VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation &...

20
Installation & Service Manual DIP-PROOFING TECHNOLOGIES INC. LEADERS IN VOLTAGE-DIP PROOFING Voltage-Dip Compensators For VDC L4T & S4T series Models 120V / 208V / 220V / 230V 50/60Hz

Transcript of VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation &...

Page 1: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

DIP-PROOFINGTECHNOLOGIES INC.LEADERS IN VOLTAGE-DIP PROOFING

Voltage-Dip Compensators

For VDC L4T & S4T series Models120V / 208V / 220V / 230V 50/60Hz

Page 2: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 2 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

NoticeIMPORTANT SAFETY INSTRUCTIONS.SAVE THESE INSTRUCTIONS!

This manual contains important instructions that should be followed duringinstallation and adjustment of VDC series Voltage Dip Compensators.

Contents

Introduction .............................................................................. 3

Theory of operation ................................................................. 3

Specifications .......................................................................... 5

VDC support for the SEMI F47 standard ................................. 7

Installation Guide ..................................................................... 9

Power Wiring............................................................................ 9

Indicator error codes.............................................................. 11

Adjustments ........................................................................... 11

Compensator Run Time......................................................... 11

I2t controlled run time curves ................................................ 12

Fault Diagnosis Chart ............................................................ 13

Mechanical Construction ....................................................... 16

Dimension Table .................................................................... 16

Mechanical Outline ................................................................ 17

Accessories ........................................................................... 18

Voltage Sag Simulator ........................................................... 19

Page 3: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 3VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

IntroductionThe reliability of electrical power to industry is in general very high, nevertheless,

voltage sags or dips do occur. These instabilities are caused by short circuits, lightningstrikes on overhead power lines and heavy load switching. The duration of such faults isgenerally shorter than one second. Power Quality data shows that voltage sags with amaximum depth of around 50% constitute 92% of all events.

Most plant can ride through such voltage dips by virtue of their mechanicaland electrical inertia. However, this is not the case with electrically held-in contactors andrelays that control the machinery. Contactors typically drop out from 5ms to 20ms afterpower is removed. Each short voltage dip now becomes a power failure and the plant mustbe restarted. This can be complicated, time-consuming and costly.

DIP-PROOFING TECHNOLOGIES’ Voltage Dip Compensators are de-signed to maintain the switchgear control voltage during voltage sags, effectively keepingthe plant connected. The stored electrical and magnetic energy is allowed to flow,supporting the mechanical inertia of the machinery. When the power is restored after ashort voltage dip, the plant is still running at near synchronous speed, the inrush currentswill be small and the stress to the system minimal. The VDC provides an economicsolution for users who need their equipment to comply with the Semi F47 standard forvoltage sag immunity.

Historically, this problem has been addressed by using DC contactors,latched contactors and intelligent controls such as PLC’s. These systems are complexand expensive and do not provide a solution for equipment already in existence. Thecurrent approach to this problem has been to employ intelligent control systems whichprovide a curative solution. In contrast, the Voltage Dip Compensator, provides apreventative solution.

Theory of operationThe VOLTAGE-DIP COMPENSATOR is designed to be maintenance free and

highly reliable. It consists of 5 static switches , a sag compensation transformer and thecontrols. The Voltage Dip Compensator block diagram is shown in Fig 1 below.

Fig 1Compensator Block Diagram

StaticSwitch - 1

Controls Static To LoadSupply in

StaticSwitch - 2

StaticSwitch - 3

Switch - 4

StaticSwitch - 5

CompensationTransformer

1 3

2

Page 4: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

The STATIC SWITCHES are robust and can withstand large current surges. Theyare ideally suited for contactor operation where high peak currents of short duration occurduring energizing.

Fig 2Compensator output waveform.

During stand-by operation, static switch1 supplies power directly to the load,staticswitches 2 to 5 are switched off and the compensation transformer carries no load. Thesupply voltage is constantly monitored for deviations; should there be a deviation fromVnom which is greater than ±10%, static switch 1 is switched off and static switch 2 isactivated. Depending on the sag depth the controls will operate static switches 2 to 5 tomaintain the compensator output voltage within ±10% of the nominal supply voltage.Theswitch-over is accomplished in 350µs. A 3.15 second timer, adjustable in increments of50ms , starts timing the compensator out. Should the input voltage recover within the settime, static switches 2 to 5 will be deactivated and static switch 1 will be switched on andthe load is reconnected to the supply. If the input voltage does not recover within the settime the load is switched back to the supply regardless of the voltage level. If I2t controlis enabled then the run time will be dynamically optimized to the longest time that loadconditions will allow.

The VDC employs tap switch fuses to prevent catastrophic damage to the unit inthe event of a tap switch failure. If a tap switch should fail the fuse will open. A VDC witha failed tap switch will continue to function normally and will attempt to serve any sags thatoccur. However if sag conditions require activation of the failed tap then the load will bedropped because there is no output from that tap.

Time ms

Vo

lts

300

200

100

0

-100

-200

-300

0 10 20 30 40 50 60 70 80 90 100

V in (Sag duration 42ms)V out

Compensator Running

Supplysags

Supplyrecovers

Page 5: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 5VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

VD

C S

4T1K

120

VD

C L

4T3K

120

Single phase supply voltage 50/60Hz:Maximum input voltage:Minimum input voltage: -50% -50%Full load current (A RMS): 8.5A 24AMaximum surge current for 3 seconds duration:

Nominal output voltage:Voltage fluctuations over full operating range:Nominal load current (A): 8.5A 24A

Power factor range:Wave shape:Nominal load (VA): 1000 3000Maximum up-time (sec):

Timer control:

I2t control:Overload current limit (A RMS): 12A 35AShort circuit current limit (A RMS): 30A 75A

Range:Setting:

System OK:Compensator running:

Maximum ambient working temperature:

Construction:Height (mm) (Dim. L3 on p10): 280 273Height (in) (Dim. L3 on p10): 11.02 10.75Width mm (in):Depth mm (in):Mass (kg): 5.0 9.0Mass (lbs): 11.0 19.8

Cable, Copper panel wire; size mm2:Cable, Copper panel wire; size AWG:Screw terminal torque Nm (lb-in):

Underwriters Laboratories Inc:

SEMI F47:

5mm2

1.76Nm (15.6lb-n)

INDICATORS

TIMER

AC OUTPUT

AC INPUT SUPPL Y

± 10%

150 (5.90)

14 AWG

110 (4.33)

2mm2

red LED

LISTINGS

CONNECTION

CUBICLE

TEMPERATURE45°C (113°F)

Extruded Aluminum

162 (6.38)

ST ANDARDS SUPPORTEDSemiconductor processing equipment voltage sag immunity.

3.15sSee Figs 9 & 10 p12

0.05 to 3.15s0.05s steps

green LED

10 AWG

311 (12.24)

120V

cos from 1 to 0Sinusoidal

120V MODELS

120V+10%

550A

The VDC family is designed for applications that must meet the SEMI F47 Voltage Sag Immu-nity Standard for Semiconductor Processing Equipment and where size and cost are critical

factors.

SpecificationsVDC L4T & S4T series 120V models

Page 6: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 6 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

VD

C S

4T1K

208

VD

C L

4T5K

208

VD

C S

4T1K

220

VD

C L

4T5K

220

VD

C S

4T1K

230

VD

C L

4T5K

230

Single phase supply voltage 50/60Hz:Maximum input voltage:Minimum input voltage: -50% -50% -50% -50% -50% -50%Full load current (A RMS):Maximum surge current for 3 cycles duration:

Nominal output voltage (V):Voltage fluctuations over full operating range:Nominal load current (A):

Power factor range:Wave shape:Nominal load (VA):Maximum up-time (sec):

Timer control:

I2t control:Overload current limit (A RMS):Short circuit current limit (A RMS):

Range:Setting:

System OK:Compensator running:

Maximum ambient working temperature:

Construction:Height (mm) (Dim. L3 on p10): 280 280 280Height (in) (Dim. L3 on p10): 11.02 11.02 11.02Width mm (in):Depth mm (in):Mass (kg):Mass (lbs):

Cable, Copper panel wire; size mm2:Cable, Copper panel wire; size AWG:Screw terminal torque Nm (lb-in):

Underwriters Laboratories Inc:

SEMI F47:

208 / 220 /230V MODELS

+10%

550A

cos from 1 to 0

ST ANDARDS SUPPORTEDSemiconductor processing equipment voltage sag immunity.

3.15sSee Figs 9 & 10 p12

0.05 to 3.15s0.05s steps

green LED

35A 75A

LISTINGS

CONNECTION

CUBICLE

TEMPERATURE45°C (113°F)

Extruded Aluminum293

162 (6.38)150 (5.90) 311 (12.24) 150 (5.90) 311 (12.24) 150 (5.90) 311 (12.24)110 (4.33)

5.0

22.7A

1000

INDICATORS

TIMER

4.3A 21.7A

red LED

208V 220V

208V 220VAC OUTPUT

AC INPUT SUPPL Y230V

230V

1.76Nm (15.6lb-in)

2mm2 5mm2 2mm2 5mm2 2mm2 5mm2

14AWG 10AWG

162 (6.38) 110 (4.33) 162 (6.38)

14AWG 10AWG 14AWG 10AWG

5.0110 (4.33)

9.0

4.8A 24A 4.6A 22.7A 4.3A 21.7A

4.8A 24A 4.6A

5000 1000 5000

12A 28A 12A 28A 12A 28A

5000

± 10%

Sinusoidal1000

35A 75A 35A 75A

293 29311.54 11.54 11.54

11.0 19.8 11.0 19.8 11.0 19.89.0 5.0 9.0

The VDC S6T & L6T series should be used for critical applications where support down to37% of nominal supply voltage is needed.

SpecificationsVDC L4T & S4T series 208V / 220V / 230V models

Page 7: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 7VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

VDC support for the SEMI F47 standardThis standard was drafted by the Semiconductor Industry to specify Voltage Sag

Immunity requirements for semiconductor processing equipment. The profile for the F47standard is shown in Fig 3.

The blue zone represents the operation area where no equipment faults mustoccur due to voltage sags on the supply. The “no fault” window is from 50ms to 1 secondwith variable depth sag to a maximum of 50% of the nominal supply voltage.

The VDC family is designed for applications that must meet the SEMI F47 VoltageSag Immunity Standard for Semiconductor Processing Equipment and where size andcost are critical factors.

The green area in Fig 4 shows the extended support provided by the VDC S4Tseries. Support times are shown in green for 120V models at a load current of 9.6 ampsand in red for 230 models at a load current of 4.3 amps.The “no fault” window is extended

For 230V models - 4.3A

Vsupply

%

0

10

20

30

40

50

60

70

80

90

100

g p

pp y

100

90

80

70

60

50

40

30

20

10

00.01 0.02 0.1 1 10 100

Sag duration sec

F47 Specification0.05 to 1 sec

58%

67%

4.1s 5.9s 8.6s12.5s

50%

VDC support provides voltage sagimmunity and extends the "no fault"equipment operation area.

78%

90%

22s 32s 46s67sFor 120V models - 9.6A

%%

Vsu

pp

ly %

0

10

20

30

40

50

60

70

80

90

100

Sag depth %

Vsu

pp

ly

100

90

80

70

60

50

40

30

20

10

00.01 0.02 0.1 1 10 100

Sag duration sec

F47 Specification0.05 to 1 sec

Required equipment voltagesag ride through capability.This is the equipment "no fault"operation area.

Fig 3SEMI F47 Standard.

Fig 4VDC extended support for the SEMI F47 Standard. Times shown are for the VDC S4T series with Iload = 9.6A for 120V models, Iload = 4.3A for 230V

models & duty cycle 1 maximum length event every 20 minutes.

Page 8: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 8 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

from 50ms to 4.1 &12.5 seconds respectively with a maximum continuous sag depth of50%. VDC L4T3K/5K support times are shown in Fig 5.

For applications that require protection against momentary interruptions and sagsrefer to our Voltage Dip Proofing Inverter (DPI) product line for a simple cost effectivesolution that is easy to intergate into OEM products or retrofit to existing equipment. TheDPI support profile is shown together with the F47 curve in Fig 6. It can be seen that theDPI provides complete protection for all sag depths and interruptions from 0 to 3 seconds.

Vsu

pp

ly %

0

10

20

30

40

50

60

70

80

90

100

Sag depth %

Vsu

pply

100

90

80

70

60

50

40

30

20

10

00.01 0.02 0.1 1 10 100

Sag duration sec

F47 Specification0.05 to 1 sec

DPI support providesvoltage sag and supplyinterruption immunity.The "no fault" equipmentoperation area is extendedto protect againstmomentar interruptionsy .

Fig 6DPI support for the SEMI F47 Standard.

Vsu

pp

ly %

0

10

20

30

40

50

60

70

80

90

100

Sag depth %

Vsu

pp

ly

100

90

80

70

60

50

40

30

20

10

00.01 0.02 0.1 1 10 100

Sag duration sec

F47 Specification0.05 to 1 sec

58%

67%

7.7s

13.5

s

23.8

s

41.7

s

50%

VDC support provides voltage sagimmunity and extends the "no fault"equipment operation area.

78%

90%

Fig 5VDC extended support for the SEMI F47 Standard. Times shown are for the VDC L4T 3K/5K series with Iload = 24A & duty

cycle 1 maximum length event every 7 minutes.

Page 9: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 9VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

Installation Guide

1. Remove the unit from its packing

2. Place the unit horizontally on a bench and visually check for anymechanical damage. Ensure that all the casing screws are tight thenshake the unit to check that there is nothing loose internally.

Note : Please inform your shipping agent if any damage has occurredduring transit : the damaged unit(s) and all packing material should bekept in case the insurers wish to inspect the damage.

3. Check that compensator voltage is the same as the system control voltage.

Refer to the rating label on the unit end plate.

WARNING: Never connect a 120V unit to a 208V or 230V supply!

4. Decide on the location where the unit is to be installed, this will probablybe inside a switch gear panel.

5. Mount the unit vertically using M6 bolts.

6. Connect unit as shown in Fig 7 using 2mm2 (14AWG), VDC S series & 5mm2

(10AWG), VDC L series copper panel wire.

7. Apply terminal screw tightening torque of 1.5 - 1.8Nm (13 - 16 lb-in).

8. This device does not have a disconnect switch. If such a switch is required itmust be provided by others.

Power Wiring

Connect Line In (Supply) to Terminal 1Connect Common Line in to Terminal 2Connect Common Line out to Terminal 3Connect Line Out (Load) to Terminal 4Connect the ground screw(s) to the panel ground point.

Fig 7Power Wiring Diagram

(Load)(Supply)

Line in

Common line in

3*2*1

Ground outGround in

Common line out

4

Line out

*Note: 2 & 3 linked internally.

Page 10: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 10 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

SystemOK

HousedBypassSwitch

Common line outCommon line in

Line OutLine In

(Load)(Supply Vnom)

DPI

Bypass

ToSupply

321

Line in Common Line Line out

To DPIor VDC

4

in out

321

Line in Common Line Line out

4

in out

Ground Ground1 2 3 4

Voltage Dip Compensator

CompensatorRunning

VDC

DIP-PROOFINGTECHNOLOGIES INC.

9. Once the unit has been mounted and the external wiring completed, powercan be applied.Turn on the power to the unit. The green LED indicator"System OK" will come on after approximately one second and the unit isfully operational.

10. In applications which require no break maintenance, a bypass switchmust be installed. Order the appropriate Bypass Switch (see p17) whichshould be connected as shown in Fig 8.

Fig 8Housed Bypass Switch Connection Diagram

Functional Description of the IndicatorsSystem OK : Green LED indicator

When the green LED is ON the system is fully functional; the unit self test& initialization routine has been run successfully.

Compensator Running : Red LED indicatorThe red LED is on when the compensator is running during a voltage dip.

Page 11: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 11VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

Indicator error codes

Test and Maintenance

There are no user serviceable parts inside the unit, if faulty return to factory or localagent for repairs.

AdjustmentsAdjustment points are marked on the control card and can be reached byremoving the front cover of the VDC; see Mechanical Construction on page 15.

Compensator Run TimeTimer controlled Run Time - SW1 (see Fig.11 page 13)

This switch sets the running time of the compensator and can be set in 50ms steps to amaximum of 3.15 seconds. To determine the run time which is currently set, add thefigures printed next to each switch that is in the ON position. For example, a running timesetting of 3.15 seconds requires these switch combinations: 1-on, 2-on, 3-on, 4-on, 5-on,6-on.

I2t controlled Run Time.

Run Time is dynamically optimized to the longest that load conditions will allow.

The I2t optimized Run Time can be determined using the curves on page 12.

To enable this option set all SW1 switches to OFF.

Factory Setting : I2t control (SW1 1-6- off)

IndicatorFlashes

Condition1 2 Profile

OKSystemGreen

Event not fully supported. Resets after 24 hours.

.estTupStartSystem OKGreen

Supply check, AC input low.

CompensatorrunningRed

Load current check, overload.

Page 12: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 12 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

Fig 10Maximum I2t controlled Up-times for VDC L4T3K & VDC L4T5K series.

Duty cycle 1 maximum length event every 7 minutes.

12.00

14.00

16.00

18.00

20.00

22.00

24.00

26.00

0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00 45.00 50.00 55.00 60.00

I2t Up-time (sec)

Lo

ad c

urr

ent

(am

ps)

Time-78% sag Time-67% sag

Time-58% sag Time-50% sag

2.00

3.00

4.00

5.00

6.00

7.00

8.00

9.00

10.00

0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0

I2t Up-time (seconds)

Lo

ad C

urr

ent

(am

ps)

Time - 78% Time - 67% Time - 58% Time - 50%

I2t controlled run time curves

Fig 9Maximum I2t controlled Up-times for VDC S4T1K series.Duty cycle 1 maximum length event every 20 minutes.

Use the curves below (Fig 9 for “S” series & Fig 10 for “L” series) to determine theI2t controlled run times for a specific load current and sag depth.

Page 13: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 13VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

Fig 11Control Card Indicator & Adjustment Locations

Fault Diagnosis Chart

Red

100msec50msec

800msec400msec

System OK

Green

Set run time

1600msec

200msec

Running

LED1

SW1

LED2

DSW1

Push & releaseto calibrate.

6

5

4

3

2

1

Note 1 : VDC setting.To activate " t controllI2 ed runtime" set allDSW1 switches to the OFF position.

Default I2t control

~ #4 Not used

DSW2

ON

- -

Note 2 : VDC setting.DSW2 is set by factory.Do not chan e setting gs.

- 4T

HC LC

AV NV

Off On

4T - 4 tap VDCHC - 3K/5K VDCLC - 1K VDCAV - Auto supply sensing onNV - Auto supply sensing off

(LEDOKSystem green) is off,no voltage on output terminals.

inputonvoltagesupplyNoterminals 1 & 2.

.supplyCheck

(LEDOKSystem green) is off.Compensator Running LED(red) flashes once every second.There is no voltage on outputterminals 3 & 4.

loadcondition,Overloadcurrent exceeds unitoverload rating.

ratingOverloadtheexceedsitifcurrent,loadCheckeliminate any devices that do not need to besupported or use a larger unit.

(LEDOKSystem green) is off,voltage on terminals 3 & 4 novoltage on 1 & 2.

arewiresloadandSupplyreversed. erminals 1 & 4.T

seconds.3>forupPoweredSystem OK LED (green) is off.Compensator Running LED(red) is off. There may / may notbe voltage on terminals 3 & 4.

failure.Unit Return to local agent or manufacturer for repair.

(LEDOKSystem green) flashestwice every second. voltagepresent on output terminals.

A.egatlovylppuswoL208/220/230V unit is being

.supply20V1awithused

model.20V1tounitChange

supplywhenfailureUnitswitched on.

onusedbeingisunit20V1A.supply220Vor208Va

model.voltagecorrecttounitChangeNote: The 120V unit will be damaged!

Symptom Probable Cause Remedy

Swap supply & load wires. Supply terminal 1 andload terminal 4.

Page 14: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 14 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

Fig 12VDC Block Wiring Diagram

R9

R11

Z5

CN

1:1

CN

1:11

CN

1:14

CN

1:16

CN

1:17

CN

1:10

CN

1:12

CN

1:6

CN

1:4

CN

2:1

CN

2:2

CN

2:3

CN

2:6

CN

2:5

Z3

CN

1:8

VDR5

CN

2:4

R8

R7

Z4R

10

Z1

CN

1:7

CN

1:13

Z2

CN

1:3

CN

1:5

CN

1:9

CN

1:15

TH1

E1 G1

C1

TH2

E2 G2

C2

Sta

ticG

1

G2

Sw

itch

JP1

JP2 CT1

TX1

JP3

JP4

1

TAP

4

TAP

3

TAP

2

TAP

1

A1

A2

Sta

tic S

witc

hdr

iver

sC

ontro

l Car

dTa

p S

witc

hD

river

s

Tap

Sw

itch

1

Tap

Sw

itch

2

Tap

Sw

itch

3

Tap

Sw

itch

4

Com

pens

atio

nTr

ansf

orm

er

220V

120V

Line

in (S

uppl

y)

Line

out

(Loa

d)4

CN

4

CN

3

AC

1A

C2

AC

1A

C2

VS

S1

CTR

L1

VS

S2

CTR

L2

G1

E1

PS

1

G2

E2

PS

2

VS

S1

CTR

L1

VS

S2

CTR

L2

G1

E1

PS

1

G2

E2

PS

2

CN

6

CN

5

Gro

und

In Out

3

Com

mon

line

2

9

6 3

8242 1 4 5

4 ta

p6

tap

F1

F2

F3

F4

Page 15: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 15VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

Notes

Page 16: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 16 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

L1 L2 L3 L4 L5 L6 L7 DVDC S4T1K120 177 (6.97) 237 (9.33) 280 (11.02)

110 (4.33) 150 (5.90) 30 (1.18) 140 (5.50) 6.0 (0.24)

VDC L4T3K120

VDC S4T1K208 177 (6.97) 237 (9.33) 280 (11.02)110 (4.33)

VDC L4T5K208

VDC S4T1K220 177 (6.97) 237 (9.33) 280 (11.02)

VDC L4T5K220

VDC S4T1K230 177 (6.97) 237 (9.33) 280 (11.02)

VDC L4T5K230

Model VDC Dimensions mm (in)

170 (6.69) 250 (9.84) 293 (11.54) 162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31)

170 (6.69) 250 (9.84) 293 (11.54) 162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31)

170 (6.69) 250 (9.84) 293 (11.54)

150 (5.90)

162 (6.38) 311 (12.24)170 (6.69) 250 (9.84) 293 (11.54)

30 (1.18) 140 (5.50) 6.0 (0.24)

110 (4.33) 150 (5.90) 30 (1.18) 140 (5.50) 6.0 (0.24)

40 (1.57) 296 (11.65) 8.0 (0.31)

110 (4.33) 150 (5.90) 30 (1.18) 140 (5.50) 6.0 (0.24)

162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31)

Mechanical Construction

VDC S series - The VDC case is made from extruded aluminium sections. The four partsthat make up the case are interlocked and secured by screws. To remove the front coverunscrew four screws : the two top screws from the end plate where the terminal block islocated and the two bottom screws from the other end plate. Slide the front cover awayfrom the terminal block to access adjustment area.

VDC L series - The VDC case is made from extruded aluminium sections. The six partsthat make up the case are interlocked and secured by screws. To remove the front coverunscrew three screws : one from the front cover and one each from the top and bottomend plates.

Dimension Table

Page 17: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 17VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

Mechanical Outline

Fig 13Dimensions of the VDC series mm (inches)

L6L4

L5

L7

L3L2L6

L1

Note 1:Terminal cover shown dashed.Note 2:Terminal #1 - Line in (Supply)Terminal #2 - Common line inTerminal #3 - Common line outTerminal #4 - Line out (Load)

GroundScrews

TerminalCover

TerminalCover

GroundScrews

HZ

POWER

VOLTS

DATE MFG

SERIAL #

MODELVOLTAGE DIP-PROOFING INVERTER

"L" series case.

Model # exampleDPI52L3K23

orVDC L4T5K120

"S" series case.

Model # exampleDPI52S50-23

orVDC S4T1K230

Ø D

L7

L5

L4

L2

L3L1

L1

*L

1*

L6

L6

1 2 3 4

1 2 3 4

Ø D

1 2 3 4

1 2 3 4

Page 18: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 18 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

GroundScrews

1 2 3 4 110

(4.3

3)

150 (5.90)

140 (5.51)

31(1

.22)

41.0

(1.6

1)41

.0(1

.61)

50(1

.97)

50

(1.

97)

120

(4.7

2)DPI

Bypass

Note 1:Dimension units.Without brackets - mm.With brackets - inches.

Note 2: Mounting holes 2 x 6 (0.25)Ø.

ToSupply

321

Line in Common Line Line out

To DPIor VDC

4

in out

321

Line in(Supply)

Common Line Line out(Load)

4

in out

AccessoriesHoused Bypass SwitchDescription

Where no-break maintenance is required a by pass switch must be installed. It connectsthe supply directly to the load, "Bypass" position, and disconnects the power terminals ofthe inverter without interrupting the supply. When in "DPI" position the load is connectedto the supply via the inverter.

SpecificationsMODEL BPSW25AELECTRICAL

Maximum current: 25AMaximum input voltage: 600Vac

TEMPERATUREMaximum working temperature: 45°C (113°F)

HOUSINGConstruction: Extruded AluminumHeight: 202mm (7.95in)Width: 150mm (5.9in)Depth: 141mm (5.55in)Mass: 1kg (2.2lbs)

Mechanical outline

Ordering

Stock No: Description5003-006 Housed By-Pass Switch 25Amp

Page 19: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Page 19VDC L4T & VDC S4T Series - Firmware ver 1.4 & up

Voltage Sag SimulatorDescription

The Sag Simulator is an effective tool toevaluate the effects of momentary voltage sagsand interruptions on industrial controls. Whenused in conjunction with a Voltage Dip-Proof-ing Inverter or a Voltage Dip Compensator andBypass switch, it may be used to prove theeffectiveness of the DPI or VDC as a solutionfor these power quality problems.The Sag Simulator is designed for 120/208/240Vac operation. The controls consist of avariac to set the sag depth, an LCD display toindicate the sag voltage value and programstatus, four programming keys to set up andoperate the simulator. A variable interrupt timersets the duration of the voltage sag and thepoint in the cycle at which it begins. Bothvariables are set using the programming keysand are indicated on the LCD display.Simulator output is short circuit and overloadprotected. A 5V synchronization pulse is pro-vided to trigger an oscilloscope. A photographappears on page 8; the specifications are shownbelow.

Sag Simulator Specifications

AC INPUT SUPPLYSupply voltage: 120/208/240Vac 50/60HzMaximum input voltage: +10%Full load current: 20A

VARIAC CONTROLVariac range: 0-240Vac RMSMaximum power: 1200VA @ 120V / 2400VA @ 240VMaximum continuous current:10A Maximum short term current for3 seconds: 20AOverload & short circuit protection: Yes

DIRECT VARIAC OUTPUTVariac range: 0-240Vac RMSMaximum power: 1200VA @ 120V / 2400VA @ 240VMaximum continuous current: 10AOverload & short circuit protection: YesSAG DELAY TIMERRange: 0.00 to 20.00 msSetting: 0.01 ms stepsSAG DURATION TIMERRange: 0.010 to 9.999 secondsSetting: 0.001 second steps

0 10 20 30 40 50 60 70 80 90 100Time ms

300

200

100

0

-100

-200

-300

Sup

ply

V

0 10 20 30 40 50 60 70 80 90 100Time ms

5

0

-5

V S

ync

Sag Duration 60ms

Sag Simulator outputSupply voltage - 220V 50Hz

Positive zerocrossing

Sag Delay5ms

Sag Depth50% Sag

Voltage110Vrms

Sync pulse output Terminals 4 & 5

Amplitude = 5V Duration = 60mS = Sag Duration

CONTROLS & INDICATORSProgramming: Four push switchesMenu/parameter indicaton: 4 x 20 LCD display

SYNC PULSE OUTPUTAmplitude: 5VPolarity: PositiveElectrically isolated output: YesDuration: Equal to sag duration

TEMPERATUREMaximum ambient working temperature: 45°C (113°F)

HOUSINGConstruction: Extruded aluminiumHeight: 390mm (15.35in )Width: 311mm (12.24in)Depth: 162mm (6.38in)Mass: 15kg (33lb)

Simulated Sag Profile

Page 20: VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation & Service Manual Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up The STATIC SWITCHES

Installation & Service Manual

Measurlogic Inc.7334 S. Alton Way, Suite 14M

Centennial CO 80134, USATel:1-877-777-6567 Fax:425-799-4780

E-mail: [email protected]: www.Measurlogic.com

Doc Ref. 3704-010 Rev 1.4 October 11 th 2012 : LPW

DIP-PROOFINGTECHNOLOGIES INC.LEADERS IN VOLTAGE-DIP PROOFING

Voltage-Dip Compensators

LineVoltage

ControlVoltage

Voltage-Dip Compensator

2

C3

B3

Interlock

Stop

Start

MainBreaker

Motor Control Centre

A typical VDC connection diagram

C2

B2

Interlock

Stop

Start

C1

B1

Interlock

Stop

Start

Bypass Switch

41 StaticSwitch - 1

Controls

StaticSwitch - 2

StaticSwitch - 3

StaticSwitch - 4

StaticSwitch - 5

CompensationTransformer

3

For VDC L4T & S4T series Models120V / 208V / 220V / 230V 50/60Hz