Installation Instructionsfor use by heating contractor
Low-Loss Header, Part Nos. 7134 791, 7134 792
for Vitodens 100, WB1A and Vitodens 200, WB2A (single-boiler installations only)
5285 318 v2.6 02/2009
Safety and Installation Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with theinstructions listed below can cause product/property damage, severe personal injury, and/or loss of life.
Working on the equipmentThe installation, adjustment, service,and maintenance of this product mustbe done by a licensed professionalheating contractor who is qualified andexperienced in the installation, service,and maintenance of hot water boilers.There are no user serviceable parts onthe boiler, burner, or control.
Ensure main power supply toequipment, the heating system, and allexternal controls has been deactivated.Close main gas supply valve. Takeprecautions in all instances to avoidaccidental activation of power duringservice work.
It is not permissible to perform servicework on any component part ensuringsafe operation of the heating system.When replacing parts, use originalViessmann or Viessmann approvedreplacement parts.
When used in conjunction with theVitodens 100 or Vitodens 200 boiler,the low-loss header acts as a hydraulicbreak, decoupling boiler and systemcircuits from each other.It is recommended to use the low-lossheader in applications in which the totalsystem flow rate exceeds the maximumboiler flow rate.Viessmann strongly recommends theuse of a low-loss header in cases wherethe system head and flow rates areunknown.
The temperature sensor connectionlocated at the top of the low-lossheader ensures low return temperaturesto the Vitodens 200 boiler only at alltimes, increasing operational efficiency.Please note that this temperaturesensor (Part No. 7134 240) forVitodens 200 must be purchasedseparately.No temperature sensor is used on theVitodens 100 boiler.In addition, the low-loss header helpseliminate air and debris from the heatingsystem.The low-loss header is available in thefollowing sizes. Select the size basedon the maximum system flow rate ofyour application.
Model No. Max. system flow rate
Type 80/50 4 m3/h / 17.6 GPM
Type 120/80 8 m3/h / 35.2 GPM
PleasefileinServiceBinder
Ensure that the installationliterature of other componentsof the Vitodens 100 orVitodens 200 boiler isreferenced.
Product Information
Fig. 1
Vitodens 200or Vitodens 100
Fig. 2
Fig. 3
2
Contents Low-Loss Header, Type120/80
Contents Low-Loss Header,Type 80/50
H Low-loss header (Type 80/50)H Sensor wellH½” BSPT/NPT adaptor (for drainvalve)
H Drain valveH Air bleed plugH Installation Instructions
The temperature sensor (Part No.7134 240) for Vitodens 200 mustbe purchased separately.
Contents Low-Loss Header, Type120/80
Contents Low-Loss Header,Type 120/80
H Low-loss header (Type 120/80)H Sensor wellH½” BSPT/NPT adaptor (for drainvalve)
H Drain valveH Air bleed plugH Installation Instructions
The temperature sensor (Part No.7134 240) for Vitodens 200 mustbe purchased separately.
Before commencing with the installationof the low-loss header, check low-lossheader orientation with respect to yourheating system.
If (when holding the low-loss headerwith the air bleed connection facingyou, as illustrated in Fig. 1)...
H the boiler is located to the left of thelow-loss header and the heatingsystem is located to the right, installthe low-loss header as illustrated inFig. 1 (with sensor well and airbleed opening located at top),following the installation steps on thefollowing page.
H the boiler is located to the right of thelow-loss header and the heatingsystem on the opposite side, performthe following steps:
1. Rotate low-loss header 180ºclockwise (from its originalorientation, see Fig. 2).
2. Remove sensor well and air bleedplug from its factory-installedlocation (now located at the bottom).
3. Install sensor well and air bleed plugon opposite end (top of low-lossheader) as illustrated in Fig. 3.
4. Proceed with the installation steps onthe following pages (depending onlow-loss header model).
Sensor wellAir bleed opening½” plugDrain
Standard Equipment
General Layout
5285318v2
.6
Fig. 4
22”/560mm
3”/80 mm
4”/100 mm
14”/360mm
10½
”/270mm
NPT
3
Low-loss header information
DimensionsOverall depth 3¼”/84 mmOverall width 11”/280 mmOverall height 22”/560 mm
Please note that the pipe connectionson the system side are at a closerdistance from each other than those onthe boiler side.
Sensor well, 200 mmAir bleed plug (c/w O-ring)Boiler supplySystem supplySystem returnBoiler return½” plugDrain
If the optional low loss headerinsulation is being installed, add extraclearance between the back of the lowloss header and the finished wall (2½” /64 mm for Type 80/50 and 4” /102 mm for Type 120/80).
Model Type 80/50
Low-loss header part number*(Vitodens 100/200)
7134791*
Connector size (NPT) inches 1¼Distance between boilersupply nipples
inchesmm
14360
Distance between systemsupply nipples
inchesmm
10½270
Matching insulation boxpart number
9560994
Additional clearance ifinstalling optional insulation
inchesmm
2½64
* Please note that the temperature sensor (Part No. 7134 240) for Vitodens 200must be purchased separately.
Overall Dimensions (Type 80/50)5285318v2
.6
IMPORTANT
IMPORTANT
Fig. 5
36”/914mm
4¾”/120 mm
4”/100 mm
25½”/650mm
21½”/550mm
NPT
4
Low-loss header information
Dimensions
Overall depth 5½”/140 mm
Overall width 12¾”/320 mm
Overall height 36”/914 mm
Please note that the pipe connections
on the system side are at a closer
distance from each other than those on
the boiler side.
Sensor well, 200 mm (for WB2
only)
Air bleed plug (c/w O-ring)
Boiler supply
System supply
System return
Boiler return
½” plug
Drain
If the optional low loss header
insulation is being installed, add extra
clearance between the back of the low
loss header and the finished wall (2½” /
64 mm for Type 80/50 and 4” /
102 mm for Type 120/80).
Model Type 120/80
Low-loss header part number*(Vitodens 100/200)
7134792*
Connector size (NPT) inches 2
Distance between boilersupply nipples
inchesmm
25½650
Distance between systemsupply nipples
inchesmm
21½550
Matching insulation boxpart number
9560993
Additional clearance ifinstalling optional insulation
inchesmm
4102
* Please note that the temperature sensor (Part No. 7134 240) for Vitodens 200
must be purchased separately.
Overall Dimensions (Type 120/80)
5285318v2.6
IMPORTANT
IMPORTANT
Fig. 6
BSPT
5
LegendLow-loss header½” Conversion adaptor(from BSPT to NPT)Drain valveAir bleed plug (c/w O-ring)Sensor well, 200 mm (Vitodens 200only, except model WB2 6-24C)Temperature sensor (Vitodens 200only, except model WB2 6-24C)½” plug0)
1. Remove low-loss header and suppliedaccessories from carton (see sectionentitled “Standard Equipment” on thefront page for a list of componentparts included with your low-lossheader).
2. Clean threads of drain valveconversion adaptor if required,and apply moderate amount of pipesealant to male BSPT ½” threads.
3. Connect ½” BSPT male end of theconversion adaptor to femaleBSPT ½” connection at the bottomof the low-loss header.
4. Connect ½” NPT female end of theconversion adaptor to ½” maleend of the drain valve .
5. Connect ½” air bleed plug (c/wO-ring) to corresponding openingon the low-loss header (located onthe top or bottom front depending onlow-loss header orientation).
6. Connect sensor well tocorresponding opening at the top ofthe low-loss header.Use hemp and pipe sealant whenmaking this connection.
7. Tighten all connections.
8. Install low-loss header only in verticalposition (see Fig. 6). Follow theinstructions attached to the low-lossheader (see Figs. 4 and 5), indicatingsystem and boiler connection sides.Make system and boiler connectionsaccordingly.
9. Insert temperature sensor probe end(Part No. 7134 240) deep into
sensor well . The other end of thelow-loss header temperature sensorcomes prewired to terminals 3 and 4on plug X7. Insert plug X7 intocorresponding terminal on boilercontrol console. See Fig. 7 on page6.
Installation Steps5285318v2
.6
6
Plug X7 wired for installation with low-loss header only
Low-loss header sensor 1. Insert plug X7 of the low-loss headersensor (Fig. 7) into terminal X7 onthe Vitodens 200 boiler controlconsole (not applicable for modelVitodens 200, WB2 6-24C).
Plug X7 wired for installation with low-loss header and DHW storage tank
DHW sensorLow-loss header sensor
The DHW sensor of the DHWstorage tank comes prewired toterminals 1 and 2 on plug X7.To connect a low-loss header sensor inaddition to the DHW sensor, performthe following steps:
1. Remove and discard plug X7 fromthe low-loss header sensor.
2. Rewire low-loss header sensor wiresto terminals 3 and 4 on plug X7 ofthe DHW sensor. See Fig. 8.
3. Insert plug X7 into terminal X7 onthe Vitodens 200 boiler controlconsole (not applicable for modelVitodens 200, WB2 6-24C).
Electrical Connection (for Vitodens 200 only)
5285318v2
.6
X7
3 421
Fig. 7
X7
3 421
Fig. 8
7
5285318v2
.6
8
Viessmann Manufacturing Company Inc.750 McMurray RoadWaterloo, Ontario • N2V 2G5 • Canada1-800-387-7373 • Fax (519) 885-0887www.viessmann.ca • [email protected]
Viessmann Manufacturing Company (U.S.) Inc.45 Access RoadWarwick, Rhode Island • 02886 • USA1-800-288-0667 • Fax (401) 732-0590www.viessmann-us.com • [email protected]
Tec
hnical
inform
ationsu
bjec
tto
chan
gewith
outno
tice.
5285318v2
.6Printedon
environm
entally
friend
ly(rec
ycledan
drecy
clab
le)pa
per.