WATER 8pp 0605 cover 1 -...
-
Upload
dangkhuong -
Category
Documents
-
view
212 -
download
0
Transcript of WATER 8pp 0605 cover 1 -...
![Page 1: WATER 8pp 0605 cover 1 - TracePartstracepartsonline.net/PartsDefs/Production/BALMORAL_PDF/10-0507201… · Bracing Designed to BS 6700 to limit structure deformation WRAS approved](https://reader031.fdocuments.in/reader031/viewer/2022030409/5a8f3fb57f8b9a78648d8091/html5/thumbnails/1.jpg)
BALMORAL TANKSQuality Strength Reliability Service
GRP Sectional Water Tanks
www.balmoraltanks.com
![Page 2: WATER 8pp 0605 cover 1 - TracePartstracepartsonline.net/PartsDefs/Production/BALMORAL_PDF/10-0507201… · Bracing Designed to BS 6700 to limit structure deformation WRAS approved](https://reader031.fdocuments.in/reader031/viewer/2022030409/5a8f3fb57f8b9a78648d8091/html5/thumbnails/2.jpg)
Balmoral GroupBalmoral Group is a privately owned
company headquartered in Aberdeen,
UK. Employing over 400 people the
company has been providing solutions
to the building, chemical, energy,
engineering, marine, and plastics
sectors since 1980.
The Group comprises three distinct
business units: Balmoral Advanced
Composites; Balmoral Marine,
Balmoral Tanks, and wholly owned
international subsidiaries: Balmoral
Norge AS in Stavanger and
Kristiansund, Norway, and Balmoral
Marine Inc and Balmoral Tanks Inc in
Houston, USA.
These business units and overseas
operations function autonomously
under the auspices of their respective
managing directors while remaining
under the overall commercial and
financial control of the Group's main
board of directors.
The enterprise is built upon research,
development and technical innovation.
It is this commitment to progress that
has helped the group achieve its
status as a market leader in its
chosen sectors.
The strategy is well recognised by
Balmoral's client base: independent
surveys link attributes such as
innovation, technology, engineering
proficiency and proactiveness with
Balmoral. The Balmoral name has
become a brand in its own right,
synonymous with product
development, technical excellence and
manufacturing efficiency.
Since its formation in 1993, Balmoral
Tanks has become the world's largest
single source designer and
manufacturer of liquid storage and
treatment products. Covering the
chemical, environmental, water,
wastewater and fuel sectors, the
enterprise designs and manufactures
rotationally moulded seamless tanks,
hot press moulded GRP and steel
sectional water tanks, air pollution
control systems, cabinets and
housings.
Hot press moulded GRP sectional
tanks, in a variety of panel sizes, are
produced and used to store potable
and non-potable water on a global
basis. These tank panels are designed
for use in varying climatic conditions
and can be provided with integrated
insulation.
Hot pressed steel tanks are
designed and manufactured by
Balmoral-owned Horseley Bridge
Tanks. Established in 1880, it is the
oldest tank manufacturing company in
the world and the pioneer of bolted
sectional water tanks.
Rotationally moulded tanks
ranging from capacities of 500 to
75,000 litres are currently produced,
and it is this flexibility and
comprehensive product range that
gives Balmoral Tanks its competitive
advantage.
The vast majority of Balmoral Tanks�
products are accredited and approved
by numerous agencies: BBA; IAB; IP;
LPCB; OFTEC and WRAS to name but
a few. In gaining these accreditations
Balmoral has raised the integrity and
standards of the tank industry around
the world.
![Page 3: WATER 8pp 0605 cover 1 - TracePartstracepartsonline.net/PartsDefs/Production/BALMORAL_PDF/10-0507201… · Bracing Designed to BS 6700 to limit structure deformation WRAS approved](https://reader031.fdocuments.in/reader031/viewer/2022030409/5a8f3fb57f8b9a78648d8091/html5/thumbnails/3.jpg)
Synonymous with product development,
technical excellence and manufacturing
efficiency, innovation lies at the heart of
Balmoral Group. It drives everything
the Group does. Huge investments have
been made in research and
development over the years and the
company benefits from its own
laboratory and testing facilities.
The very latest in computer aided
design (CAD) and finite element
analysis (FEA) software is available to
the company's engineering design team
to complement the 21st century
manufacturing plant on the factory
floor. This investment has propelled
Balmoral to the peak of the hot press
and rotational moulding industries.
Design
The design of each sectional tank panel
is modelled using FEA software. This
allows fine detail to be thoroughly
investigated and improved before
proceeding to mouldmaking and
production.
Materials
All materials used in the production and
assembly of Balmoral GRP tanks are
rigorously tested for potable water
compatibility. This includes long term
material performance and mechanical
properties, non-metallic components,
adhesives, etc. Combined, these
analyses form the basis of the
company�s extensive QC procedures.
Engineering innovationManufacturing process
Balmoral sectional tank panels are hot
press moulded in glass reinforced
plastics (GRP) using isophthalic
unsaturated polyester resins and
electrical glassfibre reinforcement.
The panels are moulded at
temperatures up to 150°C under strict
quality control disciplines. The process
results in strong, consistent panels
which are fully cured, dimensionally
accurate with sharply defined profiles
and smooth surfaces on both faces.
Drilling and finishing of the panels is
undertaken in a purpose built
controlled area, where high technology
automated drilling equipment is used
to complete production to exacting
tolerance levels.
Feature Benefit
Design Designed to BS EN 13280 (2001)
Automated manufacturing Consistent product offering dimensional stability
Automated finishing Provides high levels of accuracy
High grade materials Improved resistance to bacterial growth, increased water resistance, reduced risk of osmoticattack. Colour 00-A-05 to BS 5252
UV stabilised materials Suitable for global climatic conditions
100% opacity Prevents algae growth
Heavy duty cover Low maintenance, resists wind and snow loadings. BS 6399 Pt1 (1996)
Integrated insulation Provides U value of 0.6W/m2K. CFC and HCFC free. Suitable for water storage up to 38ºC
Exclusive sealant WRAS approved, provides optimum performance under varying climatic conditions
Bracing Designed to BS 6700 to limit structure deformation
WRAS approved Tanks compliant to WRAS Section 0135, fittings compliant to Water regulation 16 (Byelaw 30) for tanks to 4m depth
QA Balmoral Group is certified to BS EN ISO 9001:2000
Thermal insulation
Balmoral Sectional Tanks uses
expanded polystyrene (EPS)
materials in its thermally insulated
panels. This is made using a pentane
expansion agent which is CFC and
HCFC free and can be recycled by
melting down and reforming.
UV stabilised skincovering the maximum
surface area of panel
HCFC free insulation
![Page 4: WATER 8pp 0605 cover 1 - TracePartstracepartsonline.net/PartsDefs/Production/BALMORAL_PDF/10-0507201… · Bracing Designed to BS 6700 to limit structure deformation WRAS approved](https://reader031.fdocuments.in/reader031/viewer/2022030409/5a8f3fb57f8b9a78648d8091/html5/thumbnails/4.jpg)
The Balmoral range of sectional GRP
tanks may be specified as either
externally flanged base (EFB) or
internally flanged base (IFB). This
allows the use of either flat continuous
foundations, close centre beams, pier
walls or bearer beams depending upon
the type of base required. The internally
built tank (IBT) to be supported as
standard on an IFB foundation.
The EFB specification is fully self
draining allowing ease of maintenance
and cleaning.
� Flexibility of panel sizes allows
connections to be agreed on site to
suit actual tank location
� Modular design provides ease of
transport and flexibility of assembly
on either a prepared flat and level
concrete foundation, support walls
or bearer beams
� Panels are rigidly supported by a
combination of stainless steel tie
rods internally and galvanised box
sections externally
� Installation is carried out by
Balmoral approved installers, fully
trained to provide total unified
responsibility
Tank construction
500mm
500mm
500mm
500mm
120mm
50mm
100mm
Nominal height
Nominal width
80mm
500mm
500mm
EFB Externally flanged base, externally flanged sides
IFB Internally flanged base, externally flanged sides
IBT Internally flanged base, internally flanged sides
All installations require a clearanceof 500mm above manway. Aminimum clearance of 350mm isrequired above the tank to complywith water regulations.
For M100 tank built with 1x1m panels
Height up to 1m add 80mm for flanges
Height up to 2m add 80mm for flangesadd 80mm for galvanised box sectionsadd 50mm for tie rod brackets
Height from 2 to 4m add 80mm for flangesadd 60mm for galvanised box sectionsadd 50mm for tie rod brackets
For M100 tank built with 1.5x1m and 2x1m panels
Height up to 2m add 80mm for flangesadd 100mm for galvanised box sectionsadd 50mm for tie rod brackets
= 210mm over the internal dimensions for each side
= 190mm over the internal dimensions for each side
= 230mm over the internal dimensions for each side
= 80mm over the internal dimensions for each side
Box section
Tie rod bracket
External plan sizes
Flange types
Flange detail
Clearance requirements
350mm minimum
Access tofloat valve
Access forinspection
500mm minimum
Option 1 - Flat foundationFor IFB and IBT tanks. Flat screenconcrete foundation to be level and notvary more than 2mm in any one metre,measured laterally or diagonally.
Ground level
End spans 1020mm
Internal spans 1000mm
348mmmin
152mm
150mm102mm
maxGround level
150mm
500mmmin
381mmmin
500mm centres
150mm
150mm
Option 2 - Close centre beamsIFB and IBT tanks may also besupported by steel bearer beams.
Option 3 - Pier wallsFor EFB tanks allowing self drain. 1mcentres required.
Base support
� 500mm required underneath the EFB tank for installation� Health and Technical Memorandum (HTM2027) stipulates self draining base for EFB tanks� Water regulations now state that where practicably possible, outlets should be taken from tank base, ie, EFB tank
![Page 5: WATER 8pp 0605 cover 1 - TracePartstracepartsonline.net/PartsDefs/Production/BALMORAL_PDF/10-0507201… · Bracing Designed to BS 6700 to limit structure deformation WRAS approved](https://reader031.fdocuments.in/reader031/viewer/2022030409/5a8f3fb57f8b9a78648d8091/html5/thumbnails/5.jpg)
Brace wherenecessary forheavy guardsshaped to circle
Optional guards
6000
mm
max
. be
twee
n to
p of
tan
k or
pla
tfor
ms
900m
m m
ax.
2500
mm
fro
m g
roun
d
Source: BS 4211
2
4
3
5
6
7
89
101213
14
16
17
18
19
20
21
15
11
1
Description
Fixed ladderTypical arrangement of a fixed ladderaccording to BS 4211
1 Handrailing and supports
2 Screened air vent
3 Profiled heavy duty cover designed to BS 6399 Pt1 1984
4 A4 stainless steel internal fasteners and fixings
5 Float valve chamber (type AB and AF air gaps available for compliance with Byelaw 11)
6 Hinged or mechanically fixed man access
7 uPVC tubular roof support struts
8 GRP or stainless steel internal ladder
9 Connections supplied to customer requirements
10 Hot press moulded GRP panels BS EN 13280 (2001)
11 1.5 x 1m hot press moulded panel
12 316 Grade stainless steel internal tie rods
13 316 Grade stainless steel partition supports
14 Partition panels
15 2 x 1m hot press moulded panel
16 Hot press moulded GRP corner section
17 Tank supported on a flat and level foundation or pier walls or bearer beams (pier walls shown)
18 Aluminium or galvanised steel external ladder
19 Galvanised or stainless steel external fasteners and fixings
20 Galvanised steel external bracing
21 WRAS approved BALSEAL sealing strip
![Page 6: WATER 8pp 0605 cover 1 - TracePartstracepartsonline.net/PartsDefs/Production/BALMORAL_PDF/10-0507201… · Bracing Designed to BS 6700 to limit structure deformation WRAS approved](https://reader031.fdocuments.in/reader031/viewer/2022030409/5a8f3fb57f8b9a78648d8091/html5/thumbnails/6.jpg)
Balmoral M100 and M100-B30 sectional tanks
are Loss Prevention Certification Board (LPCB)
approved for fire fighting sprinkler systems.
� Sprinkler systems must comply with
BS 5306 Part 2: 1990
� A type AB air gap is required unless
connected to a dedicated water supply
� Internal ladders should be stainless steel.
External ladders compliant with BS 4211
� Water level indication is required on sprinkler
tanks
� The water in sprinkler tanks tends to be
inactive for long periods of time. Immersion
heaters or other means of preventing
freezing may be required
� In the event of a fire, large quantities of
continuous flow are required. If a vortex
inhibitor is fitted, the volume of water that
can be drawn from the tank is increased
without the inclusion of air or a reduction
in the flow rate. There are two main types
of vortex inhibitor: positive head and
suction lift
Fire fighting sprinkler systemsHigh water level
Low water level
X
Y
High water level
Low water level
X
Y
IFB 32 to 10� suction lift (Eurostan fitting)
EFB suction lift (Eurostan fitting)
Nominal bore (mm)
X (mm) Y (mm)
80 (3�) 90 140
100 (4�) 100 185
150 (6�) 120 275
200 (8�) 150 365
250 (10�) 170 455
Nominal bore (mm)
X (mm) Y (mm)
80 (3�) 160 140
100 (4�) 160 185
150 (6�) 190 275
200 (8�) 220 365
250 (10�) 240 455
300 (12�) 280 555
High water level
Low water level
X
Y
EFB positive suction head (Champion fitting close coupled)
Nominal bore (mm)
X (mm) Y (mm)
80 (3�) 160 140
100 (4�) 170 185
150 (6�) 190 275
200 (8�) 215 365
250 (8�) 240 455
300 (10�) 265 555
![Page 7: WATER 8pp 0605 cover 1 - TracePartstracepartsonline.net/PartsDefs/Production/BALMORAL_PDF/10-0507201… · Bracing Designed to BS 6700 to limit structure deformation WRAS approved](https://reader031.fdocuments.in/reader031/viewer/2022030409/5a8f3fb57f8b9a78648d8091/html5/thumbnails/7.jpg)
Recognising today�s requirement for
rapid and accurate enquiry responses,
Balmoral Tanks has committed
significant investment to its IT
resource. Coupled with this is a
determination to assist clients in their
day-to-day tasks through the strategic
use of the company�s website as a
working business tool.
Balmoral Sectional Tanks offers the
following online services:
� Enquiry submission
� Current product information
� Technical detail
� Tank selection: Guidance on
capacities and overall dimensions
� Documentation: Base drawings;
operation and maintenance
manuals
� Case studies
� Industry standards and water
regulations
A dedicated web team
operates at the
Aberdeen HQ on a
programme of continuous
improvement. Visit
www.balmoraltanks.com to see how
you can benefit by using our electronic
communication procedures.
Customer communication
Tank replacementBalmoral Tanks provides a complete tank replacement service and has
completed a significant number of full service projects in recent years.
Acting as main contractors, Balmoral Tanks is supported by in-house
health and safety, design and contract management while also
providing guidance on ACOP L8 and CDM.
Turnkey project design and installation service
� Secondary base steel design and installation
� Tank design (ISO9001) and installation
� Tank removal and responsible disposal
� Establishment of temporary supply
� Pipework re-routing
� Updating/replacement of valve systems
� Health and Safety and CDM experience
� ACOP L8
![Page 8: WATER 8pp 0605 cover 1 - TracePartstracepartsonline.net/PartsDefs/Production/BALMORAL_PDF/10-0507201… · Bracing Designed to BS 6700 to limit structure deformation WRAS approved](https://reader031.fdocuments.in/reader031/viewer/2022030409/5a8f3fb57f8b9a78648d8091/html5/thumbnails/8.jpg)
© 2005 Balmoral Group Ltd. All rights reserved. This publication is protected by copyright. No part of it may be reproduced, stored in a retrieval system, or transmitted, in any form, by any means, electronic,mechanical, photocopying, recording or otherwise, without the prior written permission of the copyright owners. Balmoral Group Ltd believe that the information printed in this brochure is accurate, and published for information only. No warrants,express or implied, are contained therein, nor does any legal liability attach to Balmoral Group Ltd for any reason whatsoever. The company�s policy is one of continuous product improvement and we reserve the right to make alterations to our rangeand specification without prior notice.Designed and produced by Balmoral Group Public Relations/Graphic Design department 02-WAT-0705 DOC REV A
Balmoral Group Ltd
¤¤
BALMORAL TANKSA division of Balmoral Group
Sales office & depotUnit 2, Coomber Way Ind Est, Croydon, Surrey CR0 4TQTel: +44 (0)208 665 4100 Fax: +44 (0)208 665 0200 Email: [email protected] www.balmoraltanks.com
GRP one-piece tanks
ModelInternal dimensions External dimensions
Length Width Height Length Width Height
Nominal volume
Litres Gallons
Balmoral one-piece tanks are manufactured to BS 13280:2001
standard using high quality glass reinforced polyester (GRP)
resins. The tanks comply with UK Water Supply Regulations
1999 and have been tested and approved by WRAS.
The suffix �LP� denotes a low profile tank while �I� denotes an insulated product
BOP50-I 737 559 559 812 634 569 230 50
BOP70-I 910 610 585 985 685 595 320 70
BOP70LP-I 1524 457 457 1599 532 467 320 70
BOP100-I 965 686 686 1040 761 696 454 100
BOP100LP-I 1220 610 610 1295 685 625 454 100
BOP110LP-I 1000 1000 500 1075 1075 510 500 110
BOP125-I 965 762 787 1040 837 797 570 125
BOP150-I 1092 864 737 1167 939 747 681 150
BOP200-I 1168 889 889 1243 964 899 910 200
BOP220-I 1000 1000 1000 1075 1075 1010 1000 220
BOP220LP-I 2000 1000 500 2150 1150 510 1000 220
BOP250-I 1524 914 813 1674 1064 823 1140 250
BOP300-I 1827 914 813 1977 1064 823 1370 300
BOP350-I 1524 1143 914 1674 1293 924 1590 350
BOP400-I 1219 1219 1219 1369 1369 1279 1820 400
BOP500-I 1524 1219 1219 1674 1369 1279 2280 500
BOP500LP-I 1829 1219 1022 1979 1369 1082 2280 500
BOP600-I 1829 1219 1219 1979 1369 1279 2730 600
BOP800-I 2438 1219 1219 2588 1369 1279 3640 800
BOP880-I 2000 1340 1500 2172 1514 1530 4020 880
BOP900-I 2000 1500 1500 2150 1650 1530 4500 900
BOP1000-I 2438 1524 1219 2588 1674 1279 4550 1000