VOLTAGE STABILITY
description
Transcript of VOLTAGE STABILITY
1
VOLTAGE STABILITY
Ph.D. SeminarIndian Institute of Technology, Bombay
Jignesh M. Solanki
2
What is voltage stability ? maintain steady acceptable voltages at all buses in the system a system enters a state of voltage instability when a disturbance, increase
in load demand inability of a power system to meet the demand for reactive power a criterion for voltage stability stability is that, bus voltage magnitude increase as reactive power injection at the same bus increase a system is voltage unstable if, V-Q sensitivity
3
voltage instability is essentially a local phenomenon voltage collapse is more complex than simple voltage
instability
4
ILLUSTRATION OF VOLTAGE INSTABILITY
Limit of satisfactory operation For higher load demand , control of power by varying load
would be unstable if load is supplied by transformers with ULTC, the tap-changer
action try to raise the load voltage. This has lower effective ZLD and due to that VR goes low still further and
It may call pure form of voltage instability.
A simple radial system for illustration of voltage stability phenomenon
5
CLASSIFICATION OF VOLTAGE STABILITY
LARGE DISTURBANCE VOLTAGE STABILITY
SMALL DISTURBANCE VOLTAGE STABILITY
TRANSIENT VOLTAGE STABILITY LONGER TERM VOLTAGE STABILITY
6
LARGE DISTURBANCE VOLTAGE STABILITY (LDVS)
It is concerned with systems ability to control voltages following large disturbances such as system faults, loss of generator or circuit contingency.
Load characteristics and the interaction of both continuous and discrete controls and protections.
Determination of LDVS requires the examination of the non-linear dynamic performance of a system over a period of time (ULTC and generator field current limiter)
7
For analysis long-term dynamic simulations are required. A criterion of large disturbance voltage stability, is that,
following a given disturbance and system control actions, voltage at all buses reach acceptable steady state levels.
8
control voltages following small perturbations load characteristics, continuous control and discrete
control Basic process a steady state nature Stability margin, identifying factors influencing stability,
examine wide range of system conditions and large number of post contingency scenarios.
A criterion for SDVS, V-Q sensitivity
SMALL DISTURBANCE VOLTAGE STABILITY (SDVS)
9
TRANSIENT VOLTAGE STABILITY 0 to 10 seconds, transient rotor angle stability
voltage voltage collapse is caused by unfavorable fast
acting load components (IM and DC converters) For severe voltage dips the reactive power demand
of IM increases, contributing to V.C Electrical islanding and under frequency load
shedding resulting V.C. when imbalance is greater than about 50%.
10
Voltage decays faster than frequency under frequency relays may not operate There are incidents where the voltage collapses before
frequency decays to the under frequency load shedding set points
Voltage and frequency for South Florida blackout
11
LONGER TERM VOLTAGE STABILITY 2-3 minutes involves high loads, high power inputs from remote
generation and a sudden large disturbance (lass of generator or loss of major transmission line)
the disturbance causes high reactive power losses and voltage sags in load areas
the tap changer sense low voltages and act to restore disturbance voltages thereby restoring load power levels
12
further sags of transmission voltages. generator farther away must then provide reactive power
this is inefficient and ineffective no longer support by generation and transmission system. partial and complete voltage collapse.
13
RELATION OF VOLTAGE STABILITY AND ROTOR ANGLE STABILITY
VOLTAGE STABILITY
Pure voltage stability transient voltage stability reactive power control concerned with load area and load
characteristics load stability voltage collapse in load area without loss of synchronism of any
generators generator current limiting is very
detrimental to both form of stability
ROTOR ANGLE STABILITY
Pure angle stability
transient RAS reactive power control integrating remote power plant to a large
system over a long transmission line generator stability voltage collapse in transmission system
remote form loads
14
VOLTAGE INSTABILITY IN MATURE POWER SYSTEM intensive use of existing generation and transmission. new generation in load areas and transmission lines from
remotely sited generation increased use of shunt capacitor bank. How V.I. can become a problem in Mature power system?
series reactive P.L. = I2 x take loading is I = 1000 amp, one line outage.
other lines peak up 25%
15
losses = (5 lines x 3 phase x 10002 x 80 ohms ) = 1200 MVA25% peak up so losses = 1500 MVA. after several years load growth assume loading is 1500
Amp. losses = 2700 MVAr 25% increase 3375 MVAr because of these non linear process, V.S. problem develop
only in few years.
16
V-Q CURVES
voltage security is closely related to reactive power and a v-q curves gives reactive power margin at the test bus.
the slope of the V-Q curves indicated the stiffness of the test bus
reactive power of the generators can be plotted on same graph
V-Q curve sketches showing effect of voltage sensitive loads and tap changers on limit
17
the effect of voltage sensitivity loads ( i.e. prior to tap changing ) will have much greater reactive power margins and much lower critical voltages
when tap changer hit limits, the curves tend to flatten out rather then turn up on the left side
18
VOLTAGE STABILITY ANALYSIS
DYNAMIC ANALYSIS
for detailed studies of specific voltage control situations. co-ordination of protection and controls and testing of
remedial measures. dynamic simulations also examine whether and how the
steady-state equilibrium point will be reached.
19
STATIC ANALYSIS
allow examination of a wide range of system conditions nature of the problem and identify the key condition
factors
20
DETERMINATION OF SHORTEST DISTANCE TO INSTABILITY
increase load from Po,Qo in some direction until an eigen value of a Jacobian is practically zero.
surface S represents the locus of all combinations of P and Q which results in a zero eigen value of Jacobian.
P1,Q1 corrosponding to this point is the stability limit which lies on or extremely near to S.
21
the load on the transmission lines is too high. the voltage sources are too far from the load centres. the source voltages are too low. large distances between generation and load. ULTC action during low voltage conditions. poor co-ordination between various control and protective
systems. insufficient load reactive compensation.
CAUSES OF VOLTAGE COLLAPSE
22
PREVENTION OF VOLTAGE COLLEPSE application of reactive power compensating devices control of network voltage and generator reactive o/p co-ordination of protection / controls control of transformer tap changers undervoltage load shedding stability margin spinning reserve operators' action
23
GENERIC DYNAMIC LOAD MODEL Pt = V or Pv = c2V2 + c1V + c0 Ps = P0V or Ps = P0(d2V2 + d1V + d0) where V is the per-unit magnitude of the voltage imposed
on the load It can be seen that, at steady-state, state variable x of the
model is constant
A generic dynamic model
24
e = Ps – P, must be zero The transient output is then determined by the transient
characteristics P = xPt The mismatch between the model output and the steady-state
load demand is the error signal e This signal is fed back to the integration block that gradually
changes the state variable x This process is continues until a new steady-state (e=0) is
reached Pt(V) = V, Ps(V) = P0Va; Qt(V) = V, Qs(V) = Q0Vb
25
LOAD MODELLING
ix3 = ixE = ixM + ixC ; iy3 = iyE + iyN + iyC Exponential load Polynomial load P(V3) = Po (V3/V3o) P = Po [aP(V/Vo)2 + bP(V/Vo) + CP]
Q(V3) = Qo (V3/V3o) Q = Qo [aQ(V/Vo)2 + bQ(V/Vo) + CQ]
, depends on load ; aP + bP + cP = aQ = bQ = cQ = 1 Po,Qo is consumed power at reference voltage complex current injected in to the network IE = - (S/V3) = -[ P(V3) – jQ(V3)/Vx3 – j Vy3 ] = ixE + j VyE
26
CONCLUSION Three key concepts of voltage stability are the load characteristics as seen from the bulk power network the available means for voltage control at generators and in the
network the ability of network to transfer power particularly reactive power
from the point of production to the point of consumption The network steady state loadability limit is not necessarily the voltage
instability limit Static power flow based analyses of the post disturbance steady state is
the useful method of analyzing longer term voltage stability The fundamental cause of voltage instability is identified as
incapability of combined transmission and generation system to meet excessive load demand in either real power or reactive power form
27
Thank You