VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation &...
Transcript of VDC S L Man1.4 us ml - Revenue Grade Electrical Submeters · 2019. 5. 24. · Installation &...
Installation & Service Manual
DIP-PROOFINGTECHNOLOGIES INC.LEADERS IN VOLTAGE-DIP PROOFING
Voltage-Dip Compensators
For VDC L4T & S4T series Models120V / 208V / 220V / 230V 50/60Hz
Installation & Service Manual
Page 2 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
NoticeIMPORTANT SAFETY INSTRUCTIONS.SAVE THESE INSTRUCTIONS!
This manual contains important instructions that should be followed duringinstallation and adjustment of VDC series Voltage Dip Compensators.
Contents
Introduction .............................................................................. 3
Theory of operation ................................................................. 3
Specifications .......................................................................... 5
VDC support for the SEMI F47 standard ................................. 7
Installation Guide ..................................................................... 9
Power Wiring............................................................................ 9
Indicator error codes.............................................................. 11
Adjustments ........................................................................... 11
Compensator Run Time......................................................... 11
I2t controlled run time curves ................................................ 12
Fault Diagnosis Chart ............................................................ 13
Mechanical Construction ....................................................... 16
Dimension Table .................................................................... 16
Mechanical Outline ................................................................ 17
Accessories ........................................................................... 18
Voltage Sag Simulator ........................................................... 19
Installation & Service Manual
Page 3VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
IntroductionThe reliability of electrical power to industry is in general very high, nevertheless,
voltage sags or dips do occur. These instabilities are caused by short circuits, lightningstrikes on overhead power lines and heavy load switching. The duration of such faults isgenerally shorter than one second. Power Quality data shows that voltage sags with amaximum depth of around 50% constitute 92% of all events.
Most plant can ride through such voltage dips by virtue of their mechanicaland electrical inertia. However, this is not the case with electrically held-in contactors andrelays that control the machinery. Contactors typically drop out from 5ms to 20ms afterpower is removed. Each short voltage dip now becomes a power failure and the plant mustbe restarted. This can be complicated, time-consuming and costly.
DIP-PROOFING TECHNOLOGIES’ Voltage Dip Compensators are de-signed to maintain the switchgear control voltage during voltage sags, effectively keepingthe plant connected. The stored electrical and magnetic energy is allowed to flow,supporting the mechanical inertia of the machinery. When the power is restored after ashort voltage dip, the plant is still running at near synchronous speed, the inrush currentswill be small and the stress to the system minimal. The VDC provides an economicsolution for users who need their equipment to comply with the Semi F47 standard forvoltage sag immunity.
Historically, this problem has been addressed by using DC contactors,latched contactors and intelligent controls such as PLC’s. These systems are complexand expensive and do not provide a solution for equipment already in existence. Thecurrent approach to this problem has been to employ intelligent control systems whichprovide a curative solution. In contrast, the Voltage Dip Compensator, provides apreventative solution.
Theory of operationThe VOLTAGE-DIP COMPENSATOR is designed to be maintenance free and
highly reliable. It consists of 5 static switches , a sag compensation transformer and thecontrols. The Voltage Dip Compensator block diagram is shown in Fig 1 below.
Fig 1Compensator Block Diagram
StaticSwitch - 1
Controls Static To LoadSupply in
StaticSwitch - 2
StaticSwitch - 3
Switch - 4
StaticSwitch - 5
CompensationTransformer
1 3
2
Installation & Service Manual
Page 4 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
The STATIC SWITCHES are robust and can withstand large current surges. Theyare ideally suited for contactor operation where high peak currents of short duration occurduring energizing.
Fig 2Compensator output waveform.
During stand-by operation, static switch1 supplies power directly to the load,staticswitches 2 to 5 are switched off and the compensation transformer carries no load. Thesupply voltage is constantly monitored for deviations; should there be a deviation fromVnom which is greater than ±10%, static switch 1 is switched off and static switch 2 isactivated. Depending on the sag depth the controls will operate static switches 2 to 5 tomaintain the compensator output voltage within ±10% of the nominal supply voltage.Theswitch-over is accomplished in 350µs. A 3.15 second timer, adjustable in increments of50ms , starts timing the compensator out. Should the input voltage recover within the settime, static switches 2 to 5 will be deactivated and static switch 1 will be switched on andthe load is reconnected to the supply. If the input voltage does not recover within the settime the load is switched back to the supply regardless of the voltage level. If I2t controlis enabled then the run time will be dynamically optimized to the longest time that loadconditions will allow.
The VDC employs tap switch fuses to prevent catastrophic damage to the unit inthe event of a tap switch failure. If a tap switch should fail the fuse will open. A VDC witha failed tap switch will continue to function normally and will attempt to serve any sags thatoccur. However if sag conditions require activation of the failed tap then the load will bedropped because there is no output from that tap.
Time ms
Vo
lts
300
200
100
0
-100
-200
-300
0 10 20 30 40 50 60 70 80 90 100
V in (Sag duration 42ms)V out
Compensator Running
Supplysags
Supplyrecovers
Installation & Service Manual
Page 5VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
VD
C S
4T1K
120
VD
C L
4T3K
120
Single phase supply voltage 50/60Hz:Maximum input voltage:Minimum input voltage: -50% -50%Full load current (A RMS): 8.5A 24AMaximum surge current for 3 seconds duration:
Nominal output voltage:Voltage fluctuations over full operating range:Nominal load current (A): 8.5A 24A
Power factor range:Wave shape:Nominal load (VA): 1000 3000Maximum up-time (sec):
Timer control:
I2t control:Overload current limit (A RMS): 12A 35AShort circuit current limit (A RMS): 30A 75A
Range:Setting:
System OK:Compensator running:
Maximum ambient working temperature:
Construction:Height (mm) (Dim. L3 on p10): 280 273Height (in) (Dim. L3 on p10): 11.02 10.75Width mm (in):Depth mm (in):Mass (kg): 5.0 9.0Mass (lbs): 11.0 19.8
Cable, Copper panel wire; size mm2:Cable, Copper panel wire; size AWG:Screw terminal torque Nm (lb-in):
Underwriters Laboratories Inc:
SEMI F47:
5mm2
1.76Nm (15.6lb-n)
INDICATORS
TIMER
AC OUTPUT
AC INPUT SUPPL Y
± 10%
150 (5.90)
14 AWG
110 (4.33)
2mm2
red LED
LISTINGS
CONNECTION
CUBICLE
TEMPERATURE45°C (113°F)
Extruded Aluminum
162 (6.38)
ST ANDARDS SUPPORTEDSemiconductor processing equipment voltage sag immunity.
3.15sSee Figs 9 & 10 p12
0.05 to 3.15s0.05s steps
green LED
10 AWG
311 (12.24)
120V
cos from 1 to 0Sinusoidal
120V MODELS
120V+10%
550A
The VDC family is designed for applications that must meet the SEMI F47 Voltage Sag Immu-nity Standard for Semiconductor Processing Equipment and where size and cost are critical
factors.
SpecificationsVDC L4T & S4T series 120V models
Installation & Service Manual
Page 6 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
VD
C S
4T1K
208
VD
C L
4T5K
208
VD
C S
4T1K
220
VD
C L
4T5K
220
VD
C S
4T1K
230
VD
C L
4T5K
230
Single phase supply voltage 50/60Hz:Maximum input voltage:Minimum input voltage: -50% -50% -50% -50% -50% -50%Full load current (A RMS):Maximum surge current for 3 cycles duration:
Nominal output voltage (V):Voltage fluctuations over full operating range:Nominal load current (A):
Power factor range:Wave shape:Nominal load (VA):Maximum up-time (sec):
Timer control:
I2t control:Overload current limit (A RMS):Short circuit current limit (A RMS):
Range:Setting:
System OK:Compensator running:
Maximum ambient working temperature:
Construction:Height (mm) (Dim. L3 on p10): 280 280 280Height (in) (Dim. L3 on p10): 11.02 11.02 11.02Width mm (in):Depth mm (in):Mass (kg):Mass (lbs):
Cable, Copper panel wire; size mm2:Cable, Copper panel wire; size AWG:Screw terminal torque Nm (lb-in):
Underwriters Laboratories Inc:
SEMI F47:
208 / 220 /230V MODELS
+10%
550A
cos from 1 to 0
ST ANDARDS SUPPORTEDSemiconductor processing equipment voltage sag immunity.
3.15sSee Figs 9 & 10 p12
0.05 to 3.15s0.05s steps
green LED
35A 75A
LISTINGS
CONNECTION
CUBICLE
TEMPERATURE45°C (113°F)
Extruded Aluminum293
162 (6.38)150 (5.90) 311 (12.24) 150 (5.90) 311 (12.24) 150 (5.90) 311 (12.24)110 (4.33)
5.0
22.7A
1000
INDICATORS
TIMER
4.3A 21.7A
red LED
208V 220V
208V 220VAC OUTPUT
AC INPUT SUPPL Y230V
230V
1.76Nm (15.6lb-in)
2mm2 5mm2 2mm2 5mm2 2mm2 5mm2
14AWG 10AWG
162 (6.38) 110 (4.33) 162 (6.38)
14AWG 10AWG 14AWG 10AWG
5.0110 (4.33)
9.0
4.8A 24A 4.6A 22.7A 4.3A 21.7A
4.8A 24A 4.6A
5000 1000 5000
12A 28A 12A 28A 12A 28A
5000
± 10%
Sinusoidal1000
35A 75A 35A 75A
293 29311.54 11.54 11.54
11.0 19.8 11.0 19.8 11.0 19.89.0 5.0 9.0
The VDC S6T & L6T series should be used for critical applications where support down to37% of nominal supply voltage is needed.
SpecificationsVDC L4T & S4T series 208V / 220V / 230V models
Installation & Service Manual
Page 7VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
VDC support for the SEMI F47 standardThis standard was drafted by the Semiconductor Industry to specify Voltage Sag
Immunity requirements for semiconductor processing equipment. The profile for the F47standard is shown in Fig 3.
The blue zone represents the operation area where no equipment faults mustoccur due to voltage sags on the supply. The “no fault” window is from 50ms to 1 secondwith variable depth sag to a maximum of 50% of the nominal supply voltage.
The VDC family is designed for applications that must meet the SEMI F47 VoltageSag Immunity Standard for Semiconductor Processing Equipment and where size andcost are critical factors.
The green area in Fig 4 shows the extended support provided by the VDC S4Tseries. Support times are shown in green for 120V models at a load current of 9.6 ampsand in red for 230 models at a load current of 4.3 amps.The “no fault” window is extended
For 230V models - 4.3A
Vsupply
%
0
10
20
30
40
50
60
70
80
90
100
g p
pp y
100
90
80
70
60
50
40
30
20
10
00.01 0.02 0.1 1 10 100
Sag duration sec
F47 Specification0.05 to 1 sec
58%
67%
4.1s 5.9s 8.6s12.5s
50%
VDC support provides voltage sagimmunity and extends the "no fault"equipment operation area.
78%
90%
22s 32s 46s67sFor 120V models - 9.6A
%%
Vsu
pp
ly %
0
10
20
30
40
50
60
70
80
90
100
Sag depth %
Vsu
pp
ly
100
90
80
70
60
50
40
30
20
10
00.01 0.02 0.1 1 10 100
Sag duration sec
F47 Specification0.05 to 1 sec
Required equipment voltagesag ride through capability.This is the equipment "no fault"operation area.
Fig 3SEMI F47 Standard.
Fig 4VDC extended support for the SEMI F47 Standard. Times shown are for the VDC S4T series with Iload = 9.6A for 120V models, Iload = 4.3A for 230V
models & duty cycle 1 maximum length event every 20 minutes.
Installation & Service Manual
Page 8 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
from 50ms to 4.1 &12.5 seconds respectively with a maximum continuous sag depth of50%. VDC L4T3K/5K support times are shown in Fig 5.
For applications that require protection against momentary interruptions and sagsrefer to our Voltage Dip Proofing Inverter (DPI) product line for a simple cost effectivesolution that is easy to intergate into OEM products or retrofit to existing equipment. TheDPI support profile is shown together with the F47 curve in Fig 6. It can be seen that theDPI provides complete protection for all sag depths and interruptions from 0 to 3 seconds.
Vsu
pp
ly %
0
10
20
30
40
50
60
70
80
90
100
Sag depth %
Vsu
pply
100
90
80
70
60
50
40
30
20
10
00.01 0.02 0.1 1 10 100
Sag duration sec
F47 Specification0.05 to 1 sec
DPI support providesvoltage sag and supplyinterruption immunity.The "no fault" equipmentoperation area is extendedto protect againstmomentar interruptionsy .
Fig 6DPI support for the SEMI F47 Standard.
Vsu
pp
ly %
0
10
20
30
40
50
60
70
80
90
100
Sag depth %
Vsu
pp
ly
100
90
80
70
60
50
40
30
20
10
00.01 0.02 0.1 1 10 100
Sag duration sec
F47 Specification0.05 to 1 sec
58%
67%
7.7s
13.5
s
23.8
s
41.7
s
50%
VDC support provides voltage sagimmunity and extends the "no fault"equipment operation area.
78%
90%
Fig 5VDC extended support for the SEMI F47 Standard. Times shown are for the VDC L4T 3K/5K series with Iload = 24A & duty
cycle 1 maximum length event every 7 minutes.
Installation & Service Manual
Page 9VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
Installation Guide
1. Remove the unit from its packing
2. Place the unit horizontally on a bench and visually check for anymechanical damage. Ensure that all the casing screws are tight thenshake the unit to check that there is nothing loose internally.
Note : Please inform your shipping agent if any damage has occurredduring transit : the damaged unit(s) and all packing material should bekept in case the insurers wish to inspect the damage.
3. Check that compensator voltage is the same as the system control voltage.
Refer to the rating label on the unit end plate.
WARNING: Never connect a 120V unit to a 208V or 230V supply!
4. Decide on the location where the unit is to be installed, this will probablybe inside a switch gear panel.
5. Mount the unit vertically using M6 bolts.
6. Connect unit as shown in Fig 7 using 2mm2 (14AWG), VDC S series & 5mm2
(10AWG), VDC L series copper panel wire.
7. Apply terminal screw tightening torque of 1.5 - 1.8Nm (13 - 16 lb-in).
8. This device does not have a disconnect switch. If such a switch is required itmust be provided by others.
Power Wiring
Connect Line In (Supply) to Terminal 1Connect Common Line in to Terminal 2Connect Common Line out to Terminal 3Connect Line Out (Load) to Terminal 4Connect the ground screw(s) to the panel ground point.
Fig 7Power Wiring Diagram
(Load)(Supply)
Line in
Common line in
3*2*1
Ground outGround in
Common line out
4
Line out
*Note: 2 & 3 linked internally.
Installation & Service Manual
Page 10 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
SystemOK
HousedBypassSwitch
Common line outCommon line in
Line OutLine In
(Load)(Supply Vnom)
DPI
Bypass
ToSupply
321
Line in Common Line Line out
To DPIor VDC
4
in out
321
Line in Common Line Line out
4
in out
Ground Ground1 2 3 4
Voltage Dip Compensator
CompensatorRunning
VDC
DIP-PROOFINGTECHNOLOGIES INC.
9. Once the unit has been mounted and the external wiring completed, powercan be applied.Turn on the power to the unit. The green LED indicator"System OK" will come on after approximately one second and the unit isfully operational.
10. In applications which require no break maintenance, a bypass switchmust be installed. Order the appropriate Bypass Switch (see p17) whichshould be connected as shown in Fig 8.
Fig 8Housed Bypass Switch Connection Diagram
Functional Description of the IndicatorsSystem OK : Green LED indicator
When the green LED is ON the system is fully functional; the unit self test& initialization routine has been run successfully.
Compensator Running : Red LED indicatorThe red LED is on when the compensator is running during a voltage dip.
Installation & Service Manual
Page 11VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
Indicator error codes
Test and Maintenance
There are no user serviceable parts inside the unit, if faulty return to factory or localagent for repairs.
AdjustmentsAdjustment points are marked on the control card and can be reached byremoving the front cover of the VDC; see Mechanical Construction on page 15.
Compensator Run TimeTimer controlled Run Time - SW1 (see Fig.11 page 13)
This switch sets the running time of the compensator and can be set in 50ms steps to amaximum of 3.15 seconds. To determine the run time which is currently set, add thefigures printed next to each switch that is in the ON position. For example, a running timesetting of 3.15 seconds requires these switch combinations: 1-on, 2-on, 3-on, 4-on, 5-on,6-on.
I2t controlled Run Time.
Run Time is dynamically optimized to the longest that load conditions will allow.
The I2t optimized Run Time can be determined using the curves on page 12.
To enable this option set all SW1 switches to OFF.
Factory Setting : I2t control (SW1 1-6- off)
IndicatorFlashes
Condition1 2 Profile
OKSystemGreen
Event not fully supported. Resets after 24 hours.
.estTupStartSystem OKGreen
Supply check, AC input low.
CompensatorrunningRed
Load current check, overload.
Installation & Service Manual
Page 12 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
Fig 10Maximum I2t controlled Up-times for VDC L4T3K & VDC L4T5K series.
Duty cycle 1 maximum length event every 7 minutes.
12.00
14.00
16.00
18.00
20.00
22.00
24.00
26.00
0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00 45.00 50.00 55.00 60.00
I2t Up-time (sec)
Lo
ad c
urr
ent
(am
ps)
Time-78% sag Time-67% sag
Time-58% sag Time-50% sag
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0
I2t Up-time (seconds)
Lo
ad C
urr
ent
(am
ps)
Time - 78% Time - 67% Time - 58% Time - 50%
I2t controlled run time curves
Fig 9Maximum I2t controlled Up-times for VDC S4T1K series.Duty cycle 1 maximum length event every 20 minutes.
Use the curves below (Fig 9 for “S” series & Fig 10 for “L” series) to determine theI2t controlled run times for a specific load current and sag depth.
Installation & Service Manual
Page 13VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
Fig 11Control Card Indicator & Adjustment Locations
Fault Diagnosis Chart
Red
100msec50msec
800msec400msec
System OK
Green
Set run time
1600msec
200msec
Running
LED1
SW1
LED2
DSW1
Push & releaseto calibrate.
6
5
4
3
2
1
Note 1 : VDC setting.To activate " t controllI2 ed runtime" set allDSW1 switches to the OFF position.
Default I2t control
~ #4 Not used
DSW2
ON
- -
Note 2 : VDC setting.DSW2 is set by factory.Do not chan e setting gs.
- 4T
HC LC
AV NV
Off On
4T - 4 tap VDCHC - 3K/5K VDCLC - 1K VDCAV - Auto supply sensing onNV - Auto supply sensing off
(LEDOKSystem green) is off,no voltage on output terminals.
inputonvoltagesupplyNoterminals 1 & 2.
.supplyCheck
(LEDOKSystem green) is off.Compensator Running LED(red) flashes once every second.There is no voltage on outputterminals 3 & 4.
loadcondition,Overloadcurrent exceeds unitoverload rating.
ratingOverloadtheexceedsitifcurrent,loadCheckeliminate any devices that do not need to besupported or use a larger unit.
(LEDOKSystem green) is off,voltage on terminals 3 & 4 novoltage on 1 & 2.
arewiresloadandSupplyreversed. erminals 1 & 4.T
seconds.3>forupPoweredSystem OK LED (green) is off.Compensator Running LED(red) is off. There may / may notbe voltage on terminals 3 & 4.
failure.Unit Return to local agent or manufacturer for repair.
(LEDOKSystem green) flashestwice every second. voltagepresent on output terminals.
A.egatlovylppuswoL208/220/230V unit is being
.supply20V1awithused
model.20V1tounitChange
supplywhenfailureUnitswitched on.
onusedbeingisunit20V1A.supply220Vor208Va
model.voltagecorrecttounitChangeNote: The 120V unit will be damaged!
Symptom Probable Cause Remedy
Swap supply & load wires. Supply terminal 1 andload terminal 4.
Installation & Service Manual
Page 14 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
Fig 12VDC Block Wiring Diagram
R9
R11
Z5
CN
1:1
CN
1:11
CN
1:14
CN
1:16
CN
1:17
CN
1:10
CN
1:12
CN
1:6
CN
1:4
CN
2:1
CN
2:2
CN
2:3
CN
2:6
CN
2:5
Z3
CN
1:8
VDR5
CN
2:4
R8
R7
Z4R
10
Z1
CN
1:7
CN
1:13
Z2
CN
1:3
CN
1:5
CN
1:9
CN
1:15
TH1
E1 G1
C1
TH2
E2 G2
C2
Sta
ticG
1
G2
Sw
itch
JP1
JP2 CT1
TX1
JP3
JP4
1
TAP
4
TAP
3
TAP
2
TAP
1
A1
A2
Sta
tic S
witc
hdr
iver
sC
ontro
l Car
dTa
p S
witc
hD
river
s
Tap
Sw
itch
1
Tap
Sw
itch
2
Tap
Sw
itch
3
Tap
Sw
itch
4
Com
pens
atio
nTr
ansf
orm
er
220V
120V
Line
in (S
uppl
y)
Line
out
(Loa
d)4
CN
4
CN
3
AC
1A
C2
AC
1A
C2
VS
S1
CTR
L1
VS
S2
CTR
L2
G1
E1
PS
1
G2
E2
PS
2
VS
S1
CTR
L1
VS
S2
CTR
L2
G1
E1
PS
1
G2
E2
PS
2
CN
6
CN
5
Gro
und
In Out
3
Com
mon
line
2
9
6 3
8242 1 4 5
4 ta
p6
tap
F1
F2
F3
F4
Installation & Service Manual
Page 15VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
Notes
Installation & Service Manual
Page 16 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
L1 L2 L3 L4 L5 L6 L7 DVDC S4T1K120 177 (6.97) 237 (9.33) 280 (11.02)
110 (4.33) 150 (5.90) 30 (1.18) 140 (5.50) 6.0 (0.24)
VDC L4T3K120
VDC S4T1K208 177 (6.97) 237 (9.33) 280 (11.02)110 (4.33)
VDC L4T5K208
VDC S4T1K220 177 (6.97) 237 (9.33) 280 (11.02)
VDC L4T5K220
VDC S4T1K230 177 (6.97) 237 (9.33) 280 (11.02)
VDC L4T5K230
Model VDC Dimensions mm (in)
170 (6.69) 250 (9.84) 293 (11.54) 162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31)
170 (6.69) 250 (9.84) 293 (11.54) 162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31)
170 (6.69) 250 (9.84) 293 (11.54)
150 (5.90)
162 (6.38) 311 (12.24)170 (6.69) 250 (9.84) 293 (11.54)
30 (1.18) 140 (5.50) 6.0 (0.24)
110 (4.33) 150 (5.90) 30 (1.18) 140 (5.50) 6.0 (0.24)
40 (1.57) 296 (11.65) 8.0 (0.31)
110 (4.33) 150 (5.90) 30 (1.18) 140 (5.50) 6.0 (0.24)
162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31)
Mechanical Construction
VDC S series - The VDC case is made from extruded aluminium sections. The four partsthat make up the case are interlocked and secured by screws. To remove the front coverunscrew four screws : the two top screws from the end plate where the terminal block islocated and the two bottom screws from the other end plate. Slide the front cover awayfrom the terminal block to access adjustment area.
VDC L series - The VDC case is made from extruded aluminium sections. The six partsthat make up the case are interlocked and secured by screws. To remove the front coverunscrew three screws : one from the front cover and one each from the top and bottomend plates.
Dimension Table
Installation & Service Manual
Page 17VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
Mechanical Outline
Fig 13Dimensions of the VDC series mm (inches)
L6L4
L5
L7
L3L2L6
L1
Note 1:Terminal cover shown dashed.Note 2:Terminal #1 - Line in (Supply)Terminal #2 - Common line inTerminal #3 - Common line outTerminal #4 - Line out (Load)
GroundScrews
TerminalCover
TerminalCover
GroundScrews
HZ
POWER
VOLTS
DATE MFG
SERIAL #
MODELVOLTAGE DIP-PROOFING INVERTER
"L" series case.
Model # exampleDPI52L3K23
orVDC L4T5K120
"S" series case.
Model # exampleDPI52S50-23
orVDC S4T1K230
Ø D
L7
L5
L4
L2
L3L1
L1
*L
1*
L6
L6
1 2 3 4
1 2 3 4
Ø D
1 2 3 4
1 2 3 4
Installation & Service Manual
Page 18 VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
GroundScrews
1 2 3 4 110
(4.3
3)
150 (5.90)
140 (5.51)
31(1
.22)
41.0
(1.6
1)41
.0(1
.61)
50(1
.97)
50
(1.
97)
120
(4.7
2)DPI
Bypass
Note 1:Dimension units.Without brackets - mm.With brackets - inches.
Note 2: Mounting holes 2 x 6 (0.25)Ø.
ToSupply
321
Line in Common Line Line out
To DPIor VDC
4
in out
321
Line in(Supply)
Common Line Line out(Load)
4
in out
AccessoriesHoused Bypass SwitchDescription
Where no-break maintenance is required a by pass switch must be installed. It connectsthe supply directly to the load, "Bypass" position, and disconnects the power terminals ofthe inverter without interrupting the supply. When in "DPI" position the load is connectedto the supply via the inverter.
SpecificationsMODEL BPSW25AELECTRICAL
Maximum current: 25AMaximum input voltage: 600Vac
TEMPERATUREMaximum working temperature: 45°C (113°F)
HOUSINGConstruction: Extruded AluminumHeight: 202mm (7.95in)Width: 150mm (5.9in)Depth: 141mm (5.55in)Mass: 1kg (2.2lbs)
Mechanical outline
Ordering
Stock No: Description5003-006 Housed By-Pass Switch 25Amp
Installation & Service Manual
Page 19VDC L4T & VDC S4T Series - Firmware ver 1.4 & up
Voltage Sag SimulatorDescription
The Sag Simulator is an effective tool toevaluate the effects of momentary voltage sagsand interruptions on industrial controls. Whenused in conjunction with a Voltage Dip-Proof-ing Inverter or a Voltage Dip Compensator andBypass switch, it may be used to prove theeffectiveness of the DPI or VDC as a solutionfor these power quality problems.The Sag Simulator is designed for 120/208/240Vac operation. The controls consist of avariac to set the sag depth, an LCD display toindicate the sag voltage value and programstatus, four programming keys to set up andoperate the simulator. A variable interrupt timersets the duration of the voltage sag and thepoint in the cycle at which it begins. Bothvariables are set using the programming keysand are indicated on the LCD display.Simulator output is short circuit and overloadprotected. A 5V synchronization pulse is pro-vided to trigger an oscilloscope. A photographappears on page 8; the specifications are shownbelow.
Sag Simulator Specifications
AC INPUT SUPPLYSupply voltage: 120/208/240Vac 50/60HzMaximum input voltage: +10%Full load current: 20A
VARIAC CONTROLVariac range: 0-240Vac RMSMaximum power: 1200VA @ 120V / 2400VA @ 240VMaximum continuous current:10A Maximum short term current for3 seconds: 20AOverload & short circuit protection: Yes
DIRECT VARIAC OUTPUTVariac range: 0-240Vac RMSMaximum power: 1200VA @ 120V / 2400VA @ 240VMaximum continuous current: 10AOverload & short circuit protection: YesSAG DELAY TIMERRange: 0.00 to 20.00 msSetting: 0.01 ms stepsSAG DURATION TIMERRange: 0.010 to 9.999 secondsSetting: 0.001 second steps
0 10 20 30 40 50 60 70 80 90 100Time ms
300
200
100
0
-100
-200
-300
Sup
ply
V
0 10 20 30 40 50 60 70 80 90 100Time ms
5
0
-5
V S
ync
Sag Duration 60ms
Sag Simulator outputSupply voltage - 220V 50Hz
Positive zerocrossing
Sag Delay5ms
Sag Depth50% Sag
Voltage110Vrms
Sync pulse output Terminals 4 & 5
Amplitude = 5V Duration = 60mS = Sag Duration
CONTROLS & INDICATORSProgramming: Four push switchesMenu/parameter indicaton: 4 x 20 LCD display
SYNC PULSE OUTPUTAmplitude: 5VPolarity: PositiveElectrically isolated output: YesDuration: Equal to sag duration
TEMPERATUREMaximum ambient working temperature: 45°C (113°F)
HOUSINGConstruction: Extruded aluminiumHeight: 390mm (15.35in )Width: 311mm (12.24in)Depth: 162mm (6.38in)Mass: 15kg (33lb)
Simulated Sag Profile
Installation & Service Manual
Measurlogic Inc.7334 S. Alton Way, Suite 14M
Centennial CO 80134, USATel:1-877-777-6567 Fax:425-799-4780
E-mail: [email protected]: www.Measurlogic.com
Doc Ref. 3704-010 Rev 1.4 October 11 th 2012 : LPW
DIP-PROOFINGTECHNOLOGIES INC.LEADERS IN VOLTAGE-DIP PROOFING
Voltage-Dip Compensators
LineVoltage
ControlVoltage
Voltage-Dip Compensator
2
C3
B3
Interlock
Stop
Start
MainBreaker
Motor Control Centre
A typical VDC connection diagram
C2
B2
Interlock
Stop
Start
C1
B1
Interlock
Stop
Start
Bypass Switch
41 StaticSwitch - 1
Controls
StaticSwitch - 2
StaticSwitch - 3
StaticSwitch - 4
StaticSwitch - 5
CompensationTransformer
3
For VDC L4T & S4T series Models120V / 208V / 220V / 230V 50/60Hz