Page 1: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Electrical Installation Condition Report

0360

[email protected]

0845 602 6683 (Head Office)0845 612 4084 (Fax)

Inspection Network LtdUnit 1bWallyford Industrial EstateWallyfordEast LothianEH21 8QJ

Page 2: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Electrical Installation Condition Report

BS7671:2001 (2011) Requirements for Electrical Installations

Client Name:      

Location:      

Contract Number:      

This Report is for the attention of:

     

Date(s) of Visit      

2

Page 3: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Contents

1 Summary and Declaration.

2 Extent and agreed limitations of the Examination.

3 Scope of Inspection and Testing.

4 Origin of Supply and Main Protective Bonding Details.

5 Distribution Board Details

6 Other parts of the installation subjected to inspection and test

7 Observations and Recommendations.

8 Rectification Log

3

Page 4: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Section 1: Summary of the Inspection and Testing

Result of Inspection and Test: Choose an item.

General Condition of the Installation: Refer to Section 7 for details of Observations and Recommendations.

This age of this installation is unknown, although much of the installation is of varying age and standard of workmanship.The installation is in a Choose an item. condition generally, however Choose an item. are in need of renewal or remedial work to bring the installation up to a satisfactory level of compliance with the latest edition of BS7671.The installation in general has been extended over the years without due regard to the provisions of any electrical regulations, and in some circuits loading and/or diversity.The level of protection to exposed and extraneous parts Choose an item..We strongly advise that consideration be given to the renewal of Choose an item..

Note:For Satisfactory status the defects with timed limitations should receive remedial attentionOn completion of the necessary remedial works the Electrical Installation Condition Report can be considered as “Satisfactory” and does not require replacement, however the remedial work will require either an Electrical Installation Certificate or a Minor Electrical Installation Works Certificate.

Declaration

This Electrical Installation Condition Report confirms the condition and status of the installation subject to Section 2 and Section 3 of this report at time of visit.Name George Morgan Instruments UsedCompany Inspection Network Ltd Multi-Function Fluke 1652 9355076Address Unit 1b

Wallyford Industrial EstateWallyfordEast LothianEH21 8QJ

Loop Impedance

Robin 4141923

Continuity NAInsulation NARCD Tester NA

Date of Inspection Click here to enter text.Date of Next Inspection

Click here to enter text.

Signature

Position in Company Engineer Surveyor

4

Page 5: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Section 2: Extent and agreed limitations of the Examination

Extent of Installation covered by this report:Type of installation: Choose an item.The premises consist of a Choose an item storey building with production, dispatch, administration and welfare areas.The installation comprises of XXXXXX distribution boards and/or consumer units, designated as INLXX to INLXX inclusive, and an Origin of Supply situated within the XXXXXX area. The installation was subjected inspection and where necessary testing, except where defined in “Limitations” below.Limitations:Scope of Examination “Type B” agreed with client, due to power not being removed from installation.Refer to “Limitations” in Scope of Inspection and Testing.No records, drawings or manuals were available at this visit.Inspection and Testing was restricted to those parts of the installation considered to be Landlord’s Fixtures and Fittings.High mounted luminaries and equipment were inaccessible and therefore not inspected nor subjected to testing.Insulation Resistance Testing was not applied to any part of this installation due to the fitting of accessories and equipment sensitive to this test.A true value of Ze (external earth loop impedance) could not be measured at the origin, as the removal of power would cause interruption to operation and/or production, however the measured value of Zs is satisfactory.Visual InspectionWhere accessible the fixed electrical installation will be subjected to visual inspection, this inspection will include accessible Distribution Boards and/or Consumer Units, accessible conductors and protective conductors, and upto 10% of socket outlets, switching devices and luminaries.The visual inspection will also include the requirement for correct labelling.Supplementary Testing-GeneralSupplementary Testing may be limited by factors such as incorrectly or ambiguously marked circuits/protective devices and, that the power could not be removed from the installation.Supplementary Testing-Continuity of Earthing Conductors and Protective BondingsContinuity Testing of accessible protective conductors to include Earthing Conductors, Main Protective Bondings, Supplementary Protective Bondings where a measurement greater than 0.05Ω will be deemed excessive.Supplementary Testing-Continuity of Earthing Conductors and Protective Bondings Accessible Circuit Protective Conductors, and upto 10% of Fixed Equipment and Machinery. A measurement greater than 1Ω will be deemed excessive.Supplementary Testing-PolarityPolarity Testing of conductors to ensure correct connection and termination at Distribution Boards and/or Consumer Units, Protective Devices (to ensure fitted to phase conductors only), and upto 10% of fixed equipment and machinery.Supplementary Testing-Earth Fault Loop ImpedanceEarth Fault Loop Impedance testing will be carried out to the Origin of Supply, accessible Distribution Boards and/or Consumer Units, accessible socket Outlets, and 10% of Fixed Equipment and Machinery. A measurement greater than the “75% Rule of Thumb” will be deemed excessive.Supplementary Testing-Operation of DevicesWhere accessible and clearly labelled upto 10% devices and switches will be tested for satisfactory operationSupplementary Testing-Residual Current Devices (RCD)All accessible and clearly labelled RCD’s to be tested. A measurement greater than 40ms for final circuits will be deemed excessive.Supplementary Testing-Prospective Fault Current –Prospective Fault Current Testing will be carried out to the Origin of Supply and accessible Distribution

5

Page 6: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Boards and/or Consumer Units.Supplementary Testing-Insulation Resistance TestingTo be carried out at the discretion of the Inspecting Engineer of up to 10% of the accessible circuits.

Section 3: Scope of Inspection and Testing

Inspection Method

To carry out a visual inspection of the electrical installation where accessible.

ElectricalTesting

To supplement the visual inspection with electrical testing as considered necessary for protection against electric shock from direct or indirect contact

Where insulation resistance testing is carried out it will be the duty of the owner/occupier to ensure that all appliances and /or accessories are unplugged before the test and reinstated after the test, and that isolation of the installation to be tested had been agreed. Inspection Network Limited will not be liable for any damage resulting from this test.

Limitations

The inspection and testing will be conducted where practicable at the discretion of the Inspecting Engineer, taking into account installation availability, accessibility and any limitations agreed with the client. High level equipment and luminaries will not be inspected/tested unless safe access facilities have been provided.

Cables concealed within trunking and conduits, or cables and conduits concealed under floors, roof spaces, ceiling voids and generally within the fabric of the building will not be visually inspected.

Supplementary testing will not be carried out on any unidentified, incorrectly identified, or ambiguously marked circuit or distribution board/consumer unit.

Insulation resistance testing will be not carried out on any circuit which contains discharge lighting, electronic or similar sensitive circuitry and accessories, this includes heating and ventilation controls. Similarly Insulation Resistance testing will not be carried out on any unidentified or incorrectly identified part of the installation.

Exclusions

The following specialist areas are subject to separate contract and do not form part of the Periodic Inspection and Test

a. Emergency lighting systemsb. Lightning protection systemsc. Lift installationsd. Potentially explosive atmosphere installations, which are subject to

local authority requirementse. Any part of the installation which involves working at heights.f. Systems in excess of 1000Voltsg. Fire, security and door entry systemsh. Data/telecommunication systemsi. Heating and ventilation controls and equipment

Report The Electrical Installation Condition Report reflects the condition and status of the installation at time of inspection and testing.

6

Page 7: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

7

Page 8: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Section 4: Origin of Supply Details

Supply Details Main Switch or Circuit Breaker Details

Location LocationCondition of service cable(s) Choose an item. Type of isolationCondition of service head Choose an item. Manufacturing

standardCondition of tails - distributor

Choose an item. Number of poles Choose an item.

Condition of tails – consumer

Choose an item. Rating A

Labels applied Choose an item. Labels applied Choose an item.Protective Device and Type Choose an item.Supply Protective Device Rating

A

Number of Live Conductors Choose an item.Configuration 3 Phase Neutral &

EarthNominal Voltage

Choose an

item.

V

Nominal Frequency 50 HzProspective Fault Current KAExternal Loop Impedance (Ze)

Ω

Main Earthing Conductor DetailsSupplier’s Earth Configuration Choose an item.Presence and condition of MET Choose an item.Earthing Conductor Type Choose an item.Earthing Conductor size Choose an item.Earthing Conductor condition Choose an item.Earth Safety Labels fitted Choose an item.Earth Current measurement A

Main Protective Bonding DetailsCross Sectional Area Minimum 10mm²Water Service Continuity Choose an item. Choose an item.

8

Page 9: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Gas Service Continuity Choose an item. Choose an item.Oil Service Continuity Choose an item. Choose an item.Structural Continuity Choose an item. Choose an item.Connections to MET Choose an item.Earth Safety Labels fitted Choose an item.

Section 5: Distribution Board Details

Distribution Board Identification

INL Switch Details

Distribution Board Location Type Choose an item.

Distribution Board Manufacturer

BS or BSEN Type

Choose an item.

Number of Ways Number of Poles

Choosean item.

Accessibility Choose an item. Rating AIntegrity Choose an item.Protective Devices Choose an item. MeasurementsRCD Details (lΔn) mA Prospective

FCKA

Polarity Choose an item. Ze/ZS (DB) ΩFinal Circuit Conductors Condition

Earth Current A

Final Circuit Identification Choose an item. RCD Time mSSupply Protective DeviceSupply Conductor Configuration

Choose an item. Notices

Number of Supply Conductors Choose an item. Two Versions Choose an item.Supply Conductors Condition Choose an item. Live

TerminalsChoose an item.

Supply Voltage and Frequency

Choosean

item.

V 50 Hz RCD Test Choose an item.

Means of Earthing Choose an item. Other Danger Choose an item.

9

Page 10: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Distribution Board Identification

INL Switch Details

Distribution Board Location Type Choose an item.

Distribution Board Manufacturer

BS or BSEN Type

Choose an item.

Number of Ways Number of Poles

Choosean item.

Accessibility Choose an item. Rating AIntegrity Choose an item.Protective Devices Choose an item. MeasurementsRCD Details (lΔn) mA Prospective

FCKA

Polarity Choose an item. Ze/ZS (DB) ΩFinal Circuit Conductors Condition

Earth Current A

Final Circuit Identification Choose an item. RCD Time mSSupply Protective DeviceSupply Conductor Configuration

Choose an item. Notices

Number of Supply Conductors Choose an item. Two Versions Choose an item.Supply Conductors Condition Choose an item. Live

TerminalsChoose an item.

Supply Voltage and Frequency

Choosean

item.

V 50 Hz RCD Test Choose an item.

Means of Earthing Choose an item. Other Danger Choose an item.

10

Page 11: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Section 6: Other parts of the installation subjected to inspection and test

Others Parts of the installation Inspected and/or Tested

√X

R2Ω

P√

ZsΩ

RCDmS

Comments(If necessary)

Presence of diagrams, chart or records √ - - - -Presence of Danger and Other Notices √ - - - -Labelling of switches, devices and terminals √ - - - -Visible Supplementary Bonding and Measurement

- √ - - -

Condition and Polarity of Switching Devices - √ √ - -Condition and Polarity of Isolation Devices - √ √ - √Phase Rotation of 3 Phase Outlets - √ √ -

For R2 where √ = A resistance measurement of less than 1Ω, and X = A resistance measurement greater than 1Ω

For P where √ = Correct polarity, and X = Incorrect Polarity

11

Page 12: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

For Zs where √ = An Earth Fault Loop Impedance value less than the maximum allowable limit, and X = An Earth Fault Loop Impedance value greater than the maximum allowable limit.

For RCD where √ = A value less than 40 mS at 5xlΔn, and X = A value greater than 40 mS at 5xlΔn

12

Page 13: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Section 7: Observations and Recommendations.

1 Observations requiring urgent immediate remedial attention:None

There is an open entry into the

There are open entries into the

There is an open entry into the distribution board/consumer unit designated as INL1.There are open entries into the distribution boards/consumer units designated as:

There are blanks missing in the facia of the distribution board/consumer unit designated as INL1.There are blanks missing in the facia of the distribution boards/consumer units designated as:

The measurement of the main earthing conductor continuity is excessive.

There are terminations and connections without containment throughout the installation.

There are exposed live conductors without insulation throughout the installation.

There are badly damaged outlets and accessories allowing access to exposed conductors and terminations at the following positions:

The following conductive part is now live due to an earth fault:

The following parts have incorrect polarity:

2 Observations which are potentially dangerous requiring urgent remedial attention:None

The measurement of the XXXXXXXX protective conductor continuity is excessive.

The means of earthing for this installation is by using utility pipework as an earth-electrode.

There is no RCD protection for this TT system.

An Earth Fault Loop Impedance value greater than the maximum allowable limit required for operation of the protective device has been measured at the following part(s) of the installation:

There are oversized and/or ineffective protective devices supplying the following circuits.

There are oversized and/or ineffective protective devices at the following positions:

There are conductors with deteriorated and/or damaged insulation throughout the

13

Page 14: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

installation.

There are single-insulated conductors without containment within reach at the following parts of the installation:

There is a voltage to earth measurement at the following parts of the installation:

There is evidence of overheating at the following positions:

The immersion heater does not have a temperature limiting device.

The insulation resistance is less than 1 MΩ on the following circuits(s):

There is no warning notice of the alternative/secondary source of electricity.

3 Observations which will contribute to the safety of the installation, but do not require immediate attention nor are potentially dangerous:None

There is no visible main protective bonding to the oil services, however tests show a measurement not greater than 0.05Ω

The main protective bonding to the oil services is less than 10mm², however tests show a measurement not greater than 0.05Ω

The main protective bonding to the oil services is not continuous, however tests show a measurement not greater than 0.05Ω

There is no visible main protective bonding to the structure, however tests show a measurement not greater than 0.05Ω

The main protective bonding to the structure is less than 10mm², however tests show a measurement not greater than 0.05Ω

The main protective bonding to the structure is not continuous, however tests show a measurement not greater than 0.05Ω

There is no visible main protective bonding to the structure, however tests show a measurement not greater than 0.05Ω

There is no visible supplementary bonding, however tests show a measurement not greater than 0.05Ω

The safety connections are not all labelled.

All socket outlets within the production/ warehouse/factory/workshop area are not RCD protected.

There are circuits are not clearly marked or are ambiguously marked within the distribution board/consumer unit designated INL1.

There are circuits are not clearly marked or are ambiguously marked within the distribution boards/consumer units designated INL1,

14

Page 15: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

The conductors are bunched and grouped within the distribution board/consumer unit designated as INL1.

The conductors are bunched and grouped within the distribution boards/consumer units designated as INL1,

There are exposed single-insulated conductors without sheathing or containment that are outwith reach throughout the installation.

There are redundant conductors within the distribution board/consumer unit designated as INL1.

There are redundant conductors within the distribution board/consumer units.

The circuit protective conductors within the ring final circuits are not connected in such a manner to allow an excessive earth leakage current.

There are damaged outlets and accessories throughout the installation.

The socket outlets are at an insufficient height.

There are socket outlets that are not RCD protected.

There are conductors within light switches that are not sheathed to indicate live conductors.

There are no diagrams, charts or records available for perusal.

There are no danger or warning notices prominently displayed on all equipment.

4 We make the following recommendations:None

All socket outlets be protected by a residual current device.

The re-wireable fuses be replaced by manual circuit breakers.

The neutral and protective conductors be fitted relative to the position of the associated line conductors within the distribution board designated as INL1.

The neutral and protective conductors be fitted relative to the position of the associated line conductors within the distribution boards.

The installation, and any associated equipment be protected from transient overvoltage events.

An isolator be fitted which can isolate the whole installation immediately after the supplier metering device.

The redundant conductors be removed throughout the installation.

The conductors be suitably contained to prevent damage by vermin attack.

All outlets, switches and means of isolation should be regularly checked for damage

15

Page 16: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

and satisfactory operation.

Where applicable all water heaters and other fixed electrical equipment be supplementary bonded to adjacent pipework and other extraneous-conductive-parts.

Unless already a fixture and brought to our attention then any immersion heater should be fitted with a temperature limiting device which requires manual reset after operation.

Warning notices should be prominently displayed with the following text “This installation has wiring colours to two versions of BS7671. Great care should be taken before undertaking extension, alteration or repair that all conductors are correctly identified.”

Warning notices be applied to the locations where the removal of any cover would expose live terminals, conductors or parts, for example distribution boards, switchgear, junction/connection boxes, unexpected high voltages, etc.

16

Page 17: We make the following recommendations:drummohrengineering.co.uk/ElectricalReport.docx  · Web viewUnless already a fixture and brought to our attention then any immersion heater

Section 8: Rectification Log.(For client use)

Defect Details Remedial Work Date Carried Out

17