Voltage Drop Presentatn
Click here to load reader
Transcript of Voltage Drop Presentatn
What is Voltage Drop
S
VD = IR = (mV/A/m)r
p.f. = 1LoadI R
Source
What is Voltage Drop
S
S
VD = IR = (mV/A/m)r
VD = IR Cos == Cos(mV/A/m)r
Load
p.f. = 1Load
p.f. = Cos
I
I
R
R
Source
Source
What is Voltage Drop
S
Source
Load p.f. = Cos
VD = IR Cos + I X Sin ==Cos(mV/A/m)r + Sin(mV/A/m)x
S
S
VD = IR = (mV/A/m)r
VD = IR Cos == Cos(mV/A/m)r
Load
p.f. = 1Load
p.f. = Cos
I R
I
I
R
R
Source
Source
X
Why Need to Control Voltage Drop
1. Meet the relevant Code (CP5: 525-01-02)
2. Maintain Proper Operation (CP5: 525-01-01)
3. Operate Best Efficiency
4. Safety Operation
5. Optimize Life Span
6. Reduce Energy Loss
7. Reduce Heat
Ways to Minimize Voltage Drop
1. Reduce Route Length
2. Bigger Cable
3. Lower Conductor Resistivity
4. Lower Cable Reactance
5. Boost up Supply Voltage
6. Use Higher Supply Voltage
7. Parallel Circuit
8. Reduce Temperature of Operation
9. Review Installation Method
DISTRIBUTION ARRANGEMENT
RADIAL RISER SUB-DISTRIBUTION
RING
Min. V.D. 0.23 % 0.18 % 0.13 % 0.11 %
Max. V.D. 0.92 % 0.47 % 0.39 % 0.28 %
Installation Cost 100 % 180 %) 170 % 210 %
Voltage Drop Vs Distribution ArrangementEach Load = 100A
Distance of Each Load = 3m
N N NN
Voltage Drop Vs Different Type of Distribution Means
Load = 100A
Distance = 100m
Voltage Drop Limit
CP5 525.01
V.D. 4%
Supply Utility Voltage Regulation = 6%
Most Electrical Appliance Operate properly within Voltage Regulation = 10%
V.D. Limit = 4%
10%
6%
4%
6%
Typical Allowable Voltage Drop
3.0%
1.5% 1%
3.0% 4%
2.5% 3%
1.0%
V.D.
10%
6%
Final Circuit Voltage Drop
Sub-Main Voltage Drop
Supply Utilities Voltage Regulation
Lift/Escalator Lighting Small Power
6% 6% 6% 6% 6%
ACMV MCC
Fire Pump UPS Load
1.0%
Voltage Drop at Steady State / Transient Condition
S B
MLoad3% 3%
1%
S B
M 3%
Load
1%
NN
3%
2%2%
Voltage Drop at Steady State / Transient Condition
S B
MLoad5%
3% 3%
6%
2%
1%
S B
M 3%
6%Load
1%
2%
NN
3%
4%
3%
2%
4%
2%
Voltage Drop with Consideration of Cable Reactance
2.5%
2.5% 2.5%2.2%
1.3%
0.9%
1.6%
6mm2 16mm2 25mm2 240mm2 500mm2
1.2%
0.3%
(Voltage Drop)r = IR (Less Than 16sq mm)
(Voltage Drop) R , X, Cos = IRCos + I X Sin
Voltage Drop with Temperature Correction Cable (R & X) data given @ Rated Cable Temp.
(e.g. 70oC Conductor Temp. for PVC Cable-30oC Ambient)
I Temp R V.D.
Load
Ambient Temp = 25oC
I(design)=20A
1/c 10sqmm PVC cable
I(table) =59A
(mV/A/m)r=3.8mV/A/m
30m
VD=3.8mV*20A*30m=2.28V
Voltage Drop with Temperature Correction Cable (R & X) data given @ Rated Cable Temp.
(e.g. 70oC Conductor Temp. for PVC Cable-30oC Ambient)
I Temp R V.D.
Load
Ambient Temp = 25oC
I(design)=20A
1/c 10sqmm PVC cable
I(table) =59A
(mV/A/m)r=3.8mV/A/m
VD=3.8mV*20A*30m=2.28V
30m
Voltage Drop with Temperature Correction