Elite-AAnalog Addressable
Fire Control Panels
(2 or 4 Loops)
(Apollo Protocol)Standard Features
UL 864 9th Edition listed
Multi-Loop 2 Analog Addressable Loops Field upgradable to 4
126 primary points per loop
Powerful, network wide cause and effects (500 total). Fully user programmable by point or zone.
800 points per panel when using devices with sub-points
Up to 10,000 ft. wiring length on SLC loop
64 Panels on a network
Programmable through a PC connection to the panel, or through keypad
Programmable relays – 5
Supervised Powered Outputs – 3
Programmable Notification Appliance Circuits: 4
Power per NAC: 1.6 Amps Max
Programmable outputs on SLC loop
Programmable Function button on front display
Fire Drill button on front display
Day and night sensitivity settings (user programmable)
Power Supply: 5.25 Amp, regulated & integrated
LCD Display: 8x40
Zonal Mode: Annunciation by zone w/o individual relationships
Panel Ring Modes: Common, Zonal, Stage 2
NAC Outputs programmable as Continuous, March, Temporal
Program Cause and Effects AND, OR, or Any Two (Cross Zone)
Battery size: Up to 17 Ah in standard enclosure; up to 52 Ah with external cabinet
Access levels: 3
Access key switch: Yes
Recognized for use in High Rise
One man walk test – Fire Test Mode
Available with semi flush trim ring
Available in Red or Gray
Product Overview
The VF1460 and VF1480 analog addressable FACP with networked releasing, supports 2 or 4 SLC loops for a total of 500 primary points or 800 points using subpoints.SLC loop communications uses standard twisted pair cabling, shielded cable is not necessary.
The panel may be configured with various communication cards; Communications options support remote programming, central station monitoring, Virtual Panel, and networking.
The Panel can be configured as a stand alone panel with just a few devices for a small building, it can also operate as the building system and can be part of a network with a total of 64 nodes serving a multiple building campus or a very large facility.
Auto Learn capability provides a convenient method to troubleshoot new installations before final programming is loaded.
VF1460 (2 Loops)
VF1480 (4 Loops)
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Primary AC: 120VAC @ 2 Amps 60hz (Optional 240 VAC 50hz)
Output DC: 24VDC @ 4 Amps
Power Supply: 5.25 Amp regulated and integrated
Charger Current: 1.25 Amps max.
Dimensions: 14.5”W x 24”H x 5”D
Weight: 25 lbs. (without batteries)
Color: Red (optional gray)
Display: 8 line x 40 character LCD (320 characters total)
Zones: 500 Zones per network
SLC loops: 2 or 4 (class A or B)
Devices per loop: 126 sensors & modules (800 addresses + sub-addresses max. per panel)
NAC Outputs: (4) 1.6 Amp @ 24VDC (class B)
Relay Outputs: (5) Form C 1 Amp @ 30VDC
Voltage Outputs: (3) 500mA @ 24VDC, reverse polarity supervised
Aux. Power: 500mA @ 24VDC
Aux. Inputs: (3) digital pull downs
Current Consumption
VF1460
VF1480
VF1465
VF1464
355 mA Standby
650 mA Alarm
455 mA Standby
765 mA Alarm
430 mA Standby
745 mA Alarm
430 mA Standby
730 mA Alarm
Added Features:
Elite with eNET (VF1465/VF1485)Network uses standard RS485 cabling
Up to 2,000 ft. between adjacent panels
115 Kbps constant network speed
Secure, fault tolerant communication
Up to 64 nodes
Elite with DACT (VF1464/VF1484)Dual line digital communicator and modem
Contact ID and SIA reporting
UL 864 9th edition listed
Zone or point reporting
Backup and duplicate reporting
Virtual Panel Capability via Ethernet
Also available:
2 loop expansion board - VF1053
Trim ring - VF1070
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Standard Features
One full SLC circuit expandable to two
3 programmable relays
5.25A power supply
Large graphic display
Real time clock
Compatible with eMATRIX graphicsannunciator
Powerful, network wide cause and effects (500 total). Fully user programmable by point or zone.
Can be networked with additional RS and/ or Elite control panels
Compatible with eVIEW Annunciator
Programmable through a PC connection to the panel
Same look and feel as Elite range
Stores 1000 last events in history log
Model ranges include with or without a Dual-Line internal DACT
Compact, stylish enclosure
Available in Red or Gray
2 Programmable NAC circuits with internal synchronization support.
Product Overview
Elite RS is a versatile range of open protocolfire alarm control panels compatible withexisting Elite fire alarm panel technology.
Available with one or two detection loopscapable of hosting up to 600 devices. Elite RS uses leading edge microprocessor basedelectronics to provide a flexible control system with high reliability and integrity.
Suitable for all small to medium sized firedetection systems,Elite RS control panelscan be expanded and networked to becomepart of much larger systems if the need arises,therefore providing a future proof solution forany installation.
With its large graphical display and ergonomicbutton and indicator layout, the Elite RScontrol panel is simple and straightforwardto understand for installers, commissioningengineers and end users alike.
Elite RS-AAnalog Addressable
Fire Control Panels
(1 or 2 Loops)
Apollo Protocol
VF0850 (1 Loop)
VF0860 (2 Loops)
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Construction: 16AWG sheet steel
Dimensions: 14.5”W x 18.9”H x 4.25” D
Weight (without batteries): 20lb
Finish (lid & box): RAL3002 (Red) or BS 00 A 05 (Gray)
Finish (product labels): BS 00 A 05 (Gray)
Mains voltage supply: 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 110V)
Mains supply fuse: 1.6A 250V
Power supply DC rating: 24V 5.25 Amps
Aux 24V supply: Fused at 500 milliamps
Battery (24 hour standby): 9Ah 12V (2 per panel) (non-networked)
Fault contact rating: 30V DC 1 Amp
Fire contact rating: 30V DC 1 Amp
Alarm contact rating: 30V DC 1 Amp
NAC output rating: 3.1V across both channels, 2.3V across any one
Detection loop: 250 milliamp output
Printer port: Serial RS232
Serial expansion port: Serial RS485
PC port: Serial RS232
Network connection: Optional network Cards allow the use of e-Net networking or VESnet networking
NAC Synchronization: Internal Support
NAC Protocols: System Sensor, Wheelock, Gentex, Amseco
Added Features:
Elite RS-A with Internal Modem/DACT
(VF0856/VF0866)Dual line digital communicator and modem
Central Station reporting; SIA and Contact ID
On-board loop start terminal connections for both primary and secondary Telco lines
Elite RS-A with Ether/DACT
(VF0854/VF0864)Dual line digital communicator and modem
Central Station reporting; SIA and Contact ID
Phone line jacks – RJ-11 (two)
Modem speed: 33.6 Kbps for program downloading
Virtual panel capability via Ethernet
Elite RS-A with Network Interface Card
(VF0852/VF0862) Network uses standard Cat 5 cabling
Up to 2,000 ft. between adjacent panels
115 Kbps constant network speed
TCP and UPD communications through VESNet
Total network delay less than 3 sec. with 127 panels
Network jacks – RJ-45 (VESNet and Ethernet)
Mapped Network; Display messages for Any or All nodes
Elite RS-A with Media Gateway®
(VF0851/VF0861)All the features of the Ether/DACT and NIC plus:
Enables network programming with direct TCP/IP access to each panel
Access point for network communications
Also available:
eNET Networking Card - VF1170
1 loop expansion board - VF1054
Trim ring - VF1071
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Standard Features
Available in Red or Gray
Up to 15 annunciatorscan be connected to eachElite or Elite RS fire control panel
Large liquid crystal display(240 x 64 pixels)
High brightness LED indications
Internal sounder
Replicates all panel controls(Elite)
Simple, two-wire serial connection
Small, Elite style enclosure
Removable electronicsfor easy installation
24V DC powered
Low power consumption
Multi language options
Connection supervised byElite fire control panel
Recess mounting using optional VF1173 kit
eVIEW - VF1172
Analog Addressable
Serial Annunciator
Product Overview
Designed and manufactured to the highest standards in a quality controlled environment the eVIEW fire alarm annunciator provides a simple and convenient method of extending the controls and indications of the Elite fire alarm control panel to other locations.
The large, graphic liquid crystal display and high brightness LED indicators duplicate the indications on the Elite fire alarm control panel at up to 15 additional locations via a simple, two-wire serial data connection.
The eVIEW is powered by 24V DC (which can be via an additional 2 conductors from the control panel or local 24V DC listed supply).
eVIEW is housed in a small enclosure which is styled similarly to the Elite control panel and is ideal for installations where a large control panel would be detrimental to décor such as entrance halls.
Up to 15 eVIEW annunciators can be connected to each control panel on the Elite network making eVIEW ideal where multiple points of indication and/or control are required such as nurses stations or shop units.
Gray version
Red version
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Construction: 18AWG sheet steel
Cable entry: 4 knockouts in back of box and 1 in left and right sides
Dimensions: 10.4”W x 7.5”H x 1.6”D
Weight: 3.5 lbs.
Finish : RAL3002 (Red) or BS 00 A 05 (Gray)
24V supply: 21 to 30V DC
Maximum ripple current: 200 millivolts
Quiescent current of panel in mains fail: 0.03 Amps
Serial data connection: 2 core RS485 (Up to 1200 metres total cable length)
Maximum terminal capacity: 12AWG
eLAN or Elite series control panel eView #1
CommsIn
CommsOut
24V In 24V Out
eView #15
CommsIn
CommsOut
24V In 24V OutComms
Aux 24V
The VES trim ring allows the eVIEW annunciator to easily be recess mounted. VES trim rings provides placement tabs that fold behind dry wall. Traditional screw mounting is available by 2 openings in each of the vertical frames. Conduit entry is not blocked by trim ring.
Trim Ring Technical Specifications
Part number: VF1173
Outter Dimensions: 11.3” W x 8.6” H x 1.3” D
Inner Dimensions: 10.3” W x 7.4”
Color: Available in Red (VF1173-10) or Gray (VF1173-40)
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Standard Features
Available in Red or Gray
Up to 504 LED’s can be controlled from any Elite panel
Select up to 12 printed colors (not including background and building outline)
Available in a range of standard enclosures to suit any applications
Custom sized units can be made upon request
Choice of Red, Green or Yellow LED’s
eMATRIX can easily be upgraded on site with minimal cost and effort
UL 864 9th edition listed
eMATRIXConfigurable Floor Plan
Mimic Annunciator
Product Overview
The eMATRIX system uses flexible, optic light guides to illuminate areas on a floor plan, laid over a high resolution grid. This unique system dispenses completely with wiring and enables indicators to be moved, removed or added on site without the need for any wiring.
All indicators can be configured to operate upon any event type and at point, zone or group level via the powerful and intuitive Loop Explorer configuration or ESP Discovery. eMATRIX can be supplied with or without LEDs and controls. Optional LEDs indicate Power on, Fire, Trouble and Disablement and optional controls are for Alarm silence, Buzzer silence, Lamp test and Reset.
Housed in attractive, slimline enclosures to match Elite fire alarm panels and with high quality, full color or floor plans, eMATRIX provides a clear, geographical indication of fire alarm activation enabling speedy identification of the source of an alarm.
View showing mimic mounted on inner door View showing LED grid View showing internal layout
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Quiescent current: See above
Supply voltage: 21 to 30V DC
Supply current: See above
Terminal capacity: 22 AWG to 12 AWG solid or stranded wire
Enclosure Size & mimic area: see ‘Enclosure Size Options’
Construction: 16 gauge mild steel
Finish: epoxy powder coat
Mimic: 3mm Clear Anti-Glare Acrylic
Cabinet locks: CAT30 key
Communications interface: RS485 – Elite serial I/O bus protocol
Maximum distance from control panel: 4000 feet using RS485 data cable
IP rating: IP30
Operating temperature: 20F to 120F
Number of indicators (standard models): AM2 size - up to 40 LED’s, AM3 size - up to 72 LED’s, AM4 size - up to 88 LED’s
Enclosure Size Options(Available in Red or Gray)
AM2
AM3
AM4
11.5”7.3”
11”13.5”
11”18.6”
14.5” Wide x 12.2” High x 3.5” DeepMax. number of LED’s = 40
Will house 1 x 8 Red LED driver PCBand 2 x 16 LED extension PCB’s
(Red, Green or Yellow)
14.5” Wide x 18.9” High x 4.25” DeepMax. number of LED’s = 72
Will house 1 x 8 Red LED driver PCBand 4 x 16 LED extension PCB’s
(Red, Green or Yellow)
14.5” Wide x 24” High x 5” DeepMax. number of LED’s = 88
Will house 1 x 8 Red LED driver PCBand 5 x 16 LED extension PCB’s
(Red, Green or Yellow)
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Part No. VF1170-00
Standard Features
Up to 64 nodes
High integrity protocol when wired Class A
Fully secure against short or open circuit faults
Simple 2-wire loop connection
Supports open ended networks for retrofit applications
Network wide test and disablement functions
Network wide cause and effect logic
Flexible configuration options
Panels configurable to act on network events or not as required
eNET - VF1170-00
Elite Networking
Product Overview
The flexibility of the Elite system can be further enhanced by connecting control panels and repeaters together using a high integrity network.
A simple 2-wire connection between each panel allows events to be transmitted to other parts of the system to provideindication or control on a system wide basis.
Using the Loop Explorer configuration soft-ware, up to 64 nodes can be programmed to respond in a variety of ways to any system events as required.
This flexibility extends the comprehensive cause and effect programming capability of Elite control panels to the entire network allowing actions, test modes or disablements to be started from any point.
The fault tolerance of the network is such that any single open or short circuit fault will not result in any loss of information. Multiple faults are isolated and the network breaks into smaller networks which continue to work autonomously.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Flexible network configuration options using simple to follow PC configuration software
Technical Specifications
Protocol: RS485
Connection: Two wire loop
Current Consumption: 40mA
Integrity: Full isolation of faulty nodes or wiring segments
Indicators: Data In and Data Out communications status
Cable length: 3900ft to adjacent nodes
(subject to cable type) (see technical manual)
Cable type: Belden 9271, Belden 9860, FP200 Gold
Compatible panels: Elite/ Elite RS (required for networking)
Two conductor loop wiring ensures network integrity by providing full isolation of faulty wiring segments.
2 Conductor
2 Conductor(Not fitted on Class B networks)
2 Conductor
Elite Control Panel Elite Control Panel
Elite Control Panel
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Powerful Event log filtering
Virtual Panel - allows direct control
Standard Features
Choice of text, graphic, event list display when an event occurs
Versatile event analysis
Total history archive
Easy to program
Secure system
Cost effective compared to other systems
Simple to use
Unlimited map linking & zoom capability
Support for 100’s of graphics
Display and control for multiple panels
Event history explore and export to text or HTML documents
GUIDE - VF1593-00
Graphical PC User Interface
for Fire Detection Systems
Product Overview
Elite fire control panels can send data to, and be controlled by, the Guide system providing a single point of control for all alarms.
The powerful 32 bit program features a stand-ard Windows look and feel and runs under Win-dows® XP, Vista or Windows® 7.
The system is highly configurable in terms of the style of presentation so that the end user can be presented with maps, text, photographs, audio or a combination of all as required.
User profiles allow the system manager to con-trol the options available to each individual system user.
A comprehensive history logging and reporting system allows analysis of events and trends to be identified to reduce unwanted alarms.
Easy to program and simple to use, Guide pro-vides a cost effective solution for fire alarm management at many levels.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Note: Guide will be operating 24 hours a day for many years. It may be desirable to include on site PC maintenance as part of the package.
Note: Guide For use with Elite Panels.
Technical Specifications
Ordering Codes
Part number
VF1593-00
VF1593-01
VF1593-02
VF1593-03
VF1593-04
VF1593-05
Description
GUIDE software - 1 node
GUIDE software - 2-4 nodes
GUIDE software - 5-8 nodes
GUIDE software - 9-16 nodes
GUIDE software - 17-32 nodes
GUIDE software - 33-64 nodes
Processor
Operating system
Memory
Hard disk
Graphics
Sound card
Loudspeaker
Monitor
Pointing device
Printer
Parallel port
Serial ports
CDROM drive
Backup drive
Recommended Minimum
Intel Pentium 1Ghz
Windows® XP/Vista
256MB minimum
10GB minimum
1024 x 768 16M colors
Any PC sound card
Any PC speakers
Any that supports above graphics driver
Mouse essential
Optional
Optional
One RS232 per network
Any
CD Writer
Notes
The faster the better, 2Ghz will provide future proofing
Will operate under Windows® 2000
The larger the better
>20GB would be better
The driver must allow this mode with large fonts. Separate Graphics
card with 256MB graphics memory recommended
More convenient if built into PC
17 inch minimum recommended, the larger the better. (1024 x 768)
Third button and wheels are supported. Touch screen option supported
Any type
Required if parallel printer to be used
Isolated converter supplied for connection to fire alarm system
Required for installation of software and updates
To back up history
Guide SystemDongle fitted
RS485
Elite Control PanelElite Control PanelElite RS Control Panel
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5600Discovery Ionization Smoke Sensor
SLC Devices
Overview
The VF5600 Discovery Ionization Smoke Detector has a molded white polycarbonate case with windresistant smoke inlets. Inside the case is a printed circuit board which has the ionization chamber mounted on one side and the signal processing and communications electronics on the other. The ionization chamber consists of a reference chamber contained inside a smoke chamber. The outer smoke chamber has inlet apertures fitted with insect resistant mesh.
Operation
The radioactive source holder and the smoke chamber form positive and negative electrodes respectively. An Americium 241 radioactive source mounted within the reference chamber irradiates the air in both chambers, producing positive and negative ions. A voltage across the electrodes produces an electric field. Ions are attracted to the Electrode of the opposite sign to their own charge; many recombine but a small electric current flows between the electrodes. At the junction between reference and smoke chambers, the sensing electrode converts variations in chamber current into voltage hanges. When smoke particles enter the ionization chamber, ions become attached to them with the result that the current flowing through the chamber decreases. This effect is greater in the chamber decreases. This effect is greater in the smoke chamber than in the reference chamber, and the imbalance causes the sensing electrode to become more positive. The analog voltage at the sensor electrode is converted to a digital format which is processed to provide on analog value or transmission to the control panel when the device is polled.
Mode
1
2
3
4
5
Pre-Alarm
(%/fT)
0.5
0.5
0.7
0.7
1.0
Alarm
(%/fT)
0.7
0.7
1.0
1.0
1.5
Ionization detector operating modes
Sectional view - Ionization Smoke Detector
Standard Features
Compatible with Elite and Elite RS control panels
5 operating modes
Drift compensation
Address is set by X-Pert card and is stored in base
User memory
Alarm flag for fast alarm reporting
Conventional false safe mode
Polarity insensitive
Fits 4” & 6” low profile base
6” audible base
4” wire relay base
Note:Bases and cards are not included with detectors, please order separately.
30 Second
Alarm Delay
No
Yes
No
Yes
No
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Stand current: 500μA
Alarm current: LED Illuminated 3.4mA
Radioactive isotope: Americium 241
Operating voltage: 17-28 VDC
Max. continuous operating temp: 140°F
Min. continuous operating temp: 32°F
Min. Operating temp: -4°F (no condensation/icing)
Storage: -22°F to 176°F
Detector weight: 3.68 oz
Detector with base weight: 5.62 oz
Dimensions: Diameter: 3.93”, Height: 1.65”, Height in base: 1.96”
Operation - continued
The VF5600 Discovery Ionization Detector, like all Ionization detectors, has some sensitivity to air movement (wind). The extent to which the analog value will change depends on the wind speed and on the orientation of the detector relative to the wind direction. Relatively small changes in wind direction can cause significant changes in analog value. For wind speeds up to 200 ft/min the change in analog value will not exceed 5 counts. Continuous operation in wind speeds greater than 400 ft/min is not however recommended. It will not under any conditions increase the probability of false alarms. Ionization smoke detectors are supplied in individual packing with a red lid serving as a dust cover which can be left in place after fitting to prevent ingress of foreign material until commissioning of the system takes place. At this point, the covers must be removed.
Engineering Specification
The Ionization smoke sensor shall be VF5600, where indicated on the plans, with one of the several addressable mounting base options available. The ionization smoke detector shall include compensation for sensor drift as part of the internal signal-processing algorithm. The ionization sensor head and twist-lock mounting base shall be UL Listed and UL Listed as compatible with the Elite Addressable Fire Alarm Control Panels.
The base shall permit free interchange of sensor heads without requiring any additional wiring or additional programming of the head or base. The smoke sensor shall contain an integral LED that shall latch in when the unit goes into alarm. RF suppression techniques shall be employed to minimize false alarms. The ionization smoke sensor shall have automatic conventional false safe mode if the detectors polling mechanism fails.
Ordering Codes
Part number
VF5600
VF5630
VF5632
VF5633
VF5636
VF5631
VF5650
VF5651
Description
Ionization Smoke Detector
4” Mounting Base
6” Low Profile Relay Base
Isolator Base
6” E-Z Fit Low Profile Base
6” Sounder Base
Blank XPERT Cards
Pre-addressed XPERT Cards
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5601Discovery Photoelectric
Smoke Sensor
SLC Devices
Photoelectric detector operating modes
Top view - Photoelectric Smoke Detector
Overview
The VF5601 Discovery Photoelectric detector uses the same outer case as the ionization smoke detector and is distinguished by the indicator LEDs which will flash when the detector is in standby state and steady red in alarm. The housing is white polycarbonate and will not fade. Terminals are nickel plated stainless steel.
Operation
Within the case is a printed circuit board which, on one side, has the light-proof chamber with integral gauze surrounding the optical measuring system and, on the other, the signal processing and communications electronics. An infra-red light emitting diode is arranged at an obtuse angle to the photo-diode. The photo-diode has an integral daylight-blocking filter. The IR LED emits a burst of light every second. In clear air the photodiode receives no light directly from the IR LED, because of the angular arrangement and the chamber Baffles. When smoke enters the chamber it scatters light from the emitter IR LED onto the photo-diode in an amount related to the smoke characteristics and density. The photo-diode signal is processed to provide an analog value for transmission when the detector is interrogated.
Standard Features
Compatible with Elite and Elite RS control panels
5 operating modes
Drift compensation
Two status LEDs
Address is set by X-Pert card and is stored in base
User memory
Alarm flag for fast alarm reporting
Conventional false safe mode
Polarity insensitive
Note:Bases and cards are not included with detectors, please order separately.
Mode
1
2
3
4
5
Pre-Alarm
(%/fT)
1.1
1.1
1.5
1.5
2.0
Alarm
(%/fT)
1.7
1.7
2.3
2.3
3.0
30 Second
Alarm Delay
No
Yes
No
Yes
No
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Stand current: 400μA
Alarm current: 3.4mA
Operating voltage: 17-28 VDC
Max. continuous operating temp: 140°F
Min. continuous operating temp: 32°F
Min. Operating temp: -4°F (no condensation/icing)
Storage: -22°F to 176°F
Detector weight: 3.68 oz
Detector with base weight: 5.62 oz
Dimensions: Diameter: 3.93”, Height: 1.65”, Height in base: 1.96”
Engineering Specification
The Photoelectric Smoke Sensor shall be VF5601, where indicated on the plans, with one of the several addressable mounting base options available. The Photoelectric Smoke detector shall include compensation for sensor drift as part of the internal signal-processing algorithm. The Photoelectric Sensor head and twist-lock mounting base shall be UL Listed and UL Listed as compatible with the Elite addressable fire alarm control panels. The base shall permit free interchange of sensor heads without requiring any additional wiring or additional programming of the head or base. The smoke sensor shall contain an integral LED that shall latch in when the unit goes into alarm. RF suppression techniques shall be employed to minimize false alarms. The Photoelectric Smoke Sensor shall have automatic conventional false safe mode if the detectors polling mechanism fails.
Ordering Codes
Part number
VF5601
VF5630
VF5632
VF5633
VF5636
VF5631
VF5650
VF5651
Description
Photoelectric Smoke Detector
4” Mounting Base
6” Low Profile Relay Base
Isolator Base
6” E-Z Fit Low Profile Base
6” Sounder Base
Blank XPERT Cards
Pre-addressed XPERT Cards
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5602Discovery Heat Detector
SLC Devices
Heat Detector response modes
Overview
The VF5602 Discovery Heat Detector has a common profile with the ionization and photo smoke detector, but has a low air flow resistance case made of self extinguishing white polycarbonate.
The VF5602 Analog Addressable Thermal Sensors are designed to provide the highest effectiveness by utilizing the latest technology. The sensor is designed for operation with the Elite addressable fire alarm control panels.
Operation
The VF5602 Heat Detector uses a single thermistor to sense the air temperature at the detector position. The thermistor is connected in a resistor network, which produces a voltage output dependent on the temperature. The design of the resistor network, together with processing algorithm in the micro-controller, gives an approximately linear characteristic from 50°F to 176°F. This line-arised signal is further processed, depending on the response mode selected, and converted to an analog output. A detector may be given an “R” or “S” suffix. The “R” suffix indicated that the detector has been shown to have a rate of rise characteristic. Such a detector will still give a rapid response even when starting from an ambient temperature well below its typical application temperature.
This type of detector is therefore suitable for areas such as unheated warehouses in which ambient temperature may be very low for long periods. The “S” suffix indicates that the detector will not respond below its minimum static response temperature even when exposed to high rates of rise of air temperature. This type is therefore suitable for areas such as kitchens and boiler rooms where large, rapid temperature changes are considered normal.
Standard Features
Compatible with Elite and Elite RS control panels
5 operating modes
Fits into addressable 4” bases or 6” E-Z Fit bases
Addressable sounder alarm base
Address is set by X-Pert card and stored in base
User memory
Alarm flag for fast alarm reporting
Fixed point or rate of rise function
Note:Bases and cards are not included with detectors, please order separately.
Mode
1
2
3
4
5
Pre-Alarm
(%/fT)
N/A
N/A
N/A
N/A
N/A
Alarm
(o F)
135o
150o
150o
200o
200o
Fixed/ ROR
Profile
FT & ROR
FT & ROR
FT
FT & ROR
FT
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Alarm current: LED Illuminated 3.4mA
Radioactive isotope: Americium 241
Operating voltage: 17-28 VDC
Max. continuous operating temp: 140°F
Min. continuous operating temp: 32°F
Min. Operating temp: -4°F (no condensation/icing)
Storage: -22°F to 176°F
Detector weight: 2.3 oz
Detector with base weight: 3.5 oz
Dimensions: Diameter: 3.94”, Height: 1.65”, Height in base: 1.96”
Engineering Specification
The thermal sensor shall be VF5602, where indicated on the plans, with one of the several addressable mounting base options available. The combination sensor head and twist-lock mounting base shall be UL listed and UL Listed as compatible with the Elite addressable fire alarm control panels. The base shall permit free interchange of sensor heads without requiring any additional wiring or additional programming of the head or base. The sensor shall contain an integral LED that shall latch in when the unit goes into alarm.
Ordering Codes
Part number
VF5602
VF5630
VF5632
VF5633
VF5636
VF5631
VF5650
VF5651
Description
Heat Detector
4” Mounting Base
6” Low Profile Relay Base
Isolator Base
6” E-Z Fit Low Profile Base
6” Sounder Base
Blank XPERT Cards
Pre-addressed XPERT Cards
Sectional view - Heat Detector
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5603Discovery Multisensor Detector
SLC Devices
Multisensor Detector operating modes
Overview
The VF5603 Discovery Multisensor Detector contains a photo smoke sensor and a thermistor temperature sensor whose outputs are combined to give the final analog value. The way in which the signals from the two sensor are combined depends on the response mode selected. The five modes provide response behavior which incorporated pure heat detection, pure smoke detection, and a combination of both. The multisensor is therefore useful over the widest range of applications. The outer smoke chamber has inlet apertures fitted with insect resistant mesh.
The Multisensor construction is similar to that of the photo detector but uses a different lid and optical moldings to accommodate the thermistor temperature sensor. The sectional view shows the arrangement of the optical chamber and the thermistor.
Operation
The signals form the optical smoke sensing element and the temperature sensor are independent, and represent the smoke level and the air temperature respectively in the vicinity of the detector. The detector’s micro-controller processes the two signals according to the mode selected. When the detectors is operating as a multisensor (i.e. Modes 1, 3, and 4) the temperature signal processing extracts only rate-of-rise information for combination with the optical signal.
In these modes the detectors will not respond to a slow temperature increase- even if the temperature reaches a high level. A large sudden change in temperature can, however, cause an alarm without the presence of smoke, if sustained for 20 seconds. The process algorithms in modes 1 to 4 incorporate drift compensation.
Standard Features
Compatible with Elite and Elite RS control panels
5 operating modes
Combines photo, smoke, and thermal sensor value for enhanced detection performance and false alarm reduction
Address is set by X-Pert addressing and is stored in the sensor base
Rate of rise heat signals
Drift compensation
Polarity insensitive
Fits 4”, 6”, or 6” low profile bases
6” audible base
4” relay base
Note:Bases and cards are not included with detectors, please order separately.
Sectional view - Multisensor Detector
Mode
1
2
3
4
5
Pre-Alarm
(%/fT)
0.9
1.3
1.7
2.2
No Response
Alarm
(%/fT)
1.3
1.9
2.6
3.3
No Response
Heat
Classification
140o ROR
140o ROR
140o ROR
140o ROR
135o FT & ROR
20 Second
Alarm Delay
Yes
Yes
Yes
Yes
No
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Stand current: 500μA
Alarm current: 3.5mA
Operating voltage: 17-28 VDC
Max. continuous operating temp: 140°F
Min. continuous operating temp: 32°F
Min. Operating temp: -4°F (no condensation/icing)
Storage: -22°F to 176°F
Detector weight: 3.68 oz
Detector with base weight: 5.62 oz
Dimensions: Diameter: 3.93”, Height: 1.65”, Height in base: 1.96”
Modes
The characteristics of the five response modes are summarized below.
Mode 1 has a very high smoke sensitivity combined with high temperature sensitivity. This gives a high overall sensitivity to both smoldering and flaming fires.
Mode 2 has smoke sensitivity similar to that of a normal photoelectric detector, but has no response to temperature. This mode is therefore equivalent to a standard photo detector. This mode is suitable for applications in which wide temperature changes occur under normal conditions.
Mode 3 has moderate smoke sensitivity combined with moderate sensitivity to heat. This combination is considered the optimum for most general applications since it offers good response to both smoldering and flaming fires.
Mode 4 has lower than normal smoke sensitivity combined with high heat sensitivity. This makes it suitable for applications in which a certain amount of fumes or smoke is considered normal.
Mode 5 has no smoke sensitivity at all, but give a pure heat detector response. In this mode the detector will respond to slowly changing temperature and has a “fixed temperature” alarm threshold at 135°F. The analog value in this mode will give the approximate air temperature over the range of 59°F to 131°F. In Mode 5, the smoke sensor is still active though it does not contribute to the analog signal. As a consequence, if the detector is used in a dirty or smoky environment the optical sensor drift flag may be activated in the heat-only mode.
Engineering Specification
The photo/heat multisensor detector shall be VF5603, where indicated on the plans, with one of the several addressable mounting base options available. The combination sensor head and twist-lock mounting base shall be UL Listed and UL Listed as compatible with the Elite addressable fire alarm control panels. The photo/heat multisensor detector shell have 5 programmable sensitivity modes. The base shall permit free interchange of sensor heads without requiring any additional wring or additional programming of the head or base. The smoke sensor shall contain an integral LED that shall latch in then the unit goes Into alarm.
Note: In testing of the multisensor detector should be carried out as for smoke detector in response modes 1-4, and for heat detection in response mode 5.
Design Note: If the multi-sensor is to be used in mode 5, heat detector spacing/coverage should be applied.
Ordering Codes
Part number
VF5603
VF5630
VF5632
VF5633
VF5636
VF5631
VF5650
VF5651
Description
Multisensor Detector
4” Mounting Base
6” Low Profile Relay Base
Isolator Base
6” E-Z Fit Low Profile Base
6” Sounder Base
Blank XPERT Cards
Pre-addressed XPERT Cards
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5669 XP95A Ionization Smoke Sensor
SLC Devices
shown in the diagram. The ions are attracted to the electrode of the opposite sign, some ions collide and recombine, but the net result is that a small electric current flows between the electrodes. At the junction between the reference and smoke chambers is the sensing electrode that is used to convert variations in the chamber currents into a voltage.
When smoke particles enter the Ionization chamber, ions become attached to them with the result that the current flowing through the Ionization chamber decreases. This effect is greater in the smoke chamber than in the reference chamber and the imbalance causes the sensing electrode to go more positive.
The voltage on the sensing electrode is monitored by the sensor electronics and is processed to produce a signal that is translated by the A/D converter in the communications ASIC ready for transmission when the device is interrogated.
Electrical Description
The detector is designed to be connected to a two wire loop circuit carrying both data and a 17V to 28V dc supply. The detector is connected to the incoming and outgoing supply via terminals L1 and L2 in the mounting base. A remote LED indicator requiring not more than 4mA at 5V may be connected between +R and -R terminals. An earth connection terminal is also provided, although this is not required for the functioning of the detector.
The detector is calibrated to give an analog value of 25±7 counts in clean air. This value increases with smoke density. A count of 55 corresponds to the UL alarm sensitivity level. See graph overleaf. Counts of 8 or less indicate fault conditions. Count levels between 45 counts and 55 counts can be used to provide an early warning of fire.
Sectional view - XP95A Ionization Smoke Detector
Standard Features
Responds well to fast burning, flaming fires
Designed to operate in a variety of environments
Minimal effects from temperature, humiditty, atmospheric pressure
Overview
The XP95A Ionization Detector uses a low activity radioactive foil to detect fires by irradiating the air in smoke chambers and causing a current flow. If smoke enters the chamber, the current flow if reduced leading to an alarm.
Operation
The XP95A Ionization Smoke Detector has a moulded self-extinguishing white polycarbonate case with wind resistant smoke inlets. Stainless steel wiper contacts connect the detector to the terminals in the mounting base. Inside the detector case is a printed circuit board that has the Ionization chamber mounted on one side and the address capture, signal processing and communications electronics on the other.
The ionization chamber system is an inner reference chamber contained inside an outer smoke chamber. The outer smoke chamber has smoke inlet apertures that are fitted with an insect resistant mesh.
The radioactive source holder and the outer smoke chamber are the positive and negative electrodes respectively. An Americium 241 radioactive source mounted within the inner reference chamber irradiates the air in both chambers to produce positive and negative ions. On applying a voltage across these electrodes an electric field is formed as
Diagram showing lines of equipotential for the XP95A Ionization Smoke Monitor
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical SpecificationsSpecifications are typical and given at 73°F and 50% relative humidity unless otherwise stated.
Detection Principle: Ionization Chamber
Chamber Configuration: Twin compensating chambers using one single sided ionising radiation source
Radioactive Isotope: Americium 241
Activity: 33.3kBq, 0.9μCi
Sampling Frequency: Continuous
Sensitivity: Nominal threshold y value of 0.7 to UL
Supply Wiring: Two wire supply, polarity insensitive
Terminal Functions:
L1&L2 supply in and out connections (polarity insensitive)+R remote indicator positive connection (internal 2.2kΩ resistance to supply +ve)-R remote indicator negative connection (internal 2.2kΩ resistance to supply - ve)
Supply Voltage: 17 to 28 Volts dc
Modulation Voltage at Detector: 5 to 9 Volts peak to peak
Quiescent Current: 280μA average, 500μA peak
Power-up Surge Current: 1mA
Alarm Indicator: Red light emitting diode (LED)
Alarm LED Current: 2mA
Remote LED Current: 4mA at 5V (measured across remote load)
Storage Temperature: -22°F to +176°F
Operating Temperature: -4°F to +158°F
Humidity: (No condensation or icing) 0% to 95% relative humidity
Wind Speed: 10m/s maximum
Atmospheric Pressure: Automatic compensation by dual chambers to maintain sensitivity up to a height of 6561m above sea level
IP Rating: 23D
Detector weight: 3.7 oz
Detector with base weight: 5.68 oz
Dimensions: Diameter: 3.93”, Height: 1.65”, Height in base: 1.96”
Materials: Detector Housing: White polycarbonate V-0 rated to UL 94 Terminals: Nickel plated stainless steel
Electrical Characteristics
The VF5669 Ionization Smoke Detectors are designed to operate in a wide variety of environments (See graphs). There are only small effects from temperature, humidity, atmospheric pressure and wind. Detectors are well protected against electromagnetic interference over a wide frequency range.
TheVF5669 Ionization Detector, like all Ionization Detectors, has some sensitivity to air movement (wind). The extent to which the analog value will change depends on the wind speed and on the orientation of the detector relative to the wind direction. Relatively small changes in wind direction can cause significant changes in analog value.
For wind speeds up to 1m/s (200ft/min) the change in analog value will not exceed 5 counts. Continuous operation in wind speeds greater than 2m/s (400ft/ min) is not recommended. However, wind speeds up to 10m/s (2000ft/min) can be tolerated for short periods and will not under any conditions increase the probability of false alarms.
Temperature (°F)
-4 14 32 50 68 86 104 122 140
Analog Value (Counts)
Analog Value (Counts)
Analog Value (Counts)
Analog Value (Counts)
Height (Ft) above sea level
Obscuration in smoke dB/m
Typical response characteristics - VF5669 Ionization Detector
Typical temperature response- VF5669 Ionization Detector
Typical pressure response- VF5669 Ionization Detector
Typical wind speed response- VF5669 Ionization Detector
-1640 0 1640 3280 4921 6561 8202
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5670
XP95A Photoelectric Smoke Sensor
SLC Devices
The IR LED emits a burst of collimated light every second. In clear air the photo-diode receives no light directly from the IR LED because of the angular arrangement and the dual mask. When smoke enters the chamber it scatters photons from the emitter IR LED onto the photo-diode in an amount related to the smoke characteristics and density. The photo-diode signal is processed by the optical ASIC and passed to the A/D converter on the communications ASIC ready for transmission when the device is interrogated.
Electrical Description
The VF5670 detector is designed to be connected to a two wire loop circuit carrying both data and a 17V to 28V dc supply. The detector is connected to the incoming and outgoing supply via terminals L1 and L2 in the mounting base. A remote LED indicator requiring not more than 4mA at 5V may be connected between the +R and -R terminals. An earth connection terminal is also provided.
The detector is calibrated to give an analog value of 25±7 counts in clean air. This value increases with smoke density. A count of 55 corresponds to the UL alarm sensitivity level. See graph overleaf.
Environmental
Characteristics
The VF5670 Photoelectric smoke detector is unaffected by wind or atmospheric pressure and operates over the temperature range -4°F to +140°F. See graph overleaf.
Top section - XP95A Photoelectric Smoke Detector
Standard Features
UL Listed and FM Approved
Wind resistant smoke inlets
Insect resistant screen
Alarm flag for fast alarm reporting
Automatic addressing with the XPERT card
Electronics free 4” or 6” bases
Ease of installation
Elegant design
Responds well to slow burning, smouldering fires
Well suited for bedrooms and escape routes
Unaffected by atmospheric pressure
Overview
The VF5670 Photoelectric Smoke Detector works on the light scatter principle and is ideal for applications where slow burning or smouldering fires are likely.
Operation
The VF5670 Photoelectric detector uses the same outer case as the ionization smoke detector and is distinguished by the indicator LED which is clear in standby and red in alarm. Within the case is a printed circuit board which on one side has the light proof labyrinth chamber with integral gauze surrounding the optical measuring system and on the other the address capture, signal processing and communications electronics.
An infrared light emitting diode within its collimator is arranged at an obtuse angle to the photo-diode. The photodiode has an integral daylightblocking filter.
Schematic Diagram - XP95A Photoelectric Smoke Detector
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical SpecificationsSpecifications are typical and given at 73°F and 50% relative humidity unless otherwise stated.
Detection Principle: Photo-electric detection of light scattered in a forward direction by smoke particles
Chamber Configuration: Horizontal optical bench housing an infrared emitter and sensor arranged radially to detect scattered light
Sensor: Silicon PIN photo-diode
Emitter: GaAs infra-red light emitting diode
Sampling Frequency: 1 second
Sensitivity: Nominal response threshold value of 0.12 dB/m when measured in accordance with UL
Supply Wiring: Two wire supply, polarity insensitive
Terminal Functions:
L1&L2 supply in and out connections (polarity insensitive)+R remote indicator positive connection (internal 2.2kΩ resistance to supply +ve)-R remote indicator negative connection (internal 2.2kΩ resistance to supply - ve)
Quiescent Current: 340μA average, 600μA peak
Power-up Surge Current: 1mA
Alarm Indicator: Clear light emitting diode (LED) emitting red light
Alarm LED Current: 4mA
Remote LED Current: 4mA at 5V (measured across remote load)
Storage Temperature: -22°F to +176°F
Operating Temperature: -4°F to +140°F
Humidity: (No condensation or icing) 0% to 95% relative humidity
Wind Speed: Unaffected by wind
Atmospheric Pressure: Unaffected
IP Rating: 23D
Detector weight: 3.7 oz
Detector with base weight: 5.54 oz
Dimensions: Diameter: 3.93”, Height: 1.65”, Height in base: 1.96”
Materials: Detector Housing: White polycarbonate V-0 rated to UL 94 Terminals: Nickel plated stainless steel
Temperature (°F)
-4 14 32 50 68 86 104 122 140
Analog Value (Counts)
Typical temperature response- VF5670 Photoelectric Smoke Detector
Analog Value (Counts)
Obscuration in smoke dB/m
Typical response characteristics - VF5670 Photoelectric Smoke Detector
Response characteristics of the VF5670 Photoelectric Detector
Overheating/thermal combustion
Smouldering/ glowing combustion
Flaming combustion
Flaming with high heat output
Flaming - clean burning
Photoelectric Detector
Very Good
Moderate/ Good
Very Good
Very Good
Poor
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5668 XP95A Heat Detector
SLC Devices
Operation
The XP95A heat detectors have a common profile with ionization and photoelectric smoke detectors but have a low air flow resistance case made of self extinguishing white polycarbonate. The devices monitor heat by using a single thermistor network which provides a voltage output proportional to the external air temperature. The standard heat detectors respond to increasing air temperature in such a way that they are classified as an A2S device. See graph overleaf. Both devices will give 55 counts at 131°F.
A high temperature CS heat detector which can be installed in a typical ambient temperature of 131°f is available. See graph overleaf. This device will give 55 counts at 194°F.
Electrical Description
The detectors are designed to be connected to a two wire loop circuit carrying both data and a 17V to 28V dc supply. The detectors are connected to the incoming and outgoing supply via terminals L1 and L2 in the mounting base. A remote LED indicator requiring not more than 4mA at 5V may be connected between +R and -R terminals. An earth connection terminal is also provided.
The detector is calibrated to give an analog value of 25±5 counts at 77°F.
Environmental
Characteristics
XP95A Standard Heat Detectors operate over the range -4°F to +158°F, the High Temperature Heat Detectors operate over the range –4°F to +248°F. The detectors are unaffected by atmospheric pressure.
Standard Features
UL Listed and FM Approved
Electronic temperature sensing
Style 4, 6, or 7 communication wiring
LED indicator
Alarm flag for fast alarm reporting
Alarm address for fast location of alarm
Automatic addressing with the XPERT card
Electronics free 4” or 6” bases
Slide-easy bases
Ease of installation
Elegant design
Ideal for environments that are dirty or smoky under normal circumstances
Well suited for warehouses, loading bays and parking areas
Unaffected by wind or atmospheric pressure
Overview
The XP95A series analog addressable heat detector head, model VF5668, is molded from white polycarbonate material with a low air flow resistance design. Stainless steel wiper contacts connect the sensor to the terminals, which are polarity insensitive, in the mounting base. Inside the sensor case is a circuit board with the sensing system on one side and the address capture, signal processing, and communication electronics on the other side.
The sensor monitors temperature by using a single thermistor network, which provides a voltage output proportional to the external air temperature. This analog voltage is converted to a digital signal, which is transmitted to the Elite Fire Alarm Control Panel for interpretation. The alarm threshold is programmed into the Elite Fire Alarm Control Panel.
Schematic Diagram - XP95A Heat Detector
Sectional view - XP95A Heat Detector
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical SpecificationsSpecifications are typical and given at 73°F and 50% relative humidity unless otherwise stated.
Detection Principle: Linear approximation over temperature range 77°F to 194°F
Sensor: Single NTC Thermistor
Sampling Frequency: Continuous
Sensitivity: 77°F to 194°F: 38°F/count -4°F returns 8 counts
Supply Wiring: Two wire supply, polarity insensitive
Terminal Functions:
L1&L2 supply in and out connections (polarity insensitive)+R remote indicator positive connection (internal 2.2kΩ resistance to supply +ve)-R remote indicator negative connection (internal 2.2kΩ resistance to supply - ve)
Supply Voltage: 16-28VDC
Modulation Voltage at Detector: 5 to 9 Volts peak to peak
Quiescent Current: 250μA average, 500μA peak
Power-up Surge Current: 1mA
Alarm Indicator: Red light emitting diode (LED)
Alarm LED Current: 2mA
Remote LED Current: 4mA at 5V (measured across remote load)
Alarm Temperature: 135°F (57°C) (55 counts in 7 bits or 110 counts in 8 bits) UL class “Ordinary”
Style: Styles 4, 6, and 7
Terminations: (Detector Head) Stainless steel wiper contacts
End-of-Line resistor: None
Address Setting: XPERT Card
Mounting: 4” or 6” round base
Termination: Field Wiring/Base Stainless Steel, Nickel Plated
Storage Temperature: -22°F to +176°F
Operating Temperature: -4°F to +158°F
Humidity: (No condensation or icing) 0% to 95% relative humidity
Wind Speed: Unaffected in fixed temperature use
Atmospheric Pressure: Unaffected
IP Rating: 53
Detector weight: 3.7 oz
Detector with base weight: 5.54 oz
Dimensions: Diameter: 3.93”, Height: 1.65”, Height in base: 1.96”
Materials: Detector Housing: White polycarbonate V-0 rated to UL 94 Terminals: Nickel plated stainless steel
Temperature (°F)
Temperature (°F)
-4 14 32 50 77 194
-4 14 32 50 68 77 131
Analog Value (Counts)
Typical response characteristics - VF5668 High temperature Heat Detector
Analog Value (Counts)
Typical response characteristics - VF5668 Standard Heat Detector
Response characteristics of the VF5668 Heat Detector
Overheating/thermal combustion
Smouldering/ glowing combustion
Flaming combustion
Flaming with high heat output
Flaming - clean burning
Heat Detector
Very Poor
Very Poor
Poor
Moderate/ Good
Moderate/ Good
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5671XP95A Multisensor Detector
SLC Devices
Sectional view - Multisensor Detector
Operation
The VF5671 Multisensor Detector contains an optical smoke sensor and a thermistor temperature sensor whose outputs are combined to give the final analog value.
The Multisensor construction is similar to that of the photoelectric detector but uses a different lid and optical mouldings to accommodate the thermistor temperature sensor. The sectional view shows the arrangement of the optical chamber and thermistor.
The signals from the optical smoke sensing element and the temperature sensor are independent, and represent the smoke level and the air temperature respectively in the vicinity of the detector. The detector’s microcontroller processes the two signals. The temperature signal processing extracts only rate of rise information for combination with the optical signal. The detector will not respond to a slow temperature increase - even if the temperature reaches a high level. A large sudden change in temperature can, however, cause an alarm without the presence of smoke, if sustained for 20 seconds.
The processing algorithms in the multisensor incorporate drift compensation. The sensitivity of the detector is considered the optimum for most general applications since it offers good response to both smouldering and flaming fires.
Standard Features
Sleek, non-fading white polycarbonate enclosure
Zero insertion force base- For easier installation and maintenance
Alarm flag for accelerated alarm reporting.·
Evaluates combined signals from ROR heat sensing element and smoke sensing chamber
Dual LED’s for 360 degree
Visibility Sensitive to a wide range of fires
Well suited for environments such as hotel bedrooms or warehouse loading bays
Unaffected by wind or atmospheric pressure
Overview
The XP95A VF5603 multisensor is basically an optical smoke detector and will therefore respond well to smoke from smouldering fires. The multisensor detector also senses air temperature. This temperature sensitivity allows the multisensor to give a response to fast burning (flame) fires, which is similar to that of an ionization detetctor. The multisensor can therefore be used as an alternative to an ionization detector.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical SpecificationsSpecifications are typical and given at 73°F and 50% relative humidity unless otherwise stated.
Detection Principle: Smoke: Photoelectric detection of light scattered by smoke particles Heat: Temperature-sensitive resistance
Supply Wiring: Two wire supply, polarity insensitive
Terminal Functions:
L1&L2 supply in and out connections (polarity insensitive)+R remote indicator positive connection (internal 2.2kΩ resistance to supply +ve)-R remote indicator negative connection (internal 2.2kΩ resistance to supply - ve)
Operating voltage: 17-28V DC
Communications protocol: Apollo XP95 5-9V peak to peak
Quiescent current: 500μA average 750μA peak
Power-up surge current: 1mA
Maximum power-up time: 10s
Alarm LED current: 3.5mA
Remote LED current: 4mA at 5V (measured across remote load)
Clean air analog value: 23 +4/-0
Alarm level analog value: 55
Alarm indicator: 2 colorless Light Emitting Diodes (LEDs); illuminated red in alarmOptional remote LED
Temperature range:
Max. continuous operating: +140°F Min. continuous operating: 32°F Min. operating (no condensation/icing): -4°F Storage -22°F to +176°F
Humidity: (No condensation) 0 to 95% relative humidity
Effect of temperature on optical detector: Less than 15% change in sensitivity over rated range. Slow changes in ambient conditions will automatically be compensated and will not affect sensitivity
Effect of atmospheric pressure on optical sensor: None
Effect of wind on optical sensor: None
IP rating: 23D
Detector weight: 3.7 oz
Detector with base weight: 5.64 oz
Dimensions: Diameter: 3.93”, Height: 1.96”, Height in base: 2.28”
Materials: Detector Housing: White polycarbonate V-0 rated to UL 94 Terminals: Nickel plated stainless steel
Technical Specifications
Smoke element only:Chamber configuration: Horizontal optical bench housing infra-red emitter and sensor, arranged radially to detect forward scattered light
Sensor: Silicon PIN photo-diode
Emitter: GaAs infra-red light emitting diode
Sampling frequency: 1 per second
Response characteristics of the VF5671 Multisensor Detector
Overheating/thermal combustion
Smouldering/ glowing combustion
Flaming combustion
Flaming with high heat output
Flaming - clean burning
Multisensor Detector
Very Good
Good
Good
Very Good
Moderate/ Good
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5604Optical Beam Detector
SLC Devices
Overview
XP95 Loop-powered Beam Detector
The XP95 beam detector has been designed to protect large open spaces such as atria, museums, churches, warehouses and factories. It is made up of three main parts: the transmitter, which projects a beam of infra-red light, the receiver, which registers the light and produces an electrical signal, and the interface, which processes the signal and generates alarm or fault signals.
The transmitter and receiver are designed to be fitted on opposite walls approximately 1ft to 2ft below the ceiling. They can protect areas up to 328ft long and 49ft wide, a total of 1794yds2. If it is difficult to fit the transmitter and the receiver to opposite walls, they may be fitted in retro mode, ie, adjacent to each other on the same wall. A reflector needs to be fitted to the opposite wall to reflect the beam from the transmitter to the receiver.
The interface contains the electronic circuitry needed to control the beam detector and communicate with the control panel via the XP95 or Discovery loop.
In clear air the receiver registers all the light sent by the transmitter. If smoke from an incipient fire is present, it rises and obscures the light to a certain extent. The decrease in the amount of light registered by the receiver causes the beam detector to change to the alarm state.
The detector compensates for signal drift and, if the limit of compensation has been reached, a fault signal is generated; the detector may optionally be set to return a fault if the beam is totally and suddenly obscured.
Loop-powered
The XP95 beam detector has been developed from designs that have been well proven in countless fire protection systems. A major advance has, however, been made, in that the XP95 beam detector is Loop-powered and needs no separate 24V supply. This not only eliminates the need for additionalequipment - it also saves both cost and time in installation.
Standard Features
Loop-powered
Compatible with XP95 and Discovery
Four selectable alarm levels
Drift compensation
Remote interface
Simple wiring
Simple alignment
Compatibility
The beam detector operates as a conventional detector, in that it changes to the alarm state at a pre-set level of smoke obscuration, but is able to communicate with the control panel and return information when interrogated. The interface will operate on both the XP95 and the Discovery protocols.
Selectable Alarm Levels
The XP95 beam detector is set on commissioning to one of four levels of obscuration, determined with reference to the environment in which it is installed. The levels are 25%, 35%, 50% and 65%, where 25% is the most sensitive and 65% the least sensitive level. A DIL switch on the interface is used to set the obscuration level.
Drift Compensation
It is possible that the amount of light registered by the receiver is decreased by factors other than incipient fires. The most obvious cause of such a change is contamination of the lens of the receiver. In order to minimise the risk of unwanted alarms, the XP95 beam detector checks its status at regular intervals and compensates for positive drift of signal. The analog value sent to the control panel is pre-set and cannot be further compensated by the panel.
Remote Interface
The optical and electronic elements of the XP95 beam detector are separate from one another, with the majority of the electronics being housed in the interface. The advantage of this is that the interface may be installed in an accessible position. If it is required to service the electronics of the beam detector, this can be done without the need for access equipment.
Simple Wiring
The transmitter and the interface of the XP95 beam detector can be wired to the nearest point of the loop. No extra wiring is necessary for any purpose.
Simple Alignment
During commissioning it is necessary to align the transmitter and receiver so that the beam is correctly projected at the receiver. By its nature the beam is invisible to the human eye, so that alignment has traditionally been a complex procedure. The XP95 beam detector makes alignment simple - a high-brightness LED behind the receiver lens flashes while the transmitter is being aligned. Once alignment is correct, the LED stops flashing.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Supply Voltage: 17-28V DC
Quiescent Current @ 24V DC: 10.5mA (Receiver and Interface), 6.0mA (Transmitter)
Alarm Current @ 24V DC: 12.0mA (Receiver and Interface), 6.0mA (Transmitter)
Fire Alarm Thresholds: 25% Obscuration (1.25dB)
35% Obscuration (1.87dB)
50% Obscuration (3.00dB)
65% Obscuration (4.55dB)
Operating Range: 25% Obscuration: 32ft-140ft (10-42m)
35% Obscuration: 32ft-215ft (10-64.5m)
50% Obscuration: 70ft-328ft (21-100m)
Retro Mode with relectors:
65% Obscuration: 20ft-148ft (6-45m)
Tolerance to Beam Misalignment at 35% obscuration:
Transmitter +1.0o; Receiver +4o, 880nm (Optical wavelength)
Receiver/ Interface Cable Type and Max. Length:
Twin twisted pair 7/31 AWG (7/0.2), 1 pair A&B, 1 pair C&D 328ft (100m)
Finish: White
IP Rating: 50
Operating Temperature: +16oF to +131oF (-10oC to +55oC)
Factory Default Settings
Fire Alarm Threshold: 35%
Alarm on Total Obscuration: Trouble
Alignment Mode/ Normal Operation: Alignment Mode
Address: 1
Ordering Codes
Part number
VF5611
VF5612
VF5613
VF5614
Description
Spare Transmitter
Spare Interface
Spare Reflector
Spare Resistor
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF4991Duct Smoke Detector
SLC Devices
Overview
The VF4991 Series Smoke Duct Detector is the latest analog addressable innovation for early detection of smoke and products of combustion present in air moving through HVAC ducts in Commercial, Industrial, and Residential applications. The unit is designed to prevent the recirculation or spread of smoke by air handling systems, fans, and blowers. Complete systems may be shut down via the building’s fire alarm control panel (FACP) in the event of smoke detection. The VF4991 is designed and built to meet all local code requirements, as well as the NFPA and ICC standards regarding HVAC supply and return duct smoke detectors. Output terminals are provided for a remote alarm indicator accessory.
The VF4991 includes many features that represent true innovations from current generation duct smoke detectors. Our traditional installer/servicer-friendly approach has been closely followed and expanded throughout the VF4991. This philosophy provides a new level of efficiency in after-purchase value to both the installer/servicer and end-user. Our attention to detail has yielded a host of “No-Tools Required” features, as well as a multi-application performance level as yet unmatched in the industry. The key features below detail many of the customer-driven innovations incorporated in the VF4991 Series. Innovative product combined with unsurpassed customer service equals the right combination for all of your projects.
Standard Features
Low-Flow Technology: Both Ionization and
Photoelectric models listed for velocities between
100-4000 ft./min
Both Ionization and Photoelectric models listed for
high temperature applications
Units supplied with slide-in XPERT Card for easy
device addressing
Patent pending “No-Tools Required” front or rear
loading and removing sampling/exhaust tubes
Patent pending “Test Port Valve” allows for aerosol
smoke testing without cover removal
Clear cover fitted with four captive “No-Tools
Required” thumbscrews
Instantaneous cover removal trouble indication
Vertical terminal block for easier wiring
Steady red LED on detector head indicates alarm
More wiring space than competitive models
Footprint allows easy retrofit in many applications
without additional drilling
Duct wall gaskets on back of enclosure are pre-
installed
Compatible with the WP-2000 weatherproof
enclosure
External mounting tabs do not require cover
removal to install
Colored cover gasket indicates proper cover seal
UL, CUL, Listed; CSFM, MEA pending
Compact, lightweight size means easy handling,
lower shipping costs
Large terminal connection screws
XP95A interchangeable “plug-in” UL268
photoelectric or ionization heads
Advanced detector head design yields internal dust
filtering
No additional screens or filters to clean
Compatible with fire alarm systems utilizing Apollo
XP95 and/or Discovery protocol
Ionization and Photoelectric versions available
Complete wiring details permanently attached to unit
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical SpecificationsModel Number: VF4991 Ionization, VF4991 Photoelectric
XP95A Detector Model Number: VF4991 Ionization 55000-550APO, VF4991 Photoelectric 55000-650APO
Sampling Tubes: STN-1.0 Sampling tube for 12” or less duct width, STN-2.5 Sampling tube for 6” to 2.5’ duct width
STN-5.0 Sampling tube for 2.5’ to 5.0’ duct width, STN-10.0 Sampling tube for 5.0’ to 10.0’ duct width
Accessories: MS-RA, -RD remote alarm indicators, WP-2000 weatherproof enclosure and TG-2000 aerosol test gas
(All available from Air Products and Controls Inc.)
Detector Compatibility: FACP utilizing Apollo XP95 and/or Discovery protocols
Air Velocity: 100 to 4,000 ft./min.
Ambient Temperature: SL-DAA-N 32ºF to 150ºF (0ºC to 66ºC), SL-DAA-P 32ºF to 140ºF (0ºC to 60ºC)
Humidity: 10 - 95% RH Non-Condensing / Non-Freezing
Wiring: Solid or stranded: #12 to #22 AWG terminals
Approvals: UL & CUL Listed (UL268A, UROX, UROX7) File # S2829, CSFM Listed (3240-1004:115), MEA Accepted (73-92-E Vol.35)
Material: Grey plastic backbox, clear plastic cover (Makrolon 94V-0)
Dimensions: 13 1/2” L x 4 1/2” W x 2 1/4” H
Max. Net Wt.: 2 lbs.
Radioactive Element: For SL-DAA-N (Ionization) Americium 241; 0.9 Micro-Curie. Do not expose to corrosive atmospheres
Hardware: 7” exhaust tube, sampling tube end cap, mounting template and mounting hardware included
Engineers and Architects SpecificationsAir duct smoke detectors shall be Air Products and Controls Inc. SL-DAA Series. For ionization detectors the model number is SL-DAA-N.For photoelectric detectors the model number is SL-DAA-P. The detectors shall be listed by Underwriters Laboratories per UL 268A.The detectors shall operate at air velocities from 100 feet per minute to 4,000 feet per minute and at temperatures of no greater than 140°F (60°C).Visual indication of alarm must be provided on the detector.Air handling unit shut down shall be accommodated via the associated FACP.Detector head shall not require additional filters or screens which must be maintained.The housing shall contain a detector base which will accept photoelectric or ionization detector heads as well as a means of detector addressing.Terminal connections shall be of the screw type, a minimum of #6 screw (#12 to #22 AWG compatible). Terminals shall be provided for remote alarm indication. All wiring must comply with local codes and regulations.A method of smoke testing the detector without removing the cover must be provided.All unit and remote accessory connection designations must be permanently affixed to the unit.Cover and sampling/exhaust tube installation or removal must not require the use of tools.Sample and exhaust tubes shall be capable of removal/installation from the front and/or rear of the detector for inspection/maintenance.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF4992Duct Smoke Detector
SLC Devices
Overview
The VF4992 Series Smoke Duct Detector is the latest analog addressable innovation for early detection of smoke and products of combustion present in air moving through HVAC ducts in Commercial, Industrial, and Residential applications. The unit is designed to prevent the recirculation or spread of smoke by air handling systems, fans, and blowers. Complete systems may be shut down via the unit’s on-board alarm contact in the event of smoke detection. The VF4992 is designed and built to meet all local code requirements, as well as the NFPA and ICC standards regarding HVAC supply and return duct smoke detectors. Output terminals are provided for a wide range of remote accessories such as horns, strobes, remote status indicators and test key switches or push buttons.
The VF4992 includes many features that represent true innovations from current generation duct smoke detectors. Our traditional installer/servicer-friendly approach has been closely followed and expanded throughout the VF4992. This philosophy provides a new level of efficiency in after-purchase value to both the installer/servicer and end-user. Our attention to detail has yielded a host of “No-Tools Required” features, as well as a multi-application performance level as yet unmatched in the industry. The key features below detail many of the customer-driven innovations incorporated in the VF4992 Series. Innovative product combined with unsurpassed customer service equals the right combination for all of your projects.
Standard Features
Patent pending “Test Port Valve” allows for
aerosol smoke testing without cover removal
Clear cover fitted with four captive “No-Tools
Required” thumbscrews
Instantaneous cover removal trouble indication
In-line terminal block for easier wiring
Steady red LED on detector head indicates alarm
operation
More wiring space than competitive models
Footprint allows easy retrofit in many
applications without additional drilling
Over 15 remote accessories available
Duct wall gaskets on back of enclosure are pre-
installed
Compatible with the WP-2000 weatherproof
enclosure
Built-in alarm relay test switch Unit includes
green pilot and red alarm visual indicators
External mounting tabs do not require cover
removal to install
Colored cover gasket indicates proper cover seal
UL, CUL Listed; CSFM, MEA pending
Compact, lightweight size means easy handling,
lower shipping costs
One set of 15A form “C” alarm contacts
Large terminal connection screws
XP95A interchangeable “plug-in” UL268
photoelectric or ionization heads
Advanced detector head design yields internal
dust filtering
No additional screens or filters to clean
Compatible with fire alarm systems utilizing
Apollo XP95 and/or Discovery protocol
Ionization and Photoelectric versions available
Complete wiring details permanently attached
to unit
Standard FeaturesLow-Flow Technology: Both Ionization and
Photoelectric models listed for velocities
between 100-4000 ft./min
Both Ionization and Photoelectric models
listed for high temperature applications
Operating voltages: 24VAC or 24VDC
Units supplied with slide-in XPERT Card for
easy device addressing
Patent pending “No-Tools Required” front
or rear loading and removing sampling/
exhaust tubes
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical SpecificationsModel Number: VF4992 Ionization 24VAC or 24VDC, VF4992 Photoelectric 24VAC or 24VDC
XP95A Detector Model Number: VF4992 Ionization 55000-550APO, VF4992 Photoelectric 55000-650APO
Detector Compatibility: FACP utilizing Apollo XP95 and/or Discovery protocols
Sampling Tubes: STN-1.0 Sampling tube for 12” or less duct width, STN-2.5 Sampling tube for 6” to 2.5’ duct width
STN-5.0 Sampling tube for 2.5’ to 5.0’ duct width, STN-10.0 Sampling tube for 5.0’ to 10.0’ duct width
Accessories: MS- and MSR- Series Remote accessories,WP-2000 weatherproof enclosure and TG-2000 aerosol test gas and T-PB power supplies (All available from Air Products and Controls Inc.)
Control Board Power Requirements (without accessories): Standby - 24VAC, 105mA; 24vDC, 26mA: Alarm - 24VAC, 195mA; 24VDC 54mA
Relay Contact Rating Alarm Contacts: Resistive load: 1 set form “C” rated at 15Amps @ 125VAC, 10Amps @ 277VAC, 7Amps @ 54mA Inductive Load: 1/4 HP @ 125/250VAC (NC), 1/3 HP @ 125/250VAC (NO)
Air Velocity: 100 to 4,000 ft./min.
Ambient Temperature: SL-DA4R-N 32ºF to 150ºF (0ºC to 66ºC), SL-DA4R-P 32ºF to 140ºF (0ºC to 60ºC)
Humidity: 10 - 95% RH Non-Condensing / Non-Freezing
Wiring: Solid or stranded: #12 to #22 AWG terminals
Approvals: UL & CUL Listed (UL268A, UROX, UROX7) File # S2829, CSFM Listed (3240-1004:116), MEA Accepted (73-92-E Vol.36)
Material: Grey plastic backbox, clear plastic cover (Makrolon 94V-0)
Dimensions: 13 1/2” L x 4 1/2” W x 2 1/4” H
Max. Net Wt.: 2.25 lbs.
Radioactive Element: For SL-DA4R-N (Ionization) Americium 241; 0.9 Micro-Curie. Do not expose to corrosive atmospheres
Hardware: 7” exhaust tube, sampling tube end cap, mounting template and mounting hardware included
Engineers and Architects SpecificationsAir duct smoke detectors shall be Air Products and Controls Inc. SL-DA4R Series. For ionization detectors the model number is SL-DA4R-N.For photoelectric detectors the model number is SL-DA4R-P. The detectors shall be listed by Underwriters Laboratories per UL 268A.The detectors shall operate at air velocities from 100 feet per minute to 4,000 feet per minute and at temperatures of no greater than 140°F (60°C).Visual indication of alarm must be provided on the detector front.A manual alarm relay/test switch located on the front of the device shall be provided.Detector head shall not require additional filters or screens which must be maintained, and control board shall include both a standby and alarm visual indications.The housing shall contain a detector base which will accept photoelectric or ionization detector heads as well as a means of detector addressing.Terminal connections shall be of the screw type, a minimum of #6 screw (#12 to #22 AWG compatible). Terminals shall be provided for remote pilot, remote alarm indications, strobe/horn, and remote test switch. All wiring must comply with local codes and regulations.A method of smoke testing the detector without removing the cover must be provided.All unit and remote accessory connection designations must be permanently affixed to the unit.Cover and sampling/exhaust tube installation or removal must not require the use of tools.Sample and exhaust tubes shall be capable of removal/installation from the front and/or rear of the detector for inspection/maintenance.
L1 L2 NC NO N/O24VCOMC+ T+ P+ AL+ C- TB+
FACPSLC
REMOTE ACCESSORY
ALARMRELAY
POWER24AC/DC
UL LISTEDCOMPATIBLE
FACP SLC(LOOP)- +- +
+OUT AC/+ N/O
+IN
TEST
+OUT
PILOT
+OUT
ALRM-
OUT
+OUTTRBL
ALARM CONTACT15A@125VAC10A@277VAC
7A@30VDC1/4HP@125/250VAC-(NC)1/3HP@125/250VAC-(NO)
SUPERVISEDUNSUPERVISED
Terminal Connections Remote Accessory Wiring
TB+
C-
AL+
P+
TR+
C+
SL-D4RMSR -SERIES REMOTE ACC. MS -SERIES REMOTE ACC.
AL+
TB+
C-
P+
TR+
C+ KEY OR PUSH BUTTONTEST SWITCH
GREEN PILOT LED
RED ALARM LED AND/OR STORBE/HORN
YELLOWTROUBLE LED
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Standard Features
Single or Dual Action
Wire head Connections
Gold Plated Alarm Contacts
Surface or Weatherproof Backbox
Optional Auxiliary Alarm Contacts
Optional Station Colors
Combined with the VF5663 or VF5608 to provide an addressable interface to the Elite SLC loop
VF3033Single Action
Addressable Pull Station
Product Overview
The VF3033 and VF3034 series pull stations areoperated by pulling the handle marked “PULL” on the front of the station as far down as it will go. At that point, the station will lock in place and is easily visible from up to 50 feet. The activation handle is reset by opening the station with the hex wrench or key, placing the handle in the normal upright position and relocking the station.
On the dual action, the push bar rotates inwardallowing the “PULL” handle to be grasped and operated by a single hand. When used with the VF6001 Fast Response Contact Module, each addressable contact monitoring module is programmed with its own unique Signaling Line Circuit (SLC) loop address.
Up to 126 devices can be placed on the Elite SLC loop. The module supervises the wiring to the contact with an End Of Line (EOL) resistor. It can be programmed to monitor normally open (NO) or normally closed (NC) contacts. If a fault condition occurs in the wiring, the module sends a trouble status signal to the fire alarm control panel. When a change of status is sensed by the fast response contact module, it sends an interrupt to the control panel indicating that an alarm has occurred.
After addressing, Manual Pull Stations are fullyconfigurable through Loop Explorer.
Application
The VF3033 and VF3034 are versatile, high- quality, metal Fire Alarm Pull Stations designed to meet any installation demand.
Available in both single (VF3033) and dual action (VF3034) configurations. VF3021 and VF3022 pull stations are integrated with the analog single contact module to provide a simple-to-install addressable pull station. The normally open contact of each station, which closes when the pull station is activated, is rated for 1 Amp, 30VDC. The contacts are gold plated to avoid risk of corrosion.
All VF3033 and VF3034 models have been tested by UL and found in compliance to the latest requirements of the American’s With Disabilities Act (ADA). VF3033 / VF3034 stations from VES are available with key reset. Key reset models are available for interchangeable keys. All models mount on a standard, single gang backbox, VES VF3007-
10 interior surface metal backbox or model VF3008-10 weatherproof backbox interior surface metal backbox or model VF3008-10 weatherproof backbox.
SLC Devices
VF3034Dual Action
Addressable Pull Station
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Rated voltage DCP powered loop: 17-41 VDC
Average consumption: 3.5mA
Alarm current: 17-28 VDC
Transmission: DCP - Digital Communication Protocol
Maximum humidity: 90% RH non-condensing
UL ambient installation temperature range: 32°F to 100°F
Operating temperature range: 14°F to 122°F
Color & case material: Red
Ordering Codes
Part number
VF3033
VF3034
VF3007-10
VF3008-10
VF3009-00
VF5608 or 63
Description
Single action addressable pull station
Dual action addressable pull station
Interior surface sheet metal backbox - red
Weatherproof surface die cast metal backbox and gasket assembly - red
Scored plastic (acrylic) breakrods (1 dozen per pack)
Fast response contact module
Engineering Specification
The Dealer shall furnish and install where indicated on the plans, dual-chamber ionization sensors, VES part number VF3033 or VF3034, depending on customer or specifier requirements.
State-of-the-art communications protocol, DCP, allows multiple system component types to be used concurrently in a system’s signal conditioning loop.
Note: All models are supplied with one scored, acrylic breakrod & one key
Typical Wiring Diagram
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF4990 Multi Flex Sounder Base Analog Addressable
Sounder Bases
Overview
The Multi-Flex family of the smoke detector sounder cases and synchronization modules provide today’s most advanced functionality and performance, delivering flexible notification capabilities for Apollo conventional and analog addressable systems.
The bases offer selectable steady or temporal pattern output and selectable high or low volume levels. The three-pulse temporal pattern is required by NFPA 72 for fire alarm evacuation for commercial and residential applications.
Available synchronization modules (SM) allow temporal pattern sounder base circuits to be completely synchronized and installed in almost limitless configurations, and also provide an onboard latching test function.
The sounder base requires an external 24VDC power supply. in the absence of a synchronization module, a means for polarity reversal is required for test and general alarm functionality. The connections for the external power supply and the communication loop are opto-isolated to prevent electrical interaction between them.
Standard Features
Compatible panel silence functions
Sync network “self tests” to ensure synchronized output if “upstream” sync signal is lost
Sounders will operate in “failsafe” mode if sync network is compromised
Sync modules available in MR-1 enclosures, snap track or chassis mount for standard 2-gang box
Intelligent trouble reporting via onboard Trouble LED
Technical Specifications - Multi Flex Sounder Base
Compatible Smoke Detectors
Sounder Base Operating Voltage
Sounder Base Alarm Currents
Sounder Base Standby Current
Sounder Base Audible Intensity
Wiring
Environmental
Material
Dimensions
Approvals
17-30VDC (24VDC nominal)
External Supply: 29mA @ 24VDC Assocaited Detector: 8mA @ 24VDC
0.03mA @ 24VDC
High Volume Selection: 85dB @ 10 feet Low Volume Selection: 75dB @ 24VDC
Solid or Stranded; #12 to #22 AWG Terminals
32oF to 100oF (0oC to 38oC) 0% to 85% RH; Non-Condensing/ Non-Freezing
Makrolon 6455 or 6555 (polycarbonate); 94V-0
6” L x 6” W x 1.6” D (152mm x 152mm x 41mm)
UL Listed File Pending - CSFM Pending - MEA Pending
Sounder Base
Part Number
Conventional (Series 65 or Series 60A)
MD-SDRT-AA MB-SDRT-CV
Analog Addressable (Discovery or XP95A)
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications - Multi Flex Synchronization Module
3.3” (83.82mm)2.6” (66.04mm)
0.77” (19.56mm)
MD-SDRT-SM/G MB-SDRT-SM/G/R MB-SDRT-SM/T MB-SDRT-SM/C MB-SDRT-SM/C/R
3.4” (87mm)2.75” (69.85mm)1.22” (30.99mm)
5.13” (131mm)3.13” (80mm)2.5” (64mm)
White ABS plastic;94V-0
Red ABS plastic;94V-0
Gray ABS plastic;94V-0
Red ABS plastic;94V-0
Metal 2-Gang Mounting Chassis with Appropraite Wall Plate Cover
18Ga. CRS, Plated with 1/2 “ Conduit Knockouts, Top and Bottom
Low-profile Snap-Track with Provided
Mounting Screws
17-30VDC FWR Unfiltered (24VDC nominal)
24VDC - Power Circuit (SM): 16mA Standby; 16mA AlarmSIL NAC - Silence Circuit (SM): 7.5mA Standby; 2mA Alarm
SYNC IN - Synchronization Signal In (SM): 4mA Standby; 15mA Alarm
TROUBLE: Always FACP monitored and reported as trouble or supervisory in all program modes. Dry N.O. contact held closed by the Powerower 24VDC input being present and the internal module circuitry being fully operational. Also supervises the presence of a sync in signal when module is programmed in the “secondary” or “sync only” modes. It is not used when the module is programmed in the “main” mode.
GENERAL ALARM: 24VDC steady or pulsed, silenceable, polarized FACP NAC Input. This input is used only when the module is programmed in the “main” or “sync only” modes. When the connected NAC is in the alarm state the module will provide a general alarm signal to all associated sounder/relay bases, causing them to sound if a horn enable alarm input is also present.
HORN ENABLE: 24VDC steady or pulsed, silenceable polarized FACP NAC input. This input is used only when the module is programmed in the “main” or “sync only” modes. When the connected NAC is in the alarm state the module will be active and ready to accept a general alarm input. The status of the connected NAC will also be monitored for subsequently being silenced from the FACP and will provide that signal to all associated sounder bases, causing them to silence. Subsequent alarms will resound as signalled from the FACP NAC connected to this input.
SYNC IN: 24VDC/protocol feed input from associated module programmed in the “main”, “secondary” or “sync only” mode. This input is always used when the module is programmed in the “secondary” or “sync only” modes. It is not used when the module is programmed in the “main” mode.
SYNC OUT: 24VDC/protocol feed output from module in all modes. When the module is programmed in the “main” or “sync only” modes, also provides distinct horn enable and general alarm status information to all associated sounder/relay bases and any modules programmed as “secondary”.
POWER 24VDC: 24VDC power feed in always required in all modes. When the module is programmed in the “sync only” mode this input could be from a shared power supply with the associated “main” programmed
module. When the module is programmed in the “secondary” mode this input will always be supplied from a new additional power source since that is the only reason it is being installed.
Input/ Output Details
Two-Gang Box
Mounted (H x W x D)
Track Mounted
(H x W x D)
Enclosure Mounted
(H x W x D)
Cover Material
Enclosure/ Mounting
Details
Operating Voltage Range
Current Requirements
Intelligent Trouble Reporting
Wiring
Environmental
Approvals
Trouble LED: ON - Test Mode SINGLE BLINK - Sync In (when in “main” mode) Double Blink - No Sync In (when in “secondary” mode) Triple Blink - Output Short
Solid or Stranded; #12 to #22 AWG Terminals
32oF to 100oF (0oC to 38oC) 0% to 85% RH; Non-Condensing/ Non-Freezing
UL Listed File Pending - CSFM Pending - MEA Pending
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5635 Low Power Relay Base
The VF5635 Low Power Relay Base incorporates a low power relay to control field equipment such as automatic door closers.
Gives a set of voltage free contacts controlled by the remote output of a detector
Draws negligible current
Sensor Bases
VF5630 Mounting Base 4”
VF5636 Mounting Base 6”
All detectors fit the VF5630 and VF5636 Mounting Bases which are low insertion force bases with stainless steel contacts for the detector terminals. XPERT cards are supplied with all bases.
XPERT addressing
One way fit
Locking feature to prevent unauthorized removal
VF5632 E-Z Fit Base
The E-Z fit base is a low profile 6” mounting base for ACC detectors.
High degree of protection against unauthorized removal
VF5640 Blank XPERT Card
A Universal address card supplied with all bases. Using a coding guide, pips are removed to set the address of the inserted detector.
Simplifies and speeds up installation and commissioning
Uses patented, proven technology
Address remains the same, no matter how often detectors are replaced
Flexibility to create any address
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5633 Isolating Base
The VF5633 Isolating Base senses and detects short circuit faults on SLC loops.
Up to 20 devices may be installed between isolating bases
XPERT addressing
SLC Isolators
VF5605 Isolator
The VF5605 Isolator is placed at intervals on the loop and ensures that, in the case of a short circuit, only the section between the isolators will be affected. When the short circuit is removed, the isolators automatically restore power and data to the isolated section.
Detects wiring short-circuits using patented technology
Minimizes disruption from short-circuits
Automatic de-isolation on short-circuit removal
Up to 20 devices may be installed between isolators
VF5634 Isolator Base
The VF5634 Isolator Base is unique and designed to only accept the Isolator.
Only accepts isolators
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
The Mini Priority Switch Monitor is designed to monitor the state of one or more single pole, volt free contacts and to report the status to Apollo compatible analog control equipment. It can also place a signal on the loop to provide early warning if a device such as a pull station is operated.
Three input states – “normal”, “fault” and “alarm”
Visible LED with remote LED connection option
Loop powered
Designed to fit into equipment with limited space
Easy to install
Monitors equipment where a fast response is required
Interrupt facility
Class A or B input capability
Mini Input Modules
VF5661 Mini Switch Monitor Module
The VF5661 Mini Switch Monitor Module is designed to monitor the state of one or more single pole, volt free contacts and to report the status to Apollo compatible analog control equipment.
Three input states – “normal”, “fault” and “alarm”
Visible LED with remote LED connection option
Loop powered
Designed to fit into equipment with limited space
Easy to install
VF5608 Mini Monitor Module
The New Mini Monitor Module is an interface within a entirely new housing. This allows the unit to be fitted onto a standard 35mm DIN-rail (using a twist-click motion) or mounted within an enclosure, for example a manual call point. It is designed to monitor the state of one or more single pole, volt free contacts connected on a single pair of cables and to report the status to Apollo compatible analog control equipment.
Designed for use where space is limited
Features a short circuit isolator as standard
Interrupt/non interrupt in one unit
“Pre-alarm” status available
LED status indication (Yellow - Fault, Green - Polling, Red - Alarm)
DIN Rail mountable
VF5660 Mini Priority Switch Monitor Module
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5662 Switch Monitor ModuleThe VF5662 Switch Monitor Module is designed to monitor the state of one or more single pole, volt free contacts connected and to report the status to Apollo compatible analog control equipment.
Three input states – “normal”, “Fault”, and “alarm”
Visible LED
Loop powered
Modules
VF5663 Priority Switch Monitor ModuleThe Priority Switch Monitor Module is designed to monitor the state of one or more single pole, volt free contacts and to report the status to Apollo compatible analog control equipment. It can also place a signal on the loop to provide early warning if a device such as a pull station is operated.
Three input states – “normal”, “Fault”, and “alarm”
Loop powered
Fast response time
Interrupt facility
Mounts on a 2-gang or 4x4 box
VF5664 Dual Priority Switch Monitor ModuleThe VF5664 Dual Priority Switch Monitor Module contains two priority switch monitor modules (55000-806) on a single plate.
Loop powered
Fast response time
Interrupt facility
Mounts on a 2-gang or 4x4 box
Two visible LEDs
VF5665 Switch Monitor Input/Output ModuleThe Switch Monitor Input/Output Module provides a voltage free, single pole, change-over relay output, a single, monitored switch input and unmonitored, non-polarized opto-coupled input.
It can report fault, switch open and switch closed levels
Visible LED
Fast Response time
Mounts on a 2-gang or 4x4 box
VF5666 Sounder Control ModuleThe Sounder Control Module monitors and controls the operation of a zone of conventional sounders and reports their status to the control panel.
Allows sounders to be operated continuously or be pulsed, 1 second on, 1 second off
May be synchronized when in pulsed operation
Can also be used for public address speakers
Visible LED
VF5667 Relay Output Module
The Relay Output Module provides a single 2-pole changeover relay.
Loop Powered
Can be placed anywhere on loop
Visible LED
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Standard Features
Sleek modern aesthetics
Finger slide switches
Voltage test points
Multiple voltages
3 audible settings 90, 95, 99 dB
8 Candela SettingsWall - 15 / 1575 / 30 / 75 / 95 / 110 / 135 / 185Ceiling - 15 / 30 / 60 / 75 / 95 / 115 / 150 / 177
Universal mounting base - Ceiling and wall mounts to 5 backbox types
Environmentally friendly -Low current draw
Compatible with UL “Regulated Voltage” using filtered DC or unfiltered VRMS input voltage
Product Overview
The VES series of notification appliances feature a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction.
The VES series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification circuit. All strobe models feature an industry first of 8 candela settings on a single appliance. Models with an audible feature 3 sound settings (90, 95, 99 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection.
The VES series of notification appliances feature a snap-on base that is designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate mounting base can be pre-wired so circuit wiring can be fully tested before the appliance is installed and the surface is finished. Once the surrounding work is complete, the appliance can be simply installed by snapping it on to the base. Resettable shorting contacts in the base, which provide continuity for circuit testing, are opened when the appliance is installed. Any removal of the appliance will indicate a trouble condition on that circuit at the control panel that supervises the circuit. The same base is used for all VES series appliances to provide consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra secure installation, while the ceiling models provide a captivated screw to prevent the screw from falling during installation.
Horns & Strobes
Model:VF4675-30
Model:VF4674-10
Model:VF4672-30
Model:VF4670-10
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Voltage test points for quick
troubleshooting and easy spot checking 8 candela settings
Common base for wall and ceiling
with 5 mounting options
Technical Specifications & Ordering Codes
Model
VF4670-10
VF4670-30
VF4671-10
VF4671-30
VF4672-10
VF4672-30
VF4673-10
VF4673-30
VF4674-10
VF4674-30
VF4675-10
VF4675-30
Strobe Candela
15 / 1575 / 30 / 75 / 95 / 110 / 135 / 185
15 / 1575 / 30 / 75 / 95 / 110 / 135 / 185
15 / 30 / 60 / 75 / 95 / 115 / 150 / 177
15 / 30 / 60 / 75 / 95 / 115 / 150 / 177
15 / 1575 / 30 / 75 / 95 / 110 / 135 / 185
15 / 1575 / 30 / 75 / 95 / 110 / 135 / 185
15 / 30 / 60 / 75 / 95 / 115 / 150 / 177
15 / 30 / 60 / 75 / 95 / 115 / 150 / 177
Type
Horn Strobe
Horn Strobe
Horn Strobe
Horn Strobe
Strobe
Strobe
Strobe
Strobe
Horn
Horn
Horn
Horn
Current Draw
Range @ 24 VDC
0.062 - 0.167
0.062 - 0.167
0.062 - 0.149
0.062 - 0.149
0.057 - 0.160
0.057 - 0.160
0.057 - 0.115
0.057 - 0.115
0.019 - 0.046
0.019 - 0.046
0.019 - 0.046
0.019 - 0.046
Mounting
UMB *
UMB *
UMB *
UMB *
UMB *
UMB *
UMB *
UMB *
UMB *
UMB *
UMB *
UMB *
General Notes
Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.
All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
Strobes are designed to operate under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 85% (± 2%) UL 464 (UL 1971).
Horns are designed to operate under UL Standard 464 for audible signal appliances (Indoor use only).
“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology “Listed Voltage Range”.
* UMB = Universal Mounting Base. 1 Gang, 2 Gang, 4” square, 3.5” octal boxes
Shape
Square
Square
Round
Round
Square
Square
Round
Round
Square
Square
Round
Round
Color
Red
White
Red
White
Red
White
Red
White
Red
White
Red
White
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VESNetCommunication and
Network Options
Standard Features
Dual-line digital communicator with line seizure on Media Gateway® and Modem DACT
33.6 Kbps modem for panel downloading
Provides network-wide programming with remote and local management
Remote programming via eSP Discovery
Transmits in SIA (SIA 8 and SIA 20) Digital Communications standard (300 bps) and Contact ID communication format
All nodes report through a single Media Gateway® to a central station and data center
VESNet configurable for Class A or B networking
Communication speed of 115 Kbps on VESNet™ and 10BaseT Ethernet interface
Built-in Firewall with messaging through LAN connections always from within VESNet
VF1150 Media Gateway® with Releasing
Supports networking, remote monitoring, virtual display and remote programming and remote displays.
VF1151 Network Interface Card (NIC) with Releasing
Used for inter-panel networking and interfaces to other systems.
VF1153 VESNet Ether/DACT
Used for single panel installations.Supports remote monitoring, virtual display, and remote programming.
Maintenance message logging
Virtual Panel ready with Media Gateway®
Built-in Web Server in the Media Gateway® for displaying Virtual Panel
Installation diagnostics at startup through eSP
Onboard Motorola 32 bit, 66 MHz RISC processor
RJ-45 (Ethernet) port for LAN connection
2 RJ-45 VESNet™ ports for network connections using standard CAT 3,5,5e,6 cable
2 RJ-11 Telco ports for phone lines for connection to RJ-31X or RJ-38
Up to 126 Fire Nodes can be installed on VESNet™
Up to 2,000 feet between nodes on VESNet™
Installation diagnostics at startup
CommunicationsInstallation
One Communications Card per Panel
1 Plug-in Ribbon Cable, 2 CAT5 wired to RJ-45 VESNet connectors
2 RJ-11 Telephone Jacks
1 RS-232 cable to panel
Ethernet RJ-45 on Media Gateway®
Powered from Panel
VESNet communication is only available on the Media Gateway® and NIC.Telephone jacks are only available on the Media Gateway® and Ether/DACT.
NMB-003 DU CANADA.CET APPAREIL NUMERIQUE DE LA CLASSE A EST CONFORME A LA NORMETHIS CLASS A DIGITAL APPARATUS COMPLIES WITH CANADIAN ICES-003.Industry Canada Electromagnetic Compatibility, ICES-003:
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
PN
: HW
-00
000
7 R
EV
ETHIS DEVICE COMPLIES WITH PART 68 RULES
FCC REG. NO.: VESAL00BVF10xx-xx
REN = 00B
JACK TYPE: RJ11C
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, ANDOPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
J7DATA
Comm ActiveComm Fault
VNet BVNet AEthernet
VE
SN
ETA
Heartbeat
POWERJ8B
REFER TO MEDIA GATEWAY INSTALLATIONMANUAL WITH RELEASING VF1627-00Rev. E02.XX
000AFD0002FB
MAXIMUM POWER REQUIREMENT: 24VDC @ 115mAFOR INDOOR DRY USE ONLYJACK J3 VESNet IS SUPERVISED AND POWER- LIMITEDJACK J5 ETHERNET IS UNSUPERVISED AND POWER- LIMITEDTHE MEDIA GATEWAY WITH RELEASING CONTAINSA DACT AT JACK 1 TELCO LINE 1 AND LINE 2.JACK 1 TELCO LINE 1 AND LINE 2 ARE SUPERVISED
TESTED TO COMPLY WITH FCC STANDARDS
PRI
TELCO
Line 1 Line 2SEC
VES, LLC620 ALLENDALE ROAD, SUITE 175KING OF PRUSSIA, PA 19406610-992-0400MODEL NO.: VF1150-00MEDIA GATEWAY WITH RELEASING
LISTED
SIGNALING
FIRE ALARM SUBASSEMBLY3PBS
LBL-000133
PN
: H
W-0
00
007
RE
V ETHIS DEVICE COMPLIES WITH PART 68 RULES
FCC REG. NO.: VESAL00BVF10xx-xx
REN = 00B
JACK TYPE: RJ11C
J7DATA
Comm Active
Comm Fault
VNet BVNet A
Heartbeat
POWERJ8
REFER TO NETWORK INTERFACE CARD(NIC) INSTALLATION MANUAL WITHRELEASING VF1629-00 Rev. E02.XX
000AFD0002FB
MAXIMUM POWER REQUIREMENT: 24 VDC @ 80 mAFOR INDOOR DRY USE ONLYJACK J3 VESNet IS SUPERVISED AND POWER- LIMITED
MODEL NO.: VF1151-00NETWORK INTERFACE CARD (NIC)WITH RELEASING
NMB-003 DU CANADA.CET APPAREIL NUMERIQUE DE LA CLASSE A EST CONFORME A LA NORME
THIS CLASS A DIGITAL APPARATUS COMPLIES WITH CANADIAN ICES-003.Industry Canada Electromagnetic Compatibility, ICES-003:
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, ANDOPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
VE
SN
ET
B
ALISTED
SIGNALING
FIRE ALARM SUBASSEMBLY3PBS
LBL-000133
VES, LLC620 ALLENDALE ROAD, SUITE 175KING OF PRUSSIA, PA 19406610-992-0400
MODEL NO.: VF1153-00MODEM-DACT ETHERNETWITH RELEASINGMAXIMUM POWER REQUIREMENT: 24 VDC @ 115 mAFOR INDOOR DRY USE ONLYJACK J5 ETHERNET IS UNSUPERVISED AND POWER- LIMITEDJACK 1 TELCO LINE 1 AND LINE 2 ARE SUPERVISED
REFER TO MODEM-DACT ETHERNETINSTALLATION MANUAL WITH RELEASINGVF1628-00, Rev. E02.XX ANDMODEM-DACT CONFIGURATION ANDREPAIR MANUAL VF1624-00, Rev.E02.XX
PN
: HW
-00
0007
RE
V E
PRI
TELCO
Line 1 Line 2SEC
Comm Active
THIS DEVICE COMPLIES WITH PART 68 RULES
FCC REG. NO.: VESAL00BVF10xx-xxREN = 00BJACK TYPE: RJ11C
Comm Fault
DATAJ7
Heartbeat
POWERJ8
VNet BVNet A
000AFD0002FB
TESTED TO COMPLY WITH FCC STANDARDSTHIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.Industry Canada Electromagnetic Compatibility, ICES-003:THIS CLASS A DIGITAL APPARATUS COMPLIES WITH CANADIAN ICES-003.CET APPAREIL NUMERIQUE DE LA CLASSE A EST CONFORME A LA NORMENMB-003 DU CANADA.
Ethernet
VES, LLC620 ALLENDALE ROAD, SUITE 175KING OF PRUSSIA, PA 19406610-992-0400
LISTED
SIGNALING
FIRE ALARM SUBASSEMBLY3PBS
LBL-000133
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
DC Input: 24 VDC on all Com
Power:
Media Gateway®
NIC
Ether/DACT
Dimensions: 2.5” W x 7.5” D x 1.125” H (includes circuit board with cover)
Operating Environment:
Low temperature
High temperature
Relative humidity
Virtual panel capability
The VES Elite Panels with a Media Gateway® can be connected to a local IT LAN and provides the ability to view a depiction of the FACP display. Virtual Panel may also allow operating the keypad, as if standing in front of the FACP.
Can be viewed by all personnel with the correct security logon
Presents an exact replica of messages on any connected Elite panel’s display
Authorized personnel with panel security access can also perform all display keypad functions from Virtual Panel locations.
Virtual Panel ships disabled and requires activation
Internet Explorer 5.5 or higher is required on the desktop PC using Virtual Panel
Standby current
100mA
75mA
75mA
Alarm current
115mA
80mA
95mA
32° +/- 3°F (0° +/- 2°C), UL 864, 65.2
120° +/- 3°F (49° +/- 2°C), UL 864, 65.3
93% +/- 2% @ 90° +/- 3°F (32° +/- 2°C), UL 864, 65.4
Added Features:
VF1221 - Elite with Media Gateway®:
All the features of the Modem/DACT and NIC: plus
Virtual Panel ready with Firewall
Enables network programming with direct TCP/IP access to each panel
Access point for network communications
VF1222 - Elite with NIC:
Network uses standard Cat 5 cabling
Up to 2,000 ft. between adjacent panels
115 Kbps constant network speed
TCP and UDP communications through VESNet
Total network delay less than 3 sec. with 127 panels
Network jacks – RJ-45 (VESNet and Ethernet)
Mapped Network; Display messages for Any or All nodes
VF1224 - Elite with VESNet Ether/DACT:
Virtual Panel ready with Firewall
Direct IP programming with eSP Discovery Transfer agent
Access point for network communications
Dual line digital communicator and modem
Central Station reporting; SIA and Contact ID
Phone line jacks – RJ-11 (two)
Modem speed: 33.6 Kbps for program downloading Note:
The Energy conversion equipment (ECE) shall be designed to function in an atmosphere having a relative humidity that can vary from 5 percent to 95 percent, non-condensing.- NFPA 111, 5.2.7
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF117116 Channel Input/Output Board VF1171 16 Channel Input/Output Board
A powerful addition to the Elite system.For LED mimics, plant alarms, plant control, voice evacuation and many other applications.
Standard Features
UL approved
16 channels Each channel configurable as input or output Inputs opto-isolated Outputs open collector transistor
Simple 2 wire connection to control panel Up to 32 boards supported per panel(512 Input/Output Channels) Inputs and outputs configurable as perfield devices Full cause and effects on all inputs and outputs
Multi drop RS485 communications
Can be used with other Elite I/O modules on the same panel
Compatible with Elite RS panels
Product Overview
To add more I/O capablity to the extensive options already offered by the Elite control panel, up to thirty two, sixteen channel I/O boards may be connected.
When using a simple two wire RS485 communications protocol, these boards may be mounted locally to the control panel or distibuted on a bus up to 3,900 feet long by using a suitable cable.
The flexibility of these boards is further enhanced by the fact that each of the channels is configurable as either an input or and output.
Each channel may also be configured to produce a variety of input actions or respond to a varierty of output types.
All channels can contribute to, or respond to, system wide cause and effects logic.
Typical uses for I/O boards include geographical LED mimic displays and plant alarm inputs.
Standard Elite control panels contain fixings for one I/O board, which can easily be connected using four small signal wires to the power and comms bus within the panel.
Consideration must be taken as to the loading on the main panel.
Technical Specifications
Supply voltage: 21 - 30V DC
Quiescent current consumption: 20mA
Current per input: 3mA (maximum)
Current per output: 100mA (maximum)
Communications: RS485 two wire
Max. distance from panel:3900 feet (using correct type of cable)
PCB size: 7.5” H x 2.4” W
Cable capacity: 2.5mm per terminal
Operating temperature:
14º F to 122º F ( -10º C to 50º C)
Operating humidity: to 95% (non condensing)
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Standard Features
Matches design & color scheme for standard Elite control panel ranges
Easy to install
Key Lockable
Designed for versatility
Choice of small or large capacity enclosure
VF071xFire Document Enclosure
Product Overview
Another addition to the VES range, the document box is designed to complement the design & color of the Elite range of control panels. The standard version Document Box will hold up to 50 A4 sheets of information on the Fire Detection or other security systems within a premises. The deep version will hold up to 100 sheets.
The “Doc Box” also doubles up as a Key Box providing 7 easily accessible formed key hooks inside the enclosure.
Available in Gray
Technical Specifications
Construction: 18AWG sheet steel
Dimensions:
VF0711 / VF0713: 14.5”W x 12.2”H x 3.4” D
VF0710 / VF0712: 14.5”W x 12.2”H x 2.5” D
Weight: 6.6lb
Finish (lid & box): RAL3002 (Red) or BS 00 A 05 (Gray)
Finish (product labels): BS 00 A 05 (Gray)
Panel Options
VF0710-xx: Standard
VF0711-xx: Deep
VF0712-xx: Standard w/ Tamper
VF0713-xx: Deep w/ Tamper
xx = 10 (Red) or 40 (Gray)
VF4683Manual Call Point
Overview
The Discovery Manual Call Point is compliant with EN54-11. The Call Point can be addressed at the commissioning stage by means of a seven-segment DIL switch. When operated, the manual call point interrupts the polling cycle for a fast response.
Standard Features
Flashing LED option
Plug and play terminal connections for fast wiring
Allow wiring continuity testing before fitting
Reports an alarm in under 0.2 seconds
Resettable element
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Standard Features
Matches design & color scheme for standard Elite control panel ranges
Easy to install
Key Lockable
Designed for versatility
Three sizes of enclosure to choose from
VF073xAncillary Enclosure
Product Overview
The Ancillary enclosure is designed to provide an organized and secure mounting enclosure for I/O cards and SLC devices. The Ancillary enclosure is manufactured in three different sizes, two different colors and with a tamper option.
The Ancillary Enclosure is customized with mounting requirements and multiple conduit entries to fit module configurations depicted in the table below.
Technical Specifications
Construction:
VF073x: 18AWG sheet steel
VF073x: 16AWG sheet steel
VF073x: 16AWG sheet steel
Dimensions:
VF0730: 14.5”W x 12.2”H x 3.4” D
VF0731: 14.5”W x 18.9”H x 4.25” D
VF0732: 14.5”W x 24”H x 5” D
Finish (lid & box): RAL3002 (Red) or BS 00 A 05 (Gray)
Finish (product labels): BS 00 A 05 (Gray)
Stan
Matchestandar
Easy to
Key Loc
Design
Three s
Panel Options (Modules must be purchased separately)
Part No. Enclosure Size I/O Modules SLC Modules
14.5”W x 12.2”H x 3.4” D 0 2VF0730-xx* 14.5”W x 12.2”H x 3.4” D 1 2 14.5”W x 12.2”H x 3.4” D 2 0
14.5”W x 18.9”H x 4.25” D 0 6 14.5”W x 18.9”H x 4.25” D 1 4 14.5”W x 18.9”H x 4.25” D 2 2 14.5”W x 18.9”H x 4.25” D 3 0
14.5”W x 24”H x 5” D 0 8 14.5”W x 24”H x 5” D 1 6VF0732-xx* 14.5”W x 24”H x 5” D 2 4 14.5”W x 24”H x 5” D 3 2 14.5”W x 24”H x 5” D 4 0
VF0731-xx*
* xx = 10 (Red) or 40 (Gray)
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VoiceAlertVoice Evacuation System
Standard Features
True Multiplex 6 Channel Distributed Audio
Integrated Fire Phone, Area of Rescue and Fan & Damper Control capability
Modular System - components added as needed
Integrated 2 Channel Digital Message Repeater
Live Microphone Page to any zone
Fast RS-485 Communication Protocol
Easy Installation and Operation
Natural Sound Voice Recordings
Built in Alarm and Alert Signals
Up to 4 Minute Message Capacity
Works with 12VDC or 24VDC Fire Alarm Panel
Listed with for use with the Elite FACP
3 Minute Message Restart on Microphone Key
Fully Supervised
Operation - Basic System includes
Master Panel (VF9700)
Master Mic Control
16 switch control points
Dual Channel DMR
High speed communication loop
Distributed Panel (VF9755)*
4 Output Zones (may be configured for 8)
Dual Channel Audio Interface
Dual Channel Amplification
Optional
Integrated Fire Phone
Area-of-Rescue
Fan and Damper system control
Maximum System Configuration
Up to 256 Distributed Panels (VF9755)
Up to 2028 monitor and control points
*Number of distributed panels to be determined by building specifications
Product Overview
The VES VoiceAlert High Rise Evacuation System operates in conjunction with the Elite Fire Alarm Control Panel (FACP) in a building to provide automatic response to life safety emergencies. The VoiceAlert system includes all necessary features to provide an effective voice evacuation system. The VoiceAlert can be custom configured to satisfy the needs of any high rise application.
Fire department authorities can easily take command of evacuation or relocation procedures and emergencies. Building management and fire brigades can monitor and control emergency response even before the professionals arrive. The VoiceAlert system includes capacity for 6 Channels of simultaneous audio. This provides for evacuation, stay-in-place, or other public address announcements and automatic messages.
Fire Fighter Phones or Warden Stations may be included as required. Area-of-Rescue stations can reassure handicapped occupants that help is on the way. Smoke control, stair pressurization, and HVAC shutdown can be completely automatic, unless controlled manually by management or fire authorities.
Military Emergency VoiceAlert
Systems - DOD Compliant
The U.S. Department of Defense is requiring mass notification systems in inhabited buildings.
The ability to quickly broadcast pre-recorded and live warnings to all personnel is considered essential in reducing casualties in the event of attack on DOD facilities.
The VoiceAlert VMX supervised emergency voice alert system meets or exceeds DOD Minimum Anti-terrorism Standards for Buildings, UFC 4-010-01. It is also compliant with UFC 4-021-01, Design and O & M Mass Notification Systems.
VF9700 Master Panel
VF9755 Distributed Panel
Voice Alert Panel OptionsVF9520
VF9521
VF9522
VF9524
VF9535
VF9558
VF9720
VF9722
VF9724
VF9726
VF9728
VF9730
VF9740
VF9742
VF9744
VF9746
VF9748
VF9750
VF9760
VF9762
VF9764
VF9768
VF9770
VF9774
VF9776
VF9778
VF9780
VF9782
VF9793
VF4405
VF4409
Mother Board
Fire Phone Input Card
Fire Phone Output Card
Warden Station
Extended Input Interface
Class A Return Module
Master Panel, 16 Zone, Red
Master Panel, 32 Zone, Red
Master Panel, 48 Zone, Red
Master Panel, 64 Zone, Red
Master Panel, 80 Zone, Red
Master Panel, 96 Zone, Red
Master Panel, 16 Zone, w/Phone, Red
Master Panel, 32 Zone, w/Phone, Red
Master Panel, 48 Zone, w/Phone, Red
Master Panel, 64 Zone, w/Phone, Red
Master Panel, 80 Zone, w/Phone, Red
Master Panel, 96 Zone, w/Phone, Red
Distributed Panel, Single, 25W, Red
Distributed Panel, Single, 50W, Red
Distributed Panel, Single, 100W, Red
Distributed Panel, Single, 50W, w/Phone, Red
Distributed Panel, Single, 100W, w/Phone, Red
Distributed Panel, Dual, 50W, Red
Distributed Panel, Dual, 100W, Red
Distributed Panel, Single, 25W, w/Phone, Red
Distributed Panel, Dual, 50W, w/Phone, Red
Distributed Panel, Dual, 100W, w/Phone, Red
Distributed Panel, Dual, 200W, w/Phone, Red
Speaker, Wall Red
Speaker Ceiling 2 Watt Red
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VoiceAlert Voice Evacuation System Components
VF9315 Audio Module Interface
Controls two VF9212/9236/9256 amplifier modules in remote distribution panels. One required when adding back up amplification to a Dual channel system. Uses an addition slot on a VF9227.
VF9316 Audio System Control
Provides digitally stored Message Control. Has two RS232 com ports.
VF9546 Back-up Amplifier switching relay
One required for each Distributed Amp when automatic switching / redundant amplification is needed. On a single Channel system the back up amplifier can be located in any 9755 Series panel. On a Dual Channel system an additional VF9315 card, and Amplifier assembly is required (the # represents the largest power amplifier in the system 25/50/100).
VF9547 Back-up Amplifier switching relay Class “A”
One required for each Distributed Amp plus the “spare” amplifier when automatic switching / redundant amplification is needed Class “A” wiring. On a single Channel system the ”spare” amplifier can be located in any 9755 Series panel. On a Dual Channel system an additional VF9315 card, and Amplifier assembly is required (the # represents the largest power amplifier in the system 25/50/100).
VF9525 Break Out Card
Used to provide terminal connections from 10 Pin ribbon cable for wiring termination. (2 required) Needed when Dual Channel Back-Up Amplification is required.
VF9545 Data Communications Controller
A VF9545 is located in the Master Panel and each Distributed Panel the VF9545 is the connection point for the NETCOMM communications. The Data loop must be wired style 6 or 7 (Style 7 preferred) (must have return data loop). Replacement Card, typically preprogrammed from the factory.
VF9537 Fiber Optic Transceiver
Provides termination for Fiber Optic communications between the Master Panel and the Distributed Panels.
VF9548 Fiber Optic Style 7 card
Master Panel Fiber Optic card (1 per system) required when Style 7 Fiber Optic communications is used. The VF9548 card converts the secondary (style 7) data loop to a data signal that can be sent on the Fiber Optic secondary loop.
VF9521 Fire Phone Interface
Provides 4 supervised Class “B” Fire Phone circuits in distributed panel (4max 16 circuits). When more then one is used in a 9755 Series panel a VF9522 card is required for each.
VF9522 Fire Phone Output Adapter
Extra terminal card that must be used with the 2nd, 3rd & 4th VF9521 cards in a 9755 Series panel.
VF9549 Fire Phone Output Adapter
Extra break out card that must be used with the 2ND, 3RD & 4TH MX-FPI cards in a 9755 Series panel. This card aligns all 4 Fire Phone circuits vertically.
VF9318 Fire Phone Relay
Warden station reverse polarity relay for NYC applications.
VF9541 Isolated Network Bridge
Network interface when a Master Panel is needed to communicate with remote Master Panels running their own systems.
VF9526 Input Interface Card
Hardwired conventional control input interface/trigger.Required when using any triggers other the VES Intelligent Interface. Provides 16 inputs and control for up to 7 additional input cards (128 inputs). System capacity for up to 16 VF9526cards (2048 inputs). TTL or dry contract input. Also accepts a reverse polarity NAC circuit trigger.
VF9315VF9316
VF9546VF9547
VF9525
VF9537 VF9548
VF9545
VF9549
VF9521
VF9522
VF9318 VF9526 VF9541
Description
Fire Phone accessories give the VMX system two-way communication capability.
Fire Phone jacks are mounted on a single gang plate. Fixed telephone and warden stations are available in surface / semi-flush mount cabinet with a thumb-turn-latch.
Ordering Information
VF9510
VF9514 - VF9517
VF9511
VF9512
Model Number Description VF9512 Telephone Jack
Brushed Stainless Steel Single Gang Plate
VF9511 Portable Handset Color - Red (6 mount in VF9510 cabinet)
VF9510 Telephone Cabinet Holds 6 VF511 Portable Handset Cabinet: Charcoal Gray std. –10 Red (Surface / Semi-Flush Mount /Key Lock 27 x 14-1/2 x 4” h-w-d)
VF9514 Fire Phone Station Coil cord / Thumb Turn Latch Cabinet: Red (Surface / Semi-Flush Mount12-3/4 x 7-1/4 x 3-3/4” h-w-d)
VF9517 Warden Station Armored cable / Thumb Turn Latch Cabinet: Red (Surface / Semi-Flush Mount12-3/4 x 7-1/4 x 3-3/4” h-w-d)
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Application
The VES VoiceAlert High Rise Evacuation System operates in conjunction with the Fire Alarm Control Panel (FACP) in a building to provide automatic response to life safety emergencies.
The VoiceAlert system includes all necessary features to provide an effective voice evacuation system. The VoiceAlert can be custom configured to satisfy the needs of any high rise application. Fire department authorities can easily take command of evacuation or relocation procedures and emergencies.
Building management and fire brigades can monitor and control emergency response even before the professionals arrive. The VoiceAlert system includes capacity for 6 Channels of simultaneous audio. This provides for evacuation, stay-in-place, or other public address announcements and automatic messages.
Fire Fighter Phones or Warden Stations may be included as required. Area-of-Rescue stations can reassure handicapped occupants that help is on the way. Smoke control, stair pressurization, and HVAC shutdown can be completely automatic, unless controlled manually by management or fire authorities.
Operation
Basic System Master Panel (VoiceAlert) Master Mic Control 16 switch control points Dual Channel DMR High speed communication loop Distributed Panel 4 Output Zones (may be configured for 8) Dual Channel Audio Interface Dual Channel Amplification
OptionalIntegrated Fire Phone Area-of-Rescue Fan and Damper system control Number of distributed panels to be determined by building specifications Maximum System Configuration Up to 256 Distributed Panels Up to 2028 monitor and control points
Standard Features
True Multiplex 6 Channel Distributed Audio Integrated Fire Phone, Area of Rescue and Fan & Damper Control capability Modular System - components added as needed Integrated 2 Channel Digital Message Repeater Live Microphone Page to any zone Fast RS-485 Communication Protocol Easy Installation and Operation Natural Sound Voice Recordings Built in Alarm and Alert Signals Up to 4 Minute Message Capacity Works with 12VDC or 24VDC Fire Alarm Panel Listed with for use with the FACP 3 Minute Message Restart on Microphone Key Fully Supervised
Master Panel
Distributed Panel
Fire Phone Station
Fire Phone Jack
Elite
Elite
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
System Diagram Basic System Configuration
Basic System Master Panel Master Mic 16 Switch Control Module Dual Channel DMR High Speed Communications Loop
Distributed Panels 4 Output Zones Dual Channel Audio Interface Dual Channel Amplification Optional Intergrated Fire PhoneArea-of– Refuge Fan and Damper System Control
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Features
Clean Dead-front Construction Digitally Recorded Automatic Evacuation Message (Up to 4 Minutes of Message Capacity) 50 Watt High Efficiency Digital Amplifier 25 or 70 VRMS Field Selectable 120 VAC Power Supply and Battery Charger Live Microphone Override of Message and Tone Analog Addressable Compatible High Reliability, No Maintenance, Fully Supervised Easy Installation and Operation Natural Sound Recordings Built in Alarm and Alert Signals Up to 4 Minute Message Capacity Works with 12VDC or 24VDC Fire Alarm Panels Works with Analog/Addressable and Microprocessor based Fire Alarm Panels. 3 Minute Message Restart on Microphone Key 24 Hour Backup with two 12V 7AHr Batteries
Description
The VF9220 Voice Evacuation System provides 50 Watts of speaker power.
The VF9220 includes all necessary features to provide an effective voice evacuation system. With the addition of zone splitters, remote microphone panels and expander modules, the VF9220 can be custom configured to satisfy the needs of most applications.
The VoiceAlert 50 has its own power supply and battery charger. Panel must be wired with 120VAC and standby bat-teries connected.
A digital message repeater (DMR) is built into the VF9220. The selection of alarm tone and automatic message repeats, as well as the 6 Hour delay of the AC power failure reporting feature are all field configurable.
The paging microphone is an integral component. Trouble” condition which will be reported locally, as well as through the FACP.
VF9220 VoiceAlert Voice Evacuation System
Model Number Description
VF9220 50W Voice Evacuation System with Power Supply / Battery Charger Paging Microphone
VF9221 50W Voice Evacuation System with 4 Speaker Zones
VF9222 50W Voice Evacuation System with 8 Speaker Zones
VF9223 50W Voice Evacuation System with 12 Speaker Zones
VF9224 50W Voice Evacuation System with 16 Speaker Zones
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Characteristic
Engineers Specification The Voice Evacuation system shall be VES VF9220 or approved equal.
The voice evacuation system shall provide 50 watts signal power and 50 watts voice power, and shall be UL listed.
The voice evacuation system shall be micro-processor based, and shall contain an integral microphone, 50 watt audio amplifier, tone generator, digital message repeater, 120VAC power supply and battery charger.
The voice evacuation message/signal shall be broadcast until the Fire Alarm Control Panel (FACP) is reset, or until fire emergency personnel interrupt the broadcast with a man-ual page. On reset system shall automatically return to standby (normal operating) condition.
Engineers Specifications (Continued)
A secondary message shall be provided which can be triggered by the closure of a contact from either the FACP or from any normally open contact device.
Remote paging microphone (s) will be supported by the system through a supervised circuit. Remote microphone may be mounted up to 5,000 feet away from the voice evacuation panel.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Features
Clean Dead-front Construction Digitally Recorded Automatic Evacuation Message (Up to 4 Minutes of Message Capacity) 100 Watt High Efficiency Digital Amplifier 25 or 70 VRMS Field Selectable 120 VAC Power Supply and Battery Charger Live Microphone Override of Message and Tone Analog Addressable Compatible High Reliability, No Maintenance, Fully Supervised Easy Installation and Operation Natural Sound Recordings Built in Alarm and Alert Signals Up to 4 Minute Message Capacity Works with 12VDC or 24VDC Fire Alarm Panels Works with Analog/Addressable and Microprocessor based Fire Alarm Panels. 3 Minute Message Restart on Microphone Key 24 Hour Backup with two 12V 7AHr Batteries Made in the USA.
Description
The VF9240 Voice Evacuation System provides 100 Watts of speaker power.
The VF9240 includes all necessary features to provide an effective voice evacuation system. With the addition of zone splitters, remote microphone panels and expander modules, VF9240 can be custom configured to satisfy the needs of most applications.
The VF9240 has its own power supply and battery charger. Panel must be wired with 120VAC and standby batteries connected.
A digital message repeater (DMR) is built into the VF9240. The selection of alarm tone and automatic message repeats, as well as the 6 Hour delay of the AC power failure reporting feature are all field configurable.
The paging microphone is an integral component. Trouble” condition which will be reported locally, as well as through the FACP.
VF9240 shown with key-lock-door removed
VF9240 VoiceAlert Voice Evacuation System
Model Number Description VF9240 100W Voice Evacuation System with
Power Supply / Battery Charger Paging Microphone Digital Message Repeater
VF9241 100W Voice Evacuation System with 4 Speaker Zones
VF9242 100W Voice Evacuation System with 8 Speaker Zones
VF9243 100W Voice Evacuation System with 12 Speaker Zones in a Large Cabinet 14.5 x 27 x 4” w*h*d*
VF9244 100W Voice Evacuation System with 16 Speaker Zones in a Large Cabinet 14.5 x 27 x 4” w*h*d*
Color— VFXXXX-10 for Red and VFXXXX– 20 for Charcoal
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Characteristic
Engineers Specification
The Voice Evacuation system shall be VES VF9240 or approved equal.
The voice evacuation system shall provide 100 watts signal power and 100 watts voice power, and shall be UL listed. All speaker circuits shall be field selectable for 25 or 70 Vrms and shall be power limited.
The voice evacuation system shall be micro-processor based, and shall contain an integral microphone, 100 watt audio amplifier, tone generator, digital message repeater, 120VAC power supply and battery charger.
Engineers Specifications (Continued)
The voice evacuation message/signal shall be broadcast until the Fire Alarm Control Panel (FACP) is reset, or until fire emergency personnel interrupt the broadcast with a manual page. On reset system shall automatically return to standby (normal operating) condition.
A secondary message shall be provided which can be triggered by the closure of a contact from either the FACP or from any normally open contact device.
Remote paging microphone (s) will be supported by the system through a supervised circuit. Remote microphone (s) may be mounted up to 5,000 feet away from the voice evacuation panel.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Features
Dead-front Construction Digitally Recorded Automatic Evacuation Message (Up to 4 Minutes of Message Capacity) 50/100 Watt Bullet-Proof Amplifier 25 or 70 VRMS Field Selectable 120 VAC Power Supply and Battery Charger Live Microphone Override of Message and Tone Analog Addressable Compatible High Reliability, No Maintenance, Fully Supervised Easy Installation and Operation Natural Sound Recordings Built in Alarm and Alert Signals Up to 4 Minute Message Capacity Works with 12VDC or 24VDC Fire Alarm Panel Works with Analog/Addressable and Microprocessor based Fire Alarm Panels.
DescriptionThe VF9260 / VF9280panels provide 200W and 150W of speaker power respectively. Speaker zones can be configured for general alarm or alarm by zone operation as required.
Digital message repeater, microphone, 120 VAC power supply and battery charger are all built in.
VoiceAlert voice evacuation panels can be configured for Churches, Restaurants, Movie Theaters, Auditoriums and High Rise buildings.
The VF9260 / VF9280 panels are an attractive surface or semi-flush mounted back boxes, with a hinged and key locked door.
The VoiceAlert device above is shown with the key-lock-door removed.
VF9260 and VF9280 VoiceAlert Voice Evacuation System
Model Number Description
VF9260 150W Voice Evacuation System with 2 Speaker Circuits 1 - 100W 1 – 50W Power Supply / Battery Charger Paging Microphone Digital Message Repeater
VF9261 150W Voice Evacuation System with 8 Speaker Zones 100W / 4Z 50W / 4Z
VF9262 150W Voice Evacuation System with 12 Speaker Zones 100W / 8Z 50W / 4Z
VF9263 150W Voice Evacuation System with 16 Speaker Zones 100W/8Z 50W/8Z
Model Number Description
VF9280 200W Voice Evacuation System with 2 Speaker Circuits 100W each Power Supply / Battery Charger Paging Microphone Digital Message Repeater
VF9281 200W Voice Evacuation System with 8 Speaker Zones 100W / 4Z 100W / 4Z
VF9282 200W Voice Evacuation System with 12 Speaker Zones 100W / 8Z 100W / 4Z
VF9283 200W Voice Evacuation System with 16 Speaker Zones 100W / 8Z 100W / 8Z
Color— VFXXXX-10 for Red, VFXXXX-20 for charcoal
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Engineers Specification
The Voice Evacuation system shall be VES or approved equal.
The voice evacuation system shall provide 100 watts sig-nal power and 100 watts voice power, and shall be UL listed. All speaker circuits shall be field selectable for 25 or 70 Vrms and shall be power limited.
The voice evacuation system shall provide 200 / 150 Watts of signal and voice power, and shall be UL listed. All speaker circuits shall be field selectable for 25 or 70 Vrms operation and shall be power limited.
The voice evacuation system shall be micro-processor based, and shall contain an integral microphone, audio amplifier, tone generator and digital message repeater.
A 120 VAC Power Supply and battery charger for standby batteries shall be included.
The voice evacuation message/signal shall be broadcast until the FACP is reset, or until fire emergency personnel interrupt the broadcast with a manual page. Remote paging microphone will be supported through a supervised circuit.
Primary Power 120VAC @ 2A
24 VDC Battery Power Standby 0.18A Alarm 2.5A
Output 100 Watts @ 25/70 VRMS Tone and Voice
50W VoiceAlert Module
Primary Power 120VAC @ 2A
24 VDC Battery Power Standby 0.13A Alarm 1.0A
Output 50 Watts @ 25/70 VRMS Tone and Voice
Backbox Dim 14.5 x 27 x 4“ w h d
Color Charcoal Grey std Redoptional
100W VoiceAlert Module
Technical Characteristic
The specifications listed above are provided per module.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Speaker and Speaker Strobes -
Wall Mounted Speakers and Speaker Strobes
Standard FeaturesApprovals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP). See approvals by model in Specifications and Ordering Information
ADA/NFPA/ANSI compliant
Complies with OSHA 29 Part 1910.165
Wall mount speaker strobe models with field selectable candela settings of 15/30/75/110cd or 135/185cd (Multi-Candela models), or 1575cd (Single Candela model)
Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 2 watts
High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ
24 VDC strobes produce 1 flash per second with wide UL“Regulated Voltage” of 16 to 33 volts using filtered DC or unfiltered VRMS input voltage
PS-12/24-8CP and PS-12/24-8MP Power Supply with built-in sync protocol
Mount to 4” square x 2-1/8” deep backbox with no extension ring required
Snap on grille cover with no visible mounting screws
Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires
Product OverviewThe VES Series of wall mounted Speakers and Speaker Strobes feature high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. They are designed to provide a sleek, aesthetic appearance for emergency voice/alarm communications systems. All speakers and speaker strobe models mount to standard 4” x 2-1/8” electrical boxes (with no extension ring required) and incorporate a speaker mounting plate for faster installation. The grille cover snaps on so no mounting screws are visible. Attractive surface boxes are also available for surface installations.
The wall mounted Speaker Strobe models use VES low current draw Series RSS strobes for wall mounted applications. Strobe options include patented MCW multi-candela strobes with field selectable candela settings of 15/30/75/110 cd or high intensity MCWH strobes with field selectable 135/185 candela. Models with 1575 candela (75 cd on axis) are also offered.
These Speakers and Speaker Strobes provide high audio output with clear audibility and are designed to meet the critical needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the hearing impaired.
The strobe portion of all wall mounted Speaker Strobes may be synchronized when used in conjunction with the VES Sync Modules or the VES PS-24-8MC Power Supply with Patented Sync Protocol. VES Series synchronized strobes offer an easy way to comply with ADA and NFPA regulations concerning photosensitive epilepsy.
The wall mounted Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired) and Standard 1480 (Speaker Appliances). All inputs employ IN/OUT wiring terminals for fast installation using #12 to #18 AWG wiring and are compatible with FACP line supervision.
Color options for the wall mounted Speakers and Speaker Strobes are red or off-white.
General NotesStrobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%).
Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology “Listed Voltage Range”.
Table1: Average RMS Current
Strobe Current - Wall MountWall mountedSpeakerStrobes
241575W 24MCW 24MCWH 15cd 15cd 30cd 75cd 110cd 135cd 185cd0.060 0.041 0.063 0.109 0.140 0.195 0.27024 vdc
UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420*RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For unfiltered FWR ratings, see installation instructions.
Table2: VF4405 UL Reverberant dBA” 10 Feet**
Watts
Wall mount Speaker
Wall mount Speaker Strobe
1/87777
1/479.579.5
1/282.582.5
18585
28888
**dBA ratings are based on UL testing under UL standard 1480.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications and Ordering Information
Model Wall Ceiling Strobe Grill Flush Mount Mount Mount Candela Color Backbox
VF4405-10
VF4405-30
VF4823-10
VF4823-30
VF4820-10
VF4820-30
VF4824-10
VF4824-30
XXXXXXXX
XX------
-
-
15 (75 on axis)
15 (75 on axis)
15/30/75/110
15/30/75/110
135/185
135/185
Red
White
Red
White
Red
White
Red
White
4’ x 4” x 2-1/8”
4’ x 4” x 2-1/8”
4’ x 4” x 2-1/8”
4’ x 4” x 2-1/8”
4’ x 4” x 2-1/8”
4’ x 4” x 2-1/8”
4’ x 4” x 2-1/8”
4’ x 4” x 2-1/8”
SurfaceMount
Backbox
VF4416-10
VF4416-30
VF4417-10
VF4417-30
VF4417-10
VF4417-30
VF4417-10
VF4417-30
MountingOptions
E,O,P,Q,R,U,Y,AA
E,O,P,Q,R,U,Y,AA
E,Q,U,BB
E,Q,U,BB
E,Q,U,BB
E,Q,U,BB
E,Q,U,BB
E,Q,U,BB
Agency Approvals
UL MEA CSFM FM BFP
XXXXXXXX
********
XXXXXXXX
XXXXXXXX
********
* Pending Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with VES standard terms and conditions.
+ -+ -
+ +
++
- -
- -
STROBE SPEAKER
TO NEXT APPLIANCEOR EOLR
TO NEXT STROBEOR EOLR
FROM PRECEDING STROBE,SYN MODULE, POWER SUPPLY OR FACP
FROM PRECEDING APPLIANCE OR VOICEDEVACUATIONPANEL
WALL MOUNTED SPEAKER AND STROBE OPERATEINDEPENDENTLY (NON-SYNC OR SYNC)
WALL MOUNTED SPEAKER STROBE APPLIANCESSYNCHRONIZED WITH DSM MODULE SINGLE CLASS “A”
F
A
C
P
Sync+
-
Sync+
-
Sync+
-
Strobe NAC Cir.
Strobe NAC Cir.
Strobe NAC Cir.
WALL MOUNTED SPEAKER STROBES SYNCHRONIZED WITH MULTIPLE DSM MODULES
Note: Figure shows interconnection to strobe through syncmodule. Speakerportion requires 2separate conductors to communications system.
DSM Interconnecting wiring system shown. Maximum Ctwenty (20)
+
-
-
+
+
+
+
+
IN 1
MINUS 1
IN 2
OUT 1
OUT 2
AUDIBLE
MINUS 2
SYNC
FACP
STROBENAC
CIRCUITRETURN
STROBENAC
CIRCUITOUT
WALL MOUNTED SPEAKER STROBE APPLIANCES &RSS STROBES SYNCHRONIZED WITH PS-12/24-8CP and PS-12/24-8MP
RSS
RSS
RSS
FACP
OUTPUTS1-4
4-CLASS“B”OR
2-CLASS“A”
Series PS-12/24 - 8MPor PS-12/24 - 8CP
EOLR
Series PS-12/24 - 8MP or PS-12/24-8CP
Architects and Engineers Specifications The speaker appliances shall be VES Series Wall Mounted Speakers and the speaker strobe appliances shall be VES Series Wall Mounted Series Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing-Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B.
All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 89 dBA at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall be of low current design. Where Multi-Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mounting. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required.
When synchronization is required, the strobe portion of the appliance shall be compatible with the VES sync modules or VES PS-24-8MC Power Supply with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate.
The speaker and speaker strobe appliances shall be designed for indoor flush mounting to 4” x 2-1/8” electrical boxes without need for an extension ring or surface mounting to VES VF4416 or VF4417 surface boxes. The speaker and speaker strobe shall incorporate a speaker mounting plate with a snap-on grille cover. The finish of the VES Series Wall Mounted speakers and speakers strobes shall be white or red.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Speaker and Speaker Strobes -
Ceiling Mounted Speaker and Speaker Strobes
Standard FeaturesApprovals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP) See approvals by model in Specifications and Ordering Information
ADA/NFPA/ANSI compliant
Complies with OSHA 29 Part 1910.165
Ceiling mount strobe models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (Multi-candela models)
Strobes produce 1 flash per second over the regulated voltage range
24 VDC with wide UL “Regulated Voltage” using filtered DC or unfiltered VRMS input voltage
Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 2 watts
High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ
Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires
Optional Extender is for mounting to 4” backboxes with no extension ring.
Product OverviewThe NEW VES Series of Ceiling Speakers and Speaker Strobes are designed for high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. These ceiling Speakers and Speaker Strobes are Multi-Candela ceiling appliances are part of the new family of ceiling mount strobe appliances that will also be available on strobes, horns and horn/strobes. Optional Extender (E60 Ext) is for mounting to 4” backboxes with no extension ring.
The ceiling mounted Speaker Strobe models incorporate the Low Current draw Series RSS Strobes. These ceiling mount round models are available in Wheelock patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd.
The ceiling mounted Speakers and Speaker Strobes provide high audio output with clear audibility and are designed to meet the critical needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the hearing impaired.
The low profile design incorporates a speaker mounting plate for faster and easier installation. Each model has a built-in level adjustment feature and snap-on cover with no visible mounting screws.
The strobe portion of all ceiling mounted series Speaker Strobes may be synchronized when used in conjunction with the VES Sync Modules or the VES PS-24-8MC Power Supply with Patented Sync Protocol. VES synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy.
The ceiling mounted series of Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired) and Standard 1480 (Speaker Appliances), and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan® lens to provide maximum reliability for effective visual signaling. All inputs are supervised and employ IN/OUT wiring terminals for fast installation using #12 to #18 AWG wiring.
Color options for the ceiling mounted series Speakers and Speaker Strobes are red and white.
General NotesStrobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%).
Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology “Listed Voltage Range”.
Table1: Average RMS Current
Strobe Current - Ceiling MountCeiling MountSpeakerStrobes
24MCC 24MCCH15cd 30cd 75cd 110cd 135cd 185cd0.045 0.070 0.119 0.159 0.195 0.27024 vdc
UL max* 0.065 0.105 0.189 0.249 0.300 0.420
*RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Table2: Ceiling Mount UL Reverberant dBA” 10 Feet**
Watts
Ceiling mount Speaker
Ceiling mount Speaker
Strobe
1/87777
1/479.579.5
1/282.582.5
18585
28888
**dBA ratings are based on UL testing under UL standard 1480.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications and Ordering Information
Model Wall Ceiling Non- Mount Mount Sync
VF4409-10
VF4409-30
VF4829-10
VF4829-30
VF4830-10
VF4830-30
VF4418-10
VF4418-30
----
XXXXXX
-
-
15/30/75/95
15/30/75/95
115/177
115/117
ModelColorWhite
-
X
-
X
-
X
X
MountingOptions
Q,U
Q,U
Q,U,V
Q,U,V
Q,U,V
Q,U,V
Agency Approvals
UL MEA CSFM FM BFP
XXXXXXXX
XXXXXXXX
XXXXXX**
********
XXXXXX
* Pending ** VF4418 is an extender ring that mounts behind the speaker to permit mounting to a 4” square x 2 1/8” deep electrical box without need for an extension ring on the box.
Architects and Engineers Specifications The speaker appliances shall be VES Series Ceiling Mounted Speakers and the Speaker Strobe appliances shall be VES Series Ceiling Mounted Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing-Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B.
All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 87 dB at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall also incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The strobe shall be of low current design. Where Multi-Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant.
When synchronization is required, the strobe portion of the appliance shall be compatible with VES sync modules or the VES PS-24-8MC Power Supply with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate.
The speaker and speaker strobe appliances shall be designed for indoor flush mounting. The speaker and speaker strobe shall incorporate a speaker mounting plate with a snap-on grille cover with no visible screws for a level, aesthetic finish and shall mount to standard electrical hardware.
The finish of the VES Series Ceiling Mounted Speakers and Speaker Strobes shall be white or red. All speaker and speaker strobe appliances shall be backward compatible.
ModelColorRed
X
-
X
-
X
-
X
StrobeCandela
Strobe Sync w/SM, DSM or PS-
12/24 -8CP
-
-
X
X
X
X
--XXXX
Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with VES standard terms and conditions.
+ -+ -
+ +
++
- -
- -
STROBE SPEAKER
TO NEXT APPLIANCEOR EOLR
TO NEXT STROBEOR EOLR
FROM PRECEDING STROBE,SYN MODULE, POWER SUPPLY OR FACP
FROM PRECEDING APPLIANCE OR VOICEDEVACUATIONPANEL
CEILING MOUNTED SPEAKER AND STROBE OPERATE INDEPENDENTLY (NON-SYNC OR SYNC)
CEILING MOUNTED SPEAKER STROBE APPLIANCESSYNCHRONIZED WITH DSM MODULE SINGLE CLASS “A”
F
A
C
P
Sync+
-
Sync+
-
Sync+
-
Strobe NAC Cir.
Strobe NAC Cir.
Strobe NAC Cir.
CEILING MOUNTED SPEAKER STROBES SYNCHRONIZED WITH MULTIPLE DSM MODULES
Note: Figure shows interconnection to strobe through syncmodule. Speakerportion requires 2separate conductors to FACP.
DSM Interconnecting wiring system shown. Maximum Ctwenty (20)
+
-
-
+
+
+
+
+
IN 1
MINUS 1
IN 2
OUT 1
OUT 2
AUDIBLE
MINUS 2
SYNC
FACP
STROBENAC
CIRCUITRETURN
STROBENAC
CIRCUITOUT
CEILING MOUNTED SPEAKER STROBE APPLIANCES& RSS STROBES SYNCHRONIZED WITH PS-12/24-8CP and PS-12/24-8MP
RSS
RSS
RSS
FACP
OUTPUTS1-4
4-CLASS“B”OR
2-CLASS“A”
Series PS-12/24 - 8MPor PS-12/24 - 8CP
EOLR
Series PS-12/24 - 8MP or PS-12/24-8CP
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Speaker and Speaker Strobes -
Vandal Proof Speaker and Speaker Strobes
Standard Features
Approvals include: CAN/ULC-S541-99 for speaker appliances and CAN/ULC-S526-02 for visual appliances
High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ
Field selectable taps for 25 VRMS operation from 1/8 watt to 2 watts
Field selectable taps for 70 VRMS operation from 1/8 watt to 8 watts.
The Vandal Proof Series of Speaker Strobes models available with 15 candela strobes featuring low current draw and low temperature compensation to reduce power consumption and wiring costs
All audio and strobe inputs are compatible with standard reverse polarity type supervisions of circuit wiring by an alarm panel
Four attractive package styles for flush, semi-flush or surface mounting to low cost electrical backboxes
Choice of vandal resistant die cast grilles or general purpose sheet metal grilles.
Sealed back speaker construction for extra protection and improved audibility
Sealed back speaker construction for extra protections and improved audibility
Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires
Product Overview
VES Vandal Proof Series provides a full range of rugged, high performance speakers and speaker strobe combinations specifically designed to meet the critical needs of the life safety industry for voice and tone signaling. Available in compact, aesthetically pleasing package styles, each vandal proof model covers both 25 or 70 volt audio systems. Their high-efficiency design provides improved evacuation signal, such as the “slow whoop” and “code-3”. The Vandal Proof Series provides unequaled performance and installation flexibility at the job site, while minimizing confusion about mounting and performance capabilities.
The Vandal Proof Series of Speaker Strobes use an Xenon flashtube with solid state circuitry enclose din a rugged Lexan® lens to provide maximum reliability for effective visible signaling.
All Vandal Proof models have IN and OUT wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at each terminal. Strobe inputs are polarized and audio inputs include a 10 uF blocking capacitor for compatibility with standard reverse polarity DC supervision of NAC circuits.
General Notes
Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range.
VF4412 Speakers are Listed for indoor/outdoor use with a temperature range of -35°C to 66°C (-31°F to 150°F) and maximum humidity of 95% RH. All other ET Speakers and Speaker Strobes are Listed for indoor use with a temperature range of 0°C to 49°C (32°F to 120°F) and maximum humidity of 85%RH.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications and Ordering Information
Model Number
VF4412
VF4414
VF4840
-
-
24
-
-
15
Speaker dB @ 10 Feet (Rated Watts)
1/8 1/4 1/2 1 2 4* 8*
78
78
78
81
81
81
84
84
84
878787
909090
Architects and Engineers Specifications The speaker appliance shall be a VES Series Vandal Proof speaker and speaker strobe appliance or equivalent. The speaker and strobes shall be ULC Listed under CAN/ULC-S541-99 and CAN/ULC-S526-02 for Fire Protective Service.All speakers shall be either 25 or 70 VRMS inputs with field selectable power taps. Strobes shall use filtered power or unfiltered power supply (full-wave-rectified). All models shall have provisions for standard reverse polarity type supervision and IN/OUT field wiring using terminals that accept #12 to #18 AWG wiring.
Combination speaker strobe appliances signals shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens or equivalent with solid state circuitry. Strobe shall meet ULC and produce a flash rate of one (1) flash per second minimum over the Listed input voltage range. The strobe intensity shall be rated per ULC for 15 candela.
The combination speaker strobe appliances shall be installed indoors and surface or flush mounted. They shall mount to standard electrical hardware requiring no additional trimplate or adapter. The appliance shall be finished in a textured red or white color.
SPEAKER AND STROBE OPERATE INDEPENDENTLY
TO NEXTAPPLIANCEOR EOLR
FROMPRECEDINGAPPLIANCEOR VOICEEVACUATIONPANEL
TO NEXTSTROBE OREOLR
FROMPRECEDINGSTROBE,SYNC MODULE,POWER SUPPLYOR FACP
SPEAKERSTROBE
+ - +
+
-
-
-+ +
+-
-
CEILING FLUSH MOUNTING
Circular Backbox for 4”Speaker available inCanada only By Others (BO)
Vandal ProofSeries
939393
969696
Strobe Voltage (VDC)
NOM
StrobeCandela
Voltage
24 VDC24 VFWR
Rated Average Current
LS
Rated Peak Current
LS
Rated Inrush Current
LS.080.081
.190
.216.250.380
Note: All VFWR voltages in table are measured with DC Volt meter. Multiply VFWR voltage by 1.11 to convert to VRMS.
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Weatherproof appliances
Standard FeaturesApprovals include: UL Standards 1971, 1638, 464 and 1480 California State Fire Marshal (CSFM) and New York City (MEA), Factory Mutual (FM) and Chicago (BFP) .
Compliance with the following requirements: NFPA, UFC, ANSI 117.1, OSHA Part 29, 1910.165, ADA
Weatherproof with extended temperature range of –40°F to 150°F (-40°C to 66°C)*
Dual Listed strobe models (UL 1638 and UL 1971)
Industry’s highest strobe candela options
Synchronize using the VES Sync Modules or panels with built-in VES Patented Sync Protocol
Models with field selectable tone, dBA and candela settings
Wall or ceiling mounting options
Surface of semi-flush mounting
IN/OUT wiring termination accepting two #12-18 AWG wires at each terminal
All strobe models are UL dual listed - meeting both UL1638 and UL1971 requirements. As dual listed appliances, these weatherproof strobes, horn strobes and speaker strobes are listed for outdoor applications under UL 1638 as well as under UL 1971, the Standard for Safety Signaling Devices for Hearing Impaired. With an extended temperature range of –31°F to 150°F (-40°C to 66°C), Wheelock weatherproof appliances meet or exceed UL outdoor test requirements for rain, humidity and corrosion resistance while providing multiple strobe intensity options, including the highest strobe ratings available for area coverage per NFPA 72 strobe spacing tables (up to 185 candela for wall mounting and 177 candela for ceiling mounting).
To enable weatherproof mounting, VES provides the industry’s widest choice of mounting options for surface or unique semi-flush installation. Models are available for surface mounting to VES weatherproof backboxes on walls or ceilings. The optional VF4987 allows the weatherproof backboxes (VF4966, VF4978 or VF4979) to be mounted to a recessed electrical box for concealed conduit installation. For semi-flush installation, the VF4988 kits allow a customer to mount the weatherproof appliances to a recessed electrical box without the need for an external weatherproof backbox. See the Backboxes, Plates and Gaskets Table on page three of this datasheet for a summarization of these mounting options and the required accessories.
All models may be synchronized using the VES Sync Modules, VES Power Supplies or other manufacturers panels incorporating the VES Patented Sync Protocol. The horn output of horn strobes can be independently controlled on 2-wire circuits using the VES patented sync protocol. VF4607 horn strobe models are 4-wire appliances; the strobes can be synchronized while the audible can be connected to a coded fire alarm system or can be set to produce any of eight selectable tones.
Product OverviewDesigned for life safety, performance and reliability, VES’s cost effective weatherpoof notification appliances includes the following Weatherproof Appliances:
Strobes
Horn Strobes
Multitone Horn Strobes
Speaker Strobes
Speakers
Speakers & Strobes
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Wiring Diagrams
Candela Ratings
Series UL 1971 UL 1638 UL 1638 VF4352, VF4832 and VF4604 @77 ˚F @-40 ˚F VF4607 UL Max Current (Strobe only)
VF4352
VF4604
VF4607
VF4832
VF4352
30** 180 115 0.138 0.168
** Wall Mount Rating only
Agency Approvals
Model- Strobe
VF4352
VF4604
VF4607
VF4832
UL MEA CSFM FM BFP
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
*
*
X
*
*
* Pending
0.155 0.150
High Med Low
Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with VES standard terms and conditions.
Ordering Information
Model Description
VF4352-10 Strobe wall Weatherproof, 75cd, Red
VF4604-10 Weatherproof Horn/ Strobe, Red (AS)
VF4607-10 Audible Multi Tone Strobe
Weatherproof, 75cd, Red
VF4832-10 Weatherproof Speaker Strobe, Wall
VF4352-10 Strobe Wall Weatherproof, 75cd, Red
VF4412-10 Speaker Vandal-Proof 8 Watt
Surface Red
VF4412-30 Speaker Vandal-Proof 8 Watt
Surface White
General NotesStrobes are designed to flash at 1 flash per second minimum over their UL Listed Regulated Voltage Range.
All candela ratings represent minimum effective Strobe intensity based on UL Standards 1971 and 1638 as indicated in candela ratings table.
FACP
NAC #1
NAC #2
SyncModule
orPS-12/24-8
PowerSupply
StrobeCircuit
AudibleCircuit
MTWP
FACP
STROBENAC
CIRCUITOUT
STROBENAC
CIRCUITRETURN
SYNC
+OUT 1
+ IN 1
MINUS 1
AUDIBLE+-
MINUS 2
+ IN 2
+ OUT 2
+-
DSM
RSSWP ASWP
ASWPRSS
RSS
RSS
FROMPRECEDING
APPLIANCE ORFACP
TO NEXTAPPLIANCE
OR EOLR
TO NEXTAPPLIANCE
OR EOLR
+_
+_
+ _
+
_
+
_RED
BLACK
STROBE AUDIBLE
+ +_ _
FROMPRECEDING
APPLIANCE ORFACP
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Ordering Information
Gasket Kit
VF4987-10
Flush Plates
VF4988-10 Red
VF4988-30 White
VF4982-10 Red
VF4982-30 White
Backboxes
VF4966-10 Red
VF4966-30 White
VF4979-10 Red
VF4979-30 White
VF4978-10 Red
VF4978-30 White
VF4977-10 Red
VF4977-30 White
Mounting Accessories
VF4982-30 VF4966-10 VF4979-10 VF4978-10 VF4977-10
Mounting Options
Backboxes, Plates
VF4352 Strobes
VF4832 Speaker Strobes
VF4604 Horn Strobes
VF4412 Speakers
VF4607 Multitone Horn Strobes
VF4979
VF4966
VF4978
VF4977
VF4966
Surface Mount FlushMountExposed Conduit Concealed Conduit
VF4979+ VF4987
VF4966+ VF4987
VF4978+ VF4987
-
VF4966+ VF4987
VF4982
VF4982
VF4988
VF4982
VF4982
Architects and Engineers Specifications General
Weatherproof notification appliances shall be UL listed for outdoor use. Weatherproof Strobe appliances shall be listed under UL Standard 1638 (Standard for Visual Signaling Appliances) for Indoor/Outdoor use and UL Standard 1971 (Standard for Safety Signaling Devices for Hearing Impaired). The appliances shall be available for optional wall mounting or ceiling mounting to weatherproof backboxes using either exposed conduit or concealed conduit, or semi-flush mounting to a recessed electrical box in walls or ceilings using VES mounting accessories.
Weatherproof Strobes
Weatherproof Strobe appliances shall produce a minimum flash rate of 60 flashes per minute over the UL Regulated Voltage Range of 16 to 33 VDC and shall incorporate a Xenon flashtube. The weatherproof strobes shall be available with UL 1971 candela ratings up to 185 cd for wall mounting and 177 cd for ceiling mounting. UL 1638 candela ratings up to 180 cd at 77°F shall be available. The strobes shall operate over an extended temperature range of –40°F to 150°F (-40°C to 66°C) and be listed for maximum humidity of 95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
Weatherproof Audibles and Audible/Strobe Combinations Weatherproof horns and multitone audibles shall be listed for Indoor/Outdoor use under UL Standard 464. The horns shall be able to produce a continuous output or a temporal code-3 output that can be synchronized. The horns shall have at least 3 sound level settings. Horn/Strobe combinations shall be able to be synchronized on a single NAC.
Multitone audibles shall be able to produce 8 distinct tones selectable by dip switch and shall have at least 2 sound level settings. Multitone Audible/Strobe combinations shall have independent inputs for the audible and strobe. The strobes shall be able to be synchronized. The audibles shall be able to be coded when operated on a separate NAC.
Weatherproof Speakers and Speaker/Strobes
Weatherproof speakers and speaker/strobes shall be listed for Indoor/Outdoor use under UL Standard 1480. All speakers shall provide field selectable taps for 1/8W to 8W operation for either 25 VRMS or 70 VRMS audio systems and shall incorporate a sealed back construction for extra protection and improved audibility. Speakers without strobes shall be VES Series VF4412. They shall be listed to produce up to 94 dBA and shall incorporate a vandal resistant grille design.
Synchronization Modules
When synchronization of strobes or temporal code-3 audibles is required, the appliances shall be compatible with the VES Series Sync Modules, VES Power Supplies or other manufacturers panels with built-in VES Patented Sync Protocol. The strobes and audibles shall not drift out of synchronization at any time during operation.
Series VF4604 audibles and strobes shall be able to be synchronized on a 2-wire circuit with the ability to silence the audible if required. The strobes on Series multitone audible/strobe appliances shall be able to be synchronized and shall be able to be operated on a separate circuit from the audibles while the audible circuit is connected to a coded or continuous NAC.
Weatherproof Mounting Accessories
Weatherproof mounting options shall include surface mounting or semi-flush mounting to walls or ceilings. Surface mounted appliances shall mount to VES VF4966, VF4977, VF4978 or VF4979 weatherproof backboxes using either exposed conduit or concealed conduit. For concealed conduit the weatherproof backbox shall be mounted to a recessed electrical box with VES’s VF4987 to provide a weatherproof seal for the electrical box. Semi-flush mounted appliances shall mount to a recessed electrical box using VES VF4982 or VF4988 flush plates to provide a weatherproof seal between the electrical box and the appliance.
VF4988-30
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
VF5350Electromagnetic Fire Door Holders
Overview
The DH Series Electromagnetic Fire Door Holders are constructed of the finest materials and workmanship available. Each door holder is made of durable die-cast metal and offered in a powdercoated finish.
Installation is easy with DH Series installation technique - an adhesive template assures alignment without secondary adjustments. No brackets are required for recessed, flush or surface mounting (the surface mounting box has three conduit ready entries). Plus, the new catch plate features two pivot points and two way adjustability to further ensure perfect alignment. Optional extension rods are also available for providing the proper gap distance between the door and wall.
The basic units offer superior reliability with built-in transient protection and low residual magnetism so they release easily even on new ADA low pressure door closers.
Standard Features
Extremely low current draw. Only 20mA at 24V saves on power supplies and backup batteries
New recessed mount for lowest profile look
Dual voltage inputs in each units reduces stocking requirements
Self-adjusting swivel catch-plate reduces installation time and adjusts to door alignment changes
Optional extension rods make installation faster
Low residual magnetism easily releases even on new ADA low pressure door closers
Built-in transient protection
Floor mount units available
S2985 R19958 3550-1039:100
MEAapproved APPROVED
200-97-E
VES LLC, 620 Allendale Road,King of Prussia, PA. 19406
E-mail: [email protected]: www.ves-network.com
Tel (US): 800.270.3066 (Toll free) Tel (non US): (001) 610.992.3378Fax: 610.992.3380
Technical Specifications
Ordering Information
Model Description
VF5350 24V AC/DC, 120 VAC Surface Mount, Electromagnetic Door Holder
VF5351 24V AC/DC, 120 VAC Recess Mount, Electromagnetic Door Holder
VF5352 24V AC/DC, 120 VAC Semi-Flush Mount, Electromagnetic Door Holder
VF5353 24V AC/DC, 120 VAC Floor Mount Electromagnetic Door Holder, Single Coil
VF5354 24V AC/DC, 120 VAC Floor Mount Electromagnetic Door Holder, Double Coil
VF5355 1” Extension Rod
VF5356 2” Extension Rod
VF5357 3” Extension Rod
VF5358 4” Adjustable Extension Rod
VF5359 Swivel Base
Model Voltage DC/mA AC/mA Terminals Holding Force
2412024V
120V
20
-
19
20
C&L
C&L
40lbs. (18.1 kg)
35lbs. (15.8kg)
Note: Holding forces listed in the above table correspond with shaded values. Non-shaded values are slightly less.
Extension Rod ApplicationsDual Voltage Terminal Diagram