VCB

2
CUSTOMER SPECS: 1. Breaker Particulars (a) Circuit breaker type Porcelain Clad VCB Service Outdoor (b) Voltage, phases and frequency 33 kV, 50 Hz, 3 Ph (c) Rated operating duty O – 0.3s min – CO – 3 min - CO (d) Rated current at reference ambient temperature A 400 (e) Short time current withstand for 1 sec duration kA (rms) 25 (f) Operating mechanism type Motor Charged spring manual trip & close facility to be provided (g) Minimum no. of auxiliary contacts 6 NO, 6 NC (h) Withstand test voltage (i) One minute power frequency kV (rms) 70 (ii) 1.2/50 sec impulse kV (peak) 170

description

Vauum CB

Transcript of VCB

Page 1: VCB

CUSTOMER SPECS:

1. Breaker Particulars

(a) Circuit breaker type Porcelain Clad VCB

Service Outdoor

(b) Voltage, phases and frequency 33 kV, 50 Hz, 3 Ph

(c) Rated operating duty O – 0.3s min – CO – 3 min - CO

(d) Rated current at reference ambient temperature

A 400

(e) Short time current withstand for 1 sec duration

kA (rms) 25

(f) Operating mechanism type Motor Charged spring manual trip & close facility to be provided

(g) Minimum no. of auxiliary contacts 6 NO, 6 NC

(h) Withstand test voltage

(i) One minute power frequency kV (rms) 70

(ii) 1.2/50 sec impulse kV (peak) 170

(i) Auxiliary control voltage(i) For closing / tripping coil 110 V DC

(ii) For spring charging motor 240 V AC

(iii) For space heaters and lighting 240 V AC

j Paint Shade 632 of IS 5

lL/R Switch & TNC Switch to be provided.