Verizon Wireless SF LM PH2 SC120bsm.sfdpw.org/pics/14WR-0140\SF LM PH2 SC120 100CD...
Transcript of Verizon Wireless SF LM PH2 SC120bsm.sfdpw.org/pics/14WR-0140\SF LM PH2 SC120 100CD...
2785 Mitchell DrWalnut Creek, CA 94598
1. Head northeast on Mitchell Dr toward Oak Grove Rd 30 ft2. Turn right onto Oak Grove Rd 0.4 mi3. Take the 2nd right onto Ygnacio Valley Rd 3.5 mi4. Continue onto Hillside Ave 0.2 mi5. Take the ramp onto CA-24 W 1.2 mi6. Merge onto CA-24 W 12.3 mi7. Take the Interstate 580 W exit 1.0 mi8. Merge onto I-580 W 0.6 mi9. Keep left at the fork, follow signs for I-80 W/San Franciscoand merge onto I-80 W/ Partial toll road 7.9 mi10. Take the exit toward Civic Center 0.2 mi11. Slight left onto Harrison St 0.1 mi12. Take the 2nd right onto 9th St 0.2 mi13. Turn left onto Howard St 243 ft14. Take the 1st left onto Dore StDestination will be on the right 210 ft
THIS IS AN UNMANNED TELECOMMUNICATIONS FACILITY FOR VERIZON WIRELESS CONSISTING OF THEINSTALLATION AND OPERATION OF ANTENNAS AND ASSOCIATED EQUIPMENT ON AN EXISTINGWOODEN POLE IN THE PUBLIC RIGHT OF WAY.
SCOPE OF WORK:
1. INSTALL NEW TELECOMMUNICATIONS EQUIPMENT BOXES ON AN EXISTING WOODEN POLETO BE INSTALLED ON GO95 COMPLIANT STANDOFF BRACKET. CONSISTING OF (1) ELECTRICALMETER, (1) DISCONNECT BOX, (1) GPS ANTENNA, (2) RRUS AND (1) CYLINDRICAL ANTENNA.
2. ALL EQUIPMENT TO BE PAINTED TO MEET JURISDICTION APPROVAL.3. UTILITY LINES BETWEEN EXISTING POINT OF CONNECTION AND POLE TO BE UNDERGROUNDED
AND/OR OVERHEAD.
SHEET NO: SHEET TITLET-1 TITLE SHEETT-2 GENERAL NOTES, LEGENDS AND ABBREVIATIONSC-1 SITE SURVEYA-1 OVERALL SITE PLANA-2 ENLARGED SITE PLAN, EQUIPMENT PLAN & ELEVATIONA-3 ELEVATIONSA-4 ELEVATIONSA-5 POLE EQUIPMENT ISO VIEWS, SMALL CELL CABINETS & SIGNAGEA-6 ANTENNA SPECS., PARCEL MAP & PHOTOSIMULATIONSE-1 ELECTRICAL SPECS, NOTES, LEGEND & ABBREVIATIONSE-2 ELECTRICAL GROUND DIAGRAMSE-3 ELECT. SINGLE-LINE DIAGRAM & DETAILS
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
SITE INFORMATION
1. 2013 CALIFORNIA BUILDING CODE, VOLUME 1 AND 2 (CBC)2. 2013 CALIFORNIA ELECTRICAL CODE (CEC)3. 2013 CALIFORNIA MECHANICAL CODE (CMC)4. 2013 CALIFORNIA PLUMBING CODE (CPC)5. 2013 CALIFORNIA CALIFORNIA FIRE CODE (CFC)6. 2013 CALIFORNIA GREEN BUILDING STANDARDS CODE7. 2010 CALIFORNIA ENERGY CODE8. CITY / COUNTY ORDINANCES
PS PROJECT I.D. #:
OWNER:
APPLICANT:
AGENT:
APN:
SITE ADDRESS:
COUNTY:
LATITUDE:
LONGITUDE
GROUND ELEV.:
ZONING:
ZONING JURISDICTION:
Client:
CODE COMPLIANCE
CONSTRUCTION WORKS AND MATERIALS MUST COMPLY WITH ALLAPPLICABLE NATIONAL, STATE AND LOCAL CODES AS ADOPTED BYLOCAL JURISDICTION, INCLUDING BUT NOT LIMITED TO:
ACCESSIBILITY REQUIREMENTS:
FACILITY IS UNMANNED AND NOT FOR HUMAN HABITATION.HANDICAPPED ACCESS NOT REQUIRED IN ACCORDANCE WITHTHE 2007 CALIFORNIA BUILDING CODE PART 2, TITLE 24, PART 2,VOLUME 1, CHAPTER11B, SECTION 11238, EXCEPTION 1
PROJECT DESCRIPTION
DRAWING INDEX
ADMINISTRATIVE REQUIREMENTS
CONTRACTOR SHALL VERIFY ALL PLANS & (E) DIMENSIONS & CONDITIONS ON THE JOB SITE & SHALLIMMEDIATELY NOTIFY THE ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK OR BE RESPONSIBLE FOR SAME IF USING 11" x 17" PLOT, DRAWINGS WILL BE HALF SCALE
PROJECT TEAM
AGENT:
VICINITY MAP
PROJECT MANAGER:
CONSTRUCTION MANAGER:
V-ONE PROJECT MANAGER:
VERIZON WIRELESS
VERIZON PROJECT MANAGER:
ARCHITECT OF RECORD:
RENE SANCHEZ5100 CLAYTON ROAD, B01 SUITE 354CONCORD, CA 94521(925) [email protected]
THREE DAYS BEFORE YOU DIG
DRIVING DIRECTIONSDIRECTIONS FROM VERIZON WIRELESS WALNUT CREEK OFFICE
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
36:1
1 A
M
T-1
RSJS
08/27/14
TITLE SHEET
SF LM PH2 SC120
SF LM PH2 SC120
(NEAR) 30 DORE ST.SAN FRANCISCO, CA 94103
JPA Pole #UnknownPeoplesoft Project #20141097234Peoplesoft Location #302036
20141097234
MODUSRYAN CROWLEY149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105(415) [email protected]
MAUREEN CRUZEN(925) [email protected]
V-ONE DESIGN GROUP5100 CLAYTON ROAD, B-1 SUITE 354CONCORD, CA 94521(925) 639-1469
(NEAR) 30 DORE ST.SAN FRANCISCO, CA 94103
(NEAR) 30 DORE ST.SAN FRANCISCO, CA 94103
302036PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
MODUSKEVIN BOWYER149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105(408) [email protected]
MODUSPG&E DORE STREETKEVIN BOWYER149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105KEVIN BOWYER(408) [email protected]
MODUSCAL BORDONARO149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105(415) [email protected]
JOINT POLE AUTHORITY
VERIZON WIRELESS2785 MITCHELL DRIVE, SUITE #9WALNUT CREEK, CA 94598
ADJACENT TO APN: 3518-002
SAN FRANCISCO
37° 46' 26.30" (NAD 83)
-122° 24' 46.91" (NAD 83)
46' AMSL
PUBLIC ROW
CITY OF SAN FRANCISCO
SITE
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
EXIT
E E
T/E
SAND
WOOD BLOCKING
STEEL
(E) MASONRY
GRAVEL
PLYWOOD
CONCRETE
EARTH
GROUT OR PLASTER
(E) BRICK
WOOD CONT.
PROPERTY/LEASE LINE
MATCH LINE
WORK POINT
CENTERLINE
EXISTING ANTENNA
GROUND ROD
NEW ANTENNA
GROUND BUS BAR
TELEPHONE BOX
ELECTRIC BOX
SPOT ELEVATION
FND. MONUMENT
REVISION
SET POINT
DETAIL REFERENCE
GRID REFERENCE
LIGHT POLE
ELEVATION REFERENCE
GROUND ACCESS WELL
MECHANICAL GRND. CONN.
SECTION REFERENCE
CHAIN LINK FENCING
OVERHEAD SERVICE
COAXIAL CABLE
CONDUCTORS
GROUND CONDUCTOR
LIGHTING FIXTURE, 1/175W. METAL HALIDE, HUBBELL CAT#MIC-0175H-336
5/8" X 10'-0" ,CU. GND ROD 30" MIN. BELOW GRADE.
OVERHEAD TELEPHONE LINE
CADWELD CONNECTION
CIRCUIT BREAKER
MECHANICAL CONNECTION
HALO GROUND CONNECTION
STEPDOWN TRANSFORMER
UTILITY METER BASE
TRANSFORMER
TOGGLE SWITCH, 1P-120V-15A, "WP"
5/8" X 10'-0" ,CU. GND ROD IN TEST WELL30" MIN. BELOW GRADE.
POLE
(N) POLE MOUNTED XFMER
(E) POLE MOUNTED XFMR
(E) PAD MOUNTED XFMER
(N) PAD MOUNTED XFMER
IONIZATION SMOKE DETECTOR W/ALARMHORN & AUXILIARY CONTACT, 120 VAC,GENTEX PART NO. 7100F
OVERHEAD POWER LINE
POWER RUN
TELCO RUN
POWER/TELCO RUN
LIGHTING FIXTURE, HIGH PRESSURE SODIUM, 1/70W, WALLMOUNTING TYPE, HUBBELL LIGHTING CATALOG #NRG-307OR 1/50W, HUBBELL LIGHTING CATALOG #NRG-121
LIGHTING FIXTURE, INCANDESCENT, 1/100W, WALLMOUNTING TYPE, HUBBELL LIGHTING CATALOG#BRH-100-06-1
LIGHTING FIXTURE, HALOGEN, QUARTZ, 1/300W, HUBBELLLIGHTING CATALOG #QL-505
EMERGENCY LIGHTING, 2/50W, HUBBELL LIGHTING CATALOG#HE6-50-2-R91
EXIT SIGN, THERMOPLASTIC LED, SINGLE FACE, UNIVERSALMOUNTING, W/BATTERY PACK, HUBBELL LIGHTING CATALOG#PRB
COMBINATION, EXIT SIGN & EMERGENCY LIGHTING,HUBBELL LIGHTING CATALOG #PRC
MANUAL TRANSFER SWITCH, 2P-240V-200A, NO FUSE,NEMA 3R ENCLOSURE
LIGHTING FIXTURE, FLUORESCENT, 10.94" x 4'-0", 2/40W,SURFACE MOUNTING TYPE, HUBBELL LIGHTING CATALOG#WSW232T
LIGHTING FIXTURE, FLUORESCENT, 10.94" x 8'-0", 2/95W,SURFACE MOUNTING TYPE, HUBBELL LIGHTING CATALOG#TWSM232T
FUSE, SIZE AND TYPE AS INDICATED.
SAFETY SWITCH, 2P-240V-60A W/60A FUSES, NEMA 3RENCLOSURE, SQ D CATALOG NO. H222NRB
GROUNDING CONDUCTOR
GROUNDING CONDUCTOR
CONDUIT UNDERGROUND
HIGH PRESSURE SODIUM
INTERIORINCH(ES)
HANGERHEADER
MAXIMUMMACHINE BOLT
MASONRY
LONG(ITUDINAL)
LINEAR FEET (FOOT)
POUND(S)LAG BOLTS
METAL
NEW
MINIMUM
OPENING
NUMBER
PRECAST CONCRETEPERSONAL COMMUNICATION SERVICES
PLYWOOD
MECHANICALMANUFACTURER
MISCELLANEOUS
ON CENTER
NOT TO SCALE
RADIUS
REQUIREDRIGID GALVANIZED STEEL
SCHEDULE
PRESSURE TREATED
REINFORCEMENT(ING)REFERENCE
POWER (CABINET)
POUNDS PER SQUARE INCHPOUNDS PER SQUARE FOOT
PRIMARY RADIO CABINET
QUANTITY
STEEL
SIMILAR
SQUARE
TOP OF FOUNDATIONTOP OF CURBTOP OF ANTENNA
STAINLESS STEEL
TOE NAIL
STANDARD
STRUCTURAL
TEMPORARYTHICK(NESS)
SPECIFICATION(S)
SHEET
POWER PROTECTION CABINET
TYPICAL
WOOD
WEIGHT
WITH
WEATHERPROOF
UNDERWRITERS LABORATORY INC.UNLESS NOTED OTHERWISE
UNDER GROUND
WIDE(WIDTH)
VERIFY IN FIELD
TOP OF PLATE (PARAPET)TOP OF STEELTOP OF WALL
PLATE, PROPERTY LINECENTERLINE
L.
WD
LPLC
INT.
MAX.
MECH.
MIN.
MTL.
MISC.
MFR.
M.B.
LB.(#)
MAS.
L.F.L.B.
HPSHGR.HDR.
IN.(")ICGB.
S.S.
W/
WT.
WD.W.P.
U.N.O.U.L.U.G.TYP.
V.I.F.
T.N.
T.O.W.
T.O.C.
T.O.S.T.O.P.
T.O.A.
T.O.F.
TEMP.
STRUC.
THK.
STL.STD.
P.T.
SPEC.
RGS.
SQ.
SIM.SHT.
SCH.
REQ'D.
RAD.(R)
REINF.REF.
QTY.PWR.
PCS
P.S.I.
PLY.
P.S.F.
PPCPRC
OPNG.
NO.(#)
P/C
O.C.
N.T.S.
(N)
GRND. GROUND
ABOVE
ALUMINUMALTERNATEANTENNA
ADDITIONAL
ABOVE FINISHED GRADEABOVE FINISHED FLOOR
ANCHOR BOLT
ALUM.ALT.ANT.
A.F.G.
ABV.
A.F.F.ADD'LACCA
A.B.
FINISH(ED)
FOUNDATIONFACE OF CONCRETE
GROUND
FOOT (FEET)
GALVANIZE(D)
GLUE LAMINATED BEAM
FINISH SURFACE
FACE OF STUDFACE OF WALL
FACE OF MASONRY
GLOBAL POSITIONING SYSTEM
GROUND FAULT CIRCUIT INTERRUPTER
FOOTING
GLB.
GPS
FLR.
F.O.C.FDN.
F.O.S.F.O.M.
F.O.W.
FT.(')FTG.
G.F.C. I.
F.S.
G
GI.
GA. GAUGE
FLOOR
CONN. CONNECTION(OR)CONSTRUCTIONCONTINUOUSPENNY (NAILS)
ELECTRICAL
DRAWING(S)
DOUGLAS FIRDEPARTMENT
ELEVATOR
ELEVATION
DOWEL(S)
DIMENSIONDIAGONALDIAMETER
DOUBLE
EXPANSIONEXTERIOR
ENGINEER
EXISTING
EDGE NAIL
FINISH GRADEFINISH FLOOR
FABRICATION(OR)
EL.
EMT.ELEV.ELEC.
EXT.EXP.
ENG.
EXST.(E)
E.N.
FAB.
F.G.FIN.
F.F.
EQ. EQUAL
CONST.CONT.
DIM.DIAG.
DEPT.
DBL.
DWG.DWL.
DIA.
EA.
D.F.
d
EACH
CANTILEVER(ED)
CAST IN PLACE
CABINET
AMPERE TRIP
APPROXIMATE(LY)ARCHITECT(URAL)
BOTTOM OF FOOTING
BOUNDARY NAILING
BARE TINNED COPPER WIRE
BACK-UP CABINET
BLOCKING
BUILDING
CONCRETECOLUMN
CEILING
B/U
CANT.
C.I.P.
CAB.
BTCW.
BLKG.
B.O.F.
B.N.
CLR.
CONC.COL.
CLG.
BM.
CLEAR
BEAM
APPR0X.
AT.ARCH.
BLK.BLDG.
BLOCK
AMPEREA
AMPERE INTERRUPTING CAPACITYAIC
AMERICAN WIRE GAUGEAWG.BATTERYBATT.BOARDBD.
BRANCHBR.BREAKERBRKR.
BASE TRANSMISSION SYSTEMBTS.
CONDUITC
CIRCUIT BREAKERCB.
CIRCUITCKT.
DEMANDDEM.
EGR. EMERGENCY GENERATOR RECEPTACLE
ENCLOSUREENCL.
FACTORFAC.FIRE ALARMF/A
FLUOR FLUORESCENT
FUSEFU
GEN. GENERATOR
GROWTH (CABINET)GR
GROUNDGND
HDBC HARD DRAWN COPPER WIRE
HEIGHTHT.
LENGTHLG.
LOW PRESSURE SODIUMLPS
MAIN LUGS ONLYMLOMOUNTEDMTD.MOUNTINGMTG.
MANUAL TRANSFER SWITCHMTS.NEUTRALN
NATIONAL ELECTRICAL MANUFACTURERS ASSOC.NEMA
OVERHEADOH
POLEP
PHASEPH
PANELBOARDPNLBD
PRIMARYPRI
RECEPTACLERCPT.
SAFETYSAF
SOFT DRAWN BARE COPPERSDBCSECONDARYSEC
SOLID NEUTRALS.N.
SURFACESURFSWITCHSWTELEPHONETEL.
VOLTVVOLT ALTERNATING CURRENTVAC
WATT OR WIREW
WITHOUTW/O
TRANSFER
CROSS-LINK POLYETHYLENETRANSFORMER
XLPE
XFERXFMR
CHEMICAL GROUND ROD(XIT GROUND ROD)
RECEPTACLE, 2P-3W-125V-15A, DUPLEX,GROUND TYPE, HUBBEL CATALOG #5362
TOGGLE SWITCH, 1P-125V-15A,HUBBELL CATALOG #HBL 1201CN
OVERHEAD ELEPHONE/OVERHEADPOWER
ANTENNA CABLE COVER ASSEMBLY
ELECTRICAL METALLIC TUBING
GENERAL NOTES FOR EXISTING CELL SITES
PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING SUBCONTRACTOR SHALL VISIT THE CELL SITE TO FAMILIARIZE WITH THE EXISTING CONDITIONSAND TO CONFIRM THAT THE WORK CAN BE ACCOMPLISHED AS SHOWN ON THE CONSTRUCTION DRAWINGS. ANY DISCREPANCY FOUNDSHALL BE BROUGHT TO THE ATTENTION OF CONTRACTOR.
SUBCONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OFEXISTING CONSTRUCTION SHOWN ON THE DRAWINGS MUST BE VERIFIED. SUBCONTRACTOR SHALL NOTIFY THE CONTRACTOR OF ANYDISCREPANCIES PRIOR TO ORDERING MATERIAL OR PROCEEDING WITH CONSTRUCTION.
THE EXISTING CELL SITE IS IN FULL COMMERCIAL OPERATION. ANY CONSTRUCTION WORK BY SUBCONTRACTOR SHALL NOT DISRUPT THEEXISTING NORMAL OPERATION. ANY WORK ON EXISTING EQUIPMENT MUST BE COORDINATED WITH CONTRACTOR. ALSO, WORK SHOULD BESCHEDULED FOR AN APPROPRIATE MAINTENANCE WINDOW USUALLY IN LOW TRAFFIC PERIODS AFTER MIDNIGHT.
SINCE THE CELL SITE IS ACTIVE, ALL SAFETY PRECAUTIONS MUST BE TAKEN WHEN WORKING AROUND HIGH LEVELS OF ELECTROMAGNETICRADIATION. EQUIPMENT SHOULD BE SHUTDOWN PRIOR TO PERFORMING ANY WORK THAT COULD EXPOSE THE WORKERS TO DANGER.PERSONAL RF EXPOSURE MONITORS ARE ADVISED TO BE WORN TO ALERT OF ANY DANGEROUS EXPOSURE LEVELS.
SUBCONTRACTOR SHALL DETERMINE ACTUAL ROUTING OF CONDUIT, POWER AND T1 CABLES, GROUNDING CABLES AS SHOWN ON THEPOWER, GROUNDING AND TELCO PLAN DRAWING. SUBCONTRACTOR SHALL UTILIZE EXISTING TRAYS AND/OR SHALL ADD NEW TRAYS ASNECESSARY. SUBCONTRACTOR SHALL CONFIRM THE ACTUAL ROUTING WITH THE CONTRACTOR.
SUBCONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND OTHER ITEMS REMOVEDFROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE RETURNED TO THE OWNER'S DESIGNATED LOCATION.
1.
2.
3.
4.
5.
6.
GENERAL CONSTRUCTION NOTES
PLANS ARE INTENDED TO BE DIAGRAMMATIC OUTLINE ONLY, UNLESS NOTED OTHERWISE. THE WORK SHALL INCLUDE FURNISHING MATERIALS,EQUIPMENT, APPURTENANCES AND LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS.
1.
THE CONTRACTOR SHALL OBTAIN, IN WRITING, AUTHORIZATION TO PROCEED BEFORE STARTING WORK ON ANY ITEM NOT CLEARLY DEFINEDOR IDENTIFIED BY THE CONTRACT DOCUMENTS.
2.
CONTRACTOR SHALL CONTACT USA (UNDERGROUND SERVICE ALERT) AT (800) 227-2600, FOR UTILITY LOCATIONS, 48 HOURS BEFOREPROCEEDING WITH ANY EXCAVATION, SITE WORK OR CONSTRUCTION.
3.
THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESSSPECIFICALLY INDICATED OTHERWISE, OR WHERE LOCAL CODES OR REGULATIONS TAKE PRECEDENCE.
4.
ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE CBC / UBC'S REQUIREMENTS REGARDING EARTHQUAKE RESISTANCE, FOR, BUT NOTLIMITED TO, PIPING, LIGHT FIXTURES, CEILING GRID, INTERIOR PARTITIONS, AND MECHANICAL EQUIPMENT. ALL WORK MUST COMPLY WITHLOCAL EARTHQUAKE CODES AND REGULATIONS.
5.
REPRESENTATIONS OF TRUE NORTH, OTHER THAN THOSE FOUND ON THE PLOT OF SURVEY DRAWINGS, SHALL NOT BE USED TO IDENTIFY ORESTABLISH BEARING OF TRUE NORTH AT THE SITE. THE CONTRACTOR SHALL RELY SOLELY ON THE PLOT OF SURVEY DRAWING AND ANYSURVEYOR'S MARKINGS AT THE SITE FOR THE ESTABLISHMENT OF TRUE NORTH, AND SHALL NOTIFY THE ARCHITECT / ENGINEER PRIOR TOPROCEEDING WITH THE WORK IF ANY DISCREPANCY IS FOUND BETWEEN THE VARIOUS ELEMENTS OF THW WORKING DRAWINGS AND THE TRUENORTH ORIENTATION AS DEPICTED ON THE CIVIL SURVEY. THE CONTRACTOR SHALL ASSUME SOLE LIABILITY FOR ANY FAILURE TO NOTIFY THEARCHITECT / ENGINEER.
6.
THE BUILDING DEPARTMENT ISSUING THE PERMITS SHALL BE NOTIFIED AT LEAST TWO WORKING DAYS PRIOR TO THE COMMENCEMENT OF WORK,OR AS OTHERWISE STIPULATED BY THE CODE ENFORCEMENT OFFICIAL HAVING JURISDICTION.
7.
DO NOT EXCAVATE OR DISTURB BEYOND THE PROPERTY LINES OR LEASE LINES, UNLESS OTHERWISE NOTED.8.
ALL EXISTING UTILITIES, FACILITIES, CONDITIONS, AND THEIR DIMENSIONS SHOWN ON THE PLAN HAVE BEEN PLOTTED FROM AVAILABLERECORDS. THE ARCHITECT / ENGINEER AND THE OWNER ASSUME NO RESPONSIBILITY WHATSOEVER AS TO THE SUFFICIENCY OR THEACCURACY OF THE INFORMATION SHOWN ON THE PLANS, OR THE MANNER OF THEIR REMOVAL OR ADJUSTMENT. CONTRACTORS SHALL BERESPONSIBLE FOR DETERMINING EXACT LOCATION OF ALL EXISTING UTILITIES AND FACILITIES PRIOR TO START OF CONSTRUCTION.CONTRACTORS SHALL ALSO OBTAIN FROM EACH UTILITY COMPANY DETAILED INFORMATION RELATIVE TO WORKING SCHEDULES ANDMETHODS OF REMOVING OR ADJUSTING EXISTING UTILITIES.
9.
CONTRACTOR SHALL VERIFY ALL EXISTING UTILITIES, BOTH HORIZONTAL AND VERTICALLY, PRIOR TO THE START OF CONSTRUCTION. ANYDISCREPANCIES OR DOUBTS AS TO THE INTERPRETATION OF PLANS SHOULD BE IMMEDIATELY REPORTED TO THE ARCHITECT / ENGINEER FORRESOLUTION AND INSTRUCTION, AND NO FURTHER WORK SHALL BE PERFORMED UNTIL THE DISCREPANCY IS CHECKED AND CORRECTED BY THEARCHITECT / ENGINEER. FAILURE TO SECURE SUCH INSTRUCTION MEANS CONTRACTOR WILL HAVE WORKED AT HIS/HER OWN RISK ANDEXPENSE.
10.
ALL NEW AND EXISTING UTILITY STRUCTURES ON SITE AND IN AREAS TO BE DISTURBED BY CONSTRUCTION SHALL BE ADJUSTED TO FINISHELEVATIONS PRIOR TO FINAL INSPECTION OF WORK.
11.
ANY DRAIN AND/OR FIELD TILE ENCOUNTERED / DISTURBED DURING CONSTRUCTION SHALL BE RETURNED TO IT'S ORIGINAL CONDITION PRIORTO COMPLETION OF WORK. SIZE, LOCATION AND TYPE OF ANY UNDERGROUND UTILITIES OR IMPROVEMENTS SHALL BE ACCURATELY NOTEDAND PLACED ON "AS-BUILT" DRAWINGS BY GENERAL CONTRACTOR, AND ISSUED TO THE ARCHITECT / ENGINEER AT COMPLETION OF PROJECT.
12.
ALL TEMPORARY EXCAVATIONS FOR THE INSTALLATION OF FOUNDATIONS, UTILITIES, ETC., SHALL BE PROPERLY LAID BACK OR BRACED INACCORDANCE WITH CORRECT OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) REQUIREMENTS.
13.
INCLUDE MISC. ITEMS PER VERIZON WIRELESS SPECIFICATIONS14.
APPLICABLE CODES, REGULATIONS AND STANDARDS:
THE EDITION OF THE AHJ ADOPTED CODES AND STANDARDS IN EFFECT ON THE DATE OF CONTRACT AWARD SHALL GOVERN THE DESIGN.
SUBCONTRACTOR'S WORK SHALL COMPLY WITH THE LATEST EDITION OF THE FOLLOWING STANDARDS:
- AMERICAN CONCRETE INSTITUTE (ACI) 318, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE- AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC), MANUAL OF STEEL CONSTRUCTION, ASD, NINTH EDITION- TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA) 222-F, STRUCTURAL STANDARD FOR STRUCTURAL ANTENNA TOWER AND ANTENNASUPPORTING STRUCTURES- INSTITUTE FOR ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) 81, GUIDE FOR MEASURING EARTH RESISTIVITY, GROUND IMPEDANCE, ANDEARTH SURFACE POTENTIALS OF A GROUND SYSTEM IEEE 1100 (1999) RECOMMENDED PRACTICE FOR POWERING AND GROUNDING OFELECTRICAL EQUIPMENT.-IEEE C62.41, RECOMMENDED PRACTICES ON SURGE VOLTAGES IN LOW VOLTAGE AC POWER CIRCUITS (FOR LOCATION CATEGORY "C3"AND "HIGH SYSTEM EXPOSURE")
TIA 607 COMMERCIAL BUILDING GROUNDING AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS TELCORDIA GR-63 NETWORKEQUIPMENT-BUILDING SYSTEM (NEBS): PHYSICAL PROTECTIONTELCORDIA GR-347 CENTRAL OFFICE POWER WIRINGTELCORDIA GR-1275 GENERAL INSTALLATION REQUIREMENTSTELCORDIA GR-1503 COAXIAL CABLE CONNECTIONS
ANY AND ALL OTHER LOCAL & STATE LAWS AND REGULATIONS
FOR ANY CONFLICTS BETWEEN SECTIONS OF LISTED CODES AND STANDARDS REGARDING MATERIAL, METHODS OF CONSTRUCTION, OR OTHERREQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN. WHERE THERE IS CONFLICT BETWEEN A GENERAL REQUIREMENT AND A SPECIFICREQUIREMENT, THE SPECIFIC REQUIREMENT SHALL GOVERN.
GENERAL TRENCHING NOTES
1. MAINTAIN 40" MINIMUM COVER FOR ALL ELECTRICAL CONDUITS.2. MAINTAIN 30" MINIMUM COVER FOR ALL TELECOMMUNICATIONS CONDUITS.3. MINIMUM 1" SAND SHADING BELOW CONDUITS, AND 6" COVERING ON TOP OF CONDUITS REQUIRED.4. ALL ELECTRICAL CONDUITS FROM POWER COMPANY FROM ANY POLE, TRANSFORMER OR OTHER LOCATIONS WILL BE SLURRY BACKFILLED.5. IN STREET SLURRY TO GRADE AND MILL DOWN 1-1/2" FOR AC CAP.6. IN DIRT SLURRY 18" FROM GRADE AND FILL 95% COMPACTION NATIVE SOIL FOR BALANCE7. WARNING TAPE TO BE PLACED IN TRENCH 12" ABOVE ALL CONDUITS AND #18 WARNING TAPE ABOVE RING.
GENERAL GROUNDING NOTES
1. 5/8" x 10' ROD, CAD WELD BELOW GRADE2. GROUND TESTED AT 5 OHMS OR LESS.3. #5 GROUND AND BOND WIRE.4. GROUNDS 3" FROM POLE.5. PLACE 3 #10 GA WIRES FROM TESCO BREAKER TO PBMD OR STRONG BOX.6. WOOD MOULDING, STAPLED EVERY 3" AND AT EACH END.
GENERAL CONDUIT NOTES
1. ALL CONDUITS WILL BE MANDRELED AND EQUIPPED WITH 3/8" PULL ROPE.2. SCHEDULE 40 CONDUIT FOR UNDERGROUND USE.3. SCHEDULE 80 CONDUIT FOR RISER USE.4. 2" GALVANIZED STEEL CONDUIT FOR ANY CONDUIT UNDER 3", STUB UP 10" THEN CONVERT TO SCHEDULE 80.5. CONVERT 4" CONDUIT TO 3" AT BASE OF POLE.6. CONTRACTOR TO STUB UP POLE 10" w/ 3" POWER CONDUIT. POWER COMPANY TO CONVERT FROM 3" STUB SCHEDULE 80 TO
2" SCHEDULE 80 FROM TOP OF STUB UP.
TYPICAL R.O.W. POLE CONSTRUCTION NOTES
1. CABLE NOT TO IMPEDE 15" CLEAR SPACE OFF POLE FACE.2. ALL CLIMB STEPS NEXT TO CONDUIT SHALL HAVE EXTENDED STEPS.3. NO BOLT THREADS TO PROTRUDE MORE THAN 1-1/2"4. ALL HOLES IN POLE LEFT FROM REARRANGEMENT OF CLIBERS TO BE FILLED.5. 90° SHORT SWEEPS UNDER ANTENNA ARM, ALL CABLES MUST TRANSITION ON THE INSIDE OR BOTTOM OF THE ARM (NO CABLE ON
TOP OF ARM).6. USE 90° CONNECTOR AT CABLE CONNECTION FOR OMNI DOWN ANTENNAS.7. USE CABLE CLAMPS TO SECURE CAB;LE TO ARMS, PLACE 2" VERIZON WIRELESS CABLE I.D. TAGS ON BOTH SIDES OF ARMS.8. USE 1/2" DIA. CABLE ON ANTENNAS UNLESS OTHERWISE SPECIFIED.9. PLACE GPS ON ARM OF SOUTHERN SKY EXPOSURE AT MINIMUM 6" FROM TRANSMIT ANTENNA WHICH IS 24" AWAY FROM CENTER
OF POLE.10. FILL VOID AROUND CABLES AT CONDUIT OPENING WITH FOAM SEALANT TO PREVENT WATER INTRUSION.
SUBCONTRACTOR'S WORK SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE, AND LOCAL CODES AS ADOPTED BY THE LOCALAUTHORITY HAVING JURISDICTION (AHJ) FOR THE LOCATION.
1.
2.
3.
4.
5.
6.
7.
ISOLATED COPPER GROUND BUS
T
E
S
T
M
1
X
XX-X
A
X
O/U
WPS
S
XXX-X
XX-X
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
36:1
2 A
M
T-2
CheckerAuthor
08/27/14
GENERAL NOTES,LEGENDS AND
ABBREVIATIONS
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
GENERAL NOTES
ABBREVIATIONSLEGEND
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
P PP P P P
DORE STREET
SECTOR A
AZIMUTH 135°EXISTING OVERHEAD
UTILITY LINES, TYP.
EXISTING PROPERTY LINES,TYP.
EXISTING BUILDING OUTLINE,TYP.
EXISTING EDGE OFCURB, TYP.
EXISTING UTILITY WOOD POLE,TYP.
EXISTING UTILITY WOODWITH TRANSFORMER. POWER POC
NEW OVERHEAD POWER TONEW METER
HOWARD STREE
T
EXISTING STEEL BOLLARD, TYP.
A-24
APN: 3518-002RCD
APN: 3518-035WMUG
APN: 3518-023WMUG
APN: 3518-023RED-MX
APN: 3518-024ARED-MX
APN: 3518-033RED-MX
APN: 3518-001
APN: 3518-040 & 041RED-MX
APN: 3518-042 & 043RED-MX
APN: 3518-032RED-MX
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
35:0
6 A
M
A-1
RSJS
08/27/14
OVERALL SITE PLAN
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
0 40' 60' 80'20'
Graphic Scale: 1 inch = 20 feet
1 SITE PLAN
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
PP
CLIMBING SPACE
EXISTING UTILITY WOOD POLE
NEW 2"Ø SCH. 80 PVC POWERCONDUIT WITH WEATHER HEAD,PAINTED MESA BROWN
NEW VERIZON WIRELESSJ-PAK-AM-200-02 ANTENNA BRACKETMOUNT PAINTED MESA BROWN
NEW VERIZON WIRELESS DUAL PHASEAMPHENOL CWD070X06 ANTENNAMOUNTED TO A NEW JPAK#AM-100-02. PAINTED MESA BROWN
3' - 0"
3' -
0"
2' -
0"
EXISTING UTILITY WOOD POLE
CLIMBING SPACE
NEW 2"Ø SCH. 80 PVC POWERCONDUIT WITH WEATHER HEAD,PAINTED MESA BROWN
NEW VERIZON WIRELESSJPAK-EM-100-06 STANDOFF BRACKETTHRU BOLTED TO EXISTING WOODUTILITY POLE PAINTED MESA BROWN
NEW VERIZON WIRELESS RRUSMOUNTED TO EXISTING UTILITY WOODPOLE, TYP. (TOTAL OF 2)
NEW 2"Ø SCH. 80 PVC COAXCONDUIT, PAINTED MESA BROWN
9"4"
1' - 7"
3' -
0"
3' - 0"
CLIMBING SPACE
EXISTING UTILITY WOOD POLE
NEW 2"Ø SCH. 80 PVC POWERCONDUIT WITH WEATHER HEAD,PAINTED MESA BROWN
NEW VERIZON WIRELESSJPAK-EM-100-06 STANDOFF BRACKETTHRU BOLTED TO EXISTING WOODUTILITY POLE PAINTED MESA BROWN
NEW VERIZON WIRELESS ELECTRICALMETER MOUNTED TO NEWJPAK-EM-100-06 STANDOFF BRACKETON EXISTING WOOD POLE. PAINTEDMESA BROWN
NEW 2"Ø SCH. 80 PVC COAXCONDUIT, PAINTED MESA BROWN
1' - 2"
1' -
0"4"
3' - 0"
3' -
0"
NEW VERIZON WIRELESS DUAL PHASEAMPHENOL CWD070X06 ANTENNAMOUNTED TO A NEW JPAK#AM-100-02. PAINTED MESA BROWN
EXISTING STREET LIGHT STANDARD
NEW VERIZON WIRELESS ELECTRICALMETER MOUNTED TO NEWJPAK-EM-100-06 STANDOFF BRACKETON EXISTING WOOD POLE. PAINTEDMESA BROWN
EXISTING UTILITY WOOD POLE
NEW VERIZON WIRELESS RRUSMOUNTED TO EXISTING UTILITY WOODPOLE, TYP. (TOTAL OF 2)
NEW 2"Ø SCH. 80 PVC COAXCONDUIT, PAINTED MESA BROWN
EXISTING OVERHEAD UTILITYLINES, TYP.
NEW OVERHEAD POWER LINE FROMEXISTING UTILITY POLE POC
EXISTING EDGE OF CURB
EXISTING STEEL BOLLARD
EXISTING BUILDINGFOOTPRINT
2
A-3
2A-4
NEAREST INHABITED BUILD
ING
7' - 8
" DISTANCE O
F PROPOSED ANTENNA TO
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
35:2
9 A
M
A-2
RSJS
08/27/14
ENLARGED SITE PLAN,EQUIPMENT PLAN &
ELEVATION
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
0 2' 3' 4'1'
Graphic Scale: 1 inch = 1 feet
0 2' 3' 4'1'
Graphic Scale: 1 inch = 1 feet
0 2' 3' 4'1'
Graphic Scale: 1 inch = 1 feet
0 4' 6' 8'2'
Graphic Scale: 1 inch = 2 feet
1 ANTENNA PLAN
2 RRUS PLAN
3 METER PLAN4 ENLARGED SITE PLAN
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
SIDEWALK LEVEL0' - 0"
EXISTINGSECONDARY
POWER29' - 8 1/2"
EXISTING STREETLIGHT
28' - 11"
TOP OF EXISTINGPOLE
30' - 2 1/2"
EXISTING UTILITY WOOD POLE
EXISTING TELCOLINE
26' - 5"
EXISTING STREET LIGHT STANDARD
SIDEWALK LEVEL0' - 0"
BOTTOM OFPROPOSED
ELECTRICALMETER
7' - 0"
EXISTINGSECONDARY
POWER29' - 8 1/2"
EXISTING STREETLIGHT
28' - 11"
VERIZONWIRELESS
CENTERLINE21' - 0"
TOP OF EXISTINGPOLE
30' - 2 1/2"
TOP OF RRUS13' - 9"
EXISTING UTILITY WOOD POLE
NEW 2"Ø SCH. 80 PVC POWERCONDUIT WITH WEATHER HEAD,PAINTED MESA BROWN
NEW VERIZON WIRELESS DUAL PHASEAMPHENOL CWD070X06 ANTENNAMOUNTED TO A NEW JPAK#AM-100-02. PAINTED MESA BROWN
NEW VERIZON WIRELESSJ-PAK-AM-200-02 ANTENNA BRACKETMOUNT PAINTED MESA BROWN
NEW 2"Ø SCH. 80 PVC COAXCONDUIT, PAINTED MESA BROWN
NEW VERIZON WIRELESS RRUSMOUNTED TO EXISTING UTILITY WOODPOLE, TYP. (TOTAL OF 2)
NEW PG&E SHUTDOWN SWITCHPAINTED MESA BROWN
NEW VERIZON WIRELESS ELECTRICALMETER MOUNTED TO NEWJPAK-EM-100-06 STANDOFF BRACKETON EXISTING WOOD POLE. PAINTEDMESA BROWN
NEW VERIZON WIRELESSJPAK-EM-100-06 STANDOFF BRACKETTHRU BOLTED TO EXISTING WOODUTILITY POLE PAINTED MESA BROWN
EXISTING TELCOLINE
26' - 5"
6' POWER SAFETY ZONE PER GO 95
6' -
0"
NEW 1"Ø SCH. 80 PVC FIBER CONDUIT,PAINTED MESA BROWN
NEW GROUND BUSS BAR MOUNTED TONEW JPAK #EM-100-06
NEW VERIZON WIRELESS GPS ANTENNAMOUNTED TO NEW PACKJPAK-EM-100-06
TOP OF VERIZONWIRELESSANTENNA
22' - 0"
TOP OF GPSANTENNA
15' - 1"
EXISTING STREET LIGHT STANDARD
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
35:4
0 A
M
A-3
RSJS
08/27/14
ELEVATIONS
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
0 4' 6' 8'2'
Graphic Scale: 1 inch = 2 feet
0 4' 6' 8'2'
Graphic Scale: 1 inch = 2 feet
1 EXISTING NORTHEAST ELEVATION 2 PROPOSED NORTHEAST ELEVATION
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
SIDEWALK LEVEL0' - 0"
EXISTINGSECONDARY
POWER29' - 8 1/2"
EXISTING STREETLIGHT
28' - 11"
TOP OF EXISTINGPOLE
30' - 2 1/2"
EXISTING UTILITY WOOD POLE
1' - 4"
EXISTING TELCOLINE
26' - 5"
EXISTING STREET LIGHT STANDARD
SIDEWALK LEVEL0' - 0"
BOTTOM OFPROPOSED
ELECTRICALMETER
7' - 0"
EXISTINGSECONDARY
POWER29' - 8 1/2"
EXISTING STREETLIGHT
28' - 11"
VERIZONWIRELESS
CENTERLINE21' - 0"
TOP OF EXISTINGPOLE
30' - 2 1/2"
TOP OF RRUS13' - 9"
EXISTING UTILITY WOOD POLE
1' - 4"
NEW VERIZON WIRELESS DUAL PHASEAMPHENOL CWD070X06 ANTENNAMOUNTED TO A NEW JPAK#AM-100-02. PAINTED MESA BROWN
NEW 2"Ø SCH. 80 PVC POWERCONDUIT WITH WEATHER HEAD,PAINTED MESA BROWN
NEW VERIZON WIRELESSJ-PAK-AM-200-02 ANTENNA BRACKETMOUNT PAINTED MESA BROWN
NEW 2"Ø SCH. 80 PVC COAXCONDUIT, PAINTED MESA BROWN
NEW VERIZON WIRELESS RRUSMOUNTED TO EXISTING UTILITY WOODPOLE, TYP. (TOTAL OF 2)
NEW VERIZON WIRELESSJPAK-EM-100-06 STANDOFF BRACKETTHRU BOLTED TO EXISTING WOODUTILITY POLE PAINTED MESA BROWN
NEW PG&E SHUTDOWN SWITCHPAINTED MESA BROWN
NEW VERIZON WIRELESS ELECTRICALMETER MOUNTED TO NEWJPAK-EM-100-06 STANDOFF BRACKETON EXISTING WOOD POLE. PAINTEDMESA BROWN
EXISTING TELCOLINE
26' - 5"
6' -
0"
6' COMMUNICATION SAFETY ZONEPER GO 95
TOP OF VERIZONWIRELESSANTENNA
22' - 0"
NEW VERIZON WIRELESS GPS ANTENNAMOUNTED TO NEW PACKJPAK-EM-100-06
NEW GROUND BUSS BAR MOUNTED TONEW JPAK #EM-100-06
TOP OF GPSANTENNA
15' - 1"
EXISTING STREET LIGHT STANDARD
NEW 1"Ø SCH. 80 PVC FIBER CONDUIT,PAINTED MESA BROWN
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
35:4
9 A
M
A-4
RSJS
08/27/14
ELEVATIONS
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
0 4' 6' 8'2'
Graphic Scale: 1 inch = 2 feet
0 4' 6' 8'2'
Graphic Scale: 1 inch = 2 feet
1 EXISTING NORTHWEST ELEVATION 2 PROPOSED NORTHWEST ELEVATION
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
NEW VINYL SIGN TO BE PROVIDED BY VERIZON WIRELESS ANDATTACHED 3' BELOW EXISTING ANTENNAS. SIGN TO BE YELLOW
NOTE:
NEW VINYL SIGN TO BE PROVIDED BY VERIZON WIRELESS AND BEPLACED ON THE POLE 13' ABOVE GROUND LEVEL. COLOR TO BEDETERMINED PRIOR TO INSTALL.
SIDEWALK LEVEL0' - 0"
BOTTOM OFPROPOSED
ELECTRICALMETER
7' - 0"
EXISTINGSECONDARY
POWER29' - 8 1/2"
EXISTING STREETLIGHT
28' - 11"
VERIZONWIRELESS
CENTERLINE21' - 0"
TOP OF EXISTINGPOLE
30' - 2 1/2"
TOP OF RRUS13' - 9"
EXISTING TELCOLINE
26' - 5"
EXISTING UTILITY WOOD POLE
NEW 2"Ø SCH. 80 PVC POWERCONDUIT WITH WEATHER HEAD,PAINTED MESA BROWN
NEW VERIZON WIRELESS DUAL PHASEAMPHENOL CWD070X06 ANTENNAMOUNTED TO A NEW JPAK#AM-100-02. PAINTED MESA BROWN
NEW VERIZON WIRELESSJ-PAK-AM-200-02 ANTENNA BRACKETMOUNT PAINTED MESA BROWN
NEW 2"Ø SCH. 80 PVC COAXCONDUIT, PAINTED MESA BROWN
NEW VERIZON WIRELESS RRUSMOUNTED TO EXISTING UTILITY WOODPOLE, TYP. (TOTAL OF 2)
NEW PG&E SHUTDOWN SWITCHPAINTED MESA BROWN
NEW VERIZON WIRELESS ELECTRICALMETER MOUNTED TO NEWJPAK-EM-100-06 STANDOFF BRACKETON EXISTING WOOD POLE. PAINTEDMESA BROWN
NEW VERIZON WIRELESSJPAK-EM-100-06 STANDOFF BRACKETTHRU BOLTED TO EXISTING WOODUTILITY POLE PAINTED MESA BROWN
1A-2
2A-2
3A-2
6' -
0"
6' POWER SAFETY ZONEPER GO 95
TOP OF VERIZONWIRELESSANTENNA
22' - 0"
1' -
8"3"
8"3"
2"3"
1' -
6"6"
1' -
6"
6' -
9"
TOP OF GPSANTENNA
15' - 1"
NEW VERIZON WIRELESS GPS ANTENNAMOUNTED TO NEW PACKJPAK-EM-100-06
NEW GROUND BUSS BAR MOUNTED TONEW JPAK #EM-100-06
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
36:0
2 A
M
A-5
RSNG
08/27/14
POLE EQUIPMENT ISOVIEWS, SMALL CELL
CABINETS & SIGNAGE
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
2 NOTICE SIGNAGE
NOTE:
EQUIPMENT IN THE 3DRENDERINGS SHOWN IN WHITEFOR CLARITY. EQUIPMENT TOBE PAINTED MESA BROWN.
5 RRUS SPECIFICATIONS
3 SHUTDOWN DISCONNECT BOX
1 FCC SIGN4 EQUIPMENT 3D VIEWS
6 SHUTDOWN DISCONNECT SWITCH
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
7 EQUIPMENT ELEVATION
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
36:0
4 A
M
A-6
RSNG
08/27/14
ANTENNA SPECS.,PARCEL MAP &
PHOTOSIMULATIONS
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
APPROXIMATE LOCATIONOF UTILITY POLE
1 ANTENNA SPECIFICATIONS
2 PARCEL PLAN3 PHOTOSIMULATIONS
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
S
T
M
EXIT
M
OVERHEAD TELEPHONE LINE
OVERHEAD TELEPHONE/OVERHEAD POWER
OVERHEAD POWER LINE
E
T/E
WPS
S
THE DRAWINGS INDICATE DIAGRAMMATICALLY THE DESIRED
TYPE. EMT SHALL BE USED ONLY FOR
A.
AND EXAMINATION WITHOUT ADDITIONAL EXPENSE TO THE
CIRCUIT DIRECTORY.
H.
I.
OWNER.
GROUNDING
NATIONAL ELECTRICAL CODE.EQUIPMENT CONDUCTORS AS REQUIRED BY ARTICLE 250 OFELECTRODE CONDUCTOR, BONDING CONDUCTORS, ANDAPPROVED GROUNDING SYSTEM INCLUDING ELECTRODES.THE CONTRACTOR SHALL PROVIDE A COMPLETE, AND
AND 10' LONG. COPPERWELD OR APPROVED EQUAL.GROUND RODS SHALL BE COPPER CLAD STEEL, 5/8" ROUND
TO WHICH THEY MAY BE SUBJECTED.RATING NOT LESS THAN MAXIMUM SHORT CIRCUIT CURRENTELECTRICAL EQUIPMENT SHALL HAVE AN INTERRUPTINGALL CIRCUIT BREAKERS, MAGNETIC STARTERS AND OTHER
7.
A.
SHOP DRAWINGS
SHALL BE SOLID. CONDUCTORS #8 AWG AND LARGER
3.
SUBSTITUTIONS4.
G.
F.
FLOOR.
TESTS
A. NO SUBSTITUTIONS ARE ALLOWED.
SHALL INSURE THAT ALL EQUIPMENT, SYSTEMS,BEFORE FINAL ACCEPTANCE OF WORK, THE CONTRACTOR
PANELBOARDS SHALL BE DEAD FRONT SAFETY TYPE WITH
FINISH. MOUNT SWITCHES AT +48" ABOVE FINISHEDSPECIFICATION GRADE WHITE (UNLESS NOTED OTHERWISE)TOGGLE SWITCHES SHALL BE 20 AMP, 120 VOLT AC,
WITH SIERRA #WPD-8 LIFT COVERPLATES.RECEPTACLES SHALL BE GROUND FAULT INTERRUPTER TYPE
PERMITS
THE INTENT OF THE DRAWINGS.
AND PAYING FOR ALL THE REQUIRED PERMITS, INSPECTIONTHE CONTRACTOR SHALL BE RESPONSIBLE FOR TAKING OUT
6'-3" ABOVE FINISHED FLOOR. PROVIDE TYPEWRITTENCIRCUIT BREAKERS. MOUNT TOP OF THE PANELBOARDS ATMAKE QUICK-BREAK BOLT-IN TYPE THERMAL MAGNETICNEUTRAL BUS, GROUND BUS AND EQUIPPED WITH QUICK-COPPER CONDUCTORS, COPPER BUS BARS, FULL SIZEDANTI-BURN SOLDERLESS COMPRESSION APPROVED FOR
FIXTURES, ETC., ARE WORKING SATISFACTORILY AND TO
5.
6.
A.
A.
E.
D.
INDICATED ON DRAWINGS OR IN DETAILS. WEATHERPROOF+12" ABOVE FINISHED FLOOR UNLESS OTHERWISEGROUNDING TYPE, NEMA 5-20R. MOUNT RECEPTACLE ATARCHITECT/ENGINEER), 20 AMP, 125 VOLT, THREE WIREWITH WHITE FINISH (UNLESS NOTED BYDUPLEX RECEPTACLES SHALL BE SPECIFICATION GRADE
DEVICES AND WIRING.ACCESSORIES SIZED PER CODE TO ACCOMMODATE ALLPROVIDE GALVANIZED COATED STEEL BOXES AND
SHALL BE USED.WEATHER, IN WHICH CASE TYPE THWN INSULATIONUNLESS CONDUCTORS INSTALLED IN CONDUIT EXPOSED TOSHALL BE STRANDED. TYPE THHN INSULATION USED
A.
THE CHANGE IS ORDERED BEFORE THE CONDUIT RUNS,
WITH ARCHITECT PRIOR TO INSTALLING.
5.
7.
6.
C.
D.
PROPOSED CHANGES BEFORE PROCEEDING.ACCEPTANCE FROM ARCHITECT/ENGINEER FOR THEAGREEMENT AS TO CHANGES NECESSARY. OBTAIN WRITTENWITH THE RESPECTIVE CONTRACTOR AND COME TOALL OTHER TRADES. WHERE CONFLICTS OCCUR, CONSULTCOORDINATE THE WORK OF THIS SECTION WITH THAT OF
WITH MECHANICAL EQUIPMENT TO AVOID INTERFERENCE.LOCATIONS ONLY. COORDINATE THE FIXTURE LOCATIONLIGHTING FIXTURES ARE SHOWN IN THEIR APPROXIMATE
INSTALLED AND NO EXTRA MATERIALS ARE REQUIRED.ETC., AND WORK DIRECTLY CONNECTED TO THE SAME IS
THE DRAWINGS. CONDUCTORS #10 AWG AND SMALLERAWG MINIMUM UNLESS SPECIFICALLY NOTED OTHERWISE ONALL WIRE AND CABLE SHALL BE COPPER, 600 VOLT, #12
NON-HARDENING MASTIC.X 4 REDCHAINLINK SLEEPERS, 6'-0" ON CENTER, SET INCONDUITS RUN ON ROOFS SHALL BE INSTALLED ON 4
ALL CONDUIT ONLY (C.O.) SHALL HAVE PULL ROPE.
MINIMUM DEPTH OF 24" BELOW GRADE.SCHEDULE 40 (UNLESS NOTED OTHERWISE) AT AALL UNDERGROUND CONDUITS SHALL BE PVC
C.
3.
EXERCISED IN EXECUTING THE WORK SO AS TO SECUREAS CLOSELY AS POSSIBLE. PROPER JUDGMENT MUST BEOUTLETS, EQUIPMENT, ETC., AND ARE TO BE FOLLOWEDLOCATIONS OR ARRANGEMENTS OF CONDUIT RUNS,
LISTED LABEL AND MAY BE USED WHERE PERMITTEDFLEXIBLE METALLIC CONDUIT SHALL HAVE U.L.
INTERIOR RUNS.
4.
B.
CONDITIONS ENCOUNTERED.
CHANGES SHALL BE MADE WITHOUT COST, PROVIDINGREARRANGEMENT OF FURNISHINGS OR EQUIPMENT, SUCHCONDITIONS IN THE BUILDING CONSTRUCTION ORARRANGEMENTS ARE NECESSARY, DUE TO FIELDIN THE EVENT CHANGES IN THE INDICATED LOCATIONS OR
SPACE LIMITATIONS OR INTERFERENCE OF STRUCTURESPACE AND TO OVERCOME LOCAL DIFFICULTIES DUE TO
VERIFY EXACT ROUTING OF ALL EXPOSED CONDUITRIGHT ANGLES TO CEILING, FLOOR OR BEAMS.CONDUIT INDICATED SHALL RUN PARALLEL OR ATCEILING OR WALLS UNLESS INDICATED OTHERWISE.CONDUIT RUNS MAY BE SURFACE MOUNTED IN
SHALL HAVE FULL SIZE GROUND WIRE.ALL CONDUIT IN EXCESS OF SIX FEET IN LENGTH"SQUEEZE" TYPE. SEAL TIGHT FLEXIBLE CONDUIT.BY CODE. FITTINGS SHALL BE "JAKE" OR
THE BEST POSSIBLE INSTALLATION IN THE AVAILABLE
C.
CONSTRUED AS TO PERMIT WORK NOT CONFORMING TO THE
FEEDERS AND BRANCH CIRCUIT WIRING INSTALLED IN A
WORK".
E. WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS
C. ALL BROCHURES, OPERATING MANUALS, CATALOG, SHOP
AT JOB COMPLETION.
1.B. CONDUIT:
2.
I.
H.
BEFORE CONSTRUCTION.
EQUIPMENT LOCATION
PERMITS AND PAY ALL REQUIRED FEES.CONTRACTOR SHALL SECURE ALL NECESSARY BUILDING
FURNISHED, INSTALLED AND CONNECTED IN PLACE."PROVIDE": INDICATES THAT ALL ITEMS ARE TO BE
ARCHITECT/ENGINEER FOR CLARIFICATION OR CORRECTIONDRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THEANY ERROR, OMISSION OR DESIGN DISCREPANCY ON THE
ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE.
LABEL, FITTINGS SHALL BE COMPRESSIONELECTRICAL METALLIC TUBING SHALL HAVE U.L.
HUNTS WRAP PROCESS NO. 3.WITH EARTH SHALL BE 1/2 LAPPED WRAPPED WITHBUILDING EXTERIOR, RIGID CONDUIT IN CONTACTROADWAYS, IN MASONRY WALLS OR EXPOSED ONSLABS, IN CONTACT WITH THE EARTH, UNDER PUBLICUSED WHEN INSTALLED IN OR UNDER CONCRETEZINC COATED WITH ZINC INTERIOR AND SHALL BERIGID CONDUIT SHALL BE U.L. LABEL GALVANIZED
LISTED AND LABELED.THE NEC, ANSI, NEMA, AND THEY SHALL BE U.L.
DRAWINGS, ETC., SHALL BE TURNED OVER TO OWNER
2.
J.
A.
11.
B.
PROJECT CLOSEOUT
A.
8.
B.
F.
BUILDING ELECTRICAL SYSTEM.
AND ARCHITECT/ENGINEER.
MANAGER IN ADVANCE. MINIMIZE DOWNTIME ON THEOUTAGE OF SERVICE WITH THE OWNER AND BUILDINGPROGRESS OF THE WORK WILL PERMIT. ARRANGE ANYCOMPLETE THE ENTIRE INSTALLATION AS SOON AS THE
FINAL ACCEPTANCE IN A MANNER ACCEPTABLE TO OWNERMATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TOIMPORTANT AS THE OPERATION. DEFECTIVE OR DAMAGED
A.
9.
OWNER, ANY DEFECTIVE MATERIAL AND EQUIPMENT WITHINORDER. REPLACE, WITHOUT ADDITIONAL COST TO THECONTRACT SHALL BE DELIVERED IN PROPER WORKINGTHE ENTIRE ELECTRICAL SYSTEM INSTALLED UNDER THIS
ALL MATERIALS SHALL BE NEW, CONFORMING WITH
SERVING UTILITIES.SERVICE INFORMATION WILL BE FURNISHED BY THEVERIFY SERVICE LOCATIONS AND REQUIREMENTS.SERVING UTILITY COMPANIES. CONTRACTOR SHALLSHALL CONFORM TO THE REQUIREMENTS OF THETELEPHONE AND ELECTRICAL METERING FACILITIES
UTILITY COMPANIES.CONFORM TO ALL REQUIREMENTS OF THE SERVING
PRODUCTS
UTILITY SERVICE
DIMENSIONS, ROUTINGS AND CIRCUITS.THE COMPLETION OF THE JOB, SHOWING ACTUALCOMPLETE ELECTRICAL "AS INSTALLED" DRAWINGS ATPROVIDE PROJECT MANAGER WITH ONE SET OF
COMPLETE AND UNDAMAGED CONDITION.RESULTING FROM WORK AND LEAVE WORK IN APROJECT MANAGER. CLEAN PREMISES OF ALL DEBRISTESTS FOR APPROVAL. SUBMIT TEST REPORTS TOSHORT CIRCUIT, AND FALL POTENTIAL GROUNDINGUPON COMPLETION OF WORK, CONDUCT CONTINUITY,
G.
GROUND
THE EXTENT OF THE WORK IS INDICATED BY THE
CONDUCTORS SHALL BE #2 STRANDED,
ETC., IT MUST BE CLEARLY UNDERSTOOD THAT TENDONS
C.DRAWINGS, SCHEDULES, AND SPECIFICATIONS AND IS
THHN (GREEN) INSULATION.
D.
E.
OF THE C.B.C.
TENDONS.
H.
G.
I.5
D.
MATERIAL AND LABOR.AND OPERATIONAL SYSTEM, WHICH INCLUDES THE COST FORTHE CONTRACTOR SHALL PREPARE A BID FOR A COMPLETE
SUCCESSFUL OPERATION OF ALL SYSTEMS.MENTIONED OR SHOWN WHICH ARE NECESSARY FORTHE COMPLETION OF ALL ELECTRICAL WORK NOTELECTRICAL SYSTEM. THE WORK SHALL ALSO INCLUDENECESSARY FOR A COMPLETE AND OPERATIONALALL LABOR, EQUIPMENT, MATERIALS AND SUPPLIESCONTRACT. THE WORK SHALL CONSIST OF FURNISHING
PAINT AT ALL GROUND CONNECTIONS SHALL BE REMOVED.
ONE COMPLETE SET OF PRINTS SHOWING "INSTALLEDSUBMIT TEST REPORTS AND FURNISH TO SMART SMRMETHODS FOR REDUCING THE RESISTANCE VALUE.NOTIFY THE OWNER FOR FUTURE INSTRUCTION ON
OHMS. IF THE RESISTANCE VALUE IS EXCEEDED,GROUNDING SYSTEM RESISTANCE SHALL NOT EXCEED
CONNECTORS EXCEPT WHERE NOTED OTHERWISE."HYGROUND" COMPRESSION SYSTEM BURNDYALL GROUND CONNECTIONS SHALL BE MADE WITH
SUBJECT TO THE TERMS AND CONDITIONS OF THE
CUT OR DAMAGED UNDER ANY CIRCUMSTANCES.AND/OR REINFORCING STEEL WILL NOT BE DRILLED INTO,
STOPPED IN ACCORDANCE WITH THE REQUIREMENTSPENETRATIONS IN FIRE RATED WALLS SHALL BE FIRE
ACCURATELY LOCATE THE REINFORCING AND/OR STEELEQUIPMENT VIA X-RAY OR OTHER DEVICES THAT CANSEARCHED FOR BY APPROPRIATE METHODS ANDARE NOT DEFINITELY KNOWN AND THEREFORE, MUST BELOCATION OF TENDONS AND/OR REINFORCING STEEL
B.
C.
BEFORE CORING.
D.GROUND
F.
E.
CONTINUITY.
B.
TO COMPLY WITH THIS PROVISION.
WHICH ARE AFFECTED.
THE CONTRACTOR ASSUMES ALL LIABILITY FOR FAILUREIMMEDIATELY UPON DISCOVERY OF ANY DISCREPANCIES.CONDITIONS AND SHALL NOTIFY THE ARCHITECTBIDDING AND CONSTRUCTION TO VERIFY ALL EXISTINGTHE CONTRACTOR SHALL MAKE A SITE VISIT PRIOR TO
IN WRITING AND CEASE WORK ON PARTS OF THE CONTRACTCONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECTMAKE THE WORK COMPLY WITH THESE REQUIREMENTS, THENECESSARY IN THE DRAWINGS OR SPECIFICATIONS TOMOST STRINGENT OF THESE CODES. SHOULD CHANGES BE
ALL NON-DIRECT BURIED TELEPHONE EQUIPMENT
COPPER AND ANNEALED #2 UNLESS NOTED OTHERWISE.ALL GROUNDING CONDUCTORS SHALL BE SOLID TINNED
GROUND ROD AND DESCRIBED TERMINATIONS.SYSTEM COMPLETE WITH CONDUCTORS,
REFER TO GROUND BUS DETAILS. PROVIDE NEW
CONNECTED AT BOTH ENDS TO MAINTAIN ELECTRICALTHE GROUND CONDUCTOR SHALL BE PROPERLYGROUNDING CONDUCTOR HAVING GREEN INSULATION.NONMETALLIC CONDUIT SHALL INCLUDE A CODE SIZED
THROUGH THE FLOOR FOR CONDUIT RUNS, PIPE RUNS,FASTENING OR ANCHORING PURPOSES, OR PENETRATIONSIN DRILLING HOLES INTO CONCRETE WHETHER FOR
OBTAIN PERMISSION FROM THE ARCHITECT/ENGINEEREQUIPMENT SHALL BE REPAIRED BY THE CONTRACTOR.AND ROOFS. ANY DAMAGE TO BUILDING STRUCTURE ORCUTTING OR DRILLING OF WALLS, FLOORS CEILINGS,LAYOUT IN ADVANCE TO ELIMINATE UNNECESSARYCUTTING, PATCHING, CHASES, OPENINGS: PROVIDE
AND LEVELING OF ALL DEVICES AND FIXTURES.LOCAL CODE REQUIREMENTS. PROVIDE PRIOR ALIGNMENTHORIZONTAL FORCES IN ACCORDANCE WITH STATE AND
A.
10. INSTALLATION
B.SHALL
GENERAL REQUIREMENTS
NOTHING IN THESE PLANS OR SPECIFICATIONS SHALL BEELECTRIC CODE AND ALL STATE AND LOCAL CODES.THE LATEST RULES AND REGULATIONS OF THE NATIONALALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH
EFFECTIVE ELECTRICAL CONTINUITY.BE METALLICALY JOINED TOGETHER TO PROVIDE
CONDUITS CONNECTED TO EQUIPMENT AND DEVICES
EQUIPMENT SHALL BE BRACED TO WITHSTANDLUMINARIES FROM UNDERSIDE OF STRUCTURAL CEILING,EQUIPMENT, FIXTURES, BOXES, PANEL, ETC., SUPPORTPROVIDE SUPPORTING DEVICES FOR ALL ELECTRICAL
1.
A.
8. APPLETON EMERGENCY GENERATOR PLUG AT 36" A.F.F. CONTRACTOR TO VERIFY EXACT LOCATION WITH LANDLORD AND UTILITY COORDINATOR.
9. PLACE "TRUE TAPE" AND PULL ROPE IN THE CONDUITS AS REQUIRED.
6. ALL WIRING SHALL BE COPPER 75° C U.N.O.
7. CONDUIT REQUIREMENTS (TYP., U.N.O.): UNDERGROUND: PVC (SCHED 40 OR 80) INDOOR: EMT (RGS IN TRAFFIC AREAS) OUTDOOR (ABOVE GRADE): RGS.
3. NOT USED
4. PROVIDE A MIN. 36" WORK CLEARANCE IN FRONT OF PANELS/SERVICE EQUIP.
5. ALL BREAKERS IN THE ELEC. PANEL ARE RATED 10,000 RMS SYMMETRICAL AMPS, 240V MAX. 75° C.
1. SERVICE POWER SHALL BE 200A, 1�, 3W. 120/208 OR 120/240V.
2. UTILITY RECEPTACLE IS A GFCI DUPLEX OUTLET INSTALLED IN THE DEADFRONT OF PPC.
SAFETY
SECONDARY
SURFACESWITCH
SOFT DRAWN BARE COPPER
SOLID NEUTRAL
TYPICAL
WITH
VOLTVOLT ALTERNATING CURRENTWATT OR WIRE
UNDERWRITER'S LABORATORY INC.UNDERGROUND
TELEPHONE
TRANSFERWITHOUT
CROSS-LINK POLYETHYLENETRANSFORMER
MANUFACTURER
MOUNTEDMOUNTING
NEUTRAL
MINIMUMMAIN LUGS ONLY
W
V
OVERHEAD
PHASEPANELBOARD
POLEPERSONALCOMMUNICATION SYSTEM
NATIONAL ELECTRICALMANUFACTURERS ASSOC.
NEW
MFR
MLO
MTG
N
MTD
MIN
NEMA
OH
PCS
PH
P
(N)
PNLBD
RECEPTACLEPOWERPRIMARY
RIGID GALVANIZED STEEL
POWER PROTECTION CABINETPRIMARY RADIO CABINET
PPCPRC
RCPTPWRPRI
RGS
W/OXFER
XLPEXFMR
TEL
VAC
W/
TYP
U.L.U/G
SDBC
SURF
SEC
SW
S.N.
SAFELEC
ENCL
FACF/A
EXIST
EMT
FT
GGEN
FU
GPSGR
GND
GFCI
FLUOR
A
AIC
ACCA
AT
BDBR
AWG
CCAB
BTSBTCWBRKR
APPROX
AMPERE
BRANCH
BARE TINNED COPPER WIRE
APPROXIMATELY
AMERICAN WIRE GAGEAMPERE TRIP
AMPERE INTERRUPTINGCAPACITY
BREAKER
ANTENNA CABLE COVER ASSEMBLY
CONDUITCABINET
BASE TRANSMISSION SYSTEM
BOARD
HDBCHPS
LPSMAX
LG
MECH
CBCKT
DEM(E)
CONTCIRCUIT
DEMANDEXISTING
CIRCUIT BREAKER
CONTINUOUS
HARD DRAWN COPPER WIRE
LOW PRESSURE SODIUM
MECHANICALMAXIMUM
HIGH PRESSURE SODIUMLENGTH
FLUORESCENT
FUSE
GENERATORGROUND FAULT CIRCUITINTERRUPTER
GROUND
FOOT/FEET
GLOBAL POSITIONING SYSTEMGROWTH
GROUNDING
ELECTRICAL METALLIC TUBINGELECTRICAL
ENCLOSURE
FIRE ALARMFACTOREXISTING
UNLESS NOTED OTHERWISEU.N.O.
EGR EMERGENCY GEN. RECEPTACLE
MANUAL TRANSFER SWITCHMTS
BATT BATTERY
LIGHTING FIXTURE, 1/175W. METAL HALIDE, HUBBELL CAT#MIC-0175H-336
5/8" X 10'-0" ,CU. GND ROD 30" MIN. BELOW GRADE.
CADWELD CONNECTION
CIRCUIT BREAKER
MECHANICAL CONNECTION
HALO GROUND CONNECTION
STEPDOWN TRANSFORMER
UTILITY METER BASE
TRANSFORMER
RECEPTACLE, 2P-3W-125V-15A, DUPLEX, GROUND TYPE,HUBBEL CATALOG #5362
TOGGLE SWITCH, 1P-120V-15A, "WP"
TOGGLE SWITCH, 1P-125V-15A, HUBBELL CATALOG #HBL1201CN
CHEMICAL GROUND ROD (XIT GROUND ROD)
5/8" X 10'-0" ,CU. GND ROD IN TEST WELL 30" MIN. BELOWGRADE.
POLE
(N) POLE MOUNTED XFMER
(E) POLE MOUNTED XFMR
(E) PAD MOUNTED XFMER
(N) PAD MOUNTED XFMER
IONIZATION SMOKE DETECTOR W/ALARM HORN & AUXILIARYCONTACT, 120 VAC, GENTEX PART NO. 7100F
POWER RUN
TELCO RUN
POWER/TELCO RUN
LIGHTING FIXTURE, HIGH PRESSURE SODIUM, 1/70W, WALLMOUNTING TYPE, HUBBELL LIGHTING CATALOG #NRG-307OR 1/50W, HUBBELL LIGHTING CATALOG #NRG-121
LIGHTING FIXTURE, INCANDESCENT, 1/100W, WALLMOUNTING TYPE, HUBBELL LIGHTING CATALOG#BRH-100-06-1
MOTOR OUTLET
EMERGENCY LIGHTING, 2/50W, HUBBELL LIGHTING CATALOG#HE6-50-2-R91
EXIT SIGN, THERMOPLASTIC LED, SINGLE FACE, UNIVERSALMOUNTING, W/BATTERY PACK, HUBBELL LIGHTING CATALOG #PRB
COMBINATION, EXIT SIGN & EMERGENCY LIGHTING,HUBBELL LIGHTING CATALOG #PRC
MANUAL TRANSFER SWITCH, 2P-240V-200A, NO FUSE,NEMA 3R ENCLOSURE
LIGHTING FIXTURE, FLUORESCENT, 10.94" x 4'-0", 2/40W,SURFACE MOUNTING TYPE, HUBBELL LIGHTING CATALOG#WSW232T
LIGHTING FIXTURE, FLUORESCENT, 10.94" x 8'-0", 2/95W,SURFACE MOUNTING TYPE, HUBBELL LIGHTING CATALOG#TWSM232T
FUSE, SIZE AND TYPE AS INDICATED.
SAFETY SWITCH, 2P-240V-60A W/60A FUSES, NEMA 3RENCLOSURE, SQ D CATALOG NO. H222NRB
GROUNDING CONDUCTOR
GROUNDING CONDUCTOR
CONDUIT UNDERGROUND
SUBMIT SHOP DRAWINGS TO THE ARCHITECT FOR APPROVALWITHIN 35 DAYS OF AWARD OF CONTRACT, SHOP DRAWINGSSHALL BE SUBMITTED IN A COMPLETE BOUND MANUALINCLUDING LIGHT FIXTURES, SERVICE METERING, TRANSFERSWITCH, PANELBOARD, AND DISCONNECT SWITCHES. THECONTRACTOR SHALL VERIFY DIMENSIONS OF EQUIPMENT TOINSURE THAT THEY FIT IN THE DESIGNATED AREA AND COMPLYWITH REQUIREMENTS OF ALL APPLICABLE CODES FORREQUIRED WORKING CLEARANCES ABOUT ELECTRICALEQUIPMENT PRIOR TO SUBMITTING SHOP DRAWINGS FORAPPROVAL. DEPARTURE FROM THE ABOVE WILL RESULT INRE-SUBMITTAL AND DELAYS.
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
36:0
6 A
M
E-1
RSJS
08/27/14
ELECTRICAL SPECS,NOTES, LEGEND &ABBREVIATIONS
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
SIDEWALK LEVEL0' - 0"
EXISTING UTILITY WOOD POLE
NEW 2"Ø SCH. 80 PVC POWERCONDUIT WITH WEATHER HEAD,PAINTED MESA BROWN
NEW VERIZON WIRELESS DUAL PHASEAMPHENOL CWD070X06 ANTENNAMOUNTED TO A NEW JPAK#AM-100-02. PAINTED MESA BROWN
NEW VERIZON WIRELESSJ-PAK-AM-200-02 ANTENNA BRACKETMOUNT PAINTED MESA BROWN
NEW 2"Ø SCH. 80 PVC COAXCONDUIT, PAINTED MESA BROWN
NEW VERIZON WIRELESS RRUSMOUNTED TO EXISTING UTILITY WOODPOLE, TYP. (TOTAL OF 2)
NEW PG&E SHUTDOWN SWITCHPAINTED MESA BROWN
NEW VERIZON WIRELESS ELECTRICALMETER MOUNTED TO NEWJPAK-EM-100-06 STANDOFF BRACKETON EXISTING WOOD POLE. PAINTEDMESA BROWN
NEW VERIZON WIRELESSJPAK-EM-100-06 STANDOFF BRACKETTHRU BOLTED TO EXISTING WOODUTILITY POLE PAINTED MESA BROWN
NEW VERIZON WIRELESS GPS ANTENNAMOUNTED TO NEW PACKJPAK-EM-100-06
NEW GROUND BUSS BAR MOUNTED TONEW JPAK #EM-100-06
NEW VERIZON WIRELESS ELECTRICALMETER MOUNTED TO NEWJPAK-EM-100-06 STANDOFF BRACKETON EXISTING WOOD POLE. PAINTEDMESA BROWN
NEW GROUND BUSS BAR MOUNTED TONEW JPAK #EM-100-06
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
36:0
9 A
M
E-2
RSJS
08/27/14
ELECTRICAL GROUNDDIAGRAMS
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
#2 SOLID TO BE CAD WELDED
10' GROUND ROD 18" MIN. COVER.COVER WITH WOOD MOULDING.
NEW MECHANICAL CRIMPEDCONNECTION TYP. PERMANUFACTURER'SRECOMMENDATIONS ANDUTILIZING PROPER CRIMPDEVICE
NEW #2 SOLID GROUND WIRE RUN IN WOODMOULDING WITH GALV. STEEL STRAPSAT 3'-0" MAX. O.C. PER PG&E STANDARDS(LOCATE NEAR EXISTING POWER GROUNDWIRE IF PRACTICAL) CRIMP TO BUSS BAR
#2 SOLID TO BE CAD WELDED
10' GROUND ROD 18" MIN. COVER.COVER WITH WOOD MOLDING.STRAP WITH GALVANIZED U NAILS.
NEW #2 SOLID GROUND WIRE RUN IN WOODMOULDING WITH GALV. STEEL STRAPSAT 3'-0" MAX. O.C. PER PG&E STANDARDS(LOCATE NEAR EXISTING POWER GROUNDWIRE IF PRACTICAL) CRIMP TO BUSS BAR
10' GROUND ROD 18" MIN. COVER.COVER WITH WOOD MOLDING.STRAP WITH GALVANIZED U NAILS.
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14
2 EQUIPMENT GROUNDING DIAGRAM 1 GROUNDING PLAN
SINGLE LINE DIAGRAM
NG
NOTES:
1. SUBCONTRACTOR SHALL PROVIDE METER WITH DIST. PANEL ANDBREAKERS FOR POWER TO THE BTS UNITS AND THE BTS/UTILITYCABINET.
2. ALL SERVICE EQUIPMENT AND INSTALLATIONS SHALL COMPLYWITH THE N.E.C. AND UTILITY COMPANY AND LOCAL CODEREQUIREMENTS.
3. SUBCONTRACTOR SHALL PROVIDE ELECTRICAL SERVICEENTRANCE EQUIPMENT WITH FAULT CURRENT RATINGS GREATERTHAN THE AVAILABLE FAULT CURRENT FROM THE POWER UTILITY.
4. FIELD ROUTE CONDUIT TO CABINETS AS REQUIRED.
5. MAXIMUM ONE WAY CIRCUIT RUN NOT TO EXCEED 75 FEET.
1. POWER AND TELCO POINTS OF CONNECTION AND ANY EASEMENTSARE PRELIMINARY AND SUBJECT TO CHANGE BY THE UTILITYCOMPANIES.
2. CONTRACTOR SHALL COORDINATE WITH UTILITY COMPANY FORFINAL AND EXACT WORK/MATERIALS REQUIREMENTS ANDCONSTRUCT TO UTILITY ENGINEERING PLANS AND SPECIFICATIONSONLY WHERE APPLICABLE PER PROJECT SCOPE OF WORK.
3. CONTRACTOR SHALL FURNISH AND INSTALL CONDUIT, PULL WIRES,CABLE PULL BOXES, CONCRETE ENCASEMENT OF CONDUIT,TRANSFORMER PAD, BARRIERS, POLE RISER TRENCHING, BACK FILL,AND UTILITY FEES, AND INCLUDE REQUIREMENTS IN SCOPE.
4. CONTRACTOR SHALL LABEL ALL MAIN DISCONNECT SWITCHES ASREQUIRED BY CODE.
POWER AND TELCO NOTES:
RRUS
M
#2 AWG GND IN 2" SCHEDULE 80CONDUIT TO NEW 5/8" Ø x 10'
GROUND ROD PER N.E.C.ARTICLE 250
EXISTING POWER POLE120/240V 3W, 1PH
2"C SCHEDULE 80 PVC CONDUIT WITHPULL ROPE, RUN UP (E) POLE OR ASSPECIFIED BY UTILITY
ELECTRICAL
POWER
20A
EXISTING POWER POLE120/240V 3W, 1PH
(2) #12AWG (MIN), + (1)# 10AWG GND IN 2 " SCHEDULE80 CONDUIT. SEE NOTES 1&5
TO TELCO SOURCEPER PLAN
GENERAL ELECTRICAL NOTES:
1. PROVIDE ALL ELECTRICAL WORK & MATERIALS AS SHOWN ON THE DWGS, AS CALLED FOR HEREIN, & AS IS NECESSARY TO FURNISH A COMPLETEINSTALLATION.
2. THE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE CURRENT ADOPTED CALIFORNIA ELECTRICAL CODE, STATE OF CALIFORNIATITLE24, ALL OTHER APPLICABLE CODES AND ORDINANCES & THE REQUIREMENTS OF THE FIRE MARSHALL. ALL EQUIPMENT & WIRING SHALL BEARTHE APPROVAL STAMP OF UNDERWRITERS LABORATORY (UL) OR AN APPROVED TESTING LABORATORY, PAYMENT FOR ALL INSPECTION FEES ANDPERMITS ARE PART OF THIS CONTRACT.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY AND GOOD CONDITION OF ALL MATERIALS & EQUIPMENT FOR THE ENTIREINSTALLATION & UNIT COMPLETION OF WORK, ERECT & MAINTAIN APPROVED & SUITABLE BARRIERS, PROTECTIVE DEVICES & WARNING SIGNS, BEFULLY RESPONSIBLE FOR ANY LOSS OR INJURY TO PERSONS OR PROPERTY RESULTING FROM NEGLIGENCE AND/OR ENFORCEMENT OF ALL SAFETYPRECAUTIONS & WARNINGS.
4. COORDINATE THE ELECTRICAL INSTALLATION WITH ALL OTHER TRADES.
5. ALL SAW CUTTING, TRENCHING, BACK FILLING & PATCHING SHALL BE PART OF THIS CONTRACT.
6. FINALIZE ALL ELECTRICAL SERVICE ARRANGEMENTS, INCLUDING VERIFICATION OF LOCATIONS, DETAILS, COORDINATION OF THE INSTALLATION &PAYMENT OF ACCRUED CHARGES WITH LOCAL POWER COMPANY, VERIFY LOCATION FOR FACILITIES & DETAILS WITH POWER UTILITY, IN ADDITIONTO THE REQUIREMENTS SHOWN IN THE CONTRACT DOCUMENTS, WORK SHALL COMPLY WITH CONSTRUCTION STANDARDS & SERVICEREQUIREMENTS OF THE RESPECTIVE UTILITIES, INCLUDING ANY SUPPLEMENTAL DWGS ISSUED & SHALL BE SUBJECT TO APPROVAL OF THESE UTILITIES.
7. ALL WIRING SHALL BE COPPER. INSULATION FOR BRANCH CIRCUIT CONDUCTORS SHALL BE TYPE "THWN" CONDUCTORS LARGER AND #6 AWGMAY BE TYPE "THWN" OR "TWN".
8. PROVIDE CONDUIT SEALS FOR ALL CONDUITS PENETRATING WEATHERPROOFING OR WEATHERPROOF ENCLOSURE ENVELOPE. MASTIC SEAL ALLCONDUIT OPENING PENETRATIONS COMPLETELY WATERTIGHT.
9. UNLESS SHOWN OTHERWISE, FUSED DISCONNECT SWITCHES SHALL BE PROVIDED WITH LOW-PEAK, S\DUAL ELEMENT FUSES SIZED TO EQUIPMENTNAMEPLATE FUSE CURRENT RATING. MOTOR STARTERS SHALL BE PROVIDED WITH SIMILARLY SIZED FUSIBLE ELEMENTS, SWITCHES AND OTHEROUTDOOR EQUIPMENT SHALL BE RATED NEMA 3R AND/OR UL LISTED FOR WET ENVIRONMENT.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING THE GROUNDING SYSTEM AND ENSURING A 5 OHM OR LESS GROUNDING PATH,ADDITIONAL GROUND RODS AND/OR CHEMICAL ROD SYSTEM SHALL BE USED TO ACHIEVE THIS REQUIREMENT IF THE GIVEN DESIGN CANNOT BEMADE TO ACHIEVE THIS REQUIREMENT.
(N) VZW100A, 120/240V, 1 PH, 3W, 42 KAICMETER WITH TEST BYPASS SWITCH, 100AMAIN AND LOAD DIST. PANEL (SEE NOTE#1) [METERING EQUIP. TYPE TO BE UTILITYAND EURSA APPROVED EQUIPMENT]
LOAD CALCULATIONS - VERIZON WIRELESS
EXISTING LOAD: 0 AMPSNEW LOAD: 10.0 AMPS MAX.
NEW TOTAL LOAD: 10.0 AMPS MAX.
POWER AND TELCO DESIGN IS BASED ON INITIALSITE VISIT.
CONTRACTOR SHALL OBTAIN CURRENT UTILITYCOORDINATOR PLANS PRIOR TO START OFCONSTRUCTION.
AVAILABLE FAULT CURRENT PER UTILITY.
NOTE: CONTRACTOR TO CHECK WITH UTILITY TOENSURE ELEC. METER IS BRACED FOR ACTUAL FAULTCURRENT.
RRUS (2) #12AWG (MIN), + (1)# 10AWG GND IN 2 " SCHEDULE80 CONDUIT. SEE NOTES 1&5
100A2P
20A
TYPE VB
TYPE VS
TYPE GL LUGTYPE XA TYPE GR
TYPE PG
TYPE LJ TYPE HA
TYPE GT
TYPE SS TYPE TA
TYPE PC TYPE RR
TYPE NDTYPE NX1
TYPE GY TYPE NC
TYPE PH TYPE GR
2
3/4"
1
5
7/16"
1"
2"
3
4
1. GALVANIZED STEEL GROUND BAR, HOLE CENTERS TO MATCH NEMADOUBLE LUG CONFIGURATION. (ACTUAL GROUND BAR SIZE WILL VARYBASED ON NUMBER OF GROUND CONNECTIONS)
2. INSULATORS, NEWTON INSTRUMENT CAT. NO. 3061-4 OR APPROVED EQUAL
3. 5/8" LOCK WASHERS, NEWTON INSTRUMENT CO., CAT. NO. 3015-8 ORAPPROVED EQUAL
4. WALL MOUNTING BRACKET, NEWTON INSTRUMENT CO., CAT NO. A-6056OR APPROVED EQUAL
5. 5/8-11 X 1" HHCS BOLTS, NEWTON INSTRUMENT CO., CAT NO. 3012-1 ORAPPROVED EQUAL
6. INSULATORS SHALL BE ELIMINATED WHEN BONDING DIRECTLY TOTOWER/MONOPINE STRUCTURE. CONNECTION TO TOWER/MONOPINESTRUCTURE SHALL BE PER MANUFACTURERS RECOMMENDATIONS.
NOTES:
2.
3.
1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECTGROUND WIRE DOWN TO GROUND BAR.
GROUNDING KIT SHALL BE TYPE AND PART NUMBER AS SUPPLIED ORRECOMMENDED BY CABLE MANUFACTURER.
WEATHER PROOFING SHALL BE (TYPE AND PART NUMBER AS SUPPLIEDOR RECOMMENDED BY CABLE MANUFACTURER.)
ANTENNA CABLE
CABLE GROUND KIT
WEATHERPROOFING KIT (SEE NOTE 3)
#6 AWG STRANDED COPPERGROUND WIRE (GROUNDEDTO GROUND BAR) (SEE NOTE1 & 2)
NOTES:
12" TO 24"
2 11
/16"
DIA
. MA
X.
(E) POLE(N) GROUNDING CONDUITOR HALF ROUND
UNDISTURBED SOIL
CADWELD
3" 0 CORE DRILL FORGROUND ROD
5/8" COPPER CLADSTEEL GROUND ROD
RESTORE SURFACE TOORIGINAL CONDITION
NOTES:
1. IF GROUND ROD ISINSTALLED IN SIDEWALK AREA,CORE DRILL SIDEWALK PRIORTO INSTALLING INSPECTIONWELL.
2. EXPOSED CONCRETE TOHAVE BROOM FINISH.
/
14 GA. HOT DIP GALV.CONDUIT STRAP
PVC CONDUIT RISER. SIZEAS PER DWGS
0.281" DIA. HOLE
14 GA. HOT DIP GALV.CONDUIT STRAP
GALV. LAG SCREW TOWOOD POLE
PVC CONDUIT RISER. SIZEAS PER DWGS
SECTION
ELEVATION
1"
.75"
.12"
Date
Drawn By
Checked By
Verizon Wireless2785 Mitchell Drive
Suite 9Walnut Creek, CA 94598
V-ONE DESIGN5100 CLAYTON ROAD, B-1 SUITE 354
CONCORD CA 94521
Client:
Design Firm:
Drawing Phase:
Site:
PROFESSIONAL SEAL:
it is a violation of law for any person, unlessthey are acting under the direction of a
licensed professional Architect/Engineer toalter this document.
149 NATOMA STREET, 3RD FLOORSAN FRANCISCO, CA 94105
8/27
/201
4 9:
36:1
0 A
M
E-3
RSJS
08/27/14
ELECT. SINGLE-LINEDIAGRAM & DETAILS
SF LM PH2 SC120(NEAR) 30 DORE ST.
SAN FRANCISCO, CA 94103302036
PG&E DORE STREET
100% CONSTRUCTION DRAWINGS
1 EXOTHERMIC WELD CONNECTION1
2 BUSS BAR1
3 CONN. OF CABLE GND. KIT TO ANT.1
4 POLE GROUNDING ROD
5 POLE CONDUIT STRAP
No. Description Date1 90% CD DRAWINGS 08/12/142 100% CD DRAWINGS 08/27/14