Voltage Drop Checking

download Voltage Drop Checking

of 6

Transcript of Voltage Drop Checking

  • 8/13/2019 Voltage Drop Checking

    1/6

    VOLTAGE DROP CHECKING :

    6.1.0 DATA:

    Transformer rating : 1.6 MVA

    Transformer impedance : 6.00%

    Highest kW motor rating : 74.6 kW

    Power factor : 0.85

    Mode of start : DOL

    Starting Current : 6 times the Full load current

    Motor Starting kVA : 526.56 kVA

    Total Base Load Except motor : 1043.6 kVA

    Total load During Starting of Motor : 1570 kVA

    Starting power factor : 0.2

    Sin : 0.97

    Base MVA : 1.6 MVA

    Base Voltage on transformer primary voltage : 0.415 kV

    Source faut kA : 31.5 kA

    Source Voltage : 11 kV

    Source fault MVA : 1.732X11X31.5

    : 600.15MVA

    Source Impendence in P.U : Base MVA /Source MVA

    : 1.6 / (600.15)

    : 0.00416 P.U

    Cable size of transformer incomer : 1CX500 Sq.mm

  • 8/13/2019 Voltage Drop Checking

    2/6

    Resistance of 11kV 500 sq.mm cable : 0.0485 ohms/km

    Reactance of 11kV 500 sq.mm cable : 0.212 ohms/km

    Length Considered : 30m

    Number of Runs : 1

    Cable resistance of transformer primary with 30 m length : 0.0485x (50/100)

    : 0.02425 ohms

    Cable reactance of transformer primary with 30 m length : 0.212x (50/100)

    : 0.106 ohms

    Cable impedance in Ohms : (0.02425)+ (0.106)

    : 0.1087 ohms

    Cable impedance in p.u : ohms X (Base MVA/kV)

    : 0.001437 P.u

    Transformer impedance : 6.00%

    Transformer impedance in P.u : 0.06 p.u

    Cable size of MDB to SDB incomer : 4RX3.5CX300Sq.mm

    Resistance of 1.1 kV 300 sq.mm cables : 0.0769 ohms/km

    Reactance of 1.1 kV 300 sq.mm cables : 0.0705 ohms/km

    Length Considered : 100m

    Number of Runs : 4

  • 8/13/2019 Voltage Drop Checking

    3/6

    Cable resistance of motor incomer with 100 m length : 0.0769x (100/1000/4)

    : 0.001925 ohms

    Cable reactance of motor incomer with 100 m length : 0.0705x (100/1000/4)

    : 0.0017625 ohms

    Cable impedance in Ohms : (0.00192)+ (0.00176)

    : 0.00260 ohms

    Cable impedance in p.u : Ohms X (Base MVA/kV)

    : 0.00260X (2.5/0.433/0.433)

    : 0.00260 X 13.33

    : 0.034 P.u

    Cable size of SDB to MCC incomer : 2RX3.5CX300Sq.mm

    Resistance of 1.1 kV 300 sq.mm cables : 0.0769 ohms/km

    Reactance of 1.1 kV 300 sq.mm cables : 0.0705 ohms/km

    Length Considered : 50m

    Number of Runs : 2

    Cable resistance of motor incomer with 50 m length : 0.0769x (50/1000/2)

    : 0.001925 ohms

    Cable reactance of motor incomer with 50 m length : 0.0705x (50/1000/2)

  • 8/13/2019 Voltage Drop Checking

    4/6

    : 0.0017625 ohms

    Cable impedance in Ohms : (0.00192)+ (0.00176)

    : 0.00260 ohms

    Cable impedance in p.u : Ohms X (Base MVA/kV)

    : 0.00260X (2.5/0.433/0.433)

    : 0.00260 X 13.33

    : 0.034 P.u

    Cable size of MCC to Motor incomer : 2RX3.5CX150Sq.mm

    Resistance of 1.1 kV 150 sq.mm cables : 0.159 ohms/km

    Reactance of 1.1 kV 150 sq.mm cables : 0.0716 ohms/km

    Length Considered : 50m

    Number of Runs : 2

    Cable resistance of motor incomer with 50 m length : 0.159x (50/1000/2)

    : 0.003975 ohms

    Cable reactance of motor incomer with 50 m length : 0.0716x (50/1000/2)

    : 0.00179 ohms

    Cable impedance in Ohms : (0.00397)+ (0.00179)

  • 8/13/2019 Voltage Drop Checking

    5/6

    : 0.00435 ohms

    Cable impedance in p.u : Ohms X (Base MVA/kV)

    : 0.00435X (2.5/0.433/0.433)

    : 0.00435 X 13.33

    : 0.05 P.u

    Total Cable Impedance : 0.05+0.034+0.034+0.00024

    : 0.1272

    Total Impedance : Source impedance +Transformer

    Impedance + Total cable Impedance

    : 0.00416+0.0625+0.1272

    : 0.1848 P.U

    Total Voltage drop during Starting : (Total load during starting of motor in

    MVA x Impedance x Sin)/Base MVA

    : ( 2.079x0.91x0.1848)/ (2.5)

  • 8/13/2019 Voltage Drop Checking

    6/6

    : 13.9%

    Maximum Allowable Voltage Drop during Starting of Highest kW motor as per Is Standard is 15% which is

    higher than our Actual Voltage drop 13.9 %. Hence 2.5 MVA transformer size is justified.