Vista 128 FBP

download Vista 128 FBP

of 144

Transcript of Vista 128 FBP

  • 7/27/2019 Vista 128 FBP

    1/144

    K0376 8/02 edited by Tech Support

    9,67$)%39,67$)%3&RPPHUFLDO)LUHDQG%XUJODU\3DUWLWLRQHG6HFXULW\6\VWHP

    ZLWK6FKHGXOLQJ

    ,QVWDOODWLRQDQG6HWXS*XLGH

    ONOFF

    1 OFF

    4 MAX

    7 INSTANT

    READY

    2AWAY

    5 TEST

    8CODE

    0

    3 STAY

    6BYPASS

    9CHIME

    #

    ARMED

    READY

    1 OFF

    4 MAX

    7INSTANT

    READY

    2AWAY

    5 TEST

    8CODE

    0

    3 STAY

    6BYPASS

    9CHIME

    #

    ARMED

    READY

    .

  • 7/27/2019 Vista 128 FBP

    2/144

    .

  • 7/27/2019 Vista 128 FBP

    3/144

    i i i

    Table of Contents

    List of Figures...................................................................................................................................vi

    Conventions Used in This Manual..............................................................................................vii

    SECTION 1: General Description ...............................................................................................1-1About th e VIS TA-128FB P /VIS TA-250FB P ............... .................. .................. ................. .................. ............. 1-1

    Fea tur es ...........................................................................................................................................................1-1

    SECTION 2: Partitioning and Panel Linking...........................................................................2-1

    Theory of P a rt itioning .....................................................................................................................................2-1

    Set ting -U p a P a rt itioned S yst em ...................................................................................................................2-1

    Com mon Lobby Logic ................. .................. ................. ................. .................. ................. ................... ........... 2-1

    Ma st er K eypa d S etup a nd Opera tion ............................................................................................................2-3

    P a nel Linking ..................................................................................................................................................2-4

    How to U se P a nel Linking ..............................................................................................................................2-5

    SECTION 3: Installing The Control............................................................................................3-1Mounting th e Cont rol Ca binet .......................................................................................................................3-1Ins ta lling th e Ca binet Lock ............................................................................................................................3-1

    G ra de A Merca nt ile P remises List ing G uidelines.........................................................................................3-1

    G ra de A Mercant ile Sa fe an d Vault List ing G uidelines ...............................................................................3-2

    Ins ta lling t he C ontrol's Cir cuit B oard ...........................................................................................................3-2

    Ins ta lling th e Keypa ds ....................................................................................................................................3-3

    Ins ta lling Ext erna l Sounders .........................................................................................................................3-4

    Auxiliar y Rela y Connections ..........................................................................................................................3-5

    Telephone Line Connections...........................................................................................................................3-7

    Wiring B urgla ry a nd P a nic D evices to Zones 1-8..........................................................................................3-8

    Ins ta lling RP M Devices ................................................................................................................................3-12Wireless Zone E xpa nsion ............... ................. ................. ................. ................. ................. .................... ...... 3-14

    Ins ta lling Out put Devices.............................................................................................................................3-17

    Ins ta lling a Remote Keys w itch.....................................................................................................................3-19

    Ins ta lling a 5140LED Ind icat or Module ......................................................................................................3-19

    Ins ta lling a Remote Keypa d Sounder ..........................................................................................................3-20

    Ins ta lling th e VA8200 P a nel Link Module..................................................................................................3-20

    Long Ra nge Ra dio C onnected to th e E CP ....................................................................................................3-21

    Long Ra nge Ra dio Connected to th e J 2 Triggers ........................................................................................3-23

    Ins ta lling th e Alpha P a ger Module..............................................................................................................3-23

    Access Cont rol U sing Vista Key ....................................................................................................................3-25

    Access Cont rol U sing t he P a ssP oint Access Contr ol Syst em .....................................................................3-26Ev ent Log Connections .................................................................................................................................3-27

    In st a lling th e 4285/4286 VIP Module .................. .................. .................. .................. .................. ................ 3-27

    Ins ta lling th e Audio Ala rm Verificat ion Module.........................................................................................3-27

    Connecting th e Tra nsformer ........................................................................................................................3-30

    Ea rt h G round Connections ...........................................................................................................................3-31

    Det ermining th e C ontrols P ower Supply Load ...........................................................................................3-31

    Det ermining t he Size of the St a ndby B a tt ery .............................................................................................3-33

  • 7/27/2019 Vista 128 FBP

    4/144

    Tabl e of Content s

    i v

    SECTION 4: Programming...........................................................................................................4-1

    Program Modes................................................................................................................................................4-1

    En terin g a nd E xiting P rogra mmin g Mode ....................................................................................................4-1

    Da ta Field P rogra mmin g Mode ......................................................................................................................4-1

    #93 Menu Mode P rogra mm ing .......................................................................................................................4-2

    Zone Number Designa tions ............................................................................................................................4-4

    Zone Response Type Definitions.....................................................................................................................4-6Zone Input Type Definitions...........................................................................................................................4-7

    P rogra mming for P a nel Linking.....................................................................................................................4-8

    P rogra mming for th e Alpha P a ger Module....................................................................................................4-8

    P rogra mming for Access Cont rol....................................................................................................................4-9

    P rogra mming for EC P Long R a nge Ra dio ...................................................................................................4-10

    P rogra mming for th e Ev ent Log...................................................................................................................4-10

    SECTION 5: Data Field Descriptions.........................................................................................5-1

    About Da ta Field P rogra mming .....................................................................................................................5-1

    P rogra mming Da ta Fields ..............................................................................................................................5-1

    SECTION 6: Scheduling Options.................................................................................................6-1

    Time Window D efinit ions ............... ................. ................. ................. ................. ................. ...................... ..... 6-2

    Open/Close S chedules Defin it ions .................. ................. .................. .................. ................. .................. ........ 6-3

    Scheduling Menu Mode...................................................................................................................................6-4

    Time Window s ............... .................. ................. ................. .................. ................. .................... .................. ..... 6-5

    D a ily Open/Close Sched ules .................. ................. .................. .................. ................. .................. ................. 6-5

    Holida y Schedules ...........................................................................................................................................6-6

    Time-D riven Ev ent s ................ .................. ................. ................. .................. ................. ................... .............. 6-7

    Limit a tion of Access Schedules ....................................................................................................................6-11

    Temporary Schedules....................................................................................................................................6-12

    User Scheduling Menu Mode........................................................................................................................6-13

    SECTION 7: Downloading Primer ..............................................................................................7-1G enera l Informa tion........................................................................................................................................7-1

    U na tt ended Dow nload ....................................................................................................................................7-1

    G ett ing On-Line w ith a Cont rol P a nel...........................................................................................................7-2

    Scheduled Dow nload .......................................................................................................................................7-3

    Dir ect-Wire Dow nload ing ...............................................................................................................................7-4

    Telco Handoff...................................................................................................................................................7-4

    SECTION 8: Setting the Real-Time Clock .................................................................................8-1

    G enera l Informa tion........................................................................................................................................8-1

    Set tin g th e Time a nd Da te .............................................................................................................................8-1

    SECTION 9: User Access Codes...................................................................................................9-1

    G enera l Informa tion........................................................................................................................................9-1

    U ser Codes & Levels of Auth orit y .................. ................... .................. .................. .................. .................. ..... 9-1

    Multiple Partition Access................................................................................................................................9-2

    Adding a Ma ster , Ma na ger, or Opera tor Code ..............................................................................................9-3

    Ch a nging a Ma st er, Ma na ger, or Operat or Code..........................................................................................9-4

    Adding a n RF Key to a n E xisting U ser..........................................................................................................9-4

    Deletin g a Ma ster , Ma na ger, or Opera tor C ode............................................................................................9-5

    Exit ing th e U ser Ed it Mode............................................................................................................................9-5

  • 7/27/2019 Vista 128 FBP

    5/144

    Table of Cont ent s

    v

    SECTION 10: Testing the System..............................................................................................10-1

    B a tt ery Test ...................................................................................................................................................10-1

    D ia ler Test ................ .................. .................. .................. .................. ................... ............... .................. ......... 10-1

    Fir e D rill Test (Code + [#] + 69) ................. ................... .................. .................. .................. ................... ...... 10-1

    One-Man Fir e Wa lk-Test (Code + [#] + 68) ................ .................. .................. .................. ..................... ...... 10-1

    B ur gla ry Wa lk-Test (Code + [5] TE S T)............................... .................. ................... .................. .................. 10-2

    Armed B urgla ry Sy st em Test .......................................................................................................................10-1Test ing Wireless Tra ns mit t ers ................. .................. .................. ................... .................. .................. ......... 10-1

    Trouble Cond it ions ................ ................. .................. ................. .................. ................. .................. ............... 10-4

    To th e In st a ller .................. ................... .................. .................. .................. .................. ............... .................. 10-5

    APPENDIX A: Regulatory Agency Statements .......................................................................A-1

    U L Ins ta lla tion Requir ement s....................................................................................................................... A-1

    U L864/NF P A Local Fir e ................. .................. .................. .................. .................. ................. ................. ..... A-1

    U L864/NFP A Cent ra l St a tion a nd Remot e St a tion Fir e ............................................................................. A-1

    U L609 G ra de A Loca l Mercant ile Pr emises/Loca l Mercan tile Sa fe & Vault ............................................. A-1

    U L365 P olice St a tion C onnected B urgla r Alar m ......................................................................................... A-2

    U L611/U L1610 Cent ra l St a tion B urgla ry Ala rm ........................................................................................ A-2

    Ca lifornia S ta te Fire Ma rsh a l (CS FM) Requir ements . ............................................................................... A-2

    APPENDIX B: Summary of System Commands......................................................................B-1

    APPENDIX C: Specifications......................................................................................................C-1

    APPENDIX D: Contact ID and Pager Event Codes................................................................D-1

    TAB LE OF CONTACT ID EVE NT COD ES ................................................................................................. D-1

    Ev ent Log a nd P a ger Alpha Descriptors.......................................................................................................D -2

    Index........................................................................................................................................ Index-1

    THE LIMITATIONS OF THIS ALARM SYSTEM

    ADEMCO LIMITED WARRANTY

  • 7/27/2019 Vista 128 FBP

    6/144

    vi

    List of Figures

    Figu re 3-1: Ins ta lling th e Lock...... . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . .3-1

    Figu re 3-2: Ca binet Atta ck Resist an ce Consider a tions ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . .. . . . . . . . . . . . . .. . . . . .3-2Figu re 3-3: Mount ing th e P C B oar d...... . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .3-2

    Figu re 3-4: Key pad C onnections to Cont rol Pa nel ..... . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .3-3

    Figu re 3-5: U sing A Su pplementa ry P ower Su pply ...... . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . .3-3

    Figu re 3-6: Ext erna l S ounder Conn ections...... . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . .3-5

    Figu re 3-7: Wiring Auxiliary Rela y for Alar m Activa tion ...... . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . ..3-6

    Figu re 3-8: Wiring Auxiliary Rela y for S moke Det ector Reset ..... . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . .3-6

    Figu re 3-9: 2-Wire S moke Det ector on Zone 1 (for zone 2 use ter mina ls 17 & 18)...... . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . .3-8

    Figu re 3-10: 4-Wire Sm oke Det ectors ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . .3-9

    Figu re 3-11: Wiring a 333P RM t o the Cont rol ..... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . .3-10

    Figu re 3-12: Wiring a 333P RM usin g a P ower S upply...... . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .3-10

    Figu re 3-13: Wiring La tchin g G la ssbrea ks t o Zone 8...... . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . .3-11

    Figu re 3-14: Wirin g a Norma lly C losed Sensor L oop for Ta mper S upervision ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .. . . . . .3-11Figu re 3-15: Wirin g a Norma lly Open S ensor Loop for Ta mper S upervision ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . .3-11

    Figu re 3-16: P olling Loop Connections to t he Cont rol P an el ..... . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . .3-13

    Figu re 3-17: P olling Loop Conn ections U sing On e 4297 Extend er Module ...... . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . .3-13

    Figu re 3-18: P olling Loop Connections U sing Mult iple Extend er Modules ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . .3-14

    Figu re 3-19: Ins ta lling t he 5881ENH C w ith Tam per P rotection ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . .. . . .3-15

    Figu re 3-20: 5881 RF Receiver (cover removed) ...... . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . ..3-15

    Figu re 3-21: 4204 Rela y Module...... . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .3-18

    Figu re 3-22: 4204CF Rela y Module...... . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . .3-18

    Figu re 3-23: Wiring th e FS A Modu le...... . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . .3-18

    Figu re 3-24: Remot e K eysw itch Wiring ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .3-19

    Figu re 3-25: Wiring th e 5140LE D In dicat or Module ...... . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . .3-20

    Figu re 3-26: Remote Keypa d S ounder Wirin g ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . .3-20Figu re 3-27: P a nel Linkin g B lock Dia gra m ....... . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . .3-20

    Figu re 3-29: Wiring Long Ra nge Ra dio to Keypa d Termin a ls...... . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . .3-22

    Figu re 3-30: Wiring th e Alpha P a ger Module...... . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . .3-24

    Figu re 3-31: Wiring th e Vista Key ...... . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . .3-26

    Figu re 3-32: Wiring th e VISTA G a tew a y Modu le ...... . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .3-26

    Figu re 3-33: P rint er C onnections t o th e 4100SM ....... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . .3-27

    Figu re 3-34: 4285/4286 VIP Module Conn ections ...... . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . .3-27

    Figu re 3-35: AAV Connect ions ...... . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . .3-30

    Figu re 3-36: Connecting th e B a ckup B a tt eries ...... . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . .3-34

    Figu re 7-1: Dir ect-Wire Dow nloa ding Conn ections...... . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . ..7-4

    VISTA-128FB P Su mma ry of Conn ections Dia gra m....... . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . Second to La st Pa ge

    VISTA-250FB P S umm a ry of Conn ections Dia gra m....... . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . . . .. . . . . . . . . . . .Insid e B a ck Cover

  • 7/27/2019 Vista 128 FBP

    7/144

    vi i

    Conventions Used in This Manual

    B efore you begin using this ma nua l, it is importa nt t ha t you understa nd the mea ning of the follow ing

    sym bols (icons).

    ULThese notes include specific information that must be followed if you are installing this system fora UL Listed application.

    These notes include information that you should be aware of before continuing with theinstallation, and that, if not observed, could result in operational difficulties.

    This symbol indicates a critical note that could seriously affect the operation of the system, orcould cause damage to the system. Please read each warning carefully. This symbol alsodenotes warnings about physical harm to the user.

    ZONE PROG?

    1 = YES 0 = NO 0

    Man y syst em options a re progra mmed in a n intera ctive mode by responding to

    alpha keypad display prompts. These prompts ar e shown in a single-line box.

    00 Additional system options are progra mmed via da ta fields, w hich a re indica ted by a sta r (T)follow ed by the da ta field number.

    PRODUCT MODEL NUMBERS:

    Unless noted otherwise, references to specific model numbers represent ADEMCO products.

  • 7/27/2019 Vista 128 FBP

    8/144

    v i i i

  • 7/27/2019 Vista 128 FBP

    9/144

    1-1

    S E C T I O N 1

    General Description

    About the VISTA-128FBP/VISTA-250FBPThe VISTA-128FBP /VISTA-250FB P is a n 8-part it ion, U L List ed commercial fire a nd bur glar y control pa nel w ith the

    following feat ures:

    U p to 128 zones for VISTA-128FB P ; 250 zones for VISTA-250FB P (har dw ired, polling loop, a nd w ireless zones)

    U p to 150 user codes for VISTA-128FB P ; 250 user codes for VIS TA-250FB P

    Supervision of Notificat ion Appliance Circuits, phone lines, keypads, R F receivers, an d output devices

    Scheduling capabilit ies (allows certain operations to be aut omat ed)

    The capa bility to link up to 8 control pa nels using P an el Linking Modules

    The VIS TA-128FB P /VISTA-250FB P can inter fa ce wit h t he following devices:

    Symphony (AUI)

    An alph a n umer ic pagin g device (VA8201)

    P a nel Lin k Module (VA8200)

    An EC P Long Range Radio that can send Contact ID messages

    An a ccess control system by using either the ADEMC O Pa ssP oint system (via the VISTA G at ewa y Module) or a

    VistaKey module (via the polling loop)

    ULThe access control function is not Listed for use with the VISTA-128FBP/VISTA-250FBP Control Panel in a ULinstallation.

    The system supports either the VistaKey or the VISTA Gateway Module, not both.

    NOTE: All references in this manual for number of zones, number of user codes, number of access cards,and the event log capacity, use the VISTA-250FBPs features. The following table lists the differencesbetween the VISTA-128FBP and the VISTA-250FBP control panels. All other features are identical.

    Feature VISTA-128FBP VISTA-250FBP

    Number of Zones 128 250

    Number of User Codes 150 250

    Number of Access Cards 250 500

    Event Log Capacity 512 1000

    VistaKey Modules 8 15

    Features

    Hardwire and Optional Expansion Zones

    P rovides 8 hardw ire zones.

    Su pports up t o 16 2-wir e smoke detectors ea ch on zone 1 an d zone 2 (32 total ).

    Automa tically resets 4-wire smoke detectors using t he J 2 output w hen a code + off is entered.

    Triggers th e built-in sounders on other h ar dwir ed smoke detectors if one smoke detector a nnun ciates a n a larm . This

    feat ure requ ires a 4204 Relay Module and /or the 333PRM.

    P rovides ta mper supervision on the ha rdw ire zones.

    Supports up t o 50 2-wire la tching gla ssbreak detectors on zone 8.

    Su pports up t o 242 ad ditiona l expan sion zones (120 for the VIS TA-128FB P ) usin g a b uilt-in polling (mult iplex) loop.

    Su pports up t o 250 wir eless zones (128 for the VIS TA-128FB P ) fewer if using ha rdw ire a nd/or polling loop zones.

  • 7/27/2019 Vista 128 FBP

    10/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    1-2

    ULThe 5881ENHC RF Receiver and the 5869 Holdup Switch Transmitter are listed for UL Commercial Burglaryapplications. All other RF receivers and transmitters are not listed for UL Commercial Burglary applications.

    Ca n program burglary zones as s i lent in t he a la rm condit ion (a larm output is s i lent and the keypad does not display

    or sound the a larm ).

    P rovides three keypad pan ic keys: 1 + (A), + # (B), and 3 + # (C).

    Peripherals Devices

    Supports u p to 31 a ddressa ble devices, (keypads, R F receivers, relay modules, etc.).

    Supervises devices (keypads, RF receivers, and relay modules) an d individua l relay s (up to 32), as w ell as syst emzones (RF receivers a nd keypa d pa nics).

    P rovides 96 output s using 4204 a nd 4204CF R ela y Modules, Fire Sy stem Annu ncia tors (FSA-8, FSA-24), and V-P lex

    Relay Modules can a ctivate outputs in response to system events (ala rm condition), at a specific t ime of day, a t

    rand om t imes, and ma nually using the #70 Relay Command Mode.

    Supports a dditiona l style-Y supervised Notificat ion Applian ce Circuits using a 4204CF.

    Supports t he ADEMC O 4285/4286 VIP Module, which a llows access to the sy stem from eith er a remote locat ion or

    on the premises

    ULThe 4285/4286 VIP Module is not Listed for use with the VISTA-128FBP/VISTA-250FBP Control Panel in a ULinstallation.

    Supports th e ADE MCO 4146 Keyswitch on a ny one of the system's 8 part it ions.

    Supports t he P S24 Pow er S upply Module, wh ich supplies tw o 24VFW, 1.7A full-wa ve rectified, unfiltered outputs.

    Arming/Disarming and Bypassing

    Ca n ar m the system w ith zones faulted (Vent Zone). These zones are a utoma tically bypassed a nd can be

    programm ed to aut omat ica lly unbypass when t he zone restores .

    Ca n a rm wit h ent ry/exit a nd in terior ty pe zones fa ulted (Arm w/Fa ult). These zones must be r estored before th e exit

    delay expires , otherwise an a la rm is generated.

    UL Vent zones cannot be used in UL installations.

    You must disable the Force Arm option (used in conjunction with the Arm w/Fault option), in UL installations.

    P rovides global arm ing capability (ability t o arm a ll partit ions the user code has a ccess to in one comma nd).

    Ca n Quick Exit an a rmed premises without ha ving to disarm a nd then rearm t he system.

    Ca n be arm ed in one of three STAY modes or Inst an t modes, automa tically bypa ssing specific burgla ry zones

    rega rdless of the zone response type.

    Can automatically bypass specific zones if no one exits the premises after arming (Auto-STAY). Auto-STAY will not

    occur if the system is ar med via a n RF t ra nsmitt er, VIP module, scheduling, access contr ol, keyswitch, or

    downloading.

    Ca n bypa ss a group of zones with one set of keystr okes.

    Supports E xit Error Logic, whereby the system can tell the dif ference between a regular a la rm a nd a n a larm caused

    by lea ving a n ent ry/exit door open. If t he system is not subsequent ly disa rmed, fa ulted ent ry/exit zone(s) and/or

    interior zones a re bypassed a nd t he system arms.

    Supports Recent C lose report, which is designed to notify the central sta tion tha t an ala rm ha s occurred wit hin 2

    minutes a f ter the exit delay has expired.

    Partitioning and Panel Linking

    Ca n contr ol 8 separ at e area s (part it ions) independently, each functioning as if it ha d its own separa te contr ol. Allfire zones must be assigned to pa rtit ion 1.

    P rovides a Common Lobby part i t ion, which can be programmed t o arm automat ica lly w hen the las t part i t ion is

    arm ed, and to disarm w hen the f irs t part i t ion is disarmed.

    P rovides a Mast er part it ion (9), used for the purpose of viewing th e sta tus of all part it ions at t he same t ime.

    Ca n display fire, burglary , panic, and t rouble conditions at a ll other pa rtit ions keypads (selectable option).

    Ca n link together up t o 8 contr ol panels. This allows users t o access an d control from a keypa d a nother control

    panel.

  • 7/27/2019 Vista 128 FBP

    11/144

    Section 1 - General Descri pti on

    1-3

    Scheduling

    Can automate system functions, such as arming, disarming, and activation of outputs (e.g. , lights).

    P rovides access schedules (for limit ing syst em a ccess to users by time).

    Provides an End User Output Programming Mode, allowing the user to control outputs.

    Access Control

    Su pports up t o 15 Vista Key m odules (15 access point s) (VISTA-128FB P supports 8 modules), wh ich a re used for

    access control. It is a single-door access control module.

    Su pport up t o 500 access car ds (250 for the VIS TA-128FB P ).

    Supports ADEMCO P assP oint system via one VISTA G at ewa y Module (VGM), for a fully integra ted a ccess control

    system.

    Ca n store a ccess control events in the event log.

    System Communication

    P rovides supervision of the phone lines (ma in a nd ba ckup)

    Supports t he 5140DLM optional ba ckup dialer for th e second phone line.

    Supports ADEMCO Contact ID ; ADE MCO High S peed; ADEMC O Express ; and 3+ 1, 4+ 1, and 4+ 2 ADE MCO and

    Ses coa /Ra dionics Low-Speed forma ts.

    The system is shipped defaulted for Contact ID communication. It is the only format capable of uniquely reporting all250 zones, as well as openings and closings for all 250 users. This requires central stations to be equipped with theADEMCO 685 receiver using software level 4.10 or higher to fully support all new VISTA-128FBP/VISTA-250FBPreport codes. If you need to update your 685 receiver, contact your distributor.

    Ca n send messag es such as ala rms, opens/closes, etc. to up to 8 paging services.

    P rovides two paging forma ts (alphan umeric requires the VA8201 Alpha P ag er Module; an d numeric sent directly

    by th e control)

    Supports D ynam ic Signaling feat ure, which prevents redundan t s ignals being sent to the centra l s ta t ion when both

    the built-in dialer a nd Long Ran ge Radio are used.

    P rovides an Audio Alar m Verificat ion (AAV) option t ha t permits voice dialog betw een an opera tor a t t he centra l

    sta tion and a person at the premises. An AAV unit , such as E ag le model 1250, is required.

    UL The Eagle Model 1250 AAV unit is not UL Listed.

    Downloading

    Supports upload and download capability .

    Ca n perform una ttended down loading (no one at the download ing computer).

    P rovides an I nsta ller U nat tended P rogram Mode. This a llows the insta ller to program th e download phone number,

    subscriber number, and primary central station receiver phone number without entering the normal program mode.

    Can periodically and automatically perform a scheduled download.

    UL Unattended and Scheduled Downloading are not UL Listed features.

    Ca n download a ccess control car dholder informa tion.

    Event Log

    P rovides a n event log (history log) tha t ca n store up to 1000 events (512 for the VIS TA-128FB P ).

    Ca n print the event log on a seria l printer or para llel printer using the VA8201 Alpha P ager Module.

    Ca n view the event log on an a lpha keypad or AUI.

  • 7/27/2019 Vista 128 FBP

    12/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    1-4

    Fire Walk-Test Mode

    P rovides an automat ic test of integrated V-Plex devices that have t he aut omat ic tes t fea ture.

    Ca n display a ll f ire zones that remain untested.

    Ca n log test results in the event log.

    Ca n report th e tes t results to the centra l s ta t ion.

    Additional Features

    P rovides tw o style-Y supervised Notificat ion Applia nce Circuits.

    P rovides an a uxiliary r elay (form C ) that can a ctivate a larm s tr oubles/supervisories, reset 4-wire smoke detectors, or

    a s a bat tery sa ver (removes power form non-critica l loads 4 hours a fter AC power loss).

    P rovides up to 60 insta ller-defined, custom w ords tha t ca n be used for zone descriptors.

    P rovides 35 keypad ma cro comman ds (each ma cro is a series of keypad comma nds of up to 32 keystrokes) using t he

    A, B, C, a nd D keys by part i t ion.

    P rovides cross-zone capa bility, which helps prevent false ala rms by preventin g a zone from going into ala rm un less

    its cross-zone is also fault ed w ithin a 5-minut e period.

    Conta ins a built-in Users Man ua l, which provides the end user with a brief explana tion of the function of a key

    wh en the user presses an y of the function keys on th e keypad for 5 seconds.

    P rovides trigger outputs, wh ich ma y interfa ce wit h Long Ran ge Radio equipment or other devices such as keysw itch

    LED s, or printer .

    P rovides an option to ha ve trouble an d supervisory conditions to aut omat ically clear from th e display wh en the zonereturn s to the read y/norma l stat e (entry of Code + OFF is not required).

    P rovides Ma int ena nce Signa l support for certa in smoke detectors (5808, 4192CP M, 4192SDM, 4192SDTM, 5192).

    At least one 2-line alpha keypad (6139/6160) must be connected to the system for programming (if you are usingkeypad programming), and must remain connected to the system in order to allow the primary user to programadditional user codes into the system at a later time.

  • 7/27/2019 Vista 128 FBP

    13/144

    2-1

    S E C T I O N 2

    Partitioning and Panel Linking

    Theory of PartitioningThis system provides the a bility to arm a nd disa rm up to 8 different area s, as if each ha d its own contr ol. These areas

    are ca lled part i t ions . A Part i t ioned system allows t he user to disarm certa in a reas while leaving other areas a rmed, or

    to limit access to certa in ar eas to specific individua ls. Ea ch system user can be a ssigned to operate a ny or all partit ions,

    an d can be given a different a uthority level in ea ch.

    B efore any thing ca n be assigned to those partit ions, you must first determine how ma ny par tit ions (1-8) ar e required.

    Following a re some facts you need to know a bout part it ioning.

    Keypads

    Ea ch keypad must be given a unique "a ddress " a nd be ass igned to one part i t ion. I t can a lso be ass igned to P art i t ion 9 ifMast er keypad operation is desired. (See Master Keypa d Setup an d Opera tion later in this section.)

    Zones

    Ea ch zone must be assigned t o one part it ion. The zones assigned t o a part it ion will be displayed on tha t par tit ion's

    keypad(s).

    All fire zones must be assigned t o partit ion 1to ensure t hat all F ire Test modes opera te correctly.

    Users

    Ea ch user may be given access to one or more pa rtit ions. If a user is to operate more tha n one par tit ion an d would like

    to ar m/disar m a ll or some of those partit ions with a single comma nd, th e user must be ena bled for G lobal Arming for

    those part it ions (when entering user codes).

    A user wit h a ccess to more than one partit ion (multiple access) can " log on" to one par tit ion from a nother par tit ion's

    keypad, provided tha t progra m field 2*18: Ena ble GOTO is enabled for ea ch part it ion he/she wa nts t o log on to from

    another.

    A part it ion can be selected as a "common lobby" pa rtit ion, and other pa rtit ions can a ffect this pa rtit ion by causin g

    ar ming/disar ming of th is part it ion to be aut omated (see Common Lobby Logic lat er in t his section).

    Setting-Up a Partitioned System

    The basic steps to settin g up a pa rtit ioned system are described below. If you need more informa tion on how to programthe options, see SECTI ON 4: Programm ing.

    1. Determ ine how ma ny part it ions the system will consist of (programm ed in field 2*00).

    2. Assign keypads to part it ions (Device Programm in gin the #93 Menu M ode).

    3. Assign zones to part it ions (Zone Programm in gin the #93 Menu M ode).

    4. Confirm zones ar e displayed at the keypad (s) assigned to those part it ions.

    5. Assign users to part it ions.

    6. En able the G OTO feature (program field 2*18) for each part it ion a multiple-access user ca n log on to (a lpha keypad

    only).7. P rogra m par tit ion-specific fields (see the SECTION 5: Data Field D escr i pt ions).

    Common Lobby Logic

    When a n insta lla t ion consis ts of a par t i t ion sha red by users of other part i t ions in a building, tha t sha red part i t ion ma y

    be assigned a s the " common lobby" pa rtit ion for the syst em (program field 1*17). An example of this might be in a

    medical building w here there a re tw o doctors offices a nd a common entr an ce area (see example tha t follows

    explanation).

    The Common Lobby feature employs logic for automa tic armin g an d disar ming of the common lobby. Two programm ing

    fields determine the wa y the common lobby will react relat ive to the stat us of other part it ions. They ar e: 1*18 Affects

    Lobby a nd 1*19 Arms Lobby.

  • 7/27/2019 Vista 128 FBP

    14/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    2-2

    1*18 Affects Lobby (must be programmed by partit ion)

    Sett ing th is field to 1 for a specific part it ion causes tha t pa rtit ion to a ffect t he operat ion of the common lobby a s follows:

    a . When the f irs t part i t ion that a f fects the lobby is disarmed, the lobby is automat ica lly disarmed.

    b. The common lobby can not be ar med unless every partit ion selected to affect the lobby is armed.

    1*19 Arms Lobby (must be programmed by partit ion)

    Sett ing th is field to 1 for a specific part it ion causes tha t pa rtit ion to a ffect t he operat ion of the common lobby a s follows:

    a. The common lobby can not be ar med unless every partit ion selected to affect the lobby is armed.

    b. Arming a part i t ion that is programmed to arm t he lobby causes the system to automa t ica lly a t t empt to arm thelobby. If an y faults exist in the lobby par tit ion, or if an other partit ion tha t a ffects the lobby is disarmed, the lobby

    cannot be arm ed, and th e message "U NABLE TO ARM LOB BY P ARTITION" is display ed.

    You cannot select a partition to "arm" the lobby unless it has first been selected to "affect" the lobby. Do not enablefield 1*19 without enabling field 1*18.

    The following chart sums up h ow th e common lobby par tit ion w ill operat e.

    1*18

    Affects Lobby

    1*19

    Arms Lobby

    Disarms whenpartition disarms?

    Attempts to armwhen partitionarms?

    Can be armed ifother partitionsdisarmed?

    0 0 NO NO YES1 0 YES NO NO

    1 1 YES YES NO

    0 1 ---ENTRY NOT ALLOWED---

    Example

    Here is an example of how the lobby would react in a typical setup.

    OFFICE 1 OFFICE 2

    MAIN ENTRANCE

    COMMON LOBBY

    V128BP-001-V0

    U ser #1 has a ccess to Office #1 and the Common Lobby.

    U ser #2 has a ccess to Office #2 and the Common Lobby.

    Office #1 is set up to affect the C ommon Lobby, but not ar m it .Office #2 is set up to affect a nd a rm t he Common Lobby.

    NOTE: In t he ta bles below, the notat ions in par entheses ( )indicate t he current s ta tus of the other part i t ion w hen the user

    ta kes act ion.

    Sequence #1:

    Office 1 Office 2 Lobby Action

    User #1: Disarms (Armed) Disarms

    User #2: (Disarmed) Disarms No Change

    User #1: Arms (Disarmed) No change

    User #2: (Armed) Arms Arms

  • 7/27/2019 Vista 128 FBP

    15/144

    Section 2 Parti t i onin g and Panel Li nki ng

    2-3

    Sequence #2:

    Office 1 Office 2 Lobby Action

    User #2: (Armed) Disarms Disarms

    User #1: Disarms (Disarmed) (No change)

    User #2: (Disarmed) Arms No Change

    User #1: Arms (Armed) No Change

    Notice that in sequence #1, becau se Office #2 was t he last to ar m, the lobby also a rmed (Office #2 is program med toaffect a nd a rm t he lobby). In sequence #2, the lobby could not a rm w hen Office #2 armed, because Office #1, wh ich

    affects t he lobby, wa s s t i l l disarmed.

    When Office #1 ar med, the lobby still did not a rm because Office #1 wa s not programmed t o arm t he lobby. U ser #1

    would have to a rm the lobby manua lly. Therefore, you would w ant to program a part i t ion to a f fect a nd a rm t he lobby if

    the users of that part it ion are expected to be the last t o leave th e building.

    Do not assign partition 1 as the common lobby if fire zones are being used in the system. All fire zones must beassigned to partition 1 to ensure all Fire Test modes operate correctly.

    How User Access Codes Affect the Common Lobby

    Codes with Global Arming

    If a code is given "global a rming" wh en it is defined (see the SECT I ON 9: U ser Access Codes), the keypad prompts the

    user to select the part it ions they wa nt to arm . Only the part it ions the user ha s access to ar e displayed. This allows the

    user to choose the partit ions to be a rmed or disarmed, an d so eliminat es the "a utoma tic" opera tion of the lobby. Keep in

    mind, however, that i f a user a t t empts to arm a ll , and another "a f fect ing" part i t ion is disarm ed, the user cannot arm thelobby, an d the messa ge "U NABLE TO ARM LOB B Y PARTITION" is displayed.

    Codes with Non-Global Arming

    If a user ar ms w ith a non-globa l code, the lobby partit ion operation is au tomat ic, a s described by fields 1*18 an d 1*19.

    Other Methods of Arming/Disarming

    Common Lobby logic remains a ctive when a rming or disarm ing a part it ion tha t a ffects a nd/or arms t he common lobby in

    one of the following m an ners:

    Quick-Arm

    Keyswitch

    Wireless But ton Wireless Keypad

    Arming/Disarming Remotely

    If a user arm s or disarms remotely (through Compass download ing softwa re), the lobby does not a utoma tically follow

    another part i t ion that is programm ed to arm or disarm t he lobby. The lobby must be armed separat ely, a f ter arming a ll

    affecting partit ions first .

    Auto-Arming/Disarming

    If scheduling is used to aut omatica lly arm an d/or disarm pa rtit ions, the common lobby partit ion does not automa tically

    follow anoth er partit ion that is program med to arm or disarm the lobby. The lobby part it ion must be scheduled to

    ar m/disar m an d must be scheduled as the last par tit ion to arm.

    If you are using auto-arming, make sure that the Auto-Arm Delay and Auto-Arm Warning periods, for the lobbypartition, (fields 2*05 and 2*06) combined are longer than that of any other partition that affects the lobby. This

    causes the lobby to arm last.

    Master Keypad Setup and Operation

    Although th is system ha s eight actua l partit ions, it provides an extra part it ion strictly for the purpose of a ssigning

    keypads as Ma ster keypads for the system.

    Assigning any keypad to Partit ion 9 in Device Programm ingin the #93 Menu M odemakes that keypad a Master keypad.

    A Mast er keypad reflects the sta tus of the entire system (Pa rtit ions 1-8) on its display at one time. This is useful

    beca use it eliminat es the need for a building security officer to ha ve to log on to va rious partit ions from one part it ion's

    keypad to f ind out w here an a larm has occurred.

  • 7/27/2019 Vista 128 FBP

    16/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    2-4

    The following is a typical display:

    S Y S T E M 1 2 3 4 5 6 7 8

    S T A T U S R R N N A B

    P ossible stat us indications include:

    A = Armed Awa y S = Armed Stay M = Armed Maximum C = Comm Fa i l

    I = Armed Ins t an t R = R ea dy N = Not Ready

    B = B ypassed/Read y = Ala rm T = TroubleF = Fire Alarm P = AC Power Fa ilure L = Low Sys tem Ba t tery

    To obta in more informat ion rega rding a pa rticular pa rtit ion, enter [] + P ar tit ion No. (e.g. , [] + [4]). This allows

    viewing only of tha t part i t ion. In order to a f fect that part i t ion, the user must use a code tha t ha s access to that

    part it ion. Also, in order for a user of any pa rtit ion to log on to P ar tit ion 9 to view the sta tus of all par tit ions, tha t user

    must ha ve access to all partit ions. Otherw ise, access is denied.

    The following is displayed for a fault condition on Zone 2 (Loading Dock Window) on Partition 1 (Warehouse) when a

    user logs on from a keypad on P ar tit ion 9:

    WHSE DISARMED

    HIT FOR FAULTS

    Pressing [] causes the following display to appear a t P ar tit ion 1's keypad(s):

    FAULT 002 LOADING

    DOCK WINDOW

    Additional zone faults a re display ed one at a t ime. To display a n ew par tit ion's sta tus, press [] + Pa rt i t ion No.

    The Armed LE D on a Ma ster keypad is lit only if all part it ions have been arm ed successfully. The Ready L ED is lit only

    if all par tit ions are "r eady t o ar m." Neither LED is lit if only some part it ions are armed a nd/or only some part it ions are

    ready.

    Press [] + [0] or [] + [9] to return t o the ma ster par tit ion. Otherw ise, if no keys are pressed for 2 minutes, the systemautoma t ica lly returns to the master part i t ion

    The sounder on a Ma ster keypad reflects t he sound of the most crit ica l condition on all of the part it ions. The priority of

    the sounds, from most to least crit ica l, is as follows:

    1. P uls ing f ire a la rm sounds

    2. Stea dy burglar a larm sounds

    3. Trouble sounds (rapid beeping)

    Silence the sounder by pressing an y key on the Master keypa d or a keypad on th e partit ion w here the condition exists.

    A Master keypad uses the same panics as Partition 1. Master keypad panics are sent to Partition 1, and will activateon Partition 1. Therefore, panics must be programmed for Partition 1.

    Panel Linking

    U p to eight VISTA-128FBP /VISTA-250FBP control pa nels ma y be netw orked, enabling a user t o control t he fea tures of

    all contr ol panels from a single locat ion. The pan el linking bus supports a n end-to-end net work lengt h of up t o 4,000 feet,

    ma king it ideal for mult i-building environments (e.g. , a shopping ma ll, college campus, etc.).

    UL Panel Linking is not permitted in UL installations.

    P a nel linking r equ ires a VA8200 P a nel Link Module (PL M) on each VIS TA-128FB P /VISTA-250FBP . U sers can lin k

    (access other control panels) in a ny of th ree different m odes: Single-P a rtit ion, S ingle-P an el Mode, Multi-P a rtit ion, Multi-

    P an el Mode, Multi-P an el View Mode. These modes are described later in th is section.

    Ea ch PLM connects to th e ECP bus on the control panel an d commun icates to each P LM via a n RS-485 bus (3-wire

    tw isted cable run ) with a ma ximum w ire-run of 4000 feet end-to-end.

  • 7/27/2019 Vista 128 FBP

    17/144

    Section 2 Parti t ionin g and Panel Li nki ng

    2-5

    Users 001-050 are the only users that can perform panel linking and are automatically assigned panellinking access when added to the system.

    An alpha keypad must be used for panel linking.

    The system may take up to 7 seconds to respond to a command when in a panel linking mode

    NOTE: A user cannot access part it ions or panels tha t th ey have not been assigned to.

    Panel Link Module Supervision

    The Panel Link Module can be supervised for its connection to the control panel. This modules supervisory zone is 8xx,

    wh ere xx = the E CP ad dress of the PLM. You must program t ha t zone with r esponse type 05 (Day/Night) in Zone

    Programmingin the #93 Menu M ode(refer to th e Programm ing Guid efor detailed program ming inst ructions). If you

    wa nt t o report the supervisory fa ilure to the centra l sta tion an d/or to a paging service, the a ppropriate reporting

    param eters for tha t zone must be programm ed.

    If you wa nt t he supervisory fa ilure of other P LM(s) on other linked contr ol pa nels to display on this control pan el, they

    must be programmed into Zone Programm ingin the #93 Menu M odewit h response type 14 in th is control pan el (refer to

    t he Programm ing Guidefor detailed programm ing instructions). The panel ID n umber for each module must m at ch the

    panel ID n umber programmed in Device Programm in gof its hos t VIS TA-128FB P /VIS TA-250FB P .

    How to Use Panel Linking

    P an el Linking can be used in any of three different modes:

    Single-Partit ion, Single-Panel displays sta tus of a pa rtit ion on a remote control pan el and a llows control of tha t

    remote control panel.

    Multi-P ar tit ion, Multi-P an el Mode displays sta tus a nd a llows arm ing/disar ming of multiple pa rtit ions a t once on a

    remote control panel.

    Multi-P an el View Mode displays sta tus a nd a llows a rming/disar ming of multiple remote control pan els at a t ime.

    NOTE: A user will not be able to access or view pa rtit ions or panels tha t th ey ha ve not been assign ed to.

    Single-Partition Single-Panel Mode

    To access the S ingle-P ar tit ion, Single P an el mode, perform the following steps:

    Step Action

    1 Enter User Code (for users 001-050) + [#] + [86].

    2 Ent er the panel ID number (01-08) of the panel you wan t to link to.

    3 En ter the part it ion number of the panel. The keypad displays AWAITING PANEL LINK . After a few

    seconds, the keypad displays t he s ta tus of the part i t ion a long with t he panel ID n umber and pa rt i t ion

    number flashing in th e upper right -ha nd corner. The user now h as full control of the remote contr ol panel.

    All functions can be performed except the following:

    Those limited by the users au thority level.

    The user cannot enter Installer Program mode

    The user cann ot execute a nother pa nel linking mode.

    NOTE:To execute an other pan el linking mode or t o access a different remote pan el, the user must first exitthis m ode (return to the origina l contr ol panel).

    4 To exit, ent er th e User Code (for users 001-050) + [#] + [85]. After a few seconds, the keypad displays t hesta t us of the original par t i t ion for the keypad.

  • 7/27/2019 Vista 128 FBP

    18/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    2-6

    Multi-Partition Multi-Panel Mode

    To perform a function in the Mult i-P ar tit ion, Multi P an el mode, follow the st eps below:

    Step Action

    1 Enter User Code (for users 001-050) + [#] + [88].

    The keypad displays the followin g:

    P ANELn n 1 2 3 4 5 6 7 8

    STATU S x x x x x x x xwh ere nn = panel ID number (01-08), 12345678 a re the pa rtit ion numbers a nd xxxxxxxx is the st at us of

    each part i t ion of that panel. Sta t us indicat ions include:

    A = Armed Awa y S = Armed Stay M = Armed Maximum

    I = Armed Ins t an t R = R ea dy N = Not Ready

    B = B ypassed/Read y = Ala rm T = Trouble

    F = Fire Alarm P = AC P ower Failure L = Low Sys tem Ba t tery

    C = Comm Fa i l

    NOTES: See ta ble later in t his section for priority of displays.

    A under a pa rtit ion number indicat es the user does NOT ha ve access to tha t par tit ion.

    2 The follow ing funct ions can be performed:

    Press [1] to a t t empt to disarm all part i t ions .

    P ress [2] to at tempt t o arm AWAY all part it ions.P ress [3] to at tempt to ar m STAY all part it ions.

    P ress [4] to a t tempt to arm MAXIMUM a ll part i t ions.

    P ress [7] to at tempt to ar m INS TANT all par tit ions.

    P ress [] to read the s ta tus of the next panel.

    Press [#] key to read th e stat us of the previous pan el.

    Press [0] to exit mode. After a few seconds, the keypad displays the status of the original partit ion of theoriginal pa nel for the keypad. Also, this mode w ill end in a pproxima tely 120 seconds if no keys a re pressed.

    NOTES:

    When performing any of the arming commands, if there are faults in any of the partit ions, none of the

    part it ions will arm . These faults must be corrected or bypassed before at tempting t o arm.

    When performing either a STAY or INS TANT ar m comman d, the sy stem a lwa ys a rms in m ode 1 (see the

    VISTA -128FBP/ VIST A-250FBP User Guidefor a d eta iled explana tion of the STAY an d IN STANT ar mingmodes).

    The user ca nnot execute an other pa nel linking mode. To execute anoth er pan el linking mode or to a ccess a

    different remote panel, the user m ust first exit t his mode (return to the original control panel).

  • 7/27/2019 Vista 128 FBP

    19/144

    Section 2 Parti t ionin g and Panel Li nki ng

    2-7

    Multi-Panel View Mode

    To perform a function in th e Multi-P anel View m ode, follow the st eps below:

    Step Action

    1 Enter User Code (for users 001-050) + [#] + [87].

    The keypad d isplays the following typical display :

    ALLP ANEL 1 2 3 4 5 6 7 8

    STATU S x x x x x x x x

    wh ere 12345678 ar e the panel ID n umbers an d xxxxxxxx is the overall sta tus of each panel. Sta tus

    indicat ions include:

    A = Armed Awa y S = Armed Stay M = Armed Maximum

    I = Armed Ins t an t R = R ea dy N = Not Ready

    B = B ypassed/Read y = Ala rm T = Trouble

    F = Fire Alarm P = AC P ower Failure L = Low Sys tem Ba t tery

    C = Comm Fa i l

    NOTE:See ta ble later in this section for priority of displays.

    2 The follow ing funct ions can be performed::

    P ress [1] to a t tempt to disarm a ll part i t ions on a ll panels .

    P ress [2] to at tempt t o arm AWAY all part it ions on all pa nels.

    P ress [3] to att empt to arm S TAY all part it ions on all panels.

    P ress [4] to a t tempt to arm MAXIMUM a ll part i t ions.

    P ress [7] to at tempt to ar m INS TANT all par tit ions.

    P ress [0] to exit mode. After a few seconds, the keypad displays the status of the original partit ion of theoriginal pa nel for the keypad. Also, this mode w ill end in a pproxima tely 120 seconds if no keys a re pressed.

    NOTES:

    When performing any of the arming commands, if there are faults in any of the partit ions of a panel, the

    system will not arm tha t panel, but will a rm a ll the other part i t ions of the other panels .

    When performing either a STAY or INSTANT a rm comman d th e system a lwa ys a rms in m ode 1.

    The user cannot execute another pa nel linking mode. In order to perform an other panel linking mode or to

    a ccess a different r emote panel, the user must first exit this m ode (return to the original control panel).

    Priority of Displays for Multi-Partition and Multi-Panel Modes

    This ta ble shows t he priority of displays if more tha n one of these conditions exists at the sa me time.

    Priority Description Display Priority Description Display

    1 Fire Alar m F 8 Not Ready N

    2 All Other Alar ms 9 Ready R

    3 AC Loss P 10 Armed STAY S

    4 Comm Fail C 11 Arm ed AWAY A

    5 System Low Ba t tery L 12 Armed INS TANT I

    6 Trouble T 13 Armed MAXIMU M M

    7 Bypass B

  • 7/27/2019 Vista 128 FBP

    20/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    2-8

  • 7/27/2019 Vista 128 FBP

    21/144

    3-1

    S E C T I O N 3

    Installing The Control

    This section describes the procedures for mounting a nd w iring t he contr ol panel an d a ll the peripheral devices.

    NOTE: All references in this manual for number of zones, number of user codes, number of access cards,and the event log capacity, use the VISTA-250FBPs features. SeeSECT I ON 1 : Gene r a l Desc r i p t i o nfor thetable listing the differences between the VISTA-128FBP and the VISTA-250FBP control panels.

    Mounting the Control Cabinet

    To mount the contr ol cabinet, perform t he following steps:

    Step Action

    1 B efore mounting the circuit board, remove the meta l knockouts for the wirin g entry tha t you will be using.

    DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEENINSTALLED.

    2 U sing fast eners or an chors (not supplied), mount the control cabinet to a sturdy wa ll in a clea n, dry ar ea

    tha t is n ot readily accessible to the genera l public. The ba ck of the ca binet ha s 4 holes for this purpose.

    ULTo provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2Cabinet Attack Resistance Considerationsto follow.

    Installing the Cabinet Lock

    To install the lock, perform the following steps:

    Step Action

    1 Remove cabin et door, th en remove th e lock

    knockout from the door. Insert the key int o the

    lock.

    2 P osition the lock in the hole, ma king certain

    tha t the la tch will make contact with the la tchbra cket w hen t he door is closed.

    3 When correctly positioned, push the lock unt il

    it is held securely by its sna p tabs.

    U se a n Ademco No. K4445 Lock (supplied).

    CABINET DOORBOTTOM

    LOCKED

    UNLOCKED

    cab_

    lock_snap-001-V0

    ADE

    MCO

    ADE

    MCO

    PUSH

    SNAPTAB

    SNAPTAB

    PUSHON LOCKUNTIL IT

    IS SEATEDSECURELY

    STEP 2STEP 1

    CHECKPOSITION

    F i gu r e 3 -1 : I n st a l l i n g t he Loc k

    Grade A Mercantile Premises Listing Guidelines

    The panel door must be supervised. Mount the

    clip-on tamper switch (supplied) to the cabinet's

    r ight s ide wall as shown in the diagra m below, and

    wire it to zone 6.

    U se a bell with a t am per-protected housing such as

    the ADE MCO AB12. The bell housing's tamper

    switch an d inner ta mper l inings must a lso be wiredto zone 6.

    Assign zone 6 to a burglary part it ion. P rogram it

    for da y t rouble/night ala rm (zone t ype 5) wh en only

    one burgla ry part it ion is used. P rogram it for 24-

    hr. a udible ala rm (zone type 7) wh en more than one

    burglary pa rt i t ion is used.

    All wiring betw een the bell and pa nel must be run

    in conduit . Rema ining w ires do not need to be run

    in conduit .

    All wiring t ha t is not run in conduit must exit from

    the knockout openings on the bott om or back of the

    cabinet .

    All unused knockouts m ust be plugged using the

    disc plugs and carria ge bolts (supplied), as

    indicat ed in the diagra m below.

    Fa sten the cabinet door to the cabinet ba ckbox

    using the 18 one-inch-long Phillips-head screws

    (supplied) aft er all wiring, progra mming, a nd

    checkout procedures have been completed.

  • 7/27/2019 Vista 128 FBP

    22/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    3-2

    PCBOARD

    (Shows typical local Grade A listing installation)

    RUN BELL WIRESIN CONDUIT

    PLUG THISKNOCKOUT

    PLUG THISKNOCKOUT

    PLUG THISKNOCKOUT

    PLUG THISKNOCKOUT

    RUN ALL REMAININGWIRE THROUGH HERE

    CLIP-ON DOORTAMPER SWITCH

    CABINETMOUNTING

    HOLE(4 PLACES)

    TO PLUG AN UNUSED KNOCKOUT OPENING,REMOVE KNOCKOUT AND INSTALL A PAIR OF

    DISC PLUGS AND A CARRIAGE BOLT AS SHOWN.

    KNOCKOUT

    OPENING

    HEX NUT ANDWASHER

    DISC PLUGS (DIMPLES IN DISCPLUG SHOULD REGISTER INSIDE

    KNOCKOUT OPENING)

    CARRIAGE BOLT

    CABINET SIDE WALL(OUTSIDE)

    cabattack-001-V0

    F i gu r e 3 -2 : Ca b in et A t t ack Resis t an ce Consid er a t i ons

    Grade A Mercantile Safe and Vault Listing Guidelines

    Follow t he guidelines given above for Gr ad e AMercantile Premises listing.

    Mount a shock sensor such as S entrol No. 5402 to

    the control's backbox. Follow th e manu facturer's

    instru ctions for proper sensor mounting. Thissensor also must be wired to zone 6.

    For sa fe and va ult applica t ions , a U L Lis tedconta ct must be used inside the cabinet thr ough

    one of the knockouts for pry-off ta mper purposes.This sensor a lso must be w ired to zone 6.

    Installing the Control's Circuit Board

    To install t he circuit board in the ca binet, perform t he

    following steps:

    Step Action

    1 Ha ng the th ree mounting clips on the ra ised

    cabinet tabs . Refer to Fi gure 3-3(Detail B ).Make sure the clip orienta tion is exactly a s

    shown in the dia gram to avoid da mage. This

    will also avoid problems with insertion and

    removal of the P C board.

    2 Insert the t op of the circuit board in to the slots

    a t the top of the cabinet . Make certa in tha t the

    board r ests in the slots a s indicated (Deta il A).

    3 Sw ing the ba se of the board into the mounting

    clips an d secure the board t o the cabinet wit hthe accompanying screws.

    Notes:

    Make certa in tha t the mounting screws a re t ight .

    This ensures th at there is a good ground connection

    between the PC board a nd the cabinet .

    Dress field wirin g a wa y from the microprocessor

    (center) section of the PC board. U se the loops on

    the left an d right sidew alls of the cabinet for

    an choring field wiring using tie wra ps (Deta il C).

    These steps are importa nt t o minimize the risk ofpanel RF interference with television reception.

    +

    +

    +

    DETAIL CSIDE VIEWOF SLOTS

    DETAIL ASIDE VIEW OFBOARD INSERTEDINTO SLOTS

    DETAIL BSIDE VIEW OF SHORTMOUNTING CLIPS(TYP.)

    hi_end_mnt-PCB

    F i gu r e 3 -3 : Moun t i n g t he PC Boa r d

  • 7/27/2019 Vista 128 FBP

    23/144

    Section 3 - I nstal l i ng the Contr ol

    3-3

    Installing the Keypads

    U p to 31 a ddressable keypads (ad dresses 00-30)

    ma y be used (you may need to use an auxiliarypower supply if the 1A aux. output is exceeded).

    U se a 2-line a lpha displa y, 6139/6160 (gra y or r ed)

    (check wit h local AHJ for approva l of keypa d color).

    To wire t he keypads, perform t he following steps:

    Step Action

    Determine wire gauge by referring to the

    Wire Run Length /G au ge ta ble below.

    Wire Run Length/Gauge Table

    Wire Gauge Length

    #22 gauge 450 feet

    #20 gauge 700 feet

    #18 gauge 1100 feet

    #16 gauge 1750 feet

    1

    2 Wire keypads to a single wire run or connect

    individual keypads to separat e wire runs .

    The ma ximum wire run length from th e

    contr ol to a keypa d, wh ich is homerun ba ckto the control, must n ot exceed the length slis ted in the ta ble.

    3 Run field wirin g from the control to the

    keypads (using sta nda rd 4-conductor cable

    of the wire ga uge determined in st ep 1).

    4 Conn ect keypa d(s) to ter mina ls 11, 12, 13,

    an d 14 on t he contr ol boar d, see Fi gur e 3-4.

    NOTE: If using only one keypad, it ma y beconnected to either Keypa d P ort 1 or 2, and

    must be mounted on, or w ithin t hree feet of

    the cabinet. The keypad on P ort 2 is

    electrically isolated from t hose on P ort 1 and

    will continue to function even if w iringproblems prevent t he other keypads from

    working properly.

    The length of all wire runs combined,regardless of the wire gauge, must notexceed 2000 feet when unshielded quadconductor cable is used (1000 feet ifunshielded cable is run in conduit, whichacts a shield, or if shielded cable is used).

    If more than one keypad is wired to one run,then the above maximum lengths must bedivided by the number of keypads on the run(e.g., the maximum length is 225 feet if twokeypads are wired on a #22 gauge run).

    RED

    KEYPADS

    BLACK

    GREEN

    YELLOW

    CONTROLTERMINALS

    12

    13

    14

    11

    kypd_conn-001-V0

    F i gu r e 3 -4 : Keypad Con nect i ons to Con t r o l Pan el

    Addressing the Keypads

    The keypads will not operate until they arephysically addressed and enabled in thesystem's Device Programmingin the #93 MenuMode.

    Set each keypad for a n individua l a ddress (00-30)

    a ccording to the keypad's instructions. Set a n alpha

    keypad for ad dress 00 an d other keypads for higher

    a ddresses (00 an d 01 are enabled in t he system's

    default progra m). Any keypads set for ad dress 02 an d

    above will appear blank unt il they a re enabled in the

    system's program . Ea ch keypad must be set for a

    dif ferent address .

    Do not set any keypads to address 31(nonaddressable mode). They will interferewith other keypads (as well as other devices)connected to the keypad terminals.

    If an OC or OPEN CIRCUIT message is

    present on a keypad, data from the control isnot reaching the keypad. Please check yourwiring.

    Supplementary Power Supply for Additional Keypads

    When t he controls a uxiliary power loa d for a ll devices

    exceeds 1A, you can power a dditiona l keypads from a

    regula ted 12VDC power supply (e.g. , ADE MCO

    AD12612 (1.2A)). U se a UL List ed, bat ter y-ba ckedsupply for UL installations.

    Connect t he addit ional keypads as shown in Fi gure 3-5,

    using the keypad w ire colors shown. Be sure to observe

    the current r at ings for the power supply used.

    Make connections directly to the screwterminals as shown in Figure 3-5. Make noconnection to the keypad blue wire (ifpresent).

    Be sure to connect the negative () terminalon the power supply unit to terminal 7 () onthe control.

    + +

    11 12 13 14

    SUPPLEMENTARY

    POWER SUPPLY

    CONTROL TERMINAL STRIP

    AUX. AUX. DATAIN

    DATAOUT

    IMPORTANT:MAKE CONNECTIONS

    DIRECTLY TO SCREWTERMINALS AS SHOWN.

    MAKE NO CONNECTION

    TO THE KEYPAD BLUEWIRE (IF PRESENT).

    TOKEYPADREDWIRE

    TOKEYPADBLKWIRE

    TOKEYPADYELWIRE

    TOKEYPADGRNWIRE

    TOKEYPADBLKWIRE

    TOKEYPADREDWIRE

    TOKEYPADGRNWIRE

    TOKEYPADYELWIRE

    pwr_sup-002-V0

    F i gu r e 3 -5 : Us i ng A Supp l emen t a r y Powe r Supp l y

  • 7/27/2019 Vista 128 FBP

    24/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    3-4

    Installing External Sounders

    The VIS TA-128FB P /VIS TA-250FB P pr ovides t w o

    Notifica tion Applian ce Circuits for operatin g fire a nd

    burgla ry ala rm notificat ion appliances. Ea ch circuit is

    ra ted a s follows: 10VDC 14VDC, 1.7A ma x., power-

    limited. NOTE:The tota l a la rm current draw n fromAuxiliary P ower 1, Auxiliary P ower 2, polling loop, Bell

    1, and B ell 2 cannot exceed 2.3 am ps for ba ttery -independent operation.

    The outputs ha s th e following options:

    Selectable for supervision.

    Selectable to activat e by individual zone

    assignments

    Selectable for confirmat ion of arm ing ding.

    Selecta ble to chime w hen ent ry/exit or perimeter

    zones are faulted.

    Selectable for steady or pulsing

    Selectable for no timeout or timeout of 2-30

    minutes .

    If you purchased a kit containing the PS24Power Supply Module, you may use thismodule to convert one or both VISTA-128FBP/VISTA-250FBP 12VDC, 1.7A style-Ysupervised Notification Appliance Circuits to24VFW, 1.7A style-Y supervised NotificationAppliance Circuits.

    UL Burglary Notification Appliance Circuits

    must be programmed for a timeout of 16minutes or longer.

    Commercial fire alarm systems requireNotification Appliance Circuits to be

    supervised.

    UL This control complies with National FireProtection Association (NFPA) requirements fortemporal pulse sounding of fire notificationappliances.

    Notification Appliance Circuit Supervision

    When su pervision is ena bled, th e VISTA-

    128FB P /VISTA-250FB P monit ors th e Notificat ion

    Appliance Circuits w iring for open an d short circuit

    fault s while the output is ina ctive. The system provides

    a t rouble indica tion (Zone 970 B ell 1; 971 Bell 2) w hen

    an open occurs; or w hen a short occurs between th e Bell

    (+ ) an d B ell (-) termina l wiring, or between th e Bell (+ )

    terminal wiring and eart h ground.

    The VIS TA-128FB P /VIS TA-250FB P in dica tes t he

    trouble condition regardless of whether th e system is

    ar med or disar med. The zone display s on the keypads,

    reports t o the event log, and tra nsmits to the centra l

    sta tion (if program med) on P ar tit ion 1. The trouble is

    clear ed from the display by entering t he user code +

    OFF.

    Wiring the Alarm Output

    The w iring of t he Notification Appliance Cir cuits

    depends upon whether y ou are going to supervise the

    circuit or not. U se the a ppropriat e procedure below foryour application.

    UL Use only UL Listed sounding devices for ULinstallations.

    Compatible Alarm Indicating Devices

    Model Device Type

    ADEMCO AB12 Grade A Bell

    System Sensor PA400B(beige/PA400R (red)

    Indoor piezo sounderrated at 90dB @ 10 feet.

    System Sensor MA-12/24 Horn

    System Sensor SS1215 ADA Strobe

    System Sensor SS121575 ADA Strobe

    System Sensor MASS1215 ADA Horn/Strobe

    System Sensor MASS121575 ADA Horn/Strobe

    System Sensor MA/SS-12 Horn/Strobe

    Wheelock LS1-12-VFR Strobe

    Wheelock MS1-12-VFR Strobe

    Wheelock MT-12-LS-VFR Horn/Strobe

    Wheelock MT4-12-LS-VFR Horn/Strobe

    Wheelock MT-12-MS-VFR Horn/Strobe

    WheelockMT4-12-MS-VFR Horn/Strobe

    Gentex GXS-2-15 Strobe

    Gentex GXS-2-1575 Strobe

    Gentex SHG-12-15 Horn/Strobe

    Gentex SHG-12-1575 Horn/Strobe

    Faraday 5336L-U-14-12-DC Horn/Strobe

    Faraday 5337-L-U-14-12-DC Horn/Strobe

  • 7/27/2019 Vista 128 FBP

    25/144

    Section 3 - I nstal l i ng the Contr ol

    3-5

    BELL 2 FACTORY DEFAULTS

    BELL 2 IS CONFIGURED AS A FIRE BELL CIRCUIT

    USE POLARIZED INDICATING DEVICES.CLASS B OPEN/SHORT SUPERVISION.

    24-HR TROUBLE RESPONSE TO FAULTS.

    ACTIVATES FOR ZONE 1-2 ALARMS (BY DEFAULT,

    ZONES 1-2 ARE ASSIGNED TO FIRE PARTITION 1)

    PULSED ALARM OUT PUT.

    NO TIMEOUT AB12 WIRING NOTES:

    DISCONNECT THE AB12'S FACTORY-WIRED CONNECTION

    FROM ITS TERMINAL #4 TO ITS OUTER BOX.

    SET FIELD 3* 17 TO "1" TO ENABLE ZONE 6 TAMPER FUNCTION.

    ASSIGN ZONE 6 TO A BURGLARY PARTITION. PROGRAM

    IT FOR DAY TROUBLE/NIGHT ALARM RESPONSE (TYPE 0 5)

    WHEN THIS BELL IS USED BY ONLY ONE BURGLARY

    PARTITION. PROGRAM IT FOR 24-HR. AUDIBLE ALARM

    RESPONSE (TYPE 07) WHEN THIS BELL IS USED BY

    MORE THAN ONE BURGLARY PARTITION.

    ALL WIRING FROM AB12 TO PANEL MUST BE RUN IN

    CONDUIT.

    AB12 BELL/BOX WIRINGTOPANEL'SBELL+

    TOPANEL'SBELL

    (e.g.,BELL1;TB3)

    (e.g.,BELL1;TB4)

    TOZONE6-(TB24)

    TOZONE6-(TB23)

    BELL

    TAMPERSWITCHES

    1 2 3 4 5 6

    2k EOLR

    AB12 OUTER BOX

    INNER LINER

    6

    belloutput-003-V0

    543BELL 1 FACTORY DEFAULTSBELL 1 IS CONFIGURED AS A BURGLARY BELL CIRCUIT

    USE NONPOLARIZED GRADE A INDICATING DEVICES

    (e.g., ADEMCO NO AB12 - SEE WIRING NOTES BELOW)

    WIRING IS NOT SUPERVISED; CUT WHITE JUMPER, W1,

    ON MAIN PCB.

    ACTIVATES FOR ZONES 3-8 ALARMS (BY DEFAULT,

    ZONES 3-8 ARE ASSIGNED TO BURGLARY PARTITION 1)

    STEADY ALARM OUTPUT

    16-MINUTE TIMEOUT.

    BELL 2BELL 1++

    2k EOLR(MODEL 610-7)

    TOPANEL'SEARTH

    GROUND

    (TB30)

    F i gu r e 3 -6 : Ex t er na l Soun der Conn ec t i o n s

    Supervising the Notification Appliance Circuits

    To wire t he NAC using the supervision featur e, perform

    the following steps:

    Step Action

    1 In sta ll a 2K EOL resist or (Model 610-7,

    supplied) across the la st n otificat ion

    applian ce on ea ch Notification Appliance

    Circuit t o be supervised.

    2 P rogra m Zone 970 (Bell 1) a nd zone 971 (Bell

    2) with a response t ype of 19 (24-HourTrouble).

    Disabling the Supervision of the NotificationAppliance Circuits

    To install t he NAC and disable the supervision feat ure,

    perform the followin g steps:

    Step Action

    1 Cut th e wh ite jumpers W1 (for B ell 1) a nd W2

    (for Bell 2) on the main P C board .

    2 P rogra m Zone 970 (Bell 1) a nd zone 971 (Bell2) with a response type of 00.

    The Notification Appliance Circuits will notrespond unless the zones are assigned to them.For fire alarms, the system displays FIRE ALARMSILENCED. This message also displays if theNotification Appliance Circuit is not supervised.

    Auxiliary Relay Connections

    The VIS TA-128FB P /VIS TA-250FB P provid es a b uilt -in

    Form C relay wit h conta cts ra ted a t 28VAC/VDC, 2.8A.

    The relay ma y be programm ed (field 361) for on e ofthe following fun ctions:

    Alar m Activation

    Trouble/Su pervisory Activa tion

    4-Wire S moke Det ector Reset

    Ba t tery Saver

    Alarm Activation

    (3

    61 = 1 or 4) Stea dy a ct ivat ion in response to ana l a r m .

    If field 361 = 1, the auxiliary relay rema ins act ive

    unt il Aux. Relay Timeout expires or unt il User Code +OFF is entered. This option can be used to provide anunsupervised Notification Applian ce Circuit for

    supplementa ry str obes, sounders, etc. when w ired to

    the Aux Power 1 or a sepa ra te power supply, see Figure

    3-7.

  • 7/27/2019 Vista 128 FBP

    26/144

    VIST A-128FBP/ VI STA-250FBP Insta l la t ion and Setup Guide

    3-6

    If field 361 = 4, the auxiliary relay rema ins act ivated

    unt il User Code + # + 67 is entered. This option can beused for elevat or recall or ventilat or shutdown on fire

    ala rms. By default , the relay is set to act ivate on a larm

    zones 1-8 wit h no tim eout (field 361 = 1).

    When field 361 = 1, the auxiliary relay can be

    programm ed to give a br ief activation for confirmat ion

    of arming ding (field 357) or Ch ime Mode (field 359).

    NOTES:

    USE NON-POLARIZED INDICATING DEVICES.

    WIRING IS NOT SUPERVISED.DO NOT EXCEED RATINGS OF THE SUPPLY USED.IF AUX. PWR. 1 OUTPUT IS USED, THE COMBINED

    ALARM CURRENT DRAIN FROM AUX. PWR. 2,BELL 1, AND BELL 2 CANNOT EXCEED 2.3A MAX.

    belloutput-005-V0

    8 12117

    AUX RELAY FACTORY DEFAULTS

    ACTIVATES FOR ZONES 1-8 ALARMS(STEADY ALARM OUTPUT).

    NO TIMEOUT.

    109

    +

    AUXPWR#1

    GROUND

    POLE

    N.O.

    N.C.

    CAN DRAW POWER FROMAUX. PWR. 1 OUTPUT ORFROM SEPARATE SUPPLY.

    ALARM

    F i g u r e 3 -7 : W i r i n g Au x i l i a r y Rel a y f or A l a rm A c t i v a t i on

    Trouble/Supervisory Activation

    (361 = 0) St eady a ctivation in response to any zone orsystem rela ted tr ouble condition or to any fire

    supervisory condition. The auxilia ry rela y rema ins

    activa ted unt il all fault conditions have been corrected

    a n d a User Code + OFF is entered.

    4-Wire Smoke Detector Reset

    (361 = 2) Momentary (6-second) activation in responseto a second entry of a User Code + OFF sequencefollowing a fire ala rm condition. This interr upts power

    to 4-wire smoke detectors connected t o ha rdw ired zones

    1-8 and polling loop zones, allowing the detectors to be

    reset. Power t o the detectors should be wired to the

    au xilia ry relay a nd to Aux. Power 1 output, see Figure3-8.

    Battery Saver

    (361 = 3) When t his option is selected, the a uxiliaryrelay is norma lly activa ted (e.g. , N.O. and pole conta cts

    a re connected) an d de-activa tes 4 hours a fter the sta rt

    of AC Loss. Using this feature, n on-critical loads, such

    a s supplementa ry keypad s, can be disconnected from

    the a uxiliary power outputs , a l lowing a smaller

    capacity ba ttery to be used. The relay r e-activa tes

    wit hin a few seconds a fter the AC power rest ores.

    +

    -

    -

    +

    -

    +

    EOL

    POWER

    SUPERVISIONRELAY

    MODULEA77-716B

    4-WIRE SMOKEDETECTORS

    2000OHMEOLR

    HEAT

    DETECTOR

    +BLK

    +

    -

    ZONE

    TERMINALS

    (15-27)

    12

    11

    10

    9

    N.O.

    POLE

    N.C.

    Aux.Pwr 1

    CONTROL

    PANEL

    SHOWN POWERED.RELAY OPENS WHENPOWER IS LOST

    AUXILIARY RELAY

    8

    7

    +

    Keypad Prt 1

    4_wiresmk-005-V0

    F i gu r e 3 -8 : Wi r i n g Aux i l i a r y Re lay for Smok e De tec t o r Reset

  • 7/27/2019 Vista 128 FBP

    27/144

    Section 3 - I nstal l i ng the Contr ol

    3-7

    Telephone Line Connections

    The VIS TA-128FB P /VIS TA-250FB P provid es one ma in

    built-in dia ler for communication to the centra l sta tion

    an d one optional 5140DLM B ackup Dia ler, both

    supervised for voltage a nd current on t he phone lines.

    Do not connect the system to telephone lines

    that require ground start service.

    ULFor Listed fire central station (UL864/NFPA 72)applications, use either a Long Range Radio(LRR) alone, the main dialer with the LRR, oruse the main dialer with the 5140DLM.

    For listed fire remote station (UL864/NFPA 72)applications, use the main dialer with the5140DLM.

    Telephone line supervision is required for ULcommercial fire alarm systems when dual linedialer is used for fire signal transmission.

    Main Dialer Connections

    To connect th e ma in dia ler, refer to the Summary of

    Connectionsdiagram and perform the following steps:

    Step Action

    1 Connect the ma in dialer to the telephone

    compan y lines using the RJ 31X cablesupplied.

    2 If the dialer output is connected to telephone

    lines tha t ha ve a telephone compa ny MTU

    inst a lled, cut t he blue jumper (W6).

    Installing the 5140DLM Backup Dialer

    Do not connect the main dialer and the backupdialer to the same telephone company line.

    To insta ll the 5140DLM, refer to the Summary of

    Connectionsdiagram and perform the following steps:

    Step Action

    1 Mount the 5140DLM to the ma in P C board

    shield.

    2 Connect the ba ckup dialer to the telephone

    compan y lines using the RJ 31X cable

    supplied.

    3 Connect the backup dialer to the J 3 connector

    on the main P C board using the r ibbon cable(supplied with the module).

    4 Connect the eart h ground screw on the

    5140DLM t o the eart h ground t ermina l (30)

    on the main P C board using 16AWG w ire.

    5 If the dialer output is connected to telephone

    lines tha t ha ve a telephone compa ny MTU

    insta lled, cut t he blue jumper on the

    5140DLM PC board.

    Telephone Line Supervision

    If the tip/ring voltage fa lls below approximat ely 25 volts

    (13 volts if the blue jumper is cut) or the handset

    current is less tha n a pproximat ely 10mA, the

    supervision circuits for th e dialer output w ill indicate a

    fau lt condition. Fault s on the phone lines are displayed

    a s zones 97 (ma in dia ler) an d 975 (backup dia ler).

    To prevent risk of shock, disconnect thephone lines at the telco jack before servicingthe panel.

    If t