4250TEU-YZJ Seaspan Ship ManagementLocal Protection Water Mist System Machinery Space
_______________________________________________________________________
_LOCAL PROTECTION WATER MISTSYSTEM MACHINERY SPACE
LOCATION-ENGINE ROOM 3RD DECK AFT,PORT SIDE
1. This system protects local hazardous area by water mist where
fire most often occur.
2. Spaces protected by this system are:
1 MAIN ENGINE
2 AE #1 & #2
3 AE#3 & #44 BOILER
5 INCINERATOR
6 PURIFIER
-
7/28/2019 Water Mist System on ship
2/10
-
7/28/2019 Water Mist System on ship
3/10
-
7/28/2019 Water Mist System on ship
4/10
4250TEU-YZJ Seaspan Ship ManagementLocal Protection Water Mist System Machinery Space
_______________________________________________________________________
_
6. Operation of this system is controlled by the water level float
switch fitted in Distill water tank. Ensure distill water tank have
sufficient water at all times.
MANUAL RELEASE OF SYSTEM
IN CASE OF FAILURE OF AUTOMATIC RELEASE.
1. Go to FIRE CONTROL STATION OR EHQ for manual
release.
2. Change over the mode of MANUAL RELEASE PANEL from
AUTOMATIC to LOCAL by key.
3. Manually activate the starting signal for pump to START bychanging the knob of affected space from AUTOMATIC to
LOCAL.
4. This action will start the pump, opens the section valve for
affected space/spaces & water mist releases to suppress the fire.
-
7/28/2019 Water Mist System on ship
5/10
4250TEU-YZJ Seaspan Ship ManagementLocal Protection Water Mist System Machinery Space
_______________________________________________________________________
_
Note: Water mist system can alsoactivate locally at the spaceprotected.
PRESS !!!!SPRINKLER RELEASE BUTTON
-
7/28/2019 Water Mist System on ship
6/10
4250TEU-YZJ Seaspan Ship ManagementLocal Protection Water Mist System Machinery Space
_______________________________________________________________________
_
LOCAL RELEASE OF WATER MIST SYSTEMIF SYSTEM STILL FAILS TO START THE PUMP
1. Go to local pump starter panel in Engine room.
2. Change over the pump mode selection switch from
AUTOMATIC to LOCAL.
3. Pump will start, ensure the valve for the affected space/spaces
is/are open.
4. Water mist releases through sprinkler nozzles to suppress the fire
in space concerned.
-
7/28/2019 Water Mist System on ship
7/10
4250TEU-YZJ Seaspan Ship ManagementLocal Protection Water Mist System Machinery Space
_______________________________________________________________________
_
NOTE !!!!!In case of electric failure ofsection valve it can be manuallyopened by turning the markedrelease button on the solenoidvalve as shown below.
-
7/28/2019 Water Mist System on ship
8/10
4250TEU-YZJ Seaspan Ship ManagementLocal Protection Water Mist System Machinery Space
_______________________________________________________________________
_
Turn to open section valvemanually.
TESTING FOR MAINTENANCE OROPERATION CHECK DURING PORTSTATE INSPECTIONS /AUDITS
1. Testing to be done in rotation to ensure all sections are workingsatisfactorily.
2. Close all outlet valves.
3. Open all test valves.
-
7/28/2019 Water Mist System on ship
9/10
4250TEU-YZJ Seaspan Ship ManagementLocal Protection Water Mist System Machinery Space
_______________________________________________________________________
_
Outlet valves Test valves SHUT
Test valve OPEN
4. Release sections in one of following ways:
- Activate two flame detectors of the one protected space for
release.
- Activate SPRINKLER RELEASE BUTTON locally in
protected space.
- From Manual Release Panel at FCS/EHQ, manually
release one section of protected space as explained earlier.
-
7/28/2019 Water Mist System on ship
10/10
4250TEU-YZJ Seaspan Ship ManagementLocal Protection Water Mist System Machinery Space
_______________________________________________________________________
_
5. Check that pump starts, correct section valve opens, water being
discharged through drain/test valves & display on fire control
panel indicates WATER MIST SYSTEM RELEASED.
6. Reset the alarm on the FCP.
7. Check that section valve is closed & pump stopped.
8. Close test valve.
9. If required repeat test for other sections.
10.Open all outlet valves.
11. Log down all tests in Log book & NS5.
PREPARED BY : CE SUNIL JAIN