Warehouse Fire

download Warehouse Fire

of 45

Transcript of Warehouse Fire

  • 8/12/2019 Warehouse Fire

    1/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    10643-02 RA RunRow Warehouse

    Stud

    Doors Closed- 20 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Fre uenc in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for stora e

    Hei ht of buildin

    Width of building

    Length of building

    Building Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 QRA\Study\Manual Door closing\Warehouse\Doors Closed- 20 m2/1800 s

    Scenario Inputs

    20.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.41

    Relative or Absolute Coordinates?

    Probability or Frequency?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? No

    4.00

    1 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    2/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\F 2m/sWeather:

    Speed: Stability: F2.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    2.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    0.28

    4.57

    0.06

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.21 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    2 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    3/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    3 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    4/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    2.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    0.28

    4.57

    0.06

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.21 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    4 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    5/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    5 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    6/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Doors Closed- 50 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50

    Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Frequency in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for storage

    Height of building

    Width of building

    Len th of buildin

    Buildin Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 RA\Stud \Manual Door closin \Warehouse\Doors Closed- 50 m2/1800 s

    Scenario Inputs

    50.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.40

    Relative or Absolute Coordinates?

    Probabilit or Fre uenc ?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? No

    4.00

    6 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    7/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\F 2m/sWeather:

    Speed: Stability: F2.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    5.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    0.28

    4.57

    0.06

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.53 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    7 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    8/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    8 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    9/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    5.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    0.28

    4.57

    0.06

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.53 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    9 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    10/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    10 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    11/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Doors Closed- 100 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50

    Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Frequency in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for storage

    Height of building

    Width of building

    Len th of buildin

    Buildin Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 RA\Stud \Manual Door closin \Warehouse\Doors Closed- 100 m2/1800 s

    Scenario Inputs

    100.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.09

    Relative or Absolute Coordinates?

    Probabilit or Fre uenc ?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? No

    4.00

    11 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    12/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\F 2m/sWeather:

    Speed: Stability: F2.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    5.93Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    0.28

    4.57

    0.06

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.62 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Ventilation

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    12 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    13/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    13 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    14/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    5.93Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    0.28

    4.57

    0.06

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.62 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Ventilation

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    14 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    15/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    15 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    16/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Doors Closed- 300 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50

    Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Frequency in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for storage

    Height of building

    Width of building

    Len th of buildin

    Buildin Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 RA\Stud \Manual Door closin \Warehouse\Doors Closed- 300 m2/1800 s

    Scenario Inputs

    300.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.01

    Relative or Absolute Coordinates?

    Probabilit or Fre uenc ?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? No

    4.00

    16 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    17/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\F 2m/sWeather:

    Speed: Stability: F2.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    5.93Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    0.28

    4.57

    0.06

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.62 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Ventilation

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    17 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    18/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    18 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    19/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    5.93Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    0.28

    4.57

    0.06

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.62 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Ventilation

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    19 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    20/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    20 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    21/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Doors O en- 20 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50

    Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Frequency in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for storage

    Height of building

    Width of building

    Len th of buildin

    Buildin Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 RA\Stud \Manual Door closin \Warehouse\Doors O en- 20 m2/1800 s

    Scenario Inputs

    20.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.05

    Relative or Absolute Coordinates?

    Probabilit or Fre uenc ?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? Yes

    21 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    22/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\F 2m/sWeather:

    Speed: Stability: F2.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    2.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.21 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    22 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    23/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    23 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    24/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    2.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.21 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    24 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    25/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    25 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    26/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Doors O en- 50 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50

    Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Frequency in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for storage

    Height of building

    Width of building

    Len th of buildin

    Buildin Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 RA\Stud \Manual Door closin \Warehouse\Doors O en- 50 m2/1800 s

    Scenario Inputs

    50.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.04

    Relative or Absolute Coordinates?

    Probabilit or Fre uenc ?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? Yes

    26 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    27/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\F 2m/sWeather:

    Speed: Stability: F2.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    5.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.53 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    27 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    28/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    28 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    29/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    5.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    0.53 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    29 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    30/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    30 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    31/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Doors O en- 100 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50

    Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Frequency in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for storage

    Height of building

    Width of building

    Len th of buildin

    Buildin Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 RA\Stud \Manual Door closin \Warehouse\Doors O en- 100 m2/1800 s

    Scenario Inputs

    100.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.01

    Relative or Absolute Coordinates?

    Probabilit or Fre uenc ?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? Yes

    31 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    32/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\F 2m/sWeather:

    Speed: Stability: F2.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    10.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    1.05 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    32 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    33/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    33 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    34/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    10.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    1.05 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    34 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    35/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    35 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    36/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Doors O en- 300 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50

    Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Frequency in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for storage

    Height of building

    Width of building

    Len th of buildin

    Buildin Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 RA\Stud \Manual Door closin \Warehouse\Doors O en- 300 m2/1800 s

    Scenario Inputs

    300.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.00

    Relative or Absolute Coordinates?

    Probabilit or Fre uenc ?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? Yes

    36 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    37/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\F 2m/sWeather:

    Speed: Stability: F2.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    30.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    3.15 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    37 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    38/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    38 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    39/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    30.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    3.15 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    39 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    40/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    40 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    41/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Doors O en- 900 m2/1800 s

    Active Mass FractionStored MassWarehouse Material Name

    fractionkg

    HN03 15,200.00 1.00

    Morpholine 15,000.00 0.99

    Diethanolamine 50,000.00 1.00

    HCL 16,920.00 1.00

    H3P04 18,800.00 1.00

    Belite (50 % Isopropanol) 4,000.00 0.50

    Sulfolane 15,000.00 0.80

    Hydrazine Hydrate 10,000.00 0.55

    MDEA 75,000.00 0.99

    Activated MDEA 25,000.00 0.80

    INEOS Activated MDEA 25,000.00 0.60

    SERDET (25% Sulphuric acid) 60,000.00 0.25

    NALCO-8514 40,000.00 0.25

    Enriched premix solution 65,000.00 0.80

    Dowtherm A Heat transfer fluid 1,000.00 0.90

    Defoamer 530 500.00 1.00

    Warehouse Inputs

    Event Frequency

    m

    Is Event Frequency in Use?

    Event Frequency Data

    Building Dimensions and Ventilation

    10.00

    65.00

    75.00

    m

    m

    /AvgeYear

    Surface area for storage

    Height of building

    Width of building

    Len th of buildin

    Buildin Wake Effects

    m2

    Yes

    Yes

    4,875.00

    8.80000E-004

    Base Case

    Data

    \10643-02 RA\Stud \Manual Door closin \Warehouse\Doors O en- 900 m2/1800 s

    Scenario Inputs

    900.00Fire surface area

    1,800.00

    492.23

    1,001.92

    0.00

    Relative or Absolute Coordinates?

    Probabilit or Fre uenc ?

    East

    North

    Probability

    Fire duration

    m

    m

    m2

    s

    fraction

    Absolute

    Probability

    /hrVentilation Factor

    Is Ventilation Factor Infinite? Yes

    41 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    42/45

  • 8/12/2019 Warehouse Fire

    43/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds

    43 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    44/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    Default Weathers\D 5m/sWeather:

    Speed: Stability: D5.00

    Average Molecular Weight

    Calculated Quantities

    Warehouse Results

    m/s

    95.40

    Mass of material in warehouse 436,420.00 kg

    Scenario Results

    90.00Mass burnin rate kg/s

    Other Results

    Velocity 0.00 m/s

    3,384.99

    15,476.86

    0.74

    322,920.00

    Moles of material

    Moles of oxygen for complete combustion

    Fraction of material that is active

    Mass of active material kg

    fraction

    kmol

    kmol

    3.09 8.83 1.83

    Average composition of Warehouse material (number of atoms):

    C: H: O:

    0.77 0.07 0.14N: S: Cl:

    0.00 0.00 0.06

    0.00 0.00 0.00

    0.00

    Br:

    Mn:

    I:

    F:

    Sn:

    P:

    Zn:

    Composition of combustion product (moles per mole of Warehouse material):

    3.09 4.34 0.08CO2: H2O: NO2:

    0.07 0.14 0.00SO2: HCl: HBr:

    0.00 0.03 0.00HF: P2O5: MnO2:

    ZnO: SnO2: I2:

    N2:

    0.00 0.00 0.00

    0.35

    4.57

    0.39

    0.26

    0.35

    Moles O2 required / mole completely combusted

    Oxygen flowrate available to fire

    fraction

    fraction

    fraction

    Molar burn rate assuming oxygen-limited fire

    Pro ortion of HCl, HF, HBr in re resentative lume

    Pro ortion of NO2 in re resentative lume

    Pro ortion of SO2 in re esentative lume

    9.46 kg/s

    kg/s

    kg/s

    Release rate for re resentative lume

    Release rate for unburned highly-toxic material

    Release rate for dioxin-generating material

    Surface or Ventilation limit flag

    50.00 degCRelease Temperature

    Ratio ox en re uired for Cate ories 10:0 & 11:0 fraction

    Ratio ox en re uired for Cate or 2:0 fraction

    0.11 fractionToxic products per unit mass Category 0

    fractionUnburned highly toxic per unit mass Category 01.77 fractionOther burned material per unit mass Category 0

    Surface

    kmol/s

    kmol/s

    kg/kmol

    n/a

    sCalculated Fire duration 1,800.00

    44 45ofDate: 11/7/2012 8:50:02PMTime:

  • 8/12/2019 Warehouse Fire

    45/45

    WAREHOUSE FIRE

    Study Folder:

    Unique Audit Number: 1,174,294

    10643-02 QRA (RunRow Warehouse) Phast Risk 6.7

    fractionPCDD & PCDF generated per unit mass Category 0

    Note:

    Category 0 are materials that form toxic combustion products

    Category 10 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of less than 100 degC

    Category 11 are highly toxic materials with LD50 for rates of less than 25mg/kg and flash points

    of more than 100 degC

    Category 2 are potential PCDD and PCDF generating compounds