VRF VPB240H4M-3G VPB120H4M-3G + VPB120H4M-3G

3
VRF SUBMITTAL DATA - OUTDOOR UNIT NOTE − Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. 495788 (201903) ©2019 Lennox Industries Inc. VRF VRF VPB240H4M-3G VPB120H4M-3G + VPB120H4M-3G FEATURES • Split coil heat exchanger • Dual hinged electrical boxes for ease of maintenance High-efficiency vapor injection inverter compressor - Each Module Intelligent Duty Cycle operation • Night Silent operation Hinged service doors Built-in service console • Built-in base pan heater Low Ambient Cooling WARRANTY Compressor - 10-year limited warranty All other components - 10-year limited warranty *See warranty for details NOTES ELECTRICAL DATA Power Supply (Volts/Phase/Hertz) 460/3/60 Minimum Circuit Ampacity (A) (2) 29.5 Maximum Overcurrent Protection (A) (2) 30 Compressor RLA (A) (2) 21 Number of Compressors (2) 1 Outdoor Fan Power Input (W) (2) 820/930 Outdoor Fan FLA (A) (2) 1.5/1.7 GENERAL DATA Connection Ratio 50% to 130% Maximum Number of Indoor Units 44 Refrigerant Type R-410A Factory Refrigerant Charge (each unit) 23.8 lbs. VRF Heat Pump Heat Pump Outdoor Unit Job: Location: Schedule No.: System Designation: Engineer: Architect: Location: Date: For: Reference Approval Review Construction SPECIFICATIONS PERFORMANCE Cooling Capacity¹ (Btu/h) Nominal 240,000 Rated² 230000 EER Ducted 11.1 Non-Ducted 10.8 IEER Ducted 20.3 Non-Ducted 22.4 Heating Capacity¹ (Btu/h) 258,000 COP47 Ducted 3.44 Non-Ducted 3.47 COP17 Ducted 2.34 Non-Ducted 2.21 DIMENSIONS (Each Module) Unit Dimensions (in) Height 64-3/8 Width 52-3/4 Depth 31-1/2 Main System Piping (in) Liquid Pipe Connection 5/8 Gas Pipe Connection 1-1/8 Balancing Pipework between Modules (in) L.P. Gas Balance Pipe Connection 1-1/8 H.P. Gas Balance Pipe Connection 3/4 Oil Balance Pipe Connection 1/4 Unit Net Weight (lb) 794 1. Cooling and Heating capacity data is rated at the following conditions: Cooling: 80°FDB / 67°FWB Indoor, 95°FDB Outdoor Heating: 70°FDB Indoor, 47°FDB / 43°FWB Outdoor. 2. Complies with AHRI 1230-2014 testing standards 3. Operating Voltage Range 410V to 525V 4. To achieve cooling lower than 5°F a Low ambient hood must be installed. This is purchased as an accessory. 5. A local 115V power outlet is available as an accessory to provide local power for maintenance.

Transcript of VRF VPB240H4M-3G VPB120H4M-3G + VPB120H4M-3G

VRF S U B M I T TA L DATA - O U T D O O R U N I T

NOTE − Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualified installer and servicing agency. 495788 (201903) ©2019 Lennox Industries Inc.

VRFVRFVPB240H4M-3G

VPB120H4M-3G + VPB120H4M-3G

FEATURES• Split coil heat exchanger• Dual hinged electrical boxes for ease of

maintenance

• High-efficiency vapor injection inverter compressor - Each Module

• Intelligent Duty Cycle operation• Night Silent operation

• Hinged service doors• Built-in service console• Built-in base pan heater• Low Ambient Cooling

WARRANTY• Compressor - 10-year limited warranty• All other components - 10-year limited warranty

*See warranty for details

NOTES

ELECTRICAL DATAPower Supply (Volts/Phase/Hertz) 460/3/60Minimum Circuit Ampacity (A) (2) 29.5Maximum Overcurrent Protection (A) (2) 30Compressor RLA (A) (2) 21Number of Compressors (2) 1Outdoor Fan Power Input (W) (2) 820/930Outdoor Fan FLA (A) (2) 1.5/1.7

GENERAL DATAConnection Ratio 50% to 130%Maximum Number of Indoor Units 44Refrigerant Type R-410AFactory Refrigerant Charge (each unit) 23.8 lbs.

VRF Heat Pump

Heat Pump Outdoor Unit

Job:

Location:

Schedule No.:

System Designation:

Engineer:

Architect:

Location:

Date:

For: Reference Approval Review Construction

SPECIFICATIONS PERFORMANCECooling Capacity¹ (Btu/h) Nominal 240,000

Rated² 230000EER Ducted 11.1

Non-Ducted 10.8IEER Ducted 20.3

Non-Ducted 22.4Heating Capacity¹ (Btu/h) 258,000

COP47 Ducted 3.44Non-Ducted 3.47

COP17 Ducted 2.34Non-Ducted 2.21

DIMENSIONS (Each Module)Unit Dimensions (in)

Height 64-3/8Width 52-3/4Depth 31-1/2

Main System Piping (in)Liquid Pipe Connection 5/8Gas Pipe Connection 1-1/8Balancing Pipework between Modules (in)L.P. Gas Balance Pipe Connection 1-1/8H.P. Gas Balance Pipe Connection 3/4Oil Balance Pipe Connection 1/4Unit Net Weight (lb) 794

1. Cooling and Heating capacity data is rated at the following conditions:

Cooling: 80°FDB / 67°FWB Indoor, 95°FDB Outdoor Heating: 70°FDB Indoor, 47°FDB / 43°FWB Outdoor.2. Complies with AHRI 1230-2014 testing standards3. Operating Voltage Range 410V to 525V4. To achieve cooling lower than 5°F a Low ambient hood must be

installed. This is purchased as an accessory.5. A local 115V power outlet is available as an accessory to provide

local power for maintenance.

NOTE − Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualified installer and servicing agency. 495788 (201903) ©2019 Lennox Industries Inc.

S U B M I T TA L DATA - O U T D O O R U N I TVPB240H4M-3G

VPB120H4M-3G + VPB120H4M-3GVRF Heat Pump

DIMENSIONAL DRAWINGS - INCHES (MM)

AA BB

DD CC

TOP VIEW

FRONT VIEW FORKLIFT SLOT(BOTH SIDES)

LAG BOLT DESIGNATION(BOTH SIDES)

(TO ACCESS LAG BOLT)

LIFTING HOLES(BOTH SIDES)

(FOR RIGGING)

11-3/4 (298)

4-1/8

(105

)

29-1/2 (749)

53-1/8 (1349)

BACK VIEW

52-3/4 (1340)

64-3/8(1635)

SIDE VIEW

6-1/4 (159)

31-1/2 (800)

18-7/8 (479)29-7/8 (759)

BASE PAN VIEW

EE

FF

CENTER OFGRAVITY

Each Module

CORNER WEIGHTS CENTER OF GRAVITYAA BB CC DD EE FF

lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm121 55 203 92 211 96 251 114 27-3/4 705 12-1/4 311

NOTE − Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualified installer and servicing agency. 495788 (201903) ©2019 Lennox Industries Inc.

S U B M I T TA L DATA - O U T D O O R U N I T

MULTI-MODULE INFORMATION

Multi-Module Dimensions

TOP VIEW

4 (102)

109-1/2 (2782)

52-3/4 (1340) 52-3/4 (1340)

NOTE - All the outdoor units manifolded together should be installed at the same elevation.

Multi-Module Power

L2 L3L1

208/230V 3Ph 60Hz or 460V 3Ph 60Hz

Power supply

Outdoor Unit (Main Unit)

L1 L2 L3

Outdoor Unit (Sub1 unit)

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

Service Disconnect

Service Disconnect

See page 1 for electrical data. Total system MCA is calcuated by adding the MCA value of each module together to get the total system MCA. Total system MOP is calcuated by adding the MOP value of each module together to get the total system MCA.

VPB240H4M-3GVPB120H4M-3G + VPB120H4M-3G

VRF Heat Pump