VENTURI FX - Antec Controls · 2019-05-20 · The Antec Controls Venturi FX is designed...
Transcript of VENTURI FX - Antec Controls · 2019-05-20 · The Antec Controls Venturi FX is designed...
VFXVENTURI FX
The Antec Controls Venturi FX is designed specifically for room pressure control and laboratory applications.
Paired with the maintenance-free, high accuracy Antec Controls Pressure Transducer (PTX) and an actuator,
the VFX achieves precise airflow measurement and control for critical environments.
During operation, the Venturi FX measures flow using ports installed non-invasive to the airflow stream, greatly
reducing the risk of lint or other airborne particulates interfering with the control or accuracy of the valve. In
addition, the Venturi FX will operate at low pressure drop while achieving a 10:1 turndown ratio. Each valve is
factory verified on NVLAP accredited airflow calibration stations (NVLAP Lab Code 201067-0 complying with
ISO/IEC 17025:2005) using N.I.S.T traceable equipment to ensure dependable and repeatable valve accuracy.
Actuator
Precision Damper
Ports are downstream of the airflow direction allowing for non-invasive
airflow measurement
Maintenance-free High Accuracy PTX Transducer
2 For more information visit www.AntecControls.com | v200
VFX Venturi FX
TYPICAL APPLICATIONSThe Venturi FX airflow control
valve is designed specifically
for precision room pressure and
fume hood control applications.
FEATURES + Controlled accuracy within +/-5% of
measured airflow when using Antec Controls
+ High Speed or Standard Speed actuation
+ Closed loop airflow measurement
+ No straight duct inlet requirements
OPTIONS & ACCESSORIESSee Valve & Accessories Section for details
+ Actuator Options
+ Insulation Options
+ Connection Options
- Slip
- Flanged
+ Connection Accessories
- Drawband Clamps
- Companion Flanges
+ Hot Water Coils
+ Electric Coils
+ Silencers
SPECIFICATIONSOperation
Temperature Rating 0 – 50°C (32 – 120°F)
Humidity Rating 10 – 95% RH non-condensing
Electrical • 24 VAC power, 1 VA, Class 2• Dual 0-10VDC analog outputs• Transducer accuracy: 3% of reading• Transducer range: 0-2 in.w.c.
Specifications subject to change without notice
PRESSURE TRANSDUCER (PTX)The Antec Controls Pressure Transducer (PTX) is a compact
differential pressure output module that utilizes a high accuracy
sensor for measuring pressure. The flow-through, non-
invasive digital sensor allows for maintenance-free pressure
measurement. This device is used with the innovative Antec
Controls flow measuring station that is the least susceptible to
contamination in the market.
3v200 | For more information visit www.AntecControls.com
VFX Venturi FX
OPERATIONAL FLOWUnit Size Minimum Flow (CFM) Maximum Flow (CFM)
108 80 800
110 120 1300
112 180 1800
114 250 2500
212 360 3600
214 500 5000
STATIC PRESSURE RANGE
LEAKAGE RATES
Pres
sure
Dro
p, in
.w.c
.
Airflow, CFM2000 40001000
Size 108Size 110
Size 112
Size 114
Size 212
Size 214
3000 500000.00
0.10
0.05
0.15
0.20
0.25
0.30
0.40
0.35
Flow Pressure
Shut
off L
eaka
ge, C
FM
System Pressure, in.w.c.1.501.00 3.00.50
Size 212
Size 114
Size 108
Size 110
Size 112
Size 214
2.502.000.000.00
4.00
3.00
2.00
1.00
5.00
6.00
7.00
8.00
10.00
9.00
Tested in accordance to ASHRAE 130:2016
4 For more information visit www.AntecControls.com | v200
VFX Venturi FX
PROTECTIVE COATINGSDepending on the application, various coatings can
be applied to protect the operation of the valve.
Aluminum Aluminum valves are used in clean air or non-
corrosive applications. Features include:
+ Aluminum valve body construction
+ Galvanized steel damper with teflon gasket and zinc-plated damper shaft
+ Stainless steel pressure sensor ports and internal hardware
Phenolic Coating – Class 1Most fume hoods require a class 1 phenolic
coating.
Features include:
+ Phenolic coated valve body construction
+ Stainless steel damper with teflon gasket
+ Stainless steel damper shaft, pressure sensor ports and internal hardware
5v200 | For more information visit www.AntecControls.com
VFX Venturi FX
DIMENSIONAL DATASingle Valve
Unit SizeD L Weight
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
A
VENTURI FXVENTURI VALVE
WITH DAMPER CONTROL266850
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
2016/05/16OF REVSHEET 1 3© Copyright PRICE INDUSTRIES 2017
Sol
id E
dge
D -1/8" (3)
L
VENTURI FX
CONSTRUCTION NOTES: • VALVE BODY: 14 Ga ALUMINUM • DAMPER BLADE: 24 Ga GALVANIZED STEEL WITH POLYETHYLENE GASKET • DAMPER SHAFT: ZINC PLATED STEEL
VENTURI FX OPERATIONAL RANGE
1.50 (38)
H
W L
SINGLE VALVE
DUAL VALVE
*WEIGHTS ARE ± 5lbs (2kg) DEPENDING ON OPTIONS
*SEE SHEET 3 FOR DETAILED SLIP/FLANGED ENDS SPECIFICATIONS
MIN. AIRFLOW MAX AIRFLOW MIN. AIRFLOW MAX AIRFLOW
CFM (L/s) CFM (L/s) CFM (L/s) CFM (L/s)
8 80 (38) 800 (378) 212 360 (170) 3600 (1700)
10 120 (57) 1300 (614) 214 500 (236) 5000 (2360)
12 180 (85) 1800 (850)
14 250 (118) 2500 (1180)
UNIT EZIS TINUEZIS
DUAL VALVESINGLE VALVE
L H W WEIGHT*
in.(mm) in.(mm) in (mm) lb (kg)
212 27.00 (686) 13.250 (337) 26.250 (667) 40 (18)
214 30.00 (762) 15.250 (387) 30.250 (768) 45 (20)
UNIT SIZE
DUAL VALVE
D L WEIGHT*
in.(mm) in.(mm) lb.(kg)
8 8 (203) 23.50 (597) 19 (8.62)
10 10 (254) 21.75 (552) 20 (9.07)
12 12 (305) 27.00 (686) 22 (9.98)
14 14 (356) 30.00 (762) 24 (10.89)
UNIT SIZE
SINGLE VALVEin. in. lb.
108 8 23.5 19
110 10 21.75 20
112 12 27 22
114 14 30 24
Dual Valve
Unit SizeL H W Weight
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
A
VENTURI FXVENTURI VALVE
WITH DAMPER CONTROL266850
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
2016/05/16OF REVSHEET 1 3© Copyright PRICE INDUSTRIES 2017
Sol
id E
dge
D -1/8" (3)
L
VENTURI FX
CONSTRUCTION NOTES: • VALVE BODY: 14 Ga ALUMINUM • DAMPER BLADE: 24 Ga GALVANIZED STEEL WITH POLYETHYLENE GASKET • DAMPER SHAFT: ZINC PLATED STEEL
VENTURI FX OPERATIONAL RANGE
1.50 (38)
H
W L
SINGLE VALVE
DUAL VALVE
*WEIGHTS ARE ± 5lbs (2kg) DEPENDING ON OPTIONS
*SEE SHEET 3 FOR DETAILED SLIP/FLANGED ENDS SPECIFICATIONS
MIN. AIRFLOW MAX AIRFLOW MIN. AIRFLOW MAX AIRFLOW
CFM (L/s) CFM (L/s) CFM (L/s) CFM (L/s)
8 80 (38) 800 (378) 212 360 (170) 3600 (1700)
10 120 (57) 1300 (614) 214 500 (236) 5000 (2360)
12 180 (85) 1800 (850)
14 250 (118) 2500 (1180)
UNIT EZIS TINUEZIS
DUAL VALVESINGLE VALVE
L H W WEIGHT*
in.(mm) in.(mm) in (mm) lb (kg)
212 27.00 (686) 13.250 (337) 26.250 (667) 40 (18)
214 30.00 (762) 15.250 (387) 30.250 (768) 45 (20)
UNIT SIZE
DUAL VALVE
D L WEIGHT*
in.(mm) in.(mm) lb.(kg)
8 8 (203) 23.50 (597) 19 (8.62)
10 10 (254) 21.75 (552) 20 (9.07)
12 12 (305) 27.00 (686) 22 (9.98)
14 14 (356) 30.00 (762) 24 (10.89)
UNIT SIZE
SINGLE VALVE
in. in. in. lb.
212 27 13.25 26.25 40
214 30 15.25 30.25 45
See current submittals on www.AntecControls.com for complete dimensional data.
PERFORMANCE DATA See current information on www.AntecControls.com
6 For more information visit www.AntecControls.com | v200
VFX Venturi FX
Product Improvement is a continuing endeavour at Antec Controls by Price. Therefore, specifications are subject to change without notice.Consult your Sales Representative for current specifications or more detailed information. Not all products may be
available in all geographic areas. All goods described in this document are warranted as described in the Limited Warranty. The complete product catalog can be viewed online at AntecControls.com
® Antec Controls by Price is a registered trademark of Price Industries Limited. © 2019. Printed in Canada. v200