Voltage Stabilisation & OptimisationTHE FACTS
![Page 2: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/2.jpg)
OVERVIEW
• Who are we?
• What is Voltage Optimisation?
• What equipment does it work on and how well?
• Historic results
• Voltage Balance
• Types of VO
• Questions…
![Page 3: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/3.jpg)
• 20 years as a power supply engineer and senior manager in NSW
electricity industry (now called Ausgrid)
• 20 years in the energy efficiency industry developing many large
energy saving projects in NSW, Qld, Vic and WA
• More than 10 years on the board of the Australasian Energy
Performance Contractors Association (now Energy Efficiency
Council)
• Implemented many successful energy saving Voltage Optimisation
solutions for Supermarkets, Office buildings and Hotels.
DEANE GUDSELL
![Page 4: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/4.jpg)
• Specialist Power Quality and Energy Saving solutions provider and manufacturer.
• Proudly Australian owned and a member of the Ampcontrol Group of companies. Ampcontrol have been providing electrical engineering services since 1968 in Australia, New Zealand and overseas.
• Market leader in Power Factor Correction manufacture and supply for over 30 years
• Introduced the European manufactured Ortea VPO to the range in 2013. Ortea have been supplying VPO and stabilisers world wide for decades.
CAPTECH
![Page 5: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/5.jpg)
CAPTECH REFERENCES
CapTech equipment can be found in all facets of industries such as in supermarkets, Schools & Universities,
Government & Office Buildings, Power Authorities, National and International Manufacturers.
![Page 6: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/6.jpg)
WHY SHOULD YOU BE INTERESTED?
VOLTAGE OPTIMISATION DELIVERS:
• REDUCED electrical energy (kWh) COSTS
• REDUCED maximum demand/penalty (KVA & KW) COSTS
• STABILISE and BALANCES supply voltage (some do)
• PROTECT plant life expectancy
• PROTECT your processes/production (some do)
![Page 7: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/7.jpg)
1. Supply voltage is 240V (415V) and is steady
2. The voltage on each phase of my supply is always balanced
3. Motors are all designed for 240V (415V) supply voltage
4. Reducing voltage below 240V will burn out my electric motor
5. Power Factor Correction is the same as Voltage Optimisation
6. All electrical equipment will use less energy with reduced voltage
7. All VPO’s deliver the same results
All of the above are wrong or at least mostly wrong
MISCONCEPTIONS
![Page 8: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/8.jpg)
• VO – Voltage Optimisation
• A reduction and balancing in electricity supply voltage that achieves a saving in energy consumption (kWh) and a reduction in maximum demand (KW & KVA).
• Achieved by better matching supply voltage with the design voltage for your electric motors.
VO DEFINITION
![Page 9: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/9.jpg)
• Supply voltage varies over time and with location
• 245 - 247V is the most commonly recorded average supply voltage
• Electricity Supply Voltage standard (AS/NZ60038-2000)
o 230V +10%/-6% (253V-216V phase to neutral)
o 400V +10%/-6% (376-440V phase to phase)
WHY? - SUPPLY VOLTAGE
Neutral
230V
400V
L1 L2
L3
![Page 10: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/10.jpg)
1. Optimisation/reduction of supply voltage will normally reduce energy
consumption of inductive electrical equipment like motors and some
older type lighting
2. Energy consumption reduction varies dependent on
– the average reduction in voltage achieved
– the stability of the reduced voltage
– the phase voltage balance
– type of electrical equipment connected.
3. Motor nameplate voltage rating is most often 220V (380V 3-phase)
VO FACTS
![Page 11: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/11.jpg)
• HVAC systems and Refrigeration are the sweet spot for VO
• Saving varies based on motor design voltage & mechanical
load
• VFD’s reduce the level of saving for motors from VO
• Inverter HVAC – no saving from VO
• Electronic Power supplies like LED lighting and IT equipment
like Gaming Machines – no saving
RULE OF THUMB
![Page 12: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/12.jpg)
OPTI netENERGY SAVING ST@BILISER
VOLTAGE STABILITY
![Page 13: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/13.jpg)
SUPERMARKET – 12.3% WHOLE SITE
12.3% energy saving year to year raw data ‐ Dungog IGA
![Page 14: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/14.jpg)
SUPERMARKET – 13% WHOLE SITE
13% whole site energy saving regression analysis, taking weather variables into accountDungog IGA
M&V using IMPVP
![Page 15: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/15.jpg)
SUPERMARKET – 14.4% WHOLE SITE
14.4% whole site kWh energy saving and 12.2% reduction in Maximum Demand
![Page 16: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/16.jpg)
AQUATIC CENTRE
Results: energy consumption saving – Aquatic centre 17% saving Regression analysis kWh taking into account temperature and relative humidity pre and post installation
M&V using IMPVP
![Page 17: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/17.jpg)
COMMERCIAL OFFICE – 11% SAVING
Results: energy consumption saving – Office Building 11% saving
Before
After
![Page 18: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/18.jpg)
ENERGY SAVINGS OPPORTUNITY
Good energy savings
![Page 19: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/19.jpg)
ENERGY SAVING OPPORTUNITY
Good energy savings
![Page 20: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/20.jpg)
ENERGY SAVING OPPORTUNITY
No saving ….. But no harm by lowering voltage
![Page 21: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/21.jpg)
• Name-plate rating for 3 phase motors is commonly 380V (220V) for 50Hz.
• Sometimes is 400V, 415V, & rarely higher
• NEMA stipulate that a motor should operate normally for
• voltage range +/-10% of the nameplate voltage
• Limit of voltage unbalance should be 1%
MOTORS
![Page 22: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/22.jpg)
• Very rare name-plate 430V …..but they do exist
• 430 VL-L = 248 VL-N
• Not for Voltage Optimisation
MOTORS – know when to fold em!
![Page 23: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/23.jpg)
EFFECT OF VOLTAGEVARIATION ON MOTORS
Reference – Electric Motors & Voltage – The Cowern Papers
Design voltage
![Page 24: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/24.jpg)
EFFECT OF VOLTAGEVARIATION ON MOTORS
Refrigeration Compressor Motor
Supply voltage
Design voltage 220V
![Page 25: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/25.jpg)
• Out of balance voltages can cause significant energy loss (heat) in three phase motors.
• Balanced voltage on each phase separately can save even more energy & improve asset life
VOLTAGE PHASE BALANCE
Supply Voltage
VO StabiliserOutput
2% Unbalanced voltage
![Page 26: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/26.jpg)
• NEMA states that three motors shall operate successfully at rated load when unbalance voltage does not exceed 1%
• Unbalanced voltages cause phase current unbalance from 6‐10 times the percentage voltage unbalance for a fully loaded motor.
• Unbalanced voltage of 2.3% can cause up to 300C temperature rise in the motor.
VOLTAGE UNBALANCE
CharacteristicAverage Voltage 230 230 230Unbalanced Voltage 0.3% 2.3% 5.4%Unbalanced Current 0.4% 17.7% 40%Increased Temerature Rise 0 30 C 40 C
Performance
Reference – Unbalanced Voltages and Electric Motors: Causes and Consequences, elongo.com
![Page 27: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/27.jpg)
• Winding insulation life is approximately halved for every 100C increase in winding temperature.
• Motor losses increase 25% with a 4% unbalance voltage
Reference – Unbalanced Voltages and Electric Motors: Causes and Consequences, elongo.com
VOLTAGE UNBALANCE
![Page 28: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/28.jpg)
SAVINGS VARY BY EQUIPMENT TYPE
0%
5%
10%
15%
20%
25%
Inverter &VRV HVAC
T5 & LEDelectronicballastlighting
Laptop &Desktop PC& Flat screen
VSD drivenmotors
Pool Pump Fan motor HVACpackaged
Refrigerator(domestic)
Commercialrefrigeration
CFL lighting Halogenlighting
T8 MagneticBallastlighting
HID lighting(magneticballast)
Energy Savingexpected from a 10% voltage reduction
low
high
![Page 29: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/29.jpg)
SAVING CALCULATION
Voltage reduction and type and mix of electrical equipment is critical to estimating the potential energy and demand savings
Load type% of total
loadkWh
usage/year
Benchmark ‐ Saving per 10% volt reduction
Saving per actual volt reduction
Energy Savings predicted kWh/yr
Refrigeration no VSD 10% 195,412 15% 15.7% 30,660 Refrigeration ‐ with VSD 0% ‐ 4% 4.2% ‐ Lighting ‐ Mag Ballast 0% ‐ 18% 18.8% ‐ Lighting ‐ Electronic Ballast 10% 195,412 0% 0.0% ‐ IT and office equipment 10% 195,412 0% 0.0% ‐ Cooking (electric) other 5% 97,706 0% 0.0% ‐ Pumps fans and general motor 0% ‐ 12% 12.6% ‐ HVAC ‐ no inverters or VSD's 55% 1,074,767 12% 12.6% 134,904 HVAC ‐ with VSD's 10% 195,412 4% 4.2% 8,176 Total 100% 1,954,122 8.9% 173,739
ENTER Total annual kWh 1,954,122 Voltage reduction possible 10.46%Target output voltage 220.0 Average Voltage 245.7
![Page 30: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/30.jpg)
CONNECTING VO & PFC
PFCL
Transformer
Main Switchboard
Circuit Breaker
11kV
LV
CT
IT
LV
220VVO
247V ?
VO
Mechanical Services
![Page 31: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/31.jpg)
TYPES OF VO
Type of VO Outcomes
Step‐down VO • Least energy saved• Output fluctuates with input volt changes• None or minimal phase voltage balancing
Automatic VO • Slow adjustments • More accurate output than Step‐down VO but not
a stable output voltage• Minimal phase voltage balancing• More energy saved than step down VO
Automatic VO Stabiliser
• Fast adjustments <20mS• Highly accurate and stable output voltage <0.5%• Accurate phase voltage balancing <1.0%• Most energy saved
![Page 32: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/32.jpg)
1. Build Quality2. Proven reliability in hot and humid environments
3. Track record4. Stability of output voltage based on speed of operation, input range
and accuracy (Fastest and most accurate output the better)5. Independent phase voltage control (balance)
6. Technical support - Depth, capability and geographic coverage of supplier in Australia
7. Business strength and longevity of both manufacturer andsupplier in Australia.
VO SUPPLIERSELECTION CRITERIA
![Page 33: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/33.jpg)
VOLTAGE OPTIMISERSOptinet series by CapTech
• Fast 18 millisecond automatic response time• Independent phase voltage control• Highly accurate output voltage +/- 0.5%• Surge Protection • Bypass switch• Input/output display• Voltage output can be set from 210-255V L-N
• Optional +/-30% voltage range for stable output (Supply input 161V-300V)
• Warranty 15 years on magnetics, 3years on other• Tens of thousands of units installed worldwide (Europe, UK, Africa, SE Asia, Middle East
and Australia)
OPTI netENERGY SAVING ST@BILISER
Supply Output
253V‐220V L‐NStable
220V +/‐0.5%
![Page 34: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/34.jpg)
Voltage Optimiser& Stabiliser referencesSome Ortea VO Australian and International reference sites:
![Page 35: Voltage stabilisation and optimisation by Captech - The facts](https://reader031.fdocuments.in/reader031/viewer/2022020113/58eeb7881a28ab977d8b4685/html5/thumbnails/35.jpg)
• Save Electrical Energy
• Reduce Electricity Demand/Penalties
• Protect expensive equipment
• Doesn’t work for everything
• Different results by equipment type
• Saving can be predicted.
VOLTAGE OPTIMISATION& STABILISATION