    t oil

  • 11

    Burner model Version

    RGL70/1-B ZM-1LN

    RGL70/2-A ZM-1LN

    Combustion head “open”

    Combustion head “closed”

    Pro

    pane Ligh

    t oil

    Combustion head “open”

    Combustion head “closed”

    Nat

    gas

    Dual fuel burner selectionModel RGL70, 1LN version

    The ratings given are based on fuel with low calorific valueand an installation altitude of 0 ft. (0 m). Depending on thealtitude of the installation, a reduction in capacity ofapproximately 1% for every 328 ft. (100 m) above sea levelshould be taken into account.

    The stated oil throughputs are based on a calorific value of140,000 BTU/Gal for light oil

    Voltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent available with various voltages from 208 - 600V, 60Hz.Different voltages and frequency are available on request.

    Standard burner motor:Isolation class F, IP 54 protection

    [“WC] Burner model RGL70/1-B, vers. ZM-1LNCombustion head G70/1- 1LN 365x85MBH Natural gas 2,730 – 24,915

    Propane 3,410 – 24,915GPH Light oil #2 29 – 163

    Nat

    gas

    Ligh

    t oil

    [MBH] 0 4,000 8,000 12,000 16,000 20,000 24,000

    [GPH] 0 20 40 60 80 100 120 140 160 180

    9876543210-1

    Ligh

    t oil

    [“WC] Burner model RGL70/2-A, vers. ZM-1LNCombustion head G70/2-1LN 365x85MBH Natural Gas 3,400 – 34,130

    Propane 4,750 – 34,130GPH Light oil #2 46 – 244

    Ligh

    t oil

    [MBH] 0 6,000 12,000 18,000 24,000 30,000 36,000

    [GPH] 0 30 60 90 120 150 180 210 240 270

    9876543210-1

    Ligh

    t oi

    l

    Pro

    pane

  • 12

    Scope of delivery

    Description GL30-ZM GL30-TM RGL30 GL40-TM RGL40 RGL70RGL50

    Burner housing, hinged flange, housing cover, Weishaupt burner motor, air regulation housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes, nozzle assembly with oil nozzle(s), combustion manager with control unit, flame sensor, flange gasket, limit switch on hinged flange, fixing bolts ● ● ● ● ● ●

    W-FM 100 combustion manager ● ● ● ● ● ●

    Double main gas valves ● ● ● ● ● ●

    Gas butterfly valve ● ● ● ● ● ●

    Pilot gas valves ● ● ● ● ● ●

    Connection piece ● ● ● ● ● ●

    Air pressure switch ● ● ● ● ● ●

    Oil pressure switch in return ● ● ● ●

    Gas pressure switch ● ● ● ● ● ●

    Adjustable regulating sleeve in the mixing head ● ● ● ● ●

    Adjustable flame tube in the mixing head ●

    Servomotor for fuel/air compound regulation via W-FM 100Servomotor for air damper ● ● ● ● ● ●Servomotor for gas butterfly ● ● ● ● ● ●Servomotor for oil regulator ● ● ● ●

    Oil pump ● ● ● ● ● ●

    Oil hoses ● ● ● ● ● ●

    2 oil solenoid valves, 1 safety valve, two stage nozzle assembly without shut off ●

    2 oil solenoid valves, 1 safety valve, two stage nozzle assembly with solenoid shut offg ● ●

    3 oil solenoid valves, 1 safety valve, three stage nozzle assembly without shut off ● ●

    2 solenoid valves in flow and return, nozzle assembly without shut off ●

    Electromagnetic clutch ● ● ● ● ● ●

  • 13

    Special equipment

    Description Size 30 Size 40 Size 50 Size 70

    Vertically firing burner version standard standard standard standard

    Air intake flange for connection of an air duct 280 003 47 280 001 68 280 000 92 280 000 13

    Combustion head extension by 6” (150 mm), model ../1-B – 290 008 96 290 009 00 290 010 78by 12” (300 mm), model ../1-B – 290 008 97 290 009 01 290 010 79

    by 6” (150 mm), model ../2-A 290 008 90 290 008 98 290 009 39 290 009 59by 12” (300 mm), model ../2-A 290 008 91 290 008 99 * *

    W-FM 100 with integrated modulating controller 290 010 60 290 010 60 290 010 60 290 010 60

    Burner controllerMechanical linkage with LFL flame safeguard in lieu of W-FM 100 -price reduction- 290 011 02 290 011 02 290 011 02 290 011 02Mechanical linkage with LGK flame safeguard in lieu of W-FM 100 -price reduction- 290 011 09 290 011 09 290 011 09 290 011 09

    Solenoid valve for air pressure switch testfor continuous run fan or post purge 290 004 29 290 004 29 290 000 31 290 000 31

    * Contact Weishaupt corporation for more detailed information

  • 14

    Technical DataSizes 30 and 40

    Description GL30/2-A RGL30/2-A

    Burner motor Model D112/110-2 D112/110-2Motor rating HP (kW) 6.7 (5.0) 6.7 (5.0)Full Load Amps (FLA) at 460 V A 8.2 8.2Speed (60 Hz) rpm 3510 3510Fan wheel colour / ø red / 248 x 100 red / 248 x 100Combustion manager Model W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45Integral pump Model J6 TA3Oil solenoid valve 110V 1/4” 20 W Model 121 K 6220

    110V 1/8” 19 W Model 121 K 2423 –55V 1/4” (supply) 20 W Model – 121 K 622055V 1/8” (return) 20 W Model – 121 K 242355V 3/8” (supply) 20 W Model – –55V 3/8” (return) 20 W Model – –

    Oil pressure switch 1 - 10 bar (return - 5 bar) Model – DSA 46 F001Oil hoses DN / Length 13/40” (1000mm) 20/40” (1000mm)Burner weight lbs (kg) 297 (135) 319 (145)

    Technical data GL40/1-B RGL40/1-BGL40/2-A RGL40/2-A

    Burner motor Model D112/140-2 D112/140-2Motor rating HP (kW) 10.5 (7.8) 10.5 (7.8)Full Load Amps (FLA) at 460 V A 11.5 11.5Speed (60 Hz) rpm 3450 3450Fan wheel colour / ø red / 275 x 100 red / 275 x 100Combustion manager Model W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45Integral pump Model J6➀ TA3Oil solenoid valve 110V 1/8” 19 W Model 121 K 2423 –

    110V 1/4” (safety valve) 20 W Model 121 K 6220 –55V 3/8” (supply) 20 W Model – 321 H 232255V 3/8” (return) 20 W Model – 121 G 2320

    Oil pressure switch 1 - 10 bar (return - 5 bar) Type – DSA 46 F001Oil hoses DN / Length 13/40” (1000mm) 20/40” (1000)Burner weight lbs (kg) 352 (160) 352 (160)

    ➀ Burners > 60 GPH (200 kg/h): oil pump J7 in lieu of J6 (refer to Special Equipment for additional cost)Burners > 72 GPH (250 kg/h): oil pump TA2 in lieu of J6 (refer to Special Equipment for additional cost)

  • 15

    Technical DataSizes 50 and 70

    Description RGL50/1-B RGL50/2-A

    Burner motor Model D132/170-2a D132/170-2Motor rating HP (kW) 14 (10.5) 20 (15)Full Load Amps (FLA) at 460 V A 17.2 23.2Speed (60 Hz) rpm 3500 3500Fan wheel colour / ø red / 330 x 100 red / 330 x 100Combustion manager Model W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45Integral pump Model TA4C T2COil solenoid valve 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322

    55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320Oil pressure switch 1 - 10 bar (return - 5 bar) Model DSA 46 F001 DSA 46 F001Oil hoses DN / Length 25/51” (1300mm) 25/51” (1300mm)Burner weight lbs (kg) 517 (235) 528 (240)

    Technical data RGL70/1-B RGL70/2-A

    Burner motor Model D160/215-2B D160/215-2Motor rating HP (kW) 25 (19) 29.5 (22)Full Load Amps (FLA) at 460 V A 32.2 36Speed (60 Hz) rpm 3400 3500Fan wheel colour / ø green / 530 x 120 green / 530 x 120Combustion manager Model W-FM100 W-FM 100Ignition unit Model W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45Integral pump Model T2C (to 175 GPH)) T2C (to 175 GPH)

    (to 600 kg/h) (to 600 kg/h)T3C (from 175 GPH) T3C (from 175 GPH)

    (from 600 kg/h) (from 600 kg/h)Oil solenoid valve 55V 1/2” (supply) 20W Model 321 H 2522 321 H 2522

    55V 1/2” (return) 20W Model 121 G 2520 121 G 2520Oil pressure switch 2 – 40 bar (flow - 18 bar) Model – –

    1 – 10 bar (return - 5 bar) Model DSA 46 F 001 DSA 46 F 001Oil hoses DN/Length 25/51” (1300mm) 25/51” (1300mm)Burner weight lbs (kg) 957 (435) 957 (435)

  • 16

    Burner fuel systems

    13a

    13a1310 16a

    Type GL30Z (oil side)

    13a

    13a1310 16a

    13a

    Types GL30T / GL40T (oil side)

    P M

    10 16a12

    15 12a1412a

    12

    55V 55V

    55V 55V

    Type RGL30 (oil side)

    P M

    10 1612

    151412a

    11

    55V

    55V

    Types RGL40 to RGL70 (oil side)

    8

    9

    12

    P

    3 4

    P

    5

    4b4b76

    Types 30 to 70 (gas side)with double main gas valves and pilot line

    Legend

    1 Isolating cock2 Main gas pressure regulator3 Low gas pressure switch4 Double main gas valves4b Pilot gas valves5 High gas pressure switch6 Isolating valve for pilot gas train7 Pilot gas pressure regulator8 Gas butterfly valve9 Burner

    10 Oil pump11 Oil filter12 Normally closed oil solenoid valve (55 V,

    electrically connected in series with 12a)12a Normally closed oil solenoid valve (55 V,

    electrically connected in series with 12,fitted against the direction of flow)

    12b Normally open bypass oil solenoid valve

    13 Normally closed oil solenoid valve13a Normally closed oil solenoid valve for

    stages 1, 2 and 314 Oil pressure switch in return15 Oil regulator16 Nozzle assembly with shut off device

    (solenoid valve)16a Nozzle assembly without shut off device17 Oil preheater18 Pt100 temperature sensor (to monitor

    minimum oil temperature)

  • 17

    Dimensions Sizes 30 and 40

    Size Dimensions in inches (mm)l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5 b6

    30/2-A 42.6 9.6 10.7 0.3 13.9 11.8 2.3 9.4 4.8 1.3 35.2 14.6 8.2 27.6 16.5 �13.0(1083) (245) (272) (8) (354) (300) (58) (238) (123) (32) (895) (371) (208) (700) (418) (�330)

    40/1-B 44.4 10.6 10.7 0.3 16.3 12.6 2.3 9.4 4.8 1.3 37.4 15.8 9.5 29.7 18.2 �13.0(1128) (270) (272) (8) (414) (320) (58) (238) (123) (32) (950) (401) (242) (755) (462) (�330)

    40/2-A 45.2 10.6 13.1 0.3 16.3 13.4 2.6 10.2 5.2 1.7 37.4 15.8 9.5 29.7 18.2 �14.6(1148) (270) (332) (8) (414) (340) (67) (258) (133) (42) (950) (401) (242) (755) (462) (�370)

    h1 h2 h3 h4 h6 d1 d2 d4 d5 d6 d7 d8➀ r1➂ r2

    30/2-A 22.5 8.1 16.0 8.1 �13.0 11.0 9.8 8.6 M12 14.2 11.2 DN50 38.2 35.0(572) (207) (407) (207) (�330) (280) (250) (218) (M12) (360) (285) (DN50) (970) (890)

    40/1-B 23.9 8.3 16.6 8.1 �13.0 11.0 9.8 8.6 M12 14.2 11.2 DN50 41.3 38.2(607) (211) (422) (207) (�330) (280) (250) (218) (M12) (360) (285) (DN50) (1050) (970)

    40/2-A 23.9 8.3 16.6 8.9 �14.6 12.6 11.4 8.6 M12 15.7 12.8 DN65 41.3 38.2(607) (211) (422) (227) (�370) (320) (290) (218) (M12) (400) (325) (DN65) (1050) (970)

    ➀ Flange connection➁ Pilot line connection either side➂ With electromagnetic clutch

    All measurements are approximate. Weishaupt reserves the right to make alterations in light of future developments.

  • 18

    Dimensions Sizes 50

    ➀ Flange connection➁ Pilot line connection either side➂ With electromagnetic clutch

    All measurements are approximate. Weishaupt reserves the right to make alterations in light of future developments.

    Size Dimensions in inches (mm)l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5 b6

    50/1-B 47.0 12.4 13.1 0.3 16.6 14.3 2.6 10.2 5.2 1.7 41.7 17.3 10.9 32.3 21.7 �14.6(1195) (315) (332) (8) (422) (363) (67) (258) (133) (42) (1060) (440) (277) (820) (550) (�370)

    50/2-A 49.0 12.4 17.6 0.3 16.6 16.3 2.8 12.1 6.2 2.6 43.3 18.3 10.9 33.9 21.7 �16.9(1245) (315) (447) (8) (422) (413) (72) (308) (158) (65) (1100) (465) (277) (860) (550) (�430)

    h1 h2 h3 h4 h6 d1 d2 d4 d5 d6 d7 d8➀ r1➂ r2

    50/1-B 28.7 10.4 20.2 8.9 �14.6 12.6 11.4 10.2 M12 15.7 12.8 DN65 46.5 39.4(730) (263) (513) (227) (�370) (319) (290) (258) (M12) (400) (325) (DN65) (1180) (1000)

    50/2-A 28.7 10.4 20.2 10.1 �16.9 15.0 13.8 10.2 M16 18.9 15.4 DN80 46.5 40.4(730) (263) (513) (257) (�430) (382) (350) (258) (M16) (480) (390) (DN80) (1180) (1025)

  • 19

    d5

    d6d7

    Dimensions Sizes 70

    Size Dimensions in inches (mm)l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5 b6

    70/1-B 64.9 19.0 16.5 0.3 24.2 20.1 3.9 13.7 7.0 3.4 55.5 23.7 13.4 44.3 29.9 �20.5(1648) (483) (419) (8) (614) (510) (100) (348) (178) (87) (1410) (602) (340) (1125) (760) (�520)

    70/2-A 65.7 19.0 17.6 0.3 24.2 20.9 3.9 14.5 7.4 3.4 55.5 23.7 13.4 44.3 29.9 �23.6(1668) (483) (447) (8) (614) (530) (100) (368) (188) (87) (1410) (602) (340) (1125) (760) (�600)

    h1 h2 h3 h4 h5 d1 d2 d3 d4 d5 d6 d7 d8➀ r1➂ r2

    70/1-B 42.3 16.5 30.5 11.9 �20.5 17.0 16.0 – 12.2 M16 18.5 17.1 DN100 59.1 51.6(1075) (420) (775) (302) (�520) (432) (406) – (310) (M16) (470) (435) (DN100) (1500) (1310)

    70/2-A 42.3 16.5 30.5 12.4 �23.6 18.5 – 18.9 12.2 M16 21.7 19.7 DN100 59.1 51.6(1075) (420) (775) (315) (�600) (470) – (480) (310) (M16) (550) (500) (DN100) (1500) (1310)

    ➀ Flange connection➁ Pilot line connection either side➂ With electromagnetic clutch

    All measurements are approximate. Weishaupt reserves the right to make alterations in light of future developments.

  • Product and customer servicethe complete Weishaupt range

    Regular maintenance reduces heatingcosts and environmental pollution. Only aproperly adjusted burner can saveenergy and be environmentally friendly.Behind each Weishaupt burner standsthe whole Weishaupt customer serviceorganization. The outstanding effortsmade in maintenance and service justifythe enormous trust placed inWeishaupt’s burners, for at Weishauptproduct and customer service belongtogether.

    Weishaupt customer service is there foryou all year round. Whenever you needhelp, be it the supply of spare parts,technical advice or a site visit. We arethere when you need us.

    Weishaupt Corporation6280 Danville RoadMississauga, ON L5T 2H7Ph.: (905) 564 0946, Fax.: (905) 564 0949www.weishaupt-corp.com

    Print No. 83203816, August 2003Printed in Germany. All rights reserved.