WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared. Learning Objectives. INTERPRETING INFRARED. By attending this session, participants will be able to: Explain the strengths and limitations of infrared (IR) thermography. - PowerPoint PPT Presentation

Transcript of WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

Page 1: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY

Interpreting Infrared

Page 2: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

2 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Learning Objectives

By attending this session, participants will be able to:• Explain the strengths and limitations of infrared (IR)

thermography.

• Interpret IR images as they relate to weatherization opportunities.

• Demonstrate how to assess the quality of installed weatherization measures using IR images.

• Use IR imaging in conjunction with blower door to track infiltration and direct air sealing activities.

INTERPRETING INFRARED

Page 3: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

3 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Infrared CapabilityINTERPRETING INFRARED

IR cannot see through anything.

• Sees surface temperatures only

• Cannot see color

• Cannot see air

Photo courtesy of Tony Gill

Page 4: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

4 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Insulation Settled in End Wall Bays

INTERPRETING INFRARED

Photo courtesy of Tony Gill

Page 5: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

5 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Missed Bay, Low Density Bays, InfiltrationINTERPRETING INFRARED

Photo courtesy of Tony Gill

Page 6: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

6 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Poorly Blown Cellulose in a Sloped CeilingINTERPRETING INFRARED

Photo courtesy of Tony Gill

Page 7: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

7 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Wind Driven Infiltration at Dropped SoffitINTERPRETING INFRARED

Photo courtesy of Tony Gill

Page 8: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

8 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Wind Driven Infiltration

Wind-driven infiltration over ceiling at eaves

side of house.

INTERPRETING INFRARED

Photo courtesy of Tony Gill

Page 9: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

9 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

IR and the Blower Door

With Blower Door RunningWithout Blower Door

Kitchen Soffit Cabinets

INTERPRETING INFRARED

Photos courtesy of Tony Gill

Page 10: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

10 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

IR and the Blower DoorINTERPRETING INFRARED

Photos courtesy of Tony Gill

Page 11: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

11 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Blower Door Driven Infiltration #1

Infiltration at light fixture

Infiltration at ceiling/wall junction

INTERPRETING INFRARED

Photo courtesy of Tony Gill

Page 12: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

12 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Blower Door Driven Infiltration #2

Infiltration at bath ceiling fan/light fixture

INTERPRETING INFRARED

Photo courtesy of Tony Gill

Power Point slides

Page 13: WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Interpreting Infrared

13 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

• IR imaging sees surface temperature only.

• Interpreting IR requires putting images in context.

• IR imaging cannot see through anything.

• Images are easiest to interpret when there is a large temperature difference, and they always require a trained technician for accurate interpretation.

• In conjunction with the blower door, IR imaging is a powerful tool for diagnosing infiltration and targeting air sealing activities.

SummaryINTERPRETING INFRARED