VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem...

12
VALVETRAB SQ... Exchangeable structure Remote indication contact Universal installation options Pulse counter Optical diagnostic and status indicator per phase NEMA 1 / IP40 metal housing NEMA 4X / IP66 housing available Remote indication contact Acoustic alarm Optical diagnostic and status indicator per phase Compact design NEMA 4X / IP66 housing VALVETRAB SQ SP VALVETRAB SQ CC VALVETRAB SQ SI VALVETRAB SQ SE 64 PHOENIX CONTACT Surge protection for the NEMA power supply unit Main range & features Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Transcript of VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem...

Page 1: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

Inhalt 9 kaliert7% Breite s

VALVETRAB SQ...

Exchangeable structure

Remote indication contact

Universal installation options

Pulse counter

Optical diagnostic and status indicator per phase

NEMA 1 / IP40 metal housing

NEMA 4X / IP66 housing available

Remote indication contact

Acoustic alarm

Optical diagnostic and status indicator per phase

Compact design

NEMA 4X / IP66 housing

VALVETRAB SQ SP

VALVETRAB SQ CC

VALVETRAB SQ SI

VALVETRAB SQ SE

VALVETRAB-SQ …

includes surge protection devices for American power supply systems. These have been specially designed for the American installation requirements.

offers complete protection against destructive surge voltages.

to the control cabinet or directly on electrical devices.

high discharge capacity of rated surge currents up to 200 kA per phase. The individual fuse for every protective path integrated in the design lends additional safety to the products.

approved as per the UL 1449 2nd edition 2007.

64 PHOENIX CONTACT

Surge protection for the NEMA power supply unitMain range & features

Max. surge current capacity

Status LEDs

Acoustic alarm

Remote indication contact

Pulse counter

Degree of protection

Short Circuit Current Rating (SCCR)

Filtering

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 2: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

Inhalt 9 kaliert7% Breite s

Comprehensive protection

Cascaded (stepped) use of VAL-SQ protective devices in building installation ensures effective protection of electrical systems.

VALVETRAB-SQ … The VALVETRAB-SQ product range

includes surge protection devices for American power supply systems. These have been specially designed for the American installation requirements.

Protection for all installation locations:– VAL-SQ SE (Service Entrance - for the

main supply)– VAL-SQ SP (Sub-Panel - for the sub-

distribution panels)– VAL-SQ CC (Control Cabinet - for the

control cabinet) – VAL-SQ SI (Small Installation - for the

equipment). The common use of protective devices

offers complete protection against destructive surge voltages.

Protective devices can be mounted next to the control cabinet or directly on electrical devices.

The devices have a protective circuit with high discharge capacity of rated surge currents up to 200 kA per phase. The individual fuse for every protective path integrated in the design lends additional safety to the products.

The entire product range has been approved as per the UL 1449 2nd edition 2007.

65PHOENIX CONTACT

Surge protection for the NEMA power supply unitMain range & features

Service Entrance Sub-Panel Control Cabinet

VAL-SQ SE VAL-SQ SP VAL-SQ CC

Features– The display with surge counter reflects

the number of power pulse currents discharged safely to ground.

– Acoustic status alarm of the protective device for the VAL-SQ SE and VAL-SQ SP products in the event of damage

– LEDs in all VAL-SQ products for continuous status monitoring of every phase

VAL-SQ SE VAL-SQ SP VAL-SQ CC VAL-SQ SI

Max. surge current capacity 120, 160 and 200 kA

120 kA 80 kA 40 kA 40 kA 25 kA

Status LEDs

Acoustic alarm - - -

Remote indication contact - - -

Pulse counter - - - - -

Degree of protection NEMA 1 / IP40 NEMA 4X / IP66 NEMA 1 / IP40 NEMA 1 / IP40 NEMA 4X / IP66 NEMA 4X / IP66

Short Circuit Current Rating (SCCR)

200 kA 200 kA 22 kA 22 kA 10, 25 and 200 kA 22 kA

Filtering -30 dB -30 dB -30 dB - -

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 3: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

Inhalt 9 kaliert7% Breite s

The selection matrix makes it easy to select suitable surge protection for the desired application.

VA

L-S

Q S

E Ideal protection for the main distributor

Multi-phase surge protection with remote indication contact, status LED, interference suppressor filter and pulse counter

VA

L-S

Q S

P Ideal protection for the sub-distribution panels

Multi-phase surge protection with remote indication contact and interference suppressor filter in a compact housing

VA

L-S

Q C

C

Adapted for the installation in the control cabinet

Multi-phase surge protection with interference suppressor filter in a compact housing

VA

L-S

Q S

I Ideal protection for small systems and equipment with limited space

Multi-phase surge protection with interference suppressor filter in a compact housing

Inst

allat

ion

loca

tion

Descr

iptio

n

66 PHOENIX CONTACT

Surge protection for the NEMA power supply unitSelection guide

Designation structure

VAL - SQ - SE 200 - 277/480Y

Product range

VALVETRAB

SQ

Range group

SE - Main supply

SP - Sub-distribution panels

CC - Control cabinet

SI - Equipment

Rated max. surge current

Voltage system / network type

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 4: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

Inhalt 9 kaliert7% Breite s

Multi-phase surge protection with remote indication contact, status LED, interference suppressor filter and

Multi-phase surge protection with remote indication contact and interference suppressor filter in a compact

Ideal protection for small systems and equipment with

2 1 200 kA

200 kA

68

2 1 160 kA 68

2 1 120 kA 68

2 4X 120 kA 200 kA 70

2 1 80 kA 22 kA 70

2 1 40 kA 22 kA 72

1, 2 4X 40 kA 22 kA 73

1, 2 4X 25 kA 10 kA 73

Max

. sur

ge cu

rren

t cap

acity

(8/2

0 µs)

UL type

NEM

A clas

s

SCCR

LED stat

us d

isplay

Acous

tic al

arm

Remot

e in

dica

tion

cont

act

Pulse

coun

ter

Groun

d co

nnec

tion

Filter

Page

67PHOENIX CONTACT

Surge protection for the NEMA power supply unitSelection guide

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 5: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

L1 L2 N GND

� �� � �

C NC NO L1 L2 L3 N GND C NC NO

� � �� � � �

Inhalt 9 kaliert7% Breite s

Description Reference Type Order No.Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.

Service entrance surge protection for 120/240 split-phase

configuration

120 kA 1 VAL-SQ SE 120-120/240S/FM 2804021 1

160 kA 1 VAL-SQ SE 160-120/240S/FM 2804034 1

200 kA 1 VAL-SQ SE 200-120/240S/FM 2804047 1

Service entrance surge protection for 120/208 Wye configuration

120 kA 2 VAL-SQ SE 120-120/208Y/FM 2803917 1

160 kA 2 VAL-SQ SE 160-120/208Y/FM 2803920 1

200 kA 2 VAL-SQ SE 200-120/208Y/FM 2803933 1

Service entrance surge protection for 277/480 Wye configuration

120 kA 3 VAL-SQ SE 120-277/480Y/FM 2804076 1

160 kA 3 VAL-SQ SE 160-277/480Y/FM 2804089 1

200 kA 3 VAL-SQ SE 200-277/480Y/FM 2804092 1

Service entrance surge protection for 347/600 Wye configuration

120 kA 4 VAL-SQ SE 120-347/600Y/FM 2804115 1

160 kA 4 VAL-SQ SE 160-347/600Y/FM 2804128 1

200 kA 4 VAL-SQ SE 200-347/600Y/FM 2804131 1

Service entrance surge protection for 480 Delta configuration

120 kA 5

160 kA 5

200 kA 5

Service entrance surge protection for 600 Delta configuration

120 kA 6

160 kA 6

200 kA 6

Service entrance surge protection for 120/240 High-Leg Delta

configuration

120 kA 7

160 kA 7

200 kA 7

Technical data 1 2 3 4

MCOV V 150 V / - 150 V / - 320 V / - 420 V / -

Suppressed voltage rating (SVR)

L-N / L-G 500 V / 500 V 500 V / 500 V 900 V / 1200 V 1200 V / 1500 V

N-G / L-L 500 V / 800 V 500 V / 800 V 1200 V /

1800 V

1500 V / 2500 V

Short circuit current rating (SCCR) 200 kA 200 kA

UL type Type 2 Type 2

Degree of protection IP40 / NEMA 1 IP40 / NEMA 1

Error/status indicator Phase LEDs / Audible alarm / Remote indicator contact Phase LEDs / Audible alarm / Remote indicator contact

Temperature range -40°C ... 60°C -40°C ... 60°C

Dimensions W / H / D 381.00 mm / 356.00 mm / 99.00 mm 381.00 mm / 356.00 mm / 99.00 mm

Test standards UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 / UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45

68 PHOENIX CONTACT

VAL-SQ SE…-120/240S/FMArrester for 120/240 V single / split phase

VAL-SQ SE ... Y/FMArrester for 120/208 V, 277/480 V, 347/600 V Wye systems

The VAL-SQ SE… provides maximum surge protection for the service entrance. These units are available with 120, 160 and 200 kA surge current ratings to protect electronic equipment in industrial, medical and commercial applications.

The VAL-SQ SE… utilizes a hybrid suppression circuit, Sine Wave Tracking, in a single, replaceable module. It provides both transient protection and up to -30 dB of noise filtration. Each surge suppression mode is individually fused.Approvals starting on page 208.

Device protection for the service entrance

Surge protection for the NEMA power supply unitSurge protection devices

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 6: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

L1 L2 L3 N GND C NC NO

� � �� � � �

L1 L2 L3 N GND C NC NO

� � �� � � �

Inhalt 9 kaliert7% Breite s

Type Order No.Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.

VAL-SQ SE 120 120/240S-R 2804348 1

VAL-SQ SE 160-120/240S-R 2804351 1

VAL-SQ SE 200-120/240S-R 2804364 1

VAL-SQ SE 120-120/208Y-R 2804173 1

VAL-SQ SE 160-120/208Y-R 2804225 1

VAL-SQ SE 200-120/208Y-R 2804270 1

VAL-SQ SE 120-277/480Y-R 2804199 1

VAL-SQ SE 160-277/480Y-R 2804241 1

VAL-SQ SE 200-277/480Y-R 2804296 1

VAL-SQ SE 120-347/600Y-R 2804209 1

VAL-SQ SE 160-347/600Y-R 2804254 1

VAL-SQ SE 200-347/600Y-R 2804306 1

VAL-SQ SE 120-480D/FM 2804144 1 VAL-SQ SE 120-480D-R 2804212 1

VAL-SQ SE 160-480D/FM 2804157 1 VAL-SQ SE 160-480D-R 2804267 1

VAL-SQ SE 200-480D/FM 2804160 1 VAL-SQ SE 200-480D-R 2804319 1

VAL-SQ SE 120-600D/FM 2804513 1 VAL-SQ SE 120-600D-R 2804539 1

VAL-SQ SE 160-600D/FM 2804520 1 VAL-SQ SE 160-600D-R 2804596 1

VAL-SQ SE 200-600D/FM 2804526 1 VAL-SQ SE 200-600D-R 2804552 1

VAL-SQ SE 120-120/240HLD/FM 2803969 1 VAL-SQ SE 120-120/240HLD-R 2804186 1

VAL-SQ SE 160-120/240HLD/FM 2803975 1 VAL-SQ SE 160-120/240HLD-R 2804238 1

VAL-SQ SE 200-120/240HLD/FM 2803988 1 VAL-SQ SE 200-120/240HLD-R 2804283 1

5 6 7

640 V / - 840 V / - 320 V / 150 V

- / - - / - 800 V / 900 V

- / 1800 V - / 2500 V 500 V / 800 V

200 kA 200 kA

Type 2 Type 2

IP40 / NEMA 1 IP40 / NEMA 1

Phase LEDs / Audible alarm / Remote indicator contact Phase LEDs / Audible alarm / Remote indicator contact

-40°C ... 60°C -40°C ... 60°C

381.00 mm / 356.00 mm / 99.00 mm 381.00 mm / 356.00 mm / 99.00 mm

UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 / UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45

69PHOENIX CONTACT

VAL-SQ SE ... D/FMArrester for 480 V, 600 V Delta systems

VAL-SQ SE ... HLD/FMArrester for 120/240-208 V High Leg Delta systems

VAL-SQ SE … -RReplacement modules for VAL-SQ SE... arresters

Surge protection for the NEMA power supply unitSurge protection devices

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 7: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

L1 L2 N GND

� �� � �

C NC NO L1 L2 L3 N GND C NC NO

� � �� � � �

Inhalt 9 kaliert7% Breite s

Description Type Order No.Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.

Service panel surge protection for 120/240 single / split-phase

configuration

80 kA VAL-SQ SP 80-120/240S/FM 2804000 1

120 kA VAL-SQ SP 120-120/240S/FM 2804018 1

Service panel surge protection for 120/208 Wye configuration

80 kA VAL-SQ SP 80-120/208Y/FM 2803894 1

120 kA VAL-SQ SP 120-120/208Y/FM 2803904 1

Service panel surge protection for 277/480 Wye configuration

80 kA

120 kA

Service panel surge protection for 120/240 High-Leg Delta

configuration

80 kA

120 kA

Service panel surge protection for 347/600 Wye configuration

80 kA

Service panel surge protection for 600 Delta configuration

80 kA

Technical data ...80-120/240S/FM ...120-120/240S/FM ...80-120/208Y/FM ...120-120/208Y/FM

MCOV 150 V / - 150 V / - 150 V / - 150 V / -

Suppressed voltage rating (SVR)

L-N / L-G 400 V / 500 V 400 V / 400 V 400 V / 500 V 400 V / 400 V

N-G / L-L 400 V / 800 V 400 V / 800 V 400 V / 800 V 400 V / 800 V

Short circuit current rating (SCCR) 22 kA 200 kA 22 kA 200 kA

UL type Type 2 Type 2 Type 2 Type 2

Connection data

Power (AWG / length) 10 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm

Remote indicator contact #24 AWG/0.205 mm² wires

(61 cm long)

#24 AWG/0.205 mm² wires

(61 cm long)

#24 AWG/0.205 mm² wires

(61 cm long)

#24 AWG/0.205 mm² wires

(61 cm long)

Degree of protection IP40 / NEMA 1 IP40 / NEMA 1

Error/status indicator Phase LEDs / Audible alarm / Remote indicator contact Phase LEDs / Audible alarm / Remote indicator contact

Temperature range -40°C ... 60°C -40°C ... 60°C

Dimensions W / H / D 250.00 mm / 122.00 mm / 79.00 mm 250.00 mm / 122.00 mm / 79.00 mm

Test standards UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 / UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45

70 PHOENIX CONTACT

VAL-SQ SP …-120/240S/FMArrester for 120/240 V split / split phase

VAL-SQ SP…-120/208Y/FMArrester for 120/208 V Wye systems

The VAL-SQ SP… provides 80 or 120 kA of surge current rating per phase. The VAL-SQ SP… SPD allows protection to be installed adjacent to service panels or near sensitive equipment. The VAL-SQ SP… includes sine wave tracking circuitry that provides up to -30 dB of noise attenuation. Each surge suppression mode is individually fused.Approvals starting on page 208.

Device protection for the service panel

Surge protection for the NEMA power supply unitSurge protection devices

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 8: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

L1 L2 L3 N GND C NC NO

� � �� � � �

L1 L2 L3 N GND C NC NO

� � �� � � �

L1 L2 L3 N GND C NC NO

� � �� � � �

Inhalt 9 kaliert7% Breite s

Type Order No.Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.

VAL-SQ SP 80-277/480Y/FM 2804050 1

VAL-SQ SP 120-277/480Y/FM 2804063 1

VAL-SQ SP 80-120/240HLD/FM 2803959 1

VAL-SQ SP 120-120/240HLD/FM 2803962 1

VAL-SQ SP 80-347/600Y/FM 2804102 1

VAL-SQ SP 80-600D/FM 2804500 1

...80-

277/480Y/FM

...120-

277/480Y/FM

...80-347/600Y/FM ...80-120/240HLD/FM ...120-120/240HLD/FM VAL-SQ SP 80-600D/FM

320 V / - 320 V / - 420 V / - 275 V / 150 V 275 V / 150 V 840 V / -

900 V / 900 V 800 V / 800 V 1200 V / 1200 V 700 V / 700 V 800 V / 800 V - / -

900 V / 1800 V 800 V / 1600 V 1200 V / 2500 V 500 V / 1300 V 400 V / 1500 V - / 2500 V

22 kA 200 kA 22 kA 22 kA 200 kA 200 kA

Type 2 Type 2 Type 2 Type 2 Type 2 Type 2

10 AWG / 61

cm

10 AWG / 61

cm

10 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm

#24

AWG/0.205

mm² wires

(61 cm long)

#24

AWG/0.205

mm² wires

(61 cm long)

#24 AWG/0.205 mm² wires

(61 cm long)

#24 AWG/0.205 mm² wires

(61 cm long)

#24 AWG/0.205 mm² wires

(61 cm long)

#24 AWG/0.205 mm² wires (61 cm long)

IP40 / NEMA 1 IP40 / NEMA 1 IP40 / NEMA 1

Phase LEDs / Audible alarm / Remote indicator contact Phase LEDs / Audible alarm / Remote indicator contact Phase LEDs / Audible alarm / Remote indicator contact

-40°C ... 60°C -40°C ... 60°C -40°C ... 60°C

250.00 mm / 122.00 mm / 79.00 mm 250.00 mm / 122.00 mm / 79.00 mm 250.00 mm / 122.00 mm / 79.00 mm

UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 / UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 / UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45 IEEE C62.45

71PHOENIX CONTACT

VAL-SQ SP …Y/FMArrester for 277/480 V and 347/600 V Wye systems

VAL-SQ SP… 120/240HLD/FMArrester for 120/240-208 V High Leg Delta systems

VAL-SQ SP 80-600D/FMArrester for 600 V Delta systems

Surge protection for the NEMA power supply unitSurge protection devices

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 9: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

L1 L2 GND N

� � �

L1 L2 L3 GND N

� � � �

Inhalt 9 kaliert7% Breite s

Description Type Order No.Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.

Component surge protection

120/240 V AC single/split phase,3-wire + Gnd VAL-SQ CC 40-120/240S 2803991 1

120/208 V AC Wye, 4-wire + Gnd VAL-SQ CC 40-120/208Y 2803881 1

Component surge protection

120 V, 2-phase with common GND-N

Component surge protection

120 V, 2-phase with separate GND-N

240 V, 2-phase with separate GND-N

Component surge protection

Up to 600 V, 3-phase with common GND-N

Technical data

MCOV 150 V / - 150 V / -

Suppressed voltage rating (SVR)

L-N / L-G 500 V / 800 V 500 V / 800 V

N-G / L-L 400 V / 800 V 400 V / 800 V

Short circuit current rating (SCCR) 22 kA 22 kA

UL type Type 2 Type 2

Connection data

Power (AWG / length) 10 AWG / 61 cm 10 AWG / 61 cm

Degree of protection IP40 / NEMA 1 IP40 / NEMA 1

Housing material Metal Metal

Error/status indicator Optical / - / - Optical / - / -

Temperature range -40°C ... 60°C -40°C ... 60°C

Dimensions W / H / D 190.00 mm / 108.00 mm / 63.00 mm 190.00 mm / 108.00 mm / 63.00 mm

Test standards UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 / UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45

72 PHOENIX CONTACT

VAL-SQ CC 40-120/240SArrester, 40 kA, for 120/240 V single / split phase

VAL-SQ CC 40-120/208YArrester, 40 kA, for 120/208 V Wye systems

The VAL-SQ CC is an economical method of protecting electronic equipment in light commercial, light industrial and residential environments. Hybrid suppressor circuit reduces leakage current end products -30 dB of noise filtration.

The VAL-SQ SI… provides surge protection in a compact, affordable package.Each surge suppression mode is individually fused.

Device protection for control cabinets and small installations

Surge protection for the NEMA power supply unitSurge protection devices

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 10: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

L1 L2 PE/N

� �

L1 L2 GND N

� � �

L1 L2 L3 PE/N

� � �

Inhalt 9 kaliert7% Breite s

Type Order No.Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.Type Order No.

Pcs. /

Pkt.

VAL-SQ SI 25-2C-120 2800003 1

VAL-SQ SI 40-2S-120 2800005 1

VAL-SQ SI 40-2S-240 2800006 1

VAL-SQ SI 40-3C-600 2800007 1

... 40-2S-120 ... 40-2S-240

120 V / - 120 V / - 240 V / - 600 V / -

500 V / - 500 V / - 900 V / - 1800 V / -

- / 900 V 800 V / - 900 V / - 2000 V / -

22 kA 25 kA 10 kA 200 kA

Type 1 & 2 Type 2 Type 2 Type 1 & 2

14 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm

IP66 / NEMA 4X IP66 / NEMA 4X IP66 / NEMA 4X

Non-metallic Non-metallic Non-metallic

Optical / - / - Optical / - / - Optical / - / -

-40°C ... 70°C -40°C ... 70°C -40°C ... 70°C

56.90 mm / 52.80 mm / 56.90 mm 76.20 mm / 69.30 mm / 91.40 mm 91.40 mm / 69.30 mm / 76.20 mm

UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 / UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 / UL 1449 2nd edition, February 2007 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45 IEEE C62.45

73PHOENIX CONTACT

VAL-SQ SI 25-2C-120Arrester, 25 kA, 2-phase

VAL-SQ SI 40-…Arrester, 40 kA, 2-phase

VAL-SQ SI 40-3C-600Arrester, 40 kA, 3-phase

Surge protection for the NEMA power supply unitSurge protection devices

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 11: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

v

Inhalt 9 kaliert7% Breite s

Network type Application

Split/Single-phase

120/240 V

Three-phase high-leg Delta

120/240-208 V

74 PHOENIX CONTACT

Surge protection for the NEMA power supply unitApplications

VAL-SQ SP

VAL-SQ SE

VAL-SQ SE VAL-SQ SI

VAL-SQ CCVAL-SQ SP

VAL-SQ SI VAL-SQ SI

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com

Page 12: VALVETRAB-SQ VALVETRAB SQ - Power/mation SQ... Exchangeable ... EM A as s C R L E D s ta y arm Rem ot e i nd ... Service entrance surge protection for 277/480 Wye configuration

Inhalt 9 kaliert7% Breite s

Network type Application

Three-phase Delta

Three-phase Wye

120/208 V277/480 V347/600 V

75PHOENIX CONTACT

Surge protection for the NEMA power supply unitApplications

VAL-SQ SE VAL-SQ SP

VAL-SQ CCVAL-SQ SPVAL-SQ SE

VAL-SQ SI

VAL-SQ SI

Courtesy of Power/mation. 1310 Energy Lane, Saint Paul, MN 55108 [email protected] - 800-843-9859 - www.powermation.com