Concrete Steel Sleeve Anchors Fire Sleeve Plastic Pipe Floor Slab Vertical Fire Sleeves Fixing Instructions May 2018 u Domus Vertical Fire Sleeves are life saving products designed to prevent the spread of fire where plastic pipes penetrate fire compartment walls or floors. It is therefore essential that they are fitted in a responsible and workmanlike manner. u The Fire Sleeves should be used where a plastic pipe penetrates a fire rated wall or floor. For vertical pipework, one unit should be installed to the underside of the floor. The soffit of the floor or the face of the wall must be smooth and where there are irregularities in the surface, the space between the flange of the unit and floor or the wall should be made good using Domus Acoustic Acrylic Sealant. u The Fire Sleeve should be fed around the plastic pipe, securing the ends together by passing the tongues on one end through the slots on the other end. The tongues should then be bent back and the unit secured to the structure using the integral fixing lugs. Caution! Product has sharp edges! Wear gloves when handling. u The Fire Sleeve must be secured to concrete and masonry construction using steel sleeve anchors. u The Fire Sleeves can also be installed in conjunction with the Domus Ventilation System. Please refer to Domus Ventilation Technical department for details. Product code Duct size Space needed around duct to fit the fire sleeve Recommended aperture Length Fire rating (minutes) DFSV100 Ø100mm 40mm Ø112mm 50mm 240 DFSV125 Ø125mm 45mm Ø132mm 50mm 240 DFSV150 Ø150mm 50mm Ø162mm 50mm 60

Transcript of Vertical May 2018 Fire Sleeves - Domus Ventilation · 2018. 5. 18. · u The Fire Sleeves should be...

  • Concrete Steel Sleeve Anchors

    Fire Sleeve

    Plastic Pipe

    Floor Slab

    Vertical Fire SleevesFixing Instructions

    May 2018

    u Domus Vertical Fire Sleeves are life saving products designed to prevent the spread of fi re where plastic pipes penetrate fi re compartment walls or fl oors. It is therefore essential that they are fi tted in a responsible and workmanlike manner.

    u The Fire Sleeves should be used where a plastic pipe penetrates a fi re rated wall or fl oor. For vertical pipework, one unit should be installed to the underside of the fl oor. The soffi t of the fl oor or the face of the wall must be smooth and where there are irregularities in the surface, the space between the fl ange of the unit and fl oor or the wall should be made good using Domus Acoustic Acrylic Sealant.

    u The Fire Sleeve should be fed around the plastic pipe, securing the ends together by passing the tongues on one end through the slots on the other end. The tongues should then be bent back and the unit secured to the structure using the integral fi xing lugs.

    Caution! Product has sharp edges! Wear gloves when handling.

    u The Fire Sleeve must be secured to concrete and masonry construction using steel sleeve anchors.

    u The Fire Sleeves can also be installed in conjunction with the Domus Ventilation System. Please refer to Domus Ventilation Technical department for details.

    Product code Duct size Space needed around duct to fi t the fi re sleeve Recommended aperture Length Fire rating (minutes)

    DFSV100 Ø100mm 40mm Ø112mm 50mm 240

    DFSV125 Ø125mm 45mm Ø132mm 50mm 240

    DFSV150 Ø150mm 50mm Ø162mm 50mm 60

  • Threaded bars with nuts and washers on both faces

    Fire Sleeve masonry wallPlasterboard partition or

    Plasterboard Steel Cavity Wall Sleeve Anchors

    Fire Sleeve

    Plastic Pipe

    Plastic Pipe

    May 2018

    Domus VentilationBlock C, Van Court, Caerphilly, CF83 3ED, United KingdomEmail: [email protected] | Tel: 03443 715 523

    www.domusventilation.co.uk

    u For horizontal pipework one unit should be fi tted to each side of the wall.

    u Where fi tting to a plasterboard partition wall one Fire Sleeve should be installed on either side of the partition and fi xed using through-bolts with nuts and washers, or secured to each side of the partition using plasterboard steel cavity wall sleeve anchors.