Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub- Committee October 26, 2011 Mira Vowles, P.E., CEM Emerging Technology Project Manager BPA Energy Efficiency

description

Variable Capacity Heat Pump RTF Sub-Committee October 26 , 2011. Mira Vowles, P.E., CEM Emerging Technology Project Manager BPA Energy Efficiency. PNW Small Office Baseline Energy Use per SF. Based on EnergyPro model for PNW locations. PNW Small Office VC HP Energy Use per SF. - PowerPoint PPT Presentation

Transcript of Variable Capacity Heat Pump RTF Sub-Committee October 26 , 2011

Page 1: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 1

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Variable Capacity Heat Pump RTF Sub-CommitteeOctober 26, 2011

Mira Vowles, P.E., CEM Emerging Technology Project ManagerBPA Energy Efficiency

Page 2: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 2

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

PNW Small Office BaselineEnergy Use per SFRTU Gas Furnace Energy Use per Square Foot

 Cooling

(kWh/SF)Heating (Th/SF) Fans (kWh/SF) Total HVAC (kWh/SF)

Seattle 0.7 0.0 6.4 7.2

Spokane 1.2 0.1 6.5 7.7

RTU Heat Pump Energy Use per Square Foot

  Cooling (kWh) Heating (kWh) Fans (kWh) Total (kWh)

Seattle 0.7 0.6 6.4 7.7

Spokane 1.2 1.8 6.5 9.5

Based on EnergyPro model for PNW locations

Page 3: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 3

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

PNW Small Office VC HPEnergy Use per SF

VRF Heat Pump Energy Use per Square Foot

 Cooling

(kWh/SF)Heating (kWh/SF)

Fans (kWh / SF) Total HVAC (kWh/SF)

 

Seattle 1.2 0.7 0.7 2.7 

Spokane 1.3 1.6 0.8 3.7 

VRF Heat Recovery Energy Use per Square Foot

 Cooling

(kWh/SF)Heating (kWh/SF)

Fans (kWh/SF)

Branch Box (kWh / SF)

Total HVAC (kWh/SF)

Seattle 1.3 0.8 0.7 0.0 2.8

Spokane 1.4 1.7 0.8 0.0 4.0

Based on EnergyPro model for PNW locations

Page 4: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 4

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Small Office VRF Savings Summary

Measure Description Location (TMY)Electric Savings

(kWh / SF)Gas Heat Offset

(Therms / SF)% HVAC Electric

Savings

Single zone RTU with gas heat replaced on burn-out to VRF HP system

Seattle 4.5 0.0 25%

Single zone RTU with gas heat replaced on burn-out to VRF HP system

Spokane 3.9 0.1 21%

Single zone RTU heat pump replaced on burn-out to VRF HP system

Seattle 5.0 28%

Single zone RTU heat pump replaced on burn-out to VRF HP system

Spokane 5.8 30%

Average 4.8 (kWh / SF) 26%

Page 5: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 5

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

PNW Medium Office Energy UseVRF Heat Pump

Cooling (kWh) Heating (kWh) Fans (kWh) Total (kWh)

Seattle 52,759 17,252 22,320 92,331

Spokane 55,515 34,124 24,510 114,149

VRF Heat RecoveryCooling (kWh) Heating (kWh) Fans (kWh) Branch Box (kWh) Total (kWh)

Seattle 53,069 9,439 22,320 1,956 86,784

Spokane 52,075 29,633 24,510 1,917 108,135

VAV Gas Boiler ReheatCooling (kWh) Heating (therms) Fans (kWh) Pumps (kWh) Total (kWh)

Seattle 87,880 3,400 53,437 618 141,935

Spokane 89,446 4,938 61,871 902 152,219

VAV Electric ReheatCooling (kWh) Heating (kWh) Fans (kWh) Total (kWh)

Seattle 85,708 58,628 52,853 197,189

Spokane 86,970 84,725 60,665 232,360

Based on EnergyPro model for PNW locations

Page 6: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 6

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

PNW Medium Office BaselineEnergy Use per SF

VAV Gas Boiler Reheat

 Cooling

(kWh/SF)Heating (Th/SF)

Fans (kWh/SF)

Pumps (kWh/SF)

Total HVAC (kWh/SF)

Seattle 2.1 0.1 1.3 0.0 3.4

Spokane 2.2 0.1 1.5 0.0 3.7

VAV Electric Reheat 

 Cooling

(kWh/SF)Heating (kWh/SF)

Fans (kWh/SF)

Total HVAC (kWh/SF)

 

Seattle 2.1 1.4 1.3 4.8 

Spokane 2.1 2.0 1.5 5.6  

Based on EnergyPro model for PNW locations

Page 7: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 7

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

PNW Medium Office VC HPEnergy Use per SF

VRF Heat Pump

 Cooling

(kWh/SF)Heating (kWh/SF)

Fans (kWh / SF)

Total HVAC (kWh/SF)

 

Seattle 1.3 0.4 0.5 2.2 

Spokane 1.3 0.8 0.6 2.8 

VRF Heat Recovery

 Cooling

(kWh/SF)Heating (kWh/SF)

Fans (kWh/SF)

Branch Box

(kWh / SF)Total HVAC (kWh/SF)

Seattle 1.3 0.2 0.5 0.0 2.1

Spokane 1.3 0.7 0.6 0.0 2.6

Based on EnergyPro model for PNW locations

Page 8: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 8

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Medium Office VRF Savings Summary

Measure Description Location (TMY)Electric Savings

(kWh / SF)Gas Heat Offset

(Therms / SF)% HVAC Electric

Savings

Packaged VAV with gas boiler replaced on burn-out to VRF HP system

Seattle 1.2 0.1 35%

Packaged VAV with gas boiler replaced on burn-out to VRF HP system

Spokane 0.9 0.1 25%

Packaged VAV with elec reheat replaced on burn-out to VRF HP system

Seattle 2.5 53%

Packaged VAV with elec reheat replaced on burn-out to VRF HP system

Spokane 2.8 51%

Average 1.9 (kWh / SF) 41%

Page 9: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 9

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Small Office VRF Cost Effectiveness

60%$343

per ton3.2BCRAverage

60.7%$41273.6860Spokane

Small Office ASHRAE System #4 (Packaged single zone heat pump)

4

65.3%$36073.1860Seattle

Small Office ASHRAE System #4 (Packaged single zone heat pump)

3

51.3%$28193.1835Spokane

Small Office ASHRAE System #3 (Packaged single zone AC with gas heat)

2

62.5%$31983.1835Seattle

Small Office ASHRAE System #3 (Packaged single zone AC with gas heat)

1

% HVAC Savings

BPA Incentive

($)

SPB (years)

BCRIncr. Cost ($ / ton)

Location (TMY)

Baseline SystemVRF HP

Measure #

60%$343

per ton3.2BCRAverage

60.7%$41273.6860Spokane

Small Office ASHRAE System #4 (Packaged single zone heat pump)

4

65.3%$36073.1860Seattle

Small Office ASHRAE System #4 (Packaged single zone heat pump)

3

51.3%$28193.1835Spokane

Small Office ASHRAE System #3 (Packaged single zone AC with gas heat)

2

62.5%$31983.1835Seattle

Small Office ASHRAE System #3 (Packaged single zone AC with gas heat)

1

% HVAC Savings

BPA Incentive

($)

SPB (years)

BCRIncr. Cost ($ / ton)

Location (TMY)

Baseline SystemVRF HP

Measure #

Page 10: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 10

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Medium Office VRF Savings Summary

33%$240

per ton4.1BCRAverage

42.5%$37865.5540Spokane

Medium Office ASHRAE System #6 (Packaged VAV with electric reheat)

8

31.5%$34854.8540Seattle

Medium Office ASHRAE System #6 (Packaged VAV with electric reheat)

7

25.0%$9932.6540Spokane

Medium Office ASHRAE System #5 (Packaged VAV with gas boiler reheat)

6

34.9%$13533.4540Seattle

Medium Office ASHRAE System #5 (Packaged VAV with gas boiler reheat)

5

% HVAC Savings

BPA Incentive

($)

SPB (years)

BCRIncr. Cost ($ / ton)

Location (TMY)

Baseline SystemVRF HP

Measure #

33%$240

per ton4.1BCRAverage

42.5%$37865.5540Spokane

Medium Office ASHRAE System #6 (Packaged VAV with electric reheat)

8

31.5%$34854.8540Seattle

Medium Office ASHRAE System #6 (Packaged VAV with electric reheat)

7

25.0%$9932.6540Spokane

Medium Office ASHRAE System #5 (Packaged VAV with gas boiler reheat)

6

34.9%$13533.4540Seattle

Medium Office ASHRAE System #5 (Packaged VAV with gas boiler reheat)

5

% HVAC Savings

BPA Incentive

($)

SPB (years)

BCRIncr. Cost ($ / ton)

Location (TMY)

Baseline SystemVRF HP

Measure #

Page 11: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 11

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Proposed VRF Measures

VC HP Measure #

Measure Description

Average Electric

Savings (kWh / ton)

Total Building % Electric Savings

1Office Building VRF HP

system retrofit (< 80 tons per building)

1,573 26%

2Office Building VRF HP system retrofit (>= 80

tons per building)1,119 41%

Page 12: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 12

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Variable Refrigerant Flow System Definition

Variable refrigerant flow (VRF) systems, either heat-pump or heat-recovery styles, provide heating and air-conditioning, and typically consist of:

1. An outdoor unit with inverter driven compressor(s) and condenser fan, over 6 tons of capacity (72,000 Btu/h),

2. Multiple indoor units with multi-speed fans, electronic expansion devices and dedicated microprocessors,

3. Refrigerant piping between the outdoor and indoor units,

4. A zone temperature control device interlocked with a system controller.

Page 13: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 13

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Office Building Definition A building used primarily for office functions, including

desk-work, reading and light equipment (computer, copier, printer, telephone, etc.) use.

Office occupancies are further defined by

overall occupant densities between 50 and 300 square feet per person,

overall lighting power densities between 0.5 and 2 watts per square foot, and

overall equipment plug loads between 0.1 and 1.5 watts per square foot.

Page 14: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 14

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

Office Building Definition

Can whole building regression analysis be used to verify savings?

How many systems need to be evaluated?

How can buildings with significant other changes be excluded?

Other?

Page 15: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 15

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

VRF Program Evaluation Questions

Can whole building regression analysis be used to verify savings?

How many systems need to be evaluated?

How can buildings with significant other changes be excluded?

Other?

Page 16: Variable Capacity Heat Pump RTF Sub-Committee October  26 , 2011

Slide 16

B O N N E V I L L E P O W E R A D M I N I S T R A T I O N

VRF Program Delivery Questions Can this be a utility equipment rebate program, instead of

an upstream program?

Limit to replacement on burn-out?

How to ensure replacement on burn-out?

Limit to baseline systems?

How to ensure baseline systems?

Other?