C O N S U L T A N C Y T E S T I N G
TESTING AUTHORITY 2007 Warrington Fire Research Aust Pty Ltd.Unit 2, 409 - 411 Hammond Road, Dandenong, Victoria 3175, P.O. Box 4282, Dandenong South, Victoria 3164, Australia.
Tel: Int+61 (0)3 9767 1066 Fax: Int+61 (0)3 9767 1001 or (0)3 9767 1051 Email: [email protected],Home Page: www.wfra.com.au A.B.N. 81 050 241 524
Warrington Fire Research Australia New Zealand United Kingdom Singapore China
WFRA Report No 2208900Issue Number 2208900a.1
Page 1 of 37
TEST DESCRIPTION
FIRE RESISTANCE TEST OF TWOSINGLE LEAF DOORSETS IN GENERALACCORDANCE WITH BS 476:PARTS 20 & 22: 1987
TEST APPLICANT
Danube GroupJebel AliUNITED ARAB EMIRATES
TEST DATE26th October 2007
-
8/14/2019 Warring Ton 30 Mts.unlocked
2/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 2 of 37
DOCUMENT REVISION STATUS
Date Issued Issue No Description
7th November 2007 2208900a.1 Initial Issue
SIGNATORIES
Prepared by: Reviewed by:
A. F. Rayner K. G. Nicholls
On behalf of Warrington Fire Research (Aust) Pty Ltd
GENERAL CONDITIONS OF USE
This report may only be reproduced in full without modifications by the
report applicant only. Copies, extracts or abridgments of this report in anyform shall not be made distributed or published by other organisationsor individuals without the permission in writing from a Director ofWarrington Fire Research (Aust) Pty Ltd.
-
8/14/2019 Warring Ton 30 Mts.unlocked
3/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 3 of 37
CONTENTS
1 CONSTRUCTION DETAILS 4Test Assembly 4Test Specimen 4Assembly and Installation Methods 4Orientation 4
2 SCHEDULE OF COMPONENTS 53 TEST PROCEDURE 8
Statement of compliance 8Variations from test standards 8
Pre-test conditioning 8Sampling / Specimen Selection 8Ambient Temperature 8Test Duration 9Instrumentation and Equipment 9
4 TEST MEASUREMENTS 10Furnace Temperature and Pressure Measurements 10Specimen Temperatures 10Deflection Measurements 10Heat flux Measurement 10Observations 10
5 TEST RESULTS 116 APPLICATION OF TEST RESULTS 12
Test Limitations 12Variations from the Tested Specimens 12Uncertainty of measurement 12
APPENDIX 1DRAWINGS OF TEST ASSEMBLY 13APPENDIX 2TEST OBSERVATIONS 19APPENDIX 3 INSTRUMENTATION POSITIONS 22APPENDIX 4TEST DATA 26
A 4.1 Furnace Temperature 26A 4.2 Furnace Pressure 26A 4.3 Specimen Temperatures 27A 4.4 Deflection Measurements 33A 4.5 Heat Flux Measurement 34
APPENDIX 5PHOTOGRAPHS 35
-
8/14/2019 Warring Ton 30 Mts.unlocked
4/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 4 of 37
1 CONSTRUCTION DETAILS
TEST ASSEMBLY
The test assembly comprised a nominal 3200mm x 3200mm x 110mm thickcored concrete block wall incorporating two single leaf particle board coredoorsets.
TEST SPECIMEN
The test specimens comprised two single leaf particle board core doorsetsreferred to as Door A and Door B for the purposes of this test report. Furtherdetails are provided in Figures A1.1 to A1.6 and the schedule of components
Section 2.
ASSEMBLY AND INSTALLATION METHODS
The cored concrete block wall was built into a steel restraint frame, incorporatingopenings for the doorsets, by a building contractor at WFRA Melbournecommencing on the 19th October 2007 and under the supervision of a WFRArepresentative. The test applicant supplied and installed the single leaf doorsets(including leafs, frames and all door hardware) commencing on the24th October 2007 and under the supervision of a WFRA representative.
ORIENTATION
The specimen was installed with Door A swinging towards the furnace andDoor B swinging away from the furnace.
-
8/14/2019 Warring Ton 30 Mts.unlocked
5/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 5 of 37
2 SCHEDULE OF COMPONENTS
ITEM DESCRIPTION
DOOR A
Leaf Size 2350mm high x 1000mm wide x 44mm (nominal) thick door leaf.
Leaf Core The leaf core was stated by the test sponsor to be nominally 44mm thickand designated as DANUBE KINGSA Core supplied by DANUBE.
KINGSA, as stated by the test sponsor, is a particleboard material andhas a nominal dry density of 580kg/m3.
Leaf edging 8mm thick (nominal) beech hardwood.
Reinforcementplates
Nil.
Leaf Facing Nil.
Leaf Seals Lorient IS8010si threshold seal was rebated into the centre of the doorleaf bottom edge.
Hinges 100mm x 75mm x 3mm hinges with 4-off screw fixings through eachplate to the door leaf and door frame. The hinges were fitted to the lefthand side of the door leaf (looking from the unexposed side) with thedoor swinging towards the furnace. Hinge areas were additionallyprotected with Lorient Intumescent Hinge Protection Kit, refer Figure
A1.6.
Hinge Locations There were 3 hinges positioned at 975mm centres with the lowest hingepositioned 210mm from the sill to the centre of the hinge.
Frame The solid timber door frame was 90mm wide x 45mm thick with a doorseat rebate of 20mm deep x 46mm wide. The frame was made fromEuropean beech hardwood of a nominal density of 600 kg/m3. Theframes were joined with a mitred and tennon joint that was glued andscrewed into position.
Frame Seals Lorient LP1504DS (Type 617) Intumescent Fire and Smoke Seals, asstated by the test sponsor, were rebated within the perimeter of the frame
and extended past hinges.Fixings The timber frame was secured to the opening in the masonry wall with
11-off (5-off per vertical side and 1-off in the head) No 10 x 100mm longsocket head screws into plastic plugs, as stated by the test sponsor, atmaximum spacing 765mm and 125mm from either end.
Lockset Dorma 515 Mortice lock (cylinder mortice lock) with striker centrallylocated nominally 1035mm from the sill and a backset of nominally60mm. The lever handles (Gainsborough generic) were to theunexposed and exposed sides. The latch throw was nominally 10mm.Mortice lockset was additionally protected with Lorient Intumescent LockProtection Kit, refer Figure A1.6.
Closer DORMA TS73V fitted to exposed side of the doorset.
-
8/14/2019 Warring Ton 30 Mts.unlocked
6/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 6 of 37
ITEM DESCRIPTION
DOOR B
Leaf Size 2350mm high x 1000mm wide x 44mm (nominal) thick door leaf.
Leaf Core The leaf core was stated by the test sponsor to be nominally 44mm thickand designated as DANUBE KINGSA Core supplied by DANUBE.
KINGSA, as stated by the test sponsor, is a particleboard material andhas a nominal dry density of 580kg/m3.
Leaf edging 8mm thick (nominal) beech hardwood.
Reinforcement
plates
Nil.
Leaf Facing Nil.
Leaf Seals Lorient IS8010si threshold seal was rebated into the centre of the doorleaf bottom edge.
Hinges 100mm x 75mm x 3mm hinges with 4-off screw fixings through eachplate to the door leaf and door frame. The hinges were fitted to the lefthand side of the door leaf (looking from the unexposed side) with thedoor swinging away from the furnace. Hinge areas were additionallyprotected with Lorient Intumescent Hinge Protection Kits, refer FigureA1.6.
Hinge Locations There were 3 hinges positioned at 975mm centres with the lowest hingepositioned 210mm from the sill to the centre of the hinge.
Frame The solid timber door frame was 90mm wide x 45mm thick with a doorseat rebate of 46mm wide x 20mm deep. The frame was made fromEuropean beech hardwood of a nominal density of 600 kg/m3. Theframes were joined with a mitred and tennon joint that was glued andscrewed into position.
Frame Seals Lorient LP1504DS (Type 617) Intumescent Fire and Smoke Seals, asstated by the test sponsor, were rebated within the perimeter of the frameand extended past hinges.
Fixings The timber frame was secured to the opening in the masonry wall with11-off (5-off per vertical side and 1-off in the head) No 10 x 100mm longsocket head screws into plastic plugs, as stated by the test sponsor, atmaximum spacing 765mm and 125mm from either end.
Lockset Dorma 515 Mortice lock (cylinder mortice lock) with striker centrallylocated nominally 1035mm from the sill and a backset of nominally60mm. The lever handles (Gainsborough generic) were to theunexposed and exposed sides. The latch throw was nominally 10mm.Mortice lockset was additionally protected with Lorient Intumescent LockProtection Kit, refer Figure A1.6.
Closer DORMA TS73V fitted to unexposed side of the doorset.
-
8/14/2019 Warring Ton 30 Mts.unlocked
7/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 7 of 37
ITEM DESCRIPTION
Supporting Construction
Description 110mm thick cored concrete block wall.
Door Sill One course of solid concrete blocks 10.31s 390mm x 190mm x 90mmwith three courses of concrete bricks 230mm x 110mm x 75mm abovewith the top course laid perpendicular to the wall to form a sill for thedoorsets.
Blocks above sill Twelve courses of cored concrete blocks were laid on the sill to form theopenings and an additional three courses were laid above the openingsincluding one lintel beam course which included a single D16
reinforcement rod with premixed concrete filling the void.
Sealant Lorient intumescent mastic was used to seal the gap (backed byRockwool on the RH side and top as gap between 15-20mm) betweenthe edge of the door frames and the opening in the concrete block wallon both sides.
-
8/14/2019 Warring Ton 30 Mts.unlocked
8/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 8 of 37
3 TEST PROCEDURE
STATEMENT OF COMPLIANCE
The test was performed in general accordance with the requirements ofBS 476: Part 20: 1987 and BS 476: Part 22: 1987 Part 6 as appropriate forinsulated doorsets, other than the variations stated below.
VARIATIONS FROM TEST STANDARDS
The furnace temperature was measured by 6-off mineral insulated metalsheathed Type K thermocouples with wire diameters not greater than 1mm andoverall diameter of 3mm with the measuring junction insulated from the sheath.
The thermocouples protruded a minimum of 25mm from steel supporting tubes.
BS 476: Part 20: 1987 specifies the furnace temperature to be measured by 6-offNickel chromium/nickel aluminium wire contained within a mineral insulation andin a heat resisting steel sheet of diameter 1.5mm, the hot junctions beingelectrically insulated from the sheath. The thermocouple hot junction shallproject 25mm from a porcelain insulator.
This variation, is considered to make the test slightly more onerous, howeverwould not have significantly affected the results of the fire-resistance test.
The furnace pressure varied more than as prescribed by BS 476: Part 22: 1987
during the period of 5-15 minutes test duration but was above that prescribed(maximum pressure level variation +2 Pa). It is considered that the test pressurehas created a more severe exposure than if tested in full accordanceBS 476: Part 22: 1987.
PRE-TEST CONDITIONING
The specimen was stored in the test laboratory prior to testing and was subjectedto indoor ambient normal laboratory conditions for approximately two days (afterwall completion) prior to testing.
SAMPLING / SPECIMEN SELECTION
The laboratory was not involved in the selection of the test specimen for test.
AMBIENT TEMPERATURE
The ambient temperature at the start of the test was 20C and remained at thisuntil the end of the test.
-
8/14/2019 Warring Ton 30 Mts.unlocked
9/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 9 of 37
TEST DURATION
The test was terminated after approximately 42 minutes at the request of the testsponsor.
INSTRUMENTATION AND EQUIPMENT
The instrumentation was provided in accordance with BS 476: Part 22: 1987except for the furnace control thermocouples as mentioned above.
The furnace temperature was measured by 6-off mineral insulated metalsheathed Type K thermocouples with wire diameters not greater than 1mm andoverall diameter of 3mm with the measuring junction insulated from the sheath.The thermocouples protruded a minimum of 25mm from steel supporting tubes.
The non fire side specimen temperatures were measured by Type Kthermocouples with wire diameters less than 0.5mm diameter soldered to 12mmdiameter 0.2mm thick copper discs covered by a 30mm 30mm 2.0 mminorganic insulating pads. The thermocouples positions are described in TableA3.1, and are shown on Figure A3.1 in Appendix 3. A roving thermocouple wasavailable to measure temperatures at positions that appear hotter than thepositions monitored by fixed thermocouples.
Deflection measurements were taken from calibrated tapes, fixed to the testspecimen, using a Telescope Levelling Instrument (Dumpy Level) Model 200B, atthe positions shown on Figure A3.2 in Appendix 3.
The furnace pressure was measured approximately 1000mm above sill level.
Cotton pads and gap gauges were available during the test to assess theperformance under the criteria for integrity up to unexposed face temperatures of300C for both Doorsets. After that time gap gauges only were available toassess the performance under the criteria for integrity.
-
8/14/2019 Warring Ton 30 Mts.unlocked
10/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 10 of 37
4 TEST MEASUREMENTS
FURNACE TEMPERATURE AND PRESSURE MEASUREMENTS
Furnace temperature and pressure data are provided in A4.1 and A4.2 inAppendix 4.1.
SPECIMEN TEMPERATURES
Specimen temperature data is provided in A4.3 and Table A4.1 in Appendix 4.
DEFLECTION MEASUREMENTS
Deflection measurement data is provided in A4.4 in Appendix 4.
HEAT FLUX MEASUREMENT
Heat Flux measurements are provided in A4.5 in Appendix 4.
OBSERVATIONS
A table that includes observations of the significant behaviour of the specimenand details of the occurrence of the various performance criteria specified inBS 476: Part 22: 1987 is provided in Appendix 2. Photographs of the specimen
are included in Appendix 5.
-
8/14/2019 Warring Ton 30 Mts.unlocked
11/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 11 of 37
5 TEST RESULTS
The specimen achieved the following performance when tested in generalaccordance with BS 476: Part 22: 1987 Section 6 as appropriate.
DOOR A
Loadbearing Capacity Not applicable
Integrity
36 minutes
Failure by sustained flaming by virtue of flameson unexposed side at bottom RH corner of door.
Insulation36 minutes
Insulation failure deemed to occur at time ofintegrity failure.
DOOR B
Loadbearing Capacity Not applicable
Integrity
41 minutes
Failure by sustained flaming by virtue of flameson unexposed side at bottom of door.
Insulation
41 minutes
Insulation failure deemed to occur at time ofintegrity failure.
-
8/14/2019 Warring Ton 30 Mts.unlocked
12/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 12 of 37
6 APPLICATION OF TEST RESULTS
TEST LIMITATIONS
The results of this fire test may be used to directly assess fire hazard, but itshould be recognized that a single test method will not provide a full assessmentof fire hazard under all fire conditions. The results only relate to the behaviour ofthe specimen of the element of the construction under the particular conditions ofthe test; they are not intended to be the sole criteria for assessing the potentialfire performance of the element in use nor do they necessarily reflect the actualbehaviour in fires.
VARIATIONS FROM THE TESTED SPECIMENSThis report details the methods of construction, the test conditions and the resultsobtained when the specific element of construction described herein was testedfollowing the procedure outlined in BS 476: Parts 20 & 22: 1987. Any significantvariation with respect to size, constructional details, loads, stresses, edge or endconditions, other than those allowed under the field of direct application in therelevant test method, is not addressed by this report. It is recommended that anyproposed variation to the tested configuration should be referred to the testsponsor in the first instance to obtain appropriate documentary evidence ofcompliance from Warrington Fire Research or another Registered TestingAuthority.
UNCERTAINTY OF MEASUREMENT
Because of the nature of fire resistance testing and the consequent difficulty inquantifying the uncertainty of measurement of fire resistance, it is not possible toprovide a stated degree of accuracy of the result.
-
8/14/2019 Warring Ton 30 Mts.unlocked
13/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 13 of 37
APPENDIX 1 DRAWINGS OF TEST ASSEMBLY
UNEXPOSED FACE ELEVATION
OPENINGS FOR DOORSETS WITHIN MASONRY WALL
Figure A1.1: Test Assembly Drawing
-
8/14/2019 Warring Ton 30 Mts.unlocked
14/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 14 of 37
UNEXPOSED FACE ELEVATION
DOORSET INSTALLATION
Figure A1.2: Door Frame Fixing Locations
-
8/14/2019 Warring Ton 30 Mts.unlocked
15/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 15 of 37
Figure A1.3: Doorset Constructional Drawing (Provided By Client)
-
8/14/2019 Warring Ton 30 Mts.unlocked
16/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 16 of 37
Figure A1.4: Doorset Frame & Leaf Sectional Drawing (Provided By Client)
-
8/14/2019 Warring Ton 30 Mts.unlocked
17/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 17 of 37
Figure A1.5: Doorset bottom Sectional Drawing (Provided By Client)
-
8/14/2019 Warring Ton 30 Mts.unlocked
18/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 18 of 37
Figure A1.6: Lorient Intumescent Kit (Provided By Client)
-
8/14/2019 Warring Ton 30 Mts.unlocked
19/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 19 of 37
APPENDIX 2 TEST OBSERVATIONS
Time
Min SecObservation
DOOR A
0 00 Fire Resistance Test was commenced and ambient air temperaturewas approximately 20C.
2 03 Smoke emission was evident from the latchset of the doorset.
2 15 Smoke emission had ceased.
3 45 Smoke emission was evident from all edges of the doorset.
4 38 Smoke emission was evident from all edges of the doorset.
3 52 Smoke emission from the doorset had ceased.
7 09 Smoke emission had reduced with emission evident from the top halfof the hinge side.
10 47 Smoke emission was evident from the top RH corner of the doorsetand middle hinge location.
13 40 Smoke emission was evident from the perimeter of the doorset.
13 58 Small amount of smoke emission evident from perimeter with somesmoke emission from wall door jamb interface.
15 10 Puffs of smoke were evident from under each doorset, stoppedalmost immediately.
22 00 Small amount of smoke emission evident from wall door jambinterface.
30 00 Doorset continued to maintain integrity in accordance withBS 476: Part 22: 1987.
30 34 Small amount of smoke emission evident from top LH corner ofdoorset.
35 06 Intermittent flaming evident on bottom edge of doorset.
36 25 Flaming of unexposed face of doorset was initiated at bottom RH
corner of door leaf.
36 35Sustained flaming of specimen continued for a period of notless than 10 seconds. Integrity failure of Door A in accordancewith BS 476: Part 22: 1987. Flaming was extinguished.
38 04 Sustained flaming of specimen continued for a period of not lessthan 10 seconds at latchset. Flaming was extinguished.
38 57 Sustained flaming of specimen continued for a period of not lessthan 10 seconds at latchset. Flaming was extinguished.
42 24 Fire resistance test was terminated at the request of the testsponsor.
-
8/14/2019 Warring Ton 30 Mts.unlocked
20/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 20 of 37
Time
Min Sec
Observation
DOOR B
0 00 Fire Resistance Test was commenced and ambient air temperaturewas approximately 19C.
1 41 Smoke emission was evident from the top RH corner of the doorset.
3 25 There was an increase in the amount of smoke emission.
3 45 Smoke emission was evident from all edges of the doorset.
4 09 Smoke emission was evident only from the top RH corner of thedoorset.
5 45 Smoke emission had dramatically reduced with emission evidentfrom the top of the doorset only.
6 21 Cotton pad was applied to the top RH corner of the doorset for aperiod of approximately 15 seconds and no discolouration wasevident.
10 12 Smoke emission was evident from top RH corner of doorset andbelow top hinge.
13 19There was a reduction in the amount of smoke emission from the topRH corner of the doorset.
14 50
Smoke emission was evident from top RH corner of doorset, below
top hinge and around middle hinge.
18 32There was a slight increase in the amount of smoke emission fromthe top hinge and top RH corner of doorset.
20 05 Smoke emission evident from middle hinge location.
25 19 Possible charring of door jamb near top hinge location was evident.
26 19Cotton pad was applied to the top hinge location of the doorset for aperiod of approximately 15 seconds and no discolouration wasevident.
28 04 Discolouration of door jamb near middle hinge location was evident.
30 00 Doorset continued to maintain integrity in accordance withBS 476: Part 22: 1987.
31 09Intermittent flaming on unexposed side evident at bottom LH side ofdoorset.
31 31Cotton pad was applied to the top RH corner of the doorset for aperiod of approximately 15 seconds and no discolouration wasevident.
32 13Glowing of frame behind leaf was evident at bottom RH corner ofdoorset.
32 47Cotton pad was applied to the bottom RH corner of the doorset for aperiod of approximately 15 seconds and no discolouration was
evident.
-
8/14/2019 Warring Ton 30 Mts.unlocked
21/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 21 of 37
Time
Min Sec
Observation
33 30Intermittent flaming on unexposed side evident at bottom LH side ofdoorset.
34 15Intermittent flaming on unexposed side evident at bottom LH side ofdoorset.
34 20 Intermittent flaming on exposed side evident at bottom of doorset.
35 47Cotton pad was applied to the top RH corner of the doorset for aperiod of approximately 15 seconds and no discolouration wasevident.
40 25 Glowing of bottom timber edge strip was evident
41 07 Glowing embers had fallen from doorset.
41 19Flaming of unexposed face of doorset was initiated at bottom RHcorner of door leaf.
41 29Sustained flaming of specimen continued for a period of notless than 10 seconds. Integrity failure of Door A in accordancewith BS 476: Part 22: 1987. Flaming was extinguished.
42 24 Fire resistance test was terminated at the request of the testsponsor.
The above observations include observations of the significant behaviour of the specimen.
-
8/14/2019 Warring Ton 30 Mts.unlocked
22/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 22 of 37
APPENDIX 3 INSTRUMENTATION POSITIONS
Figure A3.1: Thermocouple Locations
Table A3.1: Thermocouple LocationsLeaf A Leaf B
Location LocationT/C
X yDescription T/C
x yDescription
B1 287 1775 Upper west quarter point. C1 280 1770 Upper west quarter point.B2 770 1775 Upper east quarter point. C2 780 1770 Upper east quarter point.B3 528 1170 Midpoint. C3 530 1180 Midpoint.B4 287 585 Lower west quarter point. C4 280 590 Lower west quarter point.B5 770 585 Lower east quarter point. C5 780 590 Lower east quarter point.B6 960 2287 Top east corner 50mm
from edges of leaf.C6 980 2302 Top east corner 50mm
from edges of leaf.B7 960 50 Bottom east corner
50mm from edges ofleaf.
C7 980 50Bottom east corner 50mmfrom edges of leaf.
B8 895 1005 50mm west of latch. C8 895 1005 50mm west of latch.B9 970 1080 50mm above latch. C9 970 1080 50mm above latch.
A11 100 2302 Behind closerA12 262 2232 50mm below closer
Door frame A Door frame B
B10 22 1190 West midpoint C10 22 1190 West midpointB11 530 2360 Top midpoint C11 530 2360 Top midpointB12 1038 1190 East midpoint C12 1038 1190 East midpoint
B1 B2
B3
B4
B5
B7
B9
B8
B6
B10
B11
B12
C1 C2
C3
C4
C5
C7
C9
C6
C10
C11
C12
C8
A11
A12
-
8/14/2019 Warring Ton 30 Mts.unlocked
23/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 23 of 37
Figure A3.2: Deflection measurement Locations
Table A3.2: Deflection LocationsDoorset A Doorset B
Location LocationT/C
X yDescription T/C
x yDescription
DA1 945 2272 Upper east corner ofleaf.
DB1 960 1967 Upper east corner ofleaf.
DAF1 1038 2207 Upper east corner offrame.
DBF1 1038 2017 Upper east corner offrame.
DAC 528 1190 Midpoint. DBC 528 1190 Midpoint.DA2 945 100 Lower east corner of
leaf.DB2 960 70 Lower east corner of
leaf.
DAF2 1038 70 Lower east corner offrame.
DBF2 1038 110 Lower east corner offrame.
DA1
DAC
DA2 DAF2
DAF1
DB1
DBC
DB2
DBF2
DBF1
-
8/14/2019 Warring Ton 30 Mts.unlocked
24/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 24 of 37
DOOR A EXPOSED FACE ELEVATION
Figure A3.3: Doorset A Clearance measurements
-
8/14/2019 Warring Ton 30 Mts.unlocked
25/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 25 of 37
DOOR B UNEXPOSED FACE ELEVATION
Figure A3.4: Doorset B Clearance measurements
-
8/14/2019 Warring Ton 30 Mts.unlocked
26/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 26 of 37
APPENDIX 4 TEST DATA
A 4.1 FURNACE TEMPERATURE
0
200
400
600
800
1000
1200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temp
erature(C)
BS 476: Part 20: 1987 Mean Furn Max Furn Min Furn
Figure A4.1: Furnace Temperatures vs. Time.
A 4.2 FURNACE PRESSURE
Note: Furnace pressure was measured at a position approximately 1000mmabove sill level.
Time
(mins)
Pressure (Pa)
Average
Time
(mins)
Pressure (Pa)
Average
5-10 5 25-30 -1
10-15 5 30-35 -1
15-20 3 35-40 0
20-25 2 40-45 0
-
8/14/2019 Warring Ton 30 Mts.unlocked
27/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 27 of 37
A 4.3 SPECIMEN TEMPERATURES
0
2040
60
80
100
120
140
160
180
200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temperature(C)
B1 B2 B3 B4 B5 Integrity Limit
Figure A4.2: Door A Quarter point Temperatures vs. Time
0
20
40
60
80
100
120
140
160
180
200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temperature(C)
Average Integrity Limit
Figure A4.3: Average of Door A Quarter point Temperatures(B1 up to and including B5) vs. Time
-
8/14/2019 Warring Ton 30 Mts.unlocked
28/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 28 of 37
0
20
40
60
80
100
120
140
160
180200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temperature(C)
B6 B7 B8 B9 Integrity Limit
Figure A4.4: Door A Miscellaneous Temperatures vs. Time
0
20
40
60
80
100
120
140
160
180
200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temperature(C)
B10 B11 B12 Integrity Limit
Figure A4.5: Door A Doorframe Temperatures vs. Time
-
8/14/2019 Warring Ton 30 Mts.unlocked
29/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 29 of 37
0
20
40
60
80
100
120
140
160
180200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temperature(C)
C1 C2 C3 C4 C5 Integrity Limit
Figure A4.6: Door B Quarter point Temperatures vs. Time
0
20
40
60
80
100
120
140
160180
200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temperature(C)
Average Integrity Limit
Figure A4.7: Average of Door B Quarter point Temperatures(C1 up to and including C5) vs. Time
-
8/14/2019 Warring Ton 30 Mts.unlocked
30/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 30 of 37
0
20
40
60
80
100
120
140
160
180200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temperature(C)
A11 A12 C6 C7
C8 C9 Integrity Limit
Figure A4.8: Door B Miscellaneous Temperatures vs. Time
0
20
40
60
80
100
120
140
160
180
200
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Temperature(C)
B10 B11 B12 Integrity Limit
Figure A4.9: Door B Doorframe Temperatures vs. Time
-
8/14/2019 Warring Ton 30 Mts.unlocked
31/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 31 of 37
Table A4.1: Test Specimen Temperatures
Temp (C) at t (minutes)Element T/C No. Description3
t=0 t=15 t=30 t=36
Limit1,2
(Mins)
Doorset A (Eastern Doorset)
B1 Top west 23 41 63 64 -
B2 Top east 23 39 62 64 -
B3 Centre 23 38 60 62 -
B4 Bottom west 23 35 56 60 -Doorset
(1/4&mid)
B5 Bottom east 23 35 57 61 -
B6 Top RH corner 23 39 69 75 -
B7 Bottom RH corner 22 32 67 81 -
B8 LH side of latch 23 38 58 59 -Misc.
B9 Above latch 23 453 69 80 -
B10 West mid point 21 21 26 29 -
B11 Top mid point 21 23 30 36 -Frame
B12 East mid point 21 21 32 35 -
1Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at whichthe temperature recorded by the thermocouple does not rise by more than 180K above the initialtemperature.
2Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at whichthe average temperature recorded by the thermocouples (quarter points) does not rise by morethan 140K above the initial average temperature.
3Refer to Appendix 3 for locations of thermocouples as only a generic description is included inthe table.
- Under limit column indicates the temperature limit was not exceeded during the test period or upuntil the time of integrity failure if a failure occurred.
Notes:
# Indicates thermocouple fault.
-
8/14/2019 Warring Ton 30 Mts.unlocked
32/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 32 of 37
Table A4.1: Test Specimen Temperatures (continued)
Temp (C) at t (minutes)Element T/C No. Description3
t=0 t=15 t=30 t=41Limit
1,2
(Mins)
Doorset B (Eastern Doorset)
C1 Top west 23 37 60 67 -
C2 Top east 23 38 60 65 -
C3 Centre 23 37 60 65 -
C4 Bottom west 23 36 58 66 -Doorset
(1/4&mid)
C5 Bottom east 23 35 57 63 -
A11 LH side of closer 23 33 60 70 -
A12 Below closer 23 40 63 71 -
C6 Top RH corner 22 30 58 67 -
C7 Bottom RH corner 21 26 49 69 -
C8 LH side of latch 22 34 62 66 -Miscellaneous
C9 Above latch 22 32 59 69 -
C10 West mid point 22 27 48 75 -
C11 Top mid point 22 23 46 53 -
Fr
ame
C12 East mid point 21 25 33 50 -
1Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at whichthe temperature recorded by the thermocouple does not rise by more than 180K above the initialtemperature.
2Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at whichthe average temperature recorded by the thermocouples (quarter points) does not rise by morethan 140K above the initial average temperature.
3Refer to Appendix 3 for locations of thermocouples as only a generic description is included in thetable.
4These thermocouples were close to the glazing feature therefore not used to measure theinsulation performance of the doorset in accordance with BS476: Part 22: 1987.
- Under limit column indicates the temperature limit was not exceeded during the test period or upuntil the time of integrity failure if a failure occurred.
Notes:
# Indicates thermocouple fault.
-
8/14/2019 Warring Ton 30 Mts.unlocked
33/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 33 of 37
A 4.4 DEFLECTION MEASUREMENTS
-40-35-30-25
-20-15-10
-505
10152025
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Deflection(mm)
DA1 DAF1 DAC DA2 DAF2
Figure A4.10: Out-of-Plane Deflection vs. Time of Doorset A
Positive measurements show movement of leaf towards furnace and negativemeasurements show movement of leaf away from furnace.
-40-35-30-25
-20-15-10
-505
10152025
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Deflection(mm)
DB1 DBF1 DBC DB2 DBF2
Figure A4.11: Out-of-Plane Deflection vs. Time of Doorset B
Positive measurements show movement of frame towards furnace and negativemeasurements show movement of frame away from furnace.
-
8/14/2019 Warring Ton 30 Mts.unlocked
34/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 34 of 37
A 4.5 HEAT FLUX MEASUREMENT
0
1
2
3
4
5
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Irradiance(kW/m)
Recorded Radiation Emitted Radiation Integrity Limit
Figure A4.12: Heat flux emitted from Doorset A Vs TimeRadiometer located central to the door leaf at 1000mm away from the specimen.
Recorded radiation is radiation level at radiometer position and emitted radiation isradiation level (calculated) emitted from face of door leaf
0
1
2
3
4
5
0 5 10 15 20 25 30 35 40 45
Time (Minutes)
Irradiance(kW/m)
Recorded Radiation Emitted Radiation Integrity Limit
Figure A4.13: Heat flux emitted from Doorset B Vs TimeRadiometer located central to the door leaf at 1000mm away from the specimen.
Recorded radiation is radiation level at radiometer position and emitted radiation isradiation level (calculated) emitted from face of door leaf
-
8/14/2019 Warring Ton 30 Mts.unlocked
35/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 35 of 37
APPENDIX 5 PHOTOGRAPHS
Figure A5.1: Exposed face of test specimen prior to commencement of test
Figure A5.2: Unexposed face of test specimen prior to commencement of test
-
8/14/2019 Warring Ton 30 Mts.unlocked
36/37
C O N S U L T A N C Y T E S T I N G
WFRA Report No 2208900
Issue Number 2208900a.1Page 36 of 37
Figure A5.3: Sustained flaming evident atbottom RH corner of Doorset A at 3600
test duration. Integrity failure in accordancewith BS476: Part 22: 1987
Figure A5.4: Sustained flaming evident atbottom of Doorset B at 4100 test duration.
Integrity failure in accordance withBS476: Part 22: 1987
Figure A5.5: Unexposed face of test specimen after completion of fire-resistance test
-
8/14/2019 Warring Ton 30 Mts.unlocked
37/37
WFRA Report No 2208900
Issue Number 2208900a.1Page 37 of 37
Figure A5.6: Exposed face after completion of fire-resistance test