VOLTAGE DROP CHECKING :
6.1.0 DATA:
Transformer rating : 1.6 MVA
Transformer impedance : 6.00%
Highest kW motor rating : 74.6 kW
Power factor : 0.85
Mode of start : DOL
Starting Current : 6 times the Full load current
Motor Starting kVA : 526.56 kVA
Total Base Load Except motor : 1043.6 kVA
Total load During Starting of Motor : 1570 kVA
Starting power factor : 0.2
Sin : 0.97
Base MVA : 1.6 MVA
Base Voltage on transformer primary voltage : 0.415 kV
Source faut kA : 31.5 kA
Source Voltage : 11 kV
Source fault MVA : 1.732X11X31.5
: 600.15MVA
Source Impendence in P.U : Base MVA /Source MVA
: 1.6 / (600.15)
: 0.00416 P.U
Cable size of transformer incomer : 1CX500 Sq.mm
-
8/13/2019 Voltage Drop Checking
2/6
Resistance of 11kV 500 sq.mm cable : 0.0485 ohms/km
Reactance of 11kV 500 sq.mm cable : 0.212 ohms/km
Length Considered : 30m
Number of Runs : 1
Cable resistance of transformer primary with 30 m length : 0.0485x (50/100)
: 0.02425 ohms
Cable reactance of transformer primary with 30 m length : 0.212x (50/100)
: 0.106 ohms
Cable impedance in Ohms : (0.02425)+ (0.106)
: 0.1087 ohms
Cable impedance in p.u : ohms X (Base MVA/kV)
: 0.001437 P.u
Transformer impedance : 6.00%
Transformer impedance in P.u : 0.06 p.u
Cable size of MDB to SDB incomer : 4RX3.5CX300Sq.mm
Resistance of 1.1 kV 300 sq.mm cables : 0.0769 ohms/km
Reactance of 1.1 kV 300 sq.mm cables : 0.0705 ohms/km
Length Considered : 100m
Number of Runs : 4
-
8/13/2019 Voltage Drop Checking
3/6
Cable resistance of motor incomer with 100 m length : 0.0769x (100/1000/4)
: 0.001925 ohms
Cable reactance of motor incomer with 100 m length : 0.0705x (100/1000/4)
: 0.0017625 ohms
Cable impedance in Ohms : (0.00192)+ (0.00176)
: 0.00260 ohms
Cable impedance in p.u : Ohms X (Base MVA/kV)
: 0.00260X (2.5/0.433/0.433)
: 0.00260 X 13.33
: 0.034 P.u
Cable size of SDB to MCC incomer : 2RX3.5CX300Sq.mm
Resistance of 1.1 kV 300 sq.mm cables : 0.0769 ohms/km
Reactance of 1.1 kV 300 sq.mm cables : 0.0705 ohms/km
Length Considered : 50m
Number of Runs : 2
Cable resistance of motor incomer with 50 m length : 0.0769x (50/1000/2)
: 0.001925 ohms
Cable reactance of motor incomer with 50 m length : 0.0705x (50/1000/2)
-
8/13/2019 Voltage Drop Checking
4/6
: 0.0017625 ohms
Cable impedance in Ohms : (0.00192)+ (0.00176)
: 0.00260 ohms
Cable impedance in p.u : Ohms X (Base MVA/kV)
: 0.00260X (2.5/0.433/0.433)
: 0.00260 X 13.33
: 0.034 P.u
Cable size of MCC to Motor incomer : 2RX3.5CX150Sq.mm
Resistance of 1.1 kV 150 sq.mm cables : 0.159 ohms/km
Reactance of 1.1 kV 150 sq.mm cables : 0.0716 ohms/km
Length Considered : 50m
Number of Runs : 2
Cable resistance of motor incomer with 50 m length : 0.159x (50/1000/2)
: 0.003975 ohms
Cable reactance of motor incomer with 50 m length : 0.0716x (50/1000/2)
: 0.00179 ohms
Cable impedance in Ohms : (0.00397)+ (0.00179)
-
8/13/2019 Voltage Drop Checking
5/6
: 0.00435 ohms
Cable impedance in p.u : Ohms X (Base MVA/kV)
: 0.00435X (2.5/0.433/0.433)
: 0.00435 X 13.33
: 0.05 P.u
Total Cable Impedance : 0.05+0.034+0.034+0.00024
: 0.1272
Total Impedance : Source impedance +Transformer
Impedance + Total cable Impedance
: 0.00416+0.0625+0.1272
: 0.1848 P.U
Total Voltage drop during Starting : (Total load during starting of motor in
MVA x Impedance x Sin)/Base MVA
: ( 2.079x0.91x0.1848)/ (2.5)
-
8/13/2019 Voltage Drop Checking
6/6
: 13.9%
Maximum Allowable Voltage Drop during Starting of Highest kW motor as per Is Standard is 15% which is
higher than our Actual Voltage drop 13.9 %. Hence 2.5 MVA transformer size is justified.