WCDE-00088-02 BMEIA Hydram Pump Design 100420

9
BMEIA HYDRAM PUMP DESIGN Hydram Pump Background Information David Effa and Dr. Abiy Awoke WCDE-00088-02 Revision 100126 David M. Effa of the Waterloo Cases in Design Engineering (WCDE) Group and Dr. Abiy Awoke of BMEIA prepared this design case study for classroom use. The authors do not intend to illustrate either effective or ineffective handling of an engineering situation. The authors may have disguised certain names and other identifying information to protect confidentiality. The Waterloo Cases in Design Engineering Group prohibits any form of reproduction, storage or transmittal of this document without its written permission. This material is not covered under authorization of CanCopy or any reproduction rights organization. To order copies or request permission to reproduce materials contact Waterloo Cases in Design Engineering c/o Department of Mechanical Engineering, University of Waterloo, Waterloo, Ontario, Canada, N2L 3G1 e-mail: [email protected] website : www.design.uwaterloo.ca Introduction to the Hydram Pump The Hydram pump, depicted in Figure 1, is an automatic water pumping device that utilizes the energy contained in a flow of water running through it to lift a smaller volume of this water to a higher level. The phenomenon exhibited within the Hydram pump is a pressure surge, which develops when a moving mass of water is suddenly stopped. This pressure surge generated by the main flow of water is used to drive a smaller volume of water over long distances. In this way, water from a spring or stream in a valley can be pumped to a village or irrigation scheme on the hillside without an external power source. This ensures low running costs and no significant harm to the environment. Hydram pumps are simple, reliable and require minimal maintenance [1]. The basic principle behind Hydram pump function is the use of a large amount of water falling a short distance to pump a small amount of water to a higher elevation. Typically, only 2 to 20 percent of the water flowing through a Hydram pump system will actually be delivered to the storage tank or trough. The remainder is overflow and is directed back into the stream. Figure 1:- Hydram Pump [4] Hydram pumps have low pump efficiency (less than 66%) and require a suitable geographical area for implementation [2]. In the right location, however, the Hydram pump is able to pump water autonomously, with no external energy input, for years, with minimal maintenance. This makes Hydram pumps suitable for communal water supply and irrigation in rural areas with limited access to power but suitable topography and hydrology. In recent years, an increased interest in renewable energy devices and a heightened awareness of the need to match technological solutions to the needs of particular markets in developing countries, such as water supply and management, have prompted a reappraisal of Hydram pumps.

Transcript of WCDE-00088-02 BMEIA Hydram Pump Design 100420

  • BMEIA HYDRAM PUMP DESIGN Hydram Pump Background Information

    David Effa and Dr. Abiy Awoke

    WCDE-00088-02 Revision 100126

    David M. Effa of the Waterloo Cases in Design Engineering (WCDE) Group and Dr. Abiy Awoke of BMEIA prepared this design case study for

    classroom use. The authors do not intend to illustrate either effective or ineffective handling of an engineering situation. The authors may have

    disguised certain names and other identifying information to protect confidentiality.

    The Waterloo Cases in Design Engineering Group prohibits any form of reproduction, storage or transmittal of this document without its written

    permission. This material is not covered under authorization of CanCopy or any reproduction rights organization. To order copies or request

    permission to reproduce materials contact Waterloo Cases in Design Engineering c/o Department of Mechanical Engineering, University of

    Waterloo, Waterloo, Ontario, Canada, N2L 3G1 e-mail: [email protected] website : www.design.uwaterloo.ca

    Introduction to the Hydram Pump

    The Hydram pump, depicted in Figure 1, is an automatic

    water pumping device that utilizes the energy contained in a

    flow of water running through it to lift a smaller volume of

    this water to a higher level. The phenomenon exhibited

    within the Hydram pump is a pressure surge, which develops

    when a moving mass of water is suddenly stopped. This

    pressure surge generated by the main flow of water is used to

    drive a smaller volume of water over long distances. In this

    way, water from a spring or stream in a valley can be pumped

    to a village or irrigation scheme on the hillside without an

    external power source. This ensures low running costs and no

    significant harm to the environment. Hydram pumps are

    simple, reliable and require minimal maintenance [1].

    The basic principle behind Hydram pump function is the use

    of a large amount of water falling a short distance to pump a

    small amount of water to a higher elevation. Typically, only 2

    to 20 percent of the water flowing through a Hydram pump

    system will actually be delivered to the storage tank or

    trough. The remainder is overflow and is directed back into

    the stream.

    Figure 1:- Hydram Pump [4]

    Hydram pumps have low pump efficiency (less than 66%) and require a suitable geographical area for

    implementation [2]. In the right location, however, the Hydram pump is able to pump water autonomously,

    with no external energy input, for years, with minimal maintenance. This makes Hydram pumps suitable for

    communal water supply and irrigation in rural areas with limited access to power but suitable topography and

    hydrology. In recent years, an increased interest in renewable energy devices and a heightened awareness of

    the need to match technological solutions to the needs of particular markets in developing countries, such as

    water supply and management, have prompted a reappraisal of Hydram pumps.

  • 2

    BMEIA HYDRAM PUMP DESIGN WCDE-00088-02

    The main advantages of the Hydram pump can be summarized as follows:

    The Hydram pump is simple in construction and operation. High reliability means few maintenance

    requirements.

    It does not incur any running costs; as it utilizes the energy of freely available water, no fuel or

    electricity is required.

    It does not produce any pollution.

    Pumping only a small proportion of the available water flow limits the environmental impact.

    Automatic, continuous operation requires no supervision or human input.

    It has only two moving parts, the waste valve and the delivery valve, as shown in Figure 2. Both of

    these are lubricated by the water itself, thus no separate arrangement for lubrication is required.

    The main limitations are as follows:

    Hydram pump use is limited to hilly areas with year-round water sources.

    It pumps only a small fraction of the available flow and therefore requires source flows significantly

    larger than the actual water delivered.

    It is limited to small-scale applications, usually up to 1kW, but this depends on economic and other

    considerations.

    Figure 2 - Hydram pump main components

  • 3

    BMEIA HYDRAM PUMP DESIGN WCDE-00088-02

    Environmental assessment for Hydram pump applications

    The use of a Hydram pump requires the availability of a suitable and reliable supply of water, as well as a

    sufficient working fall to drive pump operation. The supply can be any source of flowing or stagnant water

    such as a spring, stream, river, lake, or dam, or even a pond fed by an artesian well. A small Hydram pump

    requires a supply flow of at least 5 to 25 litres per minute, whereas a very large Hydram system may need as

    much as 750 to 1500 litres per minute [2]. Environmental assessment is typically performed in two stages: a

    preliminary assessment to locate potential sites and a full survey to select the best option. The preliminary

    survey involves the following steps:

    Consulting relevant maps and hydrological studies;

    Traveling to potential sites to make a preliminary assessment and consult with local people regarding

    their needs and the suitability of the water source for their application; and

    Selecting one or more sites with high potential for a more detailed survey.

    The full survey of selected sites must be sufficiently detailed to provide most of the information necessary for

    accurate system design. Some of this information is indicated in Figure 3 and includes the following:

    i. Water source flow (Q) - The data must reflect the minimum flow of water in a normal year, which

    means this measurement must be taken during the dry season. To ensure the figure represents a typical

    minimum flow, local people should be consulted about flow patterns experienced over recent years.

    Some indication of maximum expected flows is also necessary.

    ii. Drive head (H) - The maximum possible drive head of the site or the average angle of the slope below

    the water source should be measured.

    iii. Delivery head (Hd) - The height from the water source to the expected point of delivery should be

    measured.

    iv. Water requirement (Qs) - This should be estimated with reference to the population to be served

    (allowing for growth) or the area of land to be irrigated.

    v. Distance over which the working fall (Ldp), from the drive tank to the hydram pump, should be

    obtained.

    vi. Length of delivery pipe from the Hydram pump to the delivery site (Lps) should be estimated.

  • 4

    BMEIA HYDRAM PUMP DESIGN WCDE-00088-02

    Figure 3 Schematic of Hydram pump system installation

    Hydram Pump Working Principles

    All Hydram pumps work on the principle of momentum, which is controlled by a cycle set up by the

    interaction of two valves in the pump. Figure 2 shows the basic components of a Hydram pump and Figure 4

    shows its operating cycle. When the waste valve is opened, water begins to flow down the drive pipe and

    through the waste valve as shown in Figure 4a. The water in the drive pipe starts to flow under the force of

    gravity, picking up speed and kinetic energy until the waste valve is forced to close. Indeed, as the flow

    increases, it reaches a speed where the drag force is sufficient to start closing the waste valve. Once the waste

    valve has begun to move, it closes very quickly as shown in Figure 4b.

    The water flowing in the drive pipe has considerable momentum which has to be dissipated. Therefore, for a

    fraction of a second, the water in the body of the pump is compressed causing a large surge in pressure. This

    type of pressure surge is known as water hammer. As pressure rises in the pump, the delivery (discharge)

    valve opens and some water flows into the pressurized air vessel above water level. The air inside the air

    vessel cushions the hydraulic pressure shock when the waste valve closes. It also improves the pumping

    efficiency by allowing a more constant flow through the delivery pipe.

  • 5

    BMEIA HYDRAM PUMP DESIGN WCDE-00088-02

    Figure 4- Hydram pump operating sequence

    In the next phase, Figure 4c, the water pressure above the delivery valve overcomes the spent momentum

    below it, forcing the delivery valve to close again. The water that made it past the delivery valve, Figure 4d, is

    then forced by the extra air pressure up the delivery pipe. The recoil also sucks a small amount of air in

    through the air valve. The air sits under the delivery valve until the next cycle, when it is pumped with the

    delivery water into the air vessel. This ensures that the air vessel stays full of air. Since the momentum of the

    water coming down the drive pipe has stopped, the waste valve falls open, allowing the water to flow down

    the drive pipe again as in Figure 4d, starting the cycle over again.

    The pumping cycle happens very quickly, typically 25 to 300 times per minute. The frequency of the cycle

    can be adjusted by changing the length of the waste valve stroke. A longer stroke produces a lower frequency.

    This means more of the water supply flows to and through the pump and more is pumped up the delivery pipe.

    The stroke is adjusted to appropriately restrict the amount of water used in accordance with the amount

    available, or if supply is unlimited, to regulate the amount delivered to match the amount needed. Generally,

    during each pumping cycle, only a very small amount of water is pumped. However, with cycle after cycle

    continuing over 24 hours, a significant amount of water can be delivered.

  • 6

    BMEIA HYDRAM PUMP DESIGN WCDE-00088-02

    Hydram pump design

    Although Hydram pumps come in a variety of shapes and sizes, they all have the same basic components, as

    shown in Figure 2. The main parts of the Hydram pump are the Hydram body, waste valve, air valve, delivery

    valve, air vessel (chamber) and relief valve. Hydram pumps have a cyclic pumping action that produces their

    characteristic beat during operation. Before designing or selecting a Hydram pump, several design factors

    must be known, including vertical fall (H), lift (Hd), available source flow (Q), required water flow ( ), drive

    pipe length (L) and delivery pipe length (l). Once this information has been obtained, a preliminary

    calculation can be made to see if the amount of water needed can be supplied by a Hydram pump. Hydram

    pump design information is listed in Appendix A.

    Hydram pump efficiency

    Hydram pump efficiency can be expressed in two ways. The first expression, known as the D'Aubuisson

    efficiency ratio, gives the efficiency of the Hydram as a machine [2]. This is the ratio between the input

    energy of the Hydram and its output energy. The second expression, known as the Rankine formula for

    efficiency, considers the Hydram as a hydraulically operated pump [2]. This takes into account the difference

    in elevation between the water surface in the supply channel and the delivery point as the actual delivery head.

    i. DAubuissons Efficiency Ratio

    (1)

    Qw is the quantity of water escaping through the waste valve (litres/min)

    Qs is the quantity of water supplied by the ram (litres/min)

    H is the fall or height of the source above the Hydram (m)

    Hd vertical distance or elevation that the water will be raised (m)

    DAubusson efficiency of the Hydram pump

    A more precise expression of the efficiency of the Hydram, taking into account the head loss due to friction

    in the supply and delivery pipes, is:

    (2)

    Where

    hsf is head loss due to friction in supply pipe (m)

    hdf is head loss due to friction in delivery pipe (m)

  • 7

    BMEIA HYDRAM PUMP DESIGN WCDE-00088-02

    ii. Rankines Formula for Efficiency

    (3)

    Using equation 1, the relationship between pump output and water source input can be expressed as [2]

    (4)

    Where

    Q is the required flow rate in litres per minute [litres/min], which is the sum of the waste

    valve and supplied water rates

    The efficiency of a Hydram pump varies inversely to the ratio between the delivery head ( ) and the supply

    head ( ), also called magnification ratio [2]. Hydram pump manufacturers, including BMEIA, have

    developed a catalogue listing the efficiency of the Hydram pump as a function of the magnification ratio.

    Most Hydram pumps operate at the best efficiency (66% to 70%), if the magnification factor is limited to 4

    [3]. Table 1 solves this formula for Hydram pumps with a magnification ratio of 4 (66% efficiencies) and a

    water supply of 1 litre per minute across varying working fall and lift heights. For supplies greater than 1

    litre/minute, performance results can be obtained by multiplying the Hydram efficiency factors provided in

    Table 1 by the number of litres supplied per minute. For example, if the working fall is 6m and the vertical

    lift above the Hydram is 20m, from Table 1 a factor of 282 can be found. For every litre per minute of water

    flowing into the Hydram, the amount delivered will be this factor in litres per day. Therefore, if 10 litres per

    minute flows into the Hydram then (10 x 282) 2820 litres per day will be delivered. Alternatively, if the total

    daily requirement of water is known per day, then this number is divided by the efficiency factor to find the

    amount of water in litres per minute that must be supplied to the Hydram. For example if 20,000 litres per day

    was required, then 20,000 282 = 70 litres per minute would have to be delivered to the Hydram.

    Hydram pumps must be designed to produce a required flow rate while generating enough pressure to lift the

    water to the desired elevation. In most cases, the fall from the water supply source to the Hydram pump must

    be at least 50 cm and the minimum flow of water needed is roughly 1-2 litres per minute (lpm). The optimum

    length of the drive pipe is 5 to 12 times the vertical distance between the source and the pump or, 500 to 1000

    times the diameter of the delivery pipe, whichever is less [5]. This length of drive pipe typically results in a

    period between pulses of 1 to 2 seconds. The drive pipe is ordinarily straight but can be curved or even wound

    in a spiral. The main requirement is that it is inelastic, strong and rigid; otherwise, efficiency would be greatly

    diminished.

  • 8

    BMEIA HYDRAM PUMP DESIGN WCDE-00088-02

    Table 1- Hydram performance data for a supply of 1 litre/minute

    Working Fall (m) Lift- Vertical height to which water is raised above the Hydram (m)

    5 7.5 10 15 20 30 40 50 60 80 100 125

    Litres delivered over 24 hours

    1.0 144 77 65 33 29 19.5 12.5

    1.5 135 96.5 70 54 36 19 15

    2.0 220 156 105 79 53 33 25 19.5 12.5

    2.5 280 200 125 100 66 40.5 32.5 24 15.5 12

    3.0 260 180 130 87 65 51 40 27 17.5 12

    3.5 215 150 100 75 60 46 31.5 20 14

    4.0 255 173 115 86 69 43 36 23 16

    5.0 310 236 155 118 94 71.5 50 36 23

    6.0 282 185 140 112 93.5 64.5 47.5 34.5

    7.0 216 163 130 109 82 60 48

    8.0 187 149 125 94 69 55

    9.0 212 168 140 105 84 62

    10.0 245 187 156 117 93 69

    12.0 295 225 187 140 113 83

    14.0 265 218 167 132 97

    16.0 250 187 150 110

    18.0 280 210 169 124

    20.0 237 188 140

    References

    [1] Dr. Tessema, Abiy Awoke Hydraulic Ram Pump System Design and Application" ESME 5th Annual

    Conference on Manufacturing and Process Industry, September 2000

    [2] Teferi Taye, "Hydraulic Hydram Pump", Journal of the Ethiopian Society of Mechanical Engineers, Vol.

    II, No. l, July 1998.

    [3] Jeffery, T. D., "Hydraulic Hydram Pumps - A Guide to Hydram Pumps Water Supply

    System", Intermediate Technology Publications, 1992.

    [4] http://www.greenandcarter.com/

    [5] Krol, J.: The automatic hydraulic Hydram . Inst. Mechanical Engineering Proc. Vol. 165 (1951) No. 64,

    pp. 53/73.

    [6] Dnadhar, M.M and Sharma, K.N, 1979, Water Power Engineering, Vikas Publishing House Pvt. Ltd.

    India.

    [7] David, J.P. and Edward, H.W., 1985, Schaum's Outline of Theory and Problems of Fluid Mechanics and

    Hydraulics, SI (Metric) Edition, McGraw-Hill Book Company, Singapore.

  • 9

    BMEIA HYDRAM PUMP DESIGN WCDE-00088-02

    APPENDIX A Important information for Hydram pump design

    Table 1 - Range of Drive Pipe Lengths for Various Pipe Diameters

    Drive Pipe Size (mm) Length (meters)

    Minimum Maximum

    13 2 13

    20 3 20

    25 4 25

    30 4.5 30

    40 6 40

    50 7.5 50

    80 12 80

    100 15 100

    Table 2 - Range of Drive Pipe Lengths for Various Pipe Diameters

    Hydram Size 1 2 3 3.5 4 5 6

    Pipe Size (mm) 32 38 51 63.5 76 101 127

    Table 3 - Hydram Capacity by Manufacturer's Size Number

    Size of Hydram

    1 2 3 3.5 4 5X 6X 5Y 6Y

    Volume of Drive Water

    Needed (liters/min)

    7-16 12-25 27-55 45-96 68-137 136-270 180-410 136-270 180-410

    Maximum Lift (m) 150 150 120 120 120 105 105 105

    Table 4 - Sizing the Delivery Pipe

    Delivery Pipe Size (mm) Flow (litres/min)

    30 6-36

    40 37-60

    50 61-90

    80 91-234

    100 235-360

    Table 5 Daily Water Requirements

    Livestock (drinking) Gallons/animal/day

    Milking cow 25-45

    Dry cow 12-30

    Calf 6-12

    Beef animal 1.5/100 lbs. weight

    Hog 4

    Horse 10-15

    Sheep 2

    100 Chickens 4-5/100 birds

    100 Turkeys 18/100 birds

    Source: Cooperative extension Service/The University of Georgia College of Agriculture and Environmental

    Sciences/Athens