Vacuum Circuit Breakers Vacuum Interrupter
Transcript of Vacuum Circuit Breakers Vacuum Interrupter
www.lsis.biz
Pro-MEC
Vacuum Circuit Breakers Vacuum Interrupter
Vacuum Circuit Breaker & Vacuum Interrupter
LSIS Pro-MEC VCB is user-friendly to give more convenience and safety by providing high speed interrupting time (3cycles), adopting the rapid auto-reclosing method, and having wide range of accessories.
7.2kV Draw-out (F class)
24kV Draw-out (F class)
Ratings H1-4Constructional and operating characteristics H1-8Control circuit diagram H1-97.2kV dimension H1-1012kV dimension H1-1917.5kV dimension H1-2424kV dimension H1-27Accessories H1-35Types and ordering information H1-40
Vacuum Circuit Breaker
Features & Ordering information H1-43
VI internal structure H1-44
Basic functions and interrupting action H1-45
VI endurance by interrupting current H1-46
Dimensions H1-48
Technical data H1-50
Vacuum Interrupter
Pro-MEC VCB/VI
H1Contents
� Key Lock � Padlock of earthing switch � Button padlock � Position switch of the earthing switch� Button cover � Locking coil of earthing switch � Position switch (Cell switch) � Shutter padlock� Preparatory trip coil (Secondary trip coil) � MOC (Mechanically operated cell switch)
� Latch checking switch � TOC (Truck operated cell switch)� Charge indicator � Code plate (Miss insertion prevention)� Position padlock � Capacitor trip device� Earthing switch Note 1)
� Rectifier
Note 1) The earthing switch is not available for 17.5kV VCB.
Wide range of accessories (optional)
LSIS Pro-MEC VCB is user-friendly to give more convenience and safety by providing high speed interrupting time (3cycles), adopting the rapid auto-reclosing method, and having wide range of accessories.
7.2kV Draw-out (F class)24kV Draw-out (F class)
Vacuum Circuit BreakerVacuum Circuit Breaker
H1-2
High reliability of the operating mechanism- Separate design of the main circuit from theoperating mechanism.
- Adopt the toggle link method.- Improved the reliability of electric circuit.- Adopt the rapid auto-reclosing method as a standard option. (O-0.3sec.-CO-3min.-CO)
�Make short of the interrupting time. (3cycles)�Increase the rated short-circuit withstand
characteristics. (1sec. to 3sec.)
�Reinforce the insulation in the conduct, by adopting themolded housing in each phase.
�Built in the device making the contacts open first whendraw in and out.
�Adopt the tulip-shape connection between the cradle andthe VCB.
High interrupting performance Great operational safety
Compasion table for VCB (Short circuit test)[ ]
Compasion table for VCB (Short circuit test)
VACUUM CIRCUIT BREAKER
H1-3
H1-4
Ratings
Vacuum Circuit Breaker
Type LVB-06��-32D LVB-06��-40D
Rated voltage (kV) 7.2 7.2
Rated normal current (A) 1250 2000 3150 1250 2000 3150
Rated frequency (Hz) 50/60 50/60
Rated short-circuit breaking current (kA) 31.5 40
Rated short-circuit breaking capacity (MVA) 390 500
Rated short-time withstand current (kA/3sec) 31.5 40
Rated short-circuit making current (kAp) 82 104
Rated breaking time (Cycle) 3 3
Rated opening time (sec) ≤ 0.04 ≤ 0.04
No-load closing time (sec) ≤ 0.06 ≤ 0.06
Withstand Power frequency (kV/min) 20 20voltage Impulse (kV/1.2×50㎲) 60 60
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
TypeMechanical M2 (10,000 times) M2 (10,000 times)
test Electrical E2 (List1) E2 (List1)
Capacitive current switching Note 1) C2 C2
MechanicalWithout maintenance (Time) 20000 20000
LifetimeMaintenance (Time) 30000 30000
ElectricalWithout maintenance (Time) 20000 20000
Maintenance (Time) 30000 30000
Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b
Fixed Visible, Fixed Visible, Fixed Visible, Fixed Visible, Fixed
E-type Visible, Tulip Visible, Clip Visible, Tulip Visible, Tulip
InstallingDraw-out
F-type Visible, Tulip Visible, Tulip Visible, Tulip Visible, Tulipmethod
type G-type Note 2) - Visible, Tulip Visible, Tulip Visible, Tulip Visible, Tulip
T Enclosed, Tulip - Enclosed, Tulip -
M-type Enclosed, Tulip - Enclosed, Tulip -
E-type (kg) 131.5 134.5 210 135 138 210
VCB F-type (kg) 132.5 135.5 211 136 139 211
Weight G, M-type (kg) 132.5(159) 135.5(160) 220 136(162.5) 139(163.5) 220 Note 3) E-type (kg) 52 60 131 52 60 131
Cradle F-type (kg) 54.5 62.5 135 54.5 62.5 135
G-type (kg) 62.5(110) 135(117) 155 62.5(110) 135(117) 155
Applied standard IEC 62271-100 IEC 62271-100
Test laboratory KERI Note 4) � �
Note 1) Applied cable-charging current switching test2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T” in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)3) ( )* indicates the weight of Enclosed Tulip installing method VCB.4) KERI: Korea Electrotechnology Research Institute
▲ Enclosed VCB(Draw-out type, G-type)
▲ G-type Cradle(Enclosed, Tulip contact)
▲ Visible, Clip contact ▲ Visible, Tulip contact ▲ Enclosed, Tulip contact
H1-5
Type LVB-12��-32D/12, 20-T, 30 LVB-12��-40D/12, 20, 30 LVB-17��-40D/12, 20, 30
Rated voltage (kV) 12 12 17.5
Rated normal current (A) 1250 2000 3150 1250 2000 3150 1250 2000 3150
Rated frequency (Hz) 60(E1,E2,C2: PT & T) 50(E1,C2:KEMA), 60(M2,E2,C2: PT & T) 60
Rated short-circuit breaking current (kA) 31.5 40 40
Rated short-circuit breaking capacity (MVA) 650 831 1200
Rated short-time withstand current (kA/3sec) 31.5 40 40
Rated short-circuit making current (kAp) 81.9 104 104
Rated breaking time (Cycle) 3 3 3
Rated opening time (sec) 0.04 0.04 ≤0.04
No-load closing time (sec) 0.06 0.06 ≤0.06
Withstand Power frequency (kV/min) 28 28 38voltage Impulse (kV/1.2×50㎲) 75 75 95
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
TypeMechanical M2 (10,000 times) M2 (10,000 times) M2 (10,000 times)
test Electrical E2 (List 1) E2 (List 1) E2 (List 1)
Capacitive current switching Note) C2 C2 C2
MechanicalWithout maintenance (Time) 20,000 20,000 20,000
LifetimeMaintenance (Time) 30,000 30,000 30,000
ElectricalWithout maintenance (Time) 20,000 20,000 20,000
Maintenance (Time) 30,000 30,000 30,000
Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b 4a4b, 10a10b
Fixed - - -
Installing E-TYPE - - -
Method Draw-out F-TYPE - - -type G-TYPE Enclosed, Tulip Visible, Tulip Enclosed, Tulip Visible, Tulip Visible, Tulip
M-TYPE Enclosed, Tulip - - -
E-TYPE (kg) - - -
VCB F-TYPE (kg) - - -
WeightG, M-TYPE (kg) 159 160 220 162 163 220 200 205 260
E-TYPE (kg) - - - - - - - - -
Cradle F-TYPE (kg) - - - - - - - - -
G, M-TYPE (kg) 110 117 155 110 117 155 175 175 200
Applied standard IEC 62271-100
Test laboratory PT & T: E1, E2, C2, M2 KEMA, PT & T
Note) Applied cable-charging current switching test
H1-6
Vacuum Circuit BreakerRatings
H1-6
▲ Fixed type VCB ▲ E-type cradle ▲ F-type cradle ▲ G-type cradle(Withdrawable by screw)
▲ G-type cradle(Withdrawable by lever)
Type LVB-20��-13D LVB-20��-13D/T LVB-20��-16D LVB-20��-16D/T LVB-20��-25D LVB-20��-25D/TRated voltage (kV) 24 24 24Rated normal current (A) 630 630 630
1250 1250 12502000
Rated frequency (Hz) 50/60 50/60 50/60Rated short-circuit breaking current (kA) 12.5 16 25Rated short-circuit breaking capacity (MVA) 520 665 1000Rated short-time withstand current (kA/3sec) 12.5 16 25Rated short-circuit making current (kAp) 32.5 40 65Rated breaking time (Cycle) 3 3 3Rated opening time (sec) ≤ 0.04 ≤ 0.04 ≤ 0.04No-load closing time (sec) ≤ 0.06 ≤ 0.06 ≤ 0.06
Withstand Power frequency (kV/min) 50 50 50voltage Impulse (kV/1.2×50㎲) 125 125 125Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
TypeMechanical M2(10,000 times) M2(10,000 times) M2(10,000 times)
test Electrical E2 (List1) E2 (List1) E2 (List1)Capacitive current switching Note 1) C2 C2 C2
MechanicalWithout maintenance (Time) 20000 20000 20000
LifetimeMaintenance (Time) 30000 30000 30000
ElectricalWithout maintenance (Time) 20000 20000 20000Maintenance (Time) 30000 30000 30000
Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b 4a4b, 10a10bFixed Visible, Fixed - Visible, Fixed - Visible, Fixed -
E-type Visible, Clip Enclosed, Tulip Visible, Clip Enclosed, Tulip Visible, Clip Enclosed, TulipInstalling
Draw-out F-type Visible, Clip Enclosed, Tulip Visible, Clip Enclosed, Tulip Visible, Clip Enclosed, Tulipmethod
type G-type Note 2) Visible, Tulip Enclosed, Tulip Visible, Tulip Enclosed, Tulip Visible, Tulip Enclosed, TulipM-type - Enclosed, Tulip - Enclosed, Tulip - Enclosed, TulipE-type (kg) 145 145 145 145 145 145
VCB F-type (kg) 145 145 145 145 145 145
WeightG, M-type (kg) 155 187 155 187 155 187/218 (2000A)E-type (kg) 80 80 80 80 80 80
Cradle F-type (kg) 82 82 82 82 82 82G-type (kg) 110 120 110 120 110 120
Applied standard IEC 62271-100 IEC 62271-100 IEC 62271-100
Test laboratory KERI � - �
KEMA - � �
Note 1) Applied cable-charging breaking current2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T” in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)
H1-7H1-7
VCBON OFF
“a” contactON OFF
“b”contactOFFON
Motor
Closing Coil (C)The coil operated only when the power is applied continuouslyover 45ms. It has built-in electrically anti-pumping circuit.
��Position of the Aux.contact switch
Note 1) Range of the normal operating voltage: 85~110%2) DC 24V is the underdeveloped rating.
Shunt coil (TC)When the VCB is 'ON' position, even though the control powerof a shunt coil is 'OFF', the VCB maintains the 'ON' position.
Note 1) Range of the normal operating voltage: 70~110%2) DC 24V is the underdeveloped rating.
Auxiliary switchStandard 4a4b / Optional 10a10b
Charge indicator ofthe closing springIndicating the condition of the closing spring.
Position indicator of the main contactsIndicating the 'Close' or the 'Open' of the main contacts.Close position: ��ON�� Open position: ��OFF��
CounterMechanically counts the switching of the VCB by 5digits analog type counter (Standard option)
Charged Discharged
Close position Open position
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
Note 1) Range of the normal operating voltage: 85~110%2) DC 24V is the underdeveloped rating.
Note) The contact capacity of the following accessories are the same with that of the Aux. switch. Position switch, Closing sp ringcontact, Charging complete indicating contact, Position switch of the earthing switch, Mechanically operated cell switch,Truck operated cell switch.
The peak value of the Consumption Charging timeRated voltageinrush current (A)
Rated current (A) power (W) (Sec.)
DC 48V 21 4 350 13DC 110V 20 3 330 12DC 125V 20 3 330 12DC 220V 17 2.6 374 12
Classification General Inductive Contact load (A) load (A) configuration
AC250V 10 5125V 10 5
Contact Ratings 250V 10 5 4a4b
DC 125V 10 5 10a10b
30V 10 5
Rated voltage Rated current (A)
DC 48V 6DC 110V 3DC 125V 3DC 220V 2.5
Rated voltage Rated current (A)
DC 48V 6DC 110V 3DC 125V 3DC 220V 2.5
H1-8
Vacuum Circuit Breaker
H1-8
Constructional and operating characteristics
Manual chargeInsert the charge handle into the manual charge hole in the front of aVCB, and rotate it to clockwise over 40times and the chargecomplete with a metal sound.
Motor chargeIf you apply the control power to a VCB, the closing spring will becharged automatically by a motor and then the control power will beturned off by the built-in limit s/w. Please use the same controlvoltage for motor, Closing coil, Trip coil.
Sequence of the switching mechanism
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
⑪
①① Charge Indicator of the closing spring
②② Close button③③ Key lock (Optional)④④ Trip button⑤⑤ Manual charge hole⑥⑥ Position indicator
of the main contacts⑦⑦ Counter⑧⑧ Screw hole for draw-in
and draw-out ⑨⑨ Nameplate⑩⑩ Mounting hole⑪⑪ Safety cover
H1-9H1-9
Control circuit diagram
∅: E
xter
nal te
rmin
al o
f VCB
52: V
acuu
m c
ircui
t bre
aker
M: S
prin
g ch
argi
ng m
otor
TC: T
rip c
oil
TC1:
Sec
onda
ry T
rip c
oil
C: C
losin
g co
ilY:
Ant
i-pum
p re
lay
52a:
Aux
iliary
swi
tch
(NO
)
52b:
Aux
iliary
swi
tch
(NC)
LS1:
Clo
sing
inte
rlock
limit s
witc
h (o
nly
with
draw
able
type
)LS
2: M
otor
sto
ppin
g, c
losin
g sp
ring
char
ged
indi
catio
nLS
3: A
nti-c
losin
g, a
nti-p
umpi
ng lim
it swi
tch
LCS1
: Ope
ning
latc
h ch
eckin
g sw
itch(
prev
entin
g clo
sing
unle
ss th
e tri
p la
tch
is pr
oper
ly re
set)
LS4,
LS5
: Pos
ition
s/w
(clo
se in
test
pos
ition)
LS6,
LS7
: Pos
ition
s/w
(clo
se in
run
posit
ion)
Note
1)
LCS1
: Lat
ch ch
eckin
g sw
itch
2) T
rip co
il sup
ervis
ion (T
rip co
il mon
itorin
g co
ntac
t)3)
Pos
ition
switc
h: 4
a (T
erm
inal N
o.: 1
, 2, 3
, 4, 5
, 6, 7
, 8)
4) T
C1: S
econ
dary
trip
coil (
Prep
arat
ory t
rip co
il Ter
mina
l No.
: 82,
83)
5) I
n fix
ed ty
pe V
CB, L
S1 (C
losing
-coil
limit s
witch
) is n
ot a
vaila
ble.
※Ab
ove
circu
it diag
ram
is b
ased
on
‘OFF
’ sta
tus o
f VCB
. and
clos
ing sp
ring
is ch
arge
d.
Opt
ional
acce
ssor
ies
Conn
ectin
g te
rmin
al a
rrang
emen
t
B Ty
peA
Type
H1-10H1-10
Vacuum Circuit Breaker7.2kV dimension (VCB)
LVB-06P-32D, 40D (Visible, Fixed) - (1250/2000A)
LVB-06P-32D, 40D (Visible, Fixed) - (3150A)
��Top
��Top
��Side��Front
��Side��Front
*125.5 applied to all 7.2kV VCB.
<Terminal conductor>
(Unit: mm)
H1-11H1-11
LVB-06E, F, G-32D, 40D E, F, G class - (1250/2000A)
LVB-06G- 32D/T, 40D/T G class (Enclosed, Tulip contact) - (1250/2000A)
��Side��Front
��Top
��Side��Front
<Terminal conductor>
(Unit: mm)
H1-12
Vacuum Circuit Breaker7.2kV dimension (VCB)
H1-12
LVB-06E-32D, 40D E class (Visible, Tulip contact) - (3150A)
��Side��Front
LVB-06F-32D, 40D F class (Visible, Tulip contact) - (3150A)
��Side��Front
��Top
��Top
(Unit: mm)
H1-13H1-13
LVB-06G-32D, 40D G class (Visible, Tulip contact) - (3150A)
��Side��Front
��Top
(Unit: mm)
H1-14
LCL-06E-32D, 40D E class (Visible, Tulip contact) - (3150A)
��Side ��Top��Front
LCL-06E-32D, 40D E class (Visible, Tulip contact)
��Front
��Top<Terminal conductor>
(Unit: mm)
��SideRating 1250A 2000A
A 10 20
Vacuum Circuit Breaker
H1-14
7.2kV dimension (Cradle)
H1-15H1-15
LCL-06F-32D, 40D F class (Visible, Tulip contact) - (3150A)��Side��Front
��Top
LCL-06F-32D, 40D F class (Visible, Tulip contact) - (1250/2000A)
��Front
��Top
<Terminal conductor>
(Unit: mm)
��SideRating 1250A 2000A
A 10 20
H1-16
Vacuum Circuit Breaker7.2kV dimension (Cradle)
H1-16
LCL-06G-32D, 40D G class(Visible, Tulip contact) - (31.5/40kA 1250/2000A)
��Side��Front
��Top
<Terminal conductor>
(Unit: mm)
Rating 1250A 2000AA 10 20
H1-17H1-17
LCL-06G-20D/T, 25D/T, 32D/T, 40D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)
��Side��Front
��Top<Terminal conductor>
(Unit: mm)
Rating 31.5/40kA1250A 2000A
A 12 25B ∅48
H1-18
Vacuum Circuit Breaker7.2kV dimension (Cradle)
H1-18
LCL-06G-32D, 40D G class (Visible, Tulip contact) - (3150A)(Unit: mm)
��Side
��Top<Terminal conductor>
<User busbar reguirement>*To connect with VCB ’s bushing terminalsuser busbar should have below dimensionsand two holes.
H1-19H1-19
��Top
12kV dimension (VCB)
LVB-12G-32D/T G class (Enclosed, Tulip contact) - (1250/2000A)
LVB-12G-40D G class (Enclosed, Tulip contact) - (1250/2000A)
(Unit: mm)
��Side��Front
470
668
496
150 150
549
726.
5
295
330325
33.5 10288
438
69
355
40kA 1250/2000A G class
��Side��Front
H1-20
Vacuum Circuit Breaker12kV dimension (VCB)
LVB-12G-40D G class (Enclosed, Tulip contact) - (3150A)
40kA 3150A G class
714
620
360
336
210210
325
290
502747
676
1034
8.5
806.
6
��Side��Front
��Top
(Unit: mm)
H1-21
12kV dimension (Cradle)
LCL-12G-25D/T, 32D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)
��Side��Front
��Top<Terminal conductor>
(Unit: mm)
Rating 25kA1250A 2000A
A 12 25B ∅48
H1-22
Vacuum Circuit Breaker12kV dimension (Cradle)
LCL-12G-40D G class (Enclosed, Tulip contact) - (1250/2000A)
RUN
731.5
94663
029
5
1235
150
150
560
600
100 662
26
8326
60
150150
1250A:12t
2000A:25t
40kA 1250/2000A G class
4-∅14 Mount hole
��Side��Front
��Top<Terminal conductor>
(Unit: mm)
H1-23
LCL-12G-32D/LCL-12G-40D G class (Enclosed, Tulip contact) - (3150A)
40kA 3150A G class
1014
230 230
120
3514
5
70
12 12
764
439
360
1100
210
724100
210
760
800
4-∅14 Mount hole
��Side��Front
��Top<Terminal conductor>
(Unit: mm)
Vacuum Circuit Breaker17.5kV dimension (Cradle)
H1-24 H1-24
(Unit: mm)
LVB-17G-40D G class (Visible, Tulip contact) - (1250/2000A)
��Front ��Side
��Front ��Side ��Top
��Top
LVB-17G-40D G class (Visible, Tulip contact) - (3150A)
H1-25
LCL-17G-40D G class (Visible, Tulip contact) - (1250/2000A)
��Side
��Top<Terminal conductor>
(Unit: mm)
H1-26
Vacuum Circuit Breaker17kV dimension (VCB)
(Unit: mm)
LCL-17G-40D G class (Visible, Tulip contact) - (3150A)
��Side
��Top<Terminal conductor>
H1-27
24kV dimension (VCB)
LVB-20P-13D, 16D, 25D (Visible, Fixed) - (630/1250/2000A)
LVB-20E, F-13D/(T), 16D/(T), 25D/(T) E, F class - (630/1250/2000A)
��Front ��Side
<Visible, Clip contact> <Enclosed, Tulip contact>
<Terminal conductor>
��Front ��Side
Note ) In case of 12.5kA & 16kA 630A, the dimension shown in parenthesis should be applied.
(Unit: mm)
H1-28
Vacuum Circuit Breaker24kV dimension (VCB)
LVB-20G-13D, 16D, 25D G class (Visible, Tulip contact) - (630/1250A)
��Front ��Side
LVB-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)
��Front ��Side
Note 1) ( ): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T, LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.
2) IP Cover applied both sides in case of 265mm phase distance.
(Unit: mm)
H1-28
H1-29
24kV dimension (Cradle)
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
LCL-20E-13D, 16D, 25D E class (Visible, Clip contact) - (630/1250/2000A)
��Front ��Side
��Top<Terminal conductor>
Rating A B T630, 1250A 768 190.5 10
2000A 778 185.5 20
(Unit: mm)
H1-30
Vacuum Circuit Breaker24kV dimension (Cradle)
(Unit: mm)
LCL-20E-13D/T, 16D/T, 25D/T E class (Enclosed, Tulip contact) - (630/1250/2000A)
145
97.5
972
280
15
115
660
40 40
25
20 67 47 4542
40.5
2-∅14
20
4-∅14
20
4-∅14
20
947.5
1167
1120
265 265
110 400
265
400
820
ST: 260
265
404.
5
10(6
30/1
250A
)20
(200
0A)
340
1033
245
40
210
210.
590
202
100
300
∅6.5
40
40
40
40
1250A
40
9080
2000A
8010
0
300
730
960
630A
7-∅14
<Terminal conductor>
��Front ��Side
��Top
Rating A B T630, 1250A 768 190.5 10
2000A 778 185.5 20
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-31
<Terminal conductor>
LCL-20F-13D, 16D, 25D F class (Visible, Clip contact) - (630/1250/2000A)
��Top
��Front(Unit: mm)
��Side
Rating A B T630, 1250A 768 190.5 10
2000A 778 185.5 20
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-32
Vacuum Circuit Breaker24kV dimension (Cradle)
(Unit: mm)
LCL-20F-13D/T, 16D/T, 25D/T F class(Enclosed, Tulip contact) - (630/1250/2000A)
��Front ��Side
Rating A B T630, 1250A 768 190.5 10
2000A 778 185.5 20
��Top
<Terminal conductor>
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-33
<Terminal conductor>
LCL-20G-13D, 16D, 25D G class (Visible, Tulip contact) - (630/1250A)
��Front ��Side
��Top
(Unit: mm)
H1-34
Vacuum Circuit Breaker24kV dimension (Cradle)
210mm
LCL-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)��Front ��Side
��Top<Terminal conductor>
��Earthing Switch
Note) ( ): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T, LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.
(Unit: mm)
H1-35
Accessories
Note) In case that position of VCBchanged to “Run” or “Test” position,“a” contact will be closed.
Accessories for VCB
<Push bar>
Key lock When it is locked by a key, the closing operation is not available(electrically and mechanically) without a Key.
Button padlock Button padlock protects 'ON' or 'OFF' button when accident is occurredby operation at discretion.It is available to operate after release button padlock.
Button coverButton cover protects 'ON' of 'OFF' button when accident isoccurred by operation at discretion. It is available to operate by pushbar.
<G class>
Position switch (Cell switch)Indicating the position (Run or Test) of a VCB, by mechanicallypressing the switch when a VCB change the position. - RUN: 2a- TEST: 2a
H1-36
Vacuum Circuit BreakerAccessories
Accessories for VCB
Secondary coil (Preparatory trip coil)The main coil and the preparatory coil is connected in parallel. Soeven though there happens a fault in the trip coil, the VCB can betripped by one of the two trip coils.
Latch checking switchWhen the Latch is in abnormal position, the Latch checking switchprevents the closing operation even though there is the 'Closing'signal.
Charge indicatorRemotely indicates the charging is completed. (Standard Feature) - Terminal No.: 9, 10
Position padlockThe hole to prevent the draw-in and out of a VCB from the presentposition.('Run' or 'Test') Standard option in the interlock lever of the E, F class draw-out typeVCB. (Hole size = ∅ 8)
H1-37
<Earthing Switch Position Switch>
<Earthing Switch Locking Coil>
Accessories for Cradle
Earthing switch (for G class draw-out type only)For the safety during the maintenance of a VCB panel, discharge thecharging current in the load side of a VCB with this earthing switch.
Padlock of earthing switch (for G class draw-out type only)The hole to prevent the accident through carelessness earthingswitch operation, the locking of the earthing switch is available whenthe switch is in 'OFF' position. (Hole size = ∅8)
Position switch of the earthing switch (for G class draw-out type only)Indicates the 'ON' or 'OFF' status of the earthing switch. (5a5b)
Locking coil of earthing switch (for G class draw-out type only)To prevent the accident through carelessness earthing switchoperation, the earthing switch can be changed to 'ON' position afterreleasing the lock by magnetizing the coils.
H1-38
Vacuum Circuit BreakerAccessories
Accessories for Cradle
Shutter padlock The hole to lock the shutters (load and line side) in close position, toincrease the safety during the maintenance of a VCB draw-outposition.(Hole size = ∅8)
Mechanically operated cell switch (MOC)-for G class draw-out type onlyThe auxiliary switch (3a4b), which Indicate the 'ON' or 'OFF' conditionof a VCB, but operated only when the VCB is in 'Run' state. (Installedin the bottom of a cradle)
Truck operated cell switch (TOC) -for G class draw-out type onlyThe auxiliary switch (3a4b), which indicate the 'Run' state of a VCBand is operated by the movement of a VCB frame. (Installed in thebottom of a cradle)
Code plate (Miss insertion prevention) -for E, F class draw-out type onlyTo prevent the insert a VCB to a cradle, when the ratings of VCB andcradle are different.
PadlockTo prevent the insert draw-in/out handle to a screw hole by operatingG class VCB temporarily
Note) #11, 21 are Early “b” contact
Note) #11, 21 are Early “b” contact
H1-39
��Dimension
��Connection diagram
Standard tool
When the control power is off, theCTD supply the power for trippinga VCB.
Capacitor trip device (CTD)
When the DC power is not available, rectify the AC power andget the DC power for closing coil.
Rectifier
Optional accessories
Manual charging handleHandle for charging the spring manually.(Standard feature)
Handle for draw-in and outHandle for draw-in and out the VCB(Standard feature in the draw-out type)
E, F class G class
Ratings SpecificationType CB-T1 CB-T2
Rated input voltage AC100/110V AC200/220VFreguency (Hz) 50/60 50/60Charging volt(V) 140/155 280/310Charging time Within 10 Sec. after the AC power offTripping time Within 30 Sec. after the AC power off
Allowable Input85% ~ 100% 85% ~ 110%voltage range
Capacitor rating(μF) 1000 560
Type AC Input voltage Output current Rating time
VCB-X 1∅ 100/110V
40A DC 10 sec.1∅ 200/220V
+
- ~ ~
150
80 40
29.5
70
100
25
��Dimension
��Connection diagram ��CDT
H1-40
Cradle
12kV
LS VCB
Rated voltage12 12kV
Installation methodG G class draw-out type
MG class draw-out type+ Bushing
Revision No.
D Pro-MEC
Rated current12 1250A20 2000A30 3150A
Breaking current32 31.5kA40 40kA
Breaking current32 31.5kA40 40kA
Auxiliary switch2B 4a4b(A type connector)2E 10a10b(A type connector)2G 4a4b(B type connector)2H 10a10b(B type connector)
LS Cradle Installation method
GG class draw-out type
Rated current12 1250A20 2000A30 3000A
Revision No.D Pro-MEC
Rated voltage12 12kV
Control voltage1A DC110V1B DC220V1C DC48V1E DC125V
AccessoriesB Position Switch (RUN/TEST:2a2a)C1 Button Padlock (ON) C2 Button Padlock (OFF)C3 Button Padlock (ON/OFF) D1 Button Cover (ON)D2 Button Cover (OFF) D3 Button Cover (ON/OFF)E Button padlock (ON)+ Button cover (OFF)F Button padlock (OFF)+ Button cover (ON)G Key Lock H Secondary Trip Coil(Preparatory trip coil)J Fire-endurable wiring cable ass’yK Opening Latch Checking SwitchS Pad Lock (G class)T Enclosed type, Tulip contact
AccessoriesT Enclosed type, Tulip contact
12 G 32 D 12 1A 2B B, C1, D1LVB
12 G 32 D 12 A, B, CLCL
Vacuum Circuit BreakerTypes and ordering information
H1-41
Cradle
17.5kV
LS Cradle
Rated voltage17 17.5kV
Installation methodP Fixed typeE E class draw-out typeF F class draw-out typeG G class draw-out type
Revision No.D Pro-MEC
Control voltage1A DC110V1B DC220V1C DC48V1E DC125V
Breaking current40 40kA
Auxiliary switch2B 4a4b(A type connector)2E 10a10b(A type connector)2G 4a4b(B type connector)2H 10a10b(B type connector)
LS VCB
Rated voltage17 17.5kV
Note) ‘A’ is for ‘G’ class only
AccessoriesA MOC (3a4b) + TOC (3a4b)
B Position Switch (RUN/TEST:2a2a)C1 Button Padlock (ON) C2 Button Padlock (OFF)C3 Button Padlock (ON/OFF) D1 Button Cover (ON)D2 Button Cover (OFF) D3 Button Cover (ON/OFF)E Button padlock (ON) + Button cover (OFF)F Button padlock (OFF) + Button cover (ON)G Key Lock H Secondary Trip Coil(Preparatory trip coil)K Opening Latch Checking SwitchS Pad Lock (G class)J Fire-endurable wiring cable ass’y
AccessoriesRated current
12 1250A20 2000A30 3150A
Installation methodE E class draw-out typeF F class draw-out typeG G class draw-out type
Breaking current Revision No.D Pro-MEC
Rated current12 1250A20 2000A30 3150A
17 G 40 D 12 1A 2B B, C1, D1LVB
17 G 40 D 12 A, B, CLCL
H1-42
Vacuum Circuit BreakerTypes and ordering information
B Position Switch (RUN/TEST:2a2a)C1 Button Padlock (ON) C2 Button Padlock (OFF)C3 Button Padlock (ON/OFF) D1 Button Cover (ON)D2 Button Cover (OFF) D3 Button Cover (ON/OFF)
EButton padlock (ON)+ Button cover (OFF)
FButton padlock (OFF)+ Button cover (ON)
G Key Lock
HSecondary Trip Coil(Preparatory trip coil)
J Fire-endurable wiring cable ass’yK Opening Latch Checking SwitchP1 Dummy VCB(AMP Jack)P2 Dummy VCB(Phoenix Jack)Q Earthing Truck(Lower terminal earthing)R Earthing Truck(Upper terminal earthing)S Pad Lock (G class)T Enclosed type, Tulip contact
N CTD(Capacitor Trip Device)O Rectifier
Cradle
24kV
Note) 1. Version E is available only at 24kV G class and its distance between phases is 210mm.2. "00" is used for ordering Earthing Truck and Dummy VCB4. Accessory only for versions D and E
Note) 1. Version E is available only at 24kV G class and its distance between phases is 210mm.2. Versions A, B and C are available only at G class VCB.
Note2)
Note1)
Note1)
Note2)
Note2)
Note2)
LS VCB
Rated voltage20 24kV
Installation methodP Fixed typeE E class draw-out typeF F class draw-out typeG G class draw-out type
M G class draw-out type+ Bushing
Revision No.D Pro-MEC
E Pro-MEC(Minimized type)
Control voltage00 -1A DC110V1B DC220V1C DC48V1E DC125V
1FAC220(M),DC110(TC)
1HAC220(M),DC220(TC)
1TAC110(M),DC110(TC)
Rated current06 630A12 1250A20 2000A
Breaking current 13 12.5kA16 16kA25 25kA
Auxiliary switch00 -2B 4a4b(A type connector)2E 10a10b(A type connector)2G 4a4b(B type connector)2H 10a10b(B type connector)
Accessories
Option
LS Cradle Installation methodE E class draw-out typeF F class draw-out typeG G class draw-out type
AccessoriesA MOS(3a4b)+ TOC(3a4b)B Earthing Switch
CEarthing Switch Position Switch+Earthing Switch Locking coil
T Enclosed type, Tulip contact
PS Position S/W Block(24kV E/F class only)
Revision No.A ConventionalD Pro-MEC
EPro-MEC
(Minimized type)
Breaking current13 12.5kA16 16kA25 25kA
Rated current06 630A12 1250A20 2000A
Rated voltage20 24kV
20 G 13 D 06 1A 2B B, C, DLVB
20 G 13 D 06 A, B, CLCL
H1-43
Vacuum InterrupterFeatures & Ordering information
Revision No
A, B…
ETC.
Null Straight type
P Potting type
C Wave type
E Embedded type
G Gas Insulation type
Modeling system
FeaturesAccumulation of more than 20 years ofvacuum-related technologies
Simplified arc extinguishing systemSpiral contact structure with Radial magneticfield provides effective dispersing of the acrenergy.
Simple structure and high qualitySealing after complete removal of gas in thevacuum chamber in order to secure a longvacuum confidentiality
Small size and light weightThe new contact material used to enhancethe competitiveness of the size
Wide rated coveragesWide interrupting range from 6kV up to40.5kV 40kA
High reliability and electrical lifeCertification by KERI and KEMA accordingto the latest standard IEC62271-100 (2008)E2, LIST3, M2
-A
Basic type
L LS
V Vacuum
7 Series No.
PLV7
H1-44
Vacuum InterrupterVI internal structure
Largely movable and fixed electrodes and main shield compose the Susol VI.The main components are shown in the following.
The vacuum rate within the VI is very high(approximately 5x10-5 Torr) and the spacing betweenfixed contact and movable contact is about 6 ~ 20mm, depending on the voltage.The contacts are in a structure that arc can easily be extinguished and the surfaces of the contactsare made of special alloy (copper - chromium) and the interior is completely sealed to prevent lossof vacuum.Therefore the wearing of the contacts can be minimized in the event of short-circuit and the arcenergy by overvoltage or switching can be reduced effectively.
Fixed electrode
Fixed seal cup
Ceramic
Fixed shield
Contacts
Bellows shield
Bellows
Movable seal cup
Arc shield
H1-45
Basic functions and interrupting action
Interrupting action by VI
Spiral contact structure (Radial magnetic field ),using the force (F = j ×B) generated by theinteraction of the radial magnetic field caused bythe current flowing through the arc between twocontacts, disperse the arc energy evenly on thesurface of contact by rotating the arc that iscontracted by the pinch effect so as to minimizecontact damage.The images show arc behavior during the arcingtime of about 8ms by shooting with high-speedcamera capable of shooting 10,000 frames persec.(0.1ms/frame) by focusing on parts of the arcingtime on the above graph and simultaneouslymeasured arc voltage also represented to show arcstate by section
In case of using the flatcontact any of the designsdo not reflect on whencontacts are opening the arcwith high temperature iscontracted and fixed in thecenter of the contacts,Which is called pinch effect.To prevent the effect twokinds of contact shapes aredesigned.One is Axial magnetic fieldwhich spreads the arcbefore its contraction, andthe other is Radial magneticfield whichpermits the contraction ofthe arc but makes it rotatedto disperse the energy.Because contracted arc isshaped like a cylinder it iscalled Contracted arc orcolumnar arc.
Arc voltage waveforms and arc image captured during arcing time
Arc driving principle in the contacts of Radial magnetic field
Current
Direction of rotating arc
Columnar arc
Radial magnetic field type contact
H1-46
Vacuum InterrupterVI endurance by interrupting current
VI model LV2 at 7.2kV�N : Operation numbers�I : Interrupting current
Num
ber[o
ps.]
Interrupting current [kA]
VI model LV3 at 7.2kV�N : Operation numbers�I : Interrupting current
Num
ber[o
ps.]
Interrupting current [kA]
VI model LV4 at 24kV�N : Operation numbers�I : Interrupting current
Num
ber[o
ps.]
Interrupting current [kA]
VI model LV5 at 17.5kV�N : Operation numbers�I : Interrupting current
Num
ber[o
ps.]
Interrupting current [kA]
H1-47
Note) 1. Above graphs represent the characteristics of the electrical life of LS Susol VCB.2. Life characteristics of each model in each rating represents the LOG-LOG graphs.
VI model LV8 at 17.5kV�N : Operation numbers�I : Interrupting current
Num
ber[o
ps.]
Interrupting current [kA]
VI model LV7-P1 at 24kV�N : Operation numbers�I : Interrupting current
Num
ber[o
ps.]
Interrupting current [kA]
VI model LV8 at 36kV�N : Operation numbers�I : Interrupting current
Num
ber[o
ps.]
Interrupting current [kA]
H1-48
Vacuum InterrupterDimensions
17-0
.30
21-0
.30 17-0
.30
LV2 LV3 LV420
0+0.5
5.2
0+0.1
0+0.1
300+0.5
LV5-P LV5A6
0+0.1
300+0
.3
-0.10
0+0.1
LV8
H1-49
60+0
.1
-0.10
0+0.1
300+0
.3
300+0.5
-0.10
4 ×90O
LV7-P1 / LV8-P LV7-C LV10404
H1-50
Technical data
Vacuum Interrupter
Rated voltage (kV)
Rated power frequency withstand voltage (kV, rms)
Rated impulse withstand voltage (kV, crest)
Rated frequency (Hz)
Rated normal current (Amp)
Rated short circuit current (Sym.) (kA)
Rated short circuit making current (kA, peak)
Rated duration of short-circuit (sec)
Interrupter weight (kg)
Moving part weight (kg)
Outline dimension (mm) a
b
c
Contact stroke (mm)
Opening speed, average 0 to 75% of full stroke (m/s)
Overtravel during opening, Max. (mm)
Closing speed, average last 33% of full stroke (m/s)
Contact bounce duration, Max. (sec)
Added force from atmospheric pressure (kg∙f)
Contact force from atmospheric pressure (kg∙f)
Contact erosion limit (mm)
Mechanical life (×104, Operations)
7.2 7.2 24/25.8 12/17.5
20 20 50 42
60 60 135 95
50/60 50/60 50/60 50/60
400/630 630/1250 630 630/1250
3 3 3 3
0.8 1.4 1.2 2.4
0.3 0.7 0.5 0.7
132 158 208 220
91 105 159 163
62 80 62 90
6±1 10 ±1 12 ±1 10±1
0 7~1.0 0 7~1.0 1.3~1.5 0.7~1.0
2 2 2 2
0 7~1.0 0 7~1.0 0 7~1.0 0.7~1.0
2 2 2 2
8.5 12.6 9 12.6
3 3 3 3
M2 M2 M2 M2
Outer view
Type LV2 LV3 LV4-E LV5-P
Elec
trical
ratin
gsM
echa
nical
data
Mec
hanic
al re
quire
men
ts
8 12.5 20 25 16 20 25
20.8 32.5 52 65 41.6 52 65
80 154 227 120 154 227
H1-51
12/17.5 24/25.8
42 65
95 125
50/60 50/60
2000
3 4
3.0 7.3
1.0 2.2
220 272
160 216
80 145
10±1 12 ±1
0.7~1.0 1.0~1.3
2 2
0.7~1.0 0.7~1.0
2 2
12.6 25.5
3 3
M2 M2
7.2/12 25.8
20/28 70
60/75 150
50/60
4000 3150
4 3
8.7
2.0
317
210
135
10±1 17 ±1
1.0~1.3
1.5
0.7~1.0
2
25.8
3
M2
40.5 17.5 36
95 38 70
185 95 170
50/60 50/60 50/60
~3150 ~3150 ~3150
4 4 4
9.8 6.6 7.3
2.6 2.2 2.2
390 272 272
329 210 216
145 135 145
17~19 12 ±1 17~19
1.3~1.5 1.0~1.3 1.3~1.5
2 2 2
0.7~1.0 0.7~1.0 0.7~1.0
2 2 2
25.1 25.8 25
3 3 3
M2 M2 M2
LV5A LV7-P1 LV7-C LV8 LV8-P LV10404
2500 ~3150
20 25 25 31.5 40 25 31.5 40 50 25 31.5 40 40 50 40
52 65 65 81.9 104 65 81.9 104 130 65 81.9 104 104 130 104
154 227 227 306 367 227 306 367 460 227 306 367 367 406 367
Contents
Features and Structure H2-2Control circuit diagram H2-4Dimensions H2-5
Vacuum Circuit Breaker for MCSG
Pro-MEC MCSG VCB
H2
H2-2
Vacuum Circuit Breaker for MCSG
Features and Structure
Features��Module type VCB��Convenient especially for fabricating MCSG
- Housing is designed like VCB compartment style- MCSG panel can be easily constructed if combined with Low voltage compartment, Busbar
compartment and Cable compartment.
��Convenient for maintenance and offering high safely- Earthing switch can be operated from outside of the panel, and which makes earthing of 3 phases at the
same time.- Without opening the compartment panel door, breaker can be drawn in or out electrically or manually
��Main functions- Breaker : draw- in or out electrically or manually- Compartment : 3-positions
��Standard- IEC 62271-100
①① Name plate②② Manual closing button③③ Keylock④④ Manual trip button⑤⑤ Manual charging hole⑥⑥ Contact position
indicator⑦⑦ Closing spring
charge indicator⑧⑧ Operation counter⑨⑨ Insertion &
Draw-out screw⑩⑩ Geared Mechanism
⑦⑦
②②
③③
④④
⑧⑧
⑨⑨
⑩⑩
⑤⑤
⑥⑥
①①
Compartment Earthing switch Bushings Shutter
Electricaldrive unit
H2-33
Ratings
Rated voltage (kV) 25.8Rated normal current (A) 630 2000Rated frequency (Hz) 60Rated short-circuit breaking current (kA) 25Rated short-circuit breaking capacity (MVA) 1100Rated short-time withstand current (kA) 25/3sRated short-circuit making current (kA) 65Rated breaking time (Cycles) 3Withstand Power frequency (kV) 50/1minvoltage Impulse (kV/1.2××50㎲㎲ ) 125TRV rising rate (kV/㎲㎲ ) 0.47TRV max. (kV) 41Rated operating sequence O-0.3s-CO-3min-COMechanical lifetime 10,000operationsElectrical lifetime 10,000operationsRated control voltage (V) DC 110VRated trip voltage( V) DC 110VStandard auxiliary switch 4a4b, 8a8bRated opening time (s) ≤ 0.04No-load closing time (s) ≤ 0.06Rated charging motor current (A) ≤ 7Rated closing coil current (A) ≤ 5Rated trip coil current (A) ≤ 5Closing spring charging time (s) ≤ 12Draw-in/out motor voltage (V) DC 110VDraw-in/out motor current (A) ≤ 5Distance between phases (mm) 265
Weight (kg) breaker 205 236.5 compartment 281 293
Installing GApplied standard IEC 62271-100
LVB‐‐25□□-25□□/06 LVB‐‐25□□-25□□/20Type
Rated voltage25 25.8kV
Installation methodG Gclass draw-out
Auxiliary switch2G 4a4b(B type connector)2H 8a8b(B type connector)
��Breaker
25 G 25 I 06 1A 2B B,C,DLVB
��CCrraaddllee((CCoommppaarrttmmeenntt))
LS VCB
Breaking current25 25kA
Version
Rated current06 630A20 2000A
AccessoriesB Position SwitchC1 Button Padlock(ON) C2 Button Padlock(OFF)C3 Button Padlock(ON/OFF) D1 Button Cover(ON)D2 Button Cover(OFF) D3 Button Cover(ON/OFF)E Button Padlock(ON)+Button Cover(OFF)F Button Padlock(OFF)+Button Cover(ON)G Key Lock H Secondary Trip Coil
Rated voltage25 25.8kV
LS VCB
25 C 13 D 06 A,B,CLCL
Version Rated current06 630A20 2000A
Breaking current25 25kA
Installation methodC Bushing
AccessoriesB Earthing SwitchE Door
Control voltage1A DC110V1B DC220V1C DC48V1E DC125V1F AC220(M), DC110(TC)1H AC220(M), DC220(TC)1T AC110(M), DC110(TC)
H2-4
Vacuum Circuit Breaker for MCSGControl circuit diagram
MOTOR POWER SOURCEA1 A2
P NN
N
M
C
A3 A4CS
TRIP POWER SOURCE
CLOSING POWER SOURCE
A5 A6CSCW(인입)
CCW
(인출)
PP
PAu
xilia
ry s
witc
h
Posi
tion
S/W
Indi
catio
n fo
r clo
sing
spr
ing
"cha
rged
" is
ava
ilabl
e.
913
14 4389
X44
1LS
62
3452
b35
3389
Y34
3389
X34
652
a
6'
4389
Y89
X89
Y44
2189
Y22
1516
1722
2426
2840
4244
46
2325
2729
4143
4547
2325
2729
4143
4547
3638
5052
5456
5870
13
1PS
1PS
23
24
24
3638
5052
5456
5870
3739
5153
5557
5971
3739
5153
5557
5971
2224
2628
4042
4446
13 14
13 14
10
1D C B A
D C B A
23
41
23
4
5051
5253
5
1314
1516
17
67
89
109
1011
1213
1415
16
3637
3839
12
34
56
A1A2
A3A4
A5A6
78
910
1112
1314
2223 ( 4
a 4b
)
( 8a
8b )
SEC
ON
DA
RY
DIS
CO
NN
ECT
WIR
ING
( TO
P VI
EW )
2425
2627
2829
1516
1D C B A
D C B A
23
41
23
4
5051
5253
5
1314
1516
17
67
89
109
1011
12
5455
5657
5859
70
4243
4445
4647
71
1314
1516
3637
3839
4041
12
34
56
A1A2
A3A4
A5A6
78
910
1112
1314
2223
2425
2627
2829
1516
4 5
Yb
Ya
52b
LS1
63 4
7 8
343
64
2121 1 5 1 230 31
LS2
LS3
TC1 2
89X
8 9
1LS
52 21
89X
22 89Y
8 9
89M
4a4b
8a8b
1 2
Y
Run
Test
∅: E
xter
nal te
rmin
al o
f VCB
52: V
acuu
m c
ircui
t bre
aker
M: S
prin
g ch
argi
ng m
otor
TC: T
rip c
oil
TC1
: Sec
onda
ry tr
ip c
oil
C: C
losin
g co
ilY
: Ant
i-pum
p re
lay
52a
: Aux
iliary
swi
tch
(NO
)52
b: A
uxilia
ry s
witc
h (N
C)LS
1: C
losin
g in
terlo
ck lim
it swi
tch(
only
with
draw
able
type
)LS
2: M
otor
sto
ppin
g, c
losin
g sp
ring
char
ged
indi
catio
nLS
3: A
nti-c
losin
g, A
nti-p
umpi
ng lim
it swi
tch
LS5
: "O
ff" a
t Tes
t Pos
ition
LS6
: "O
ff" a
t Run
Pos
ition
PS1
: Pos
ition
S/W
("On"
at T
est P
ositio
n)PS
2 : P
ositio
n S/
W("O
n" a
t Run
Pos
ition)
89X
: Aux
iliary
Rel
ay fo
r Ins
ertin
g89
Y : A
uxilia
ry R
elay
for w
ithdr
awin
g89
M :
Mot
or fo
r with
draw
ing
and
Inse
rting
Note
. Diag
ram
show
s the
circ
uit b
reak
er in
pos
ition“
OFF
”with
clos
ing sp
ring“
Char
ged”
H2-5
Dimensions10
82
1365
7010
375
A
A
35
53 538941000
15.4
265 265
(183
.4)
(212
.4)
963553 1
95
652.
4
183.
4
1365
340
372.
6
26.8
st:31010
263.8180Lead wire(2m)
293.8
410
B B
C
1
TEST RUN
Earthing
45
3086
3060
60
8634
0
45 95
9681000
425
425
190
265 265175
425
2-∅13
(Earthing)∅6.5
3-∅10
5012
8
844
700
265
205
600
50
20
41065
513 16.8370 40
340 40 483963
50
950 17
510
3
15 933 (15)
700
3-∅11(Mounting Hole)
3-∅11×22(Mounting Hole)
<Front> <Rear> <Front> <Rear>
20-M8 POP NUT(DP:18)
<B-B Section View>
<C-View(Cover 2 Cutting)>
<A-A Section View>
User Bus
Cradle(Compartment) - w/o Earthing Switch
630A
2000A
265 265
860 350 50
445
445
481785
886912
1013
340
340
608
G type breaker + track(electric draw-in/out)
��Rear��Front
��Top
H2-6
Vacuum Circuit Breaker for MCSGDimensions
<B-B Section View>
2525
600
1717
8383
340
2626
20
340 40 483 50 70
700
950
50
100 100763
140 150
1565 ∅19
9-∅11Mounting Hole
50
370 40 16.8513
20-M8 POP NUT(DP:18)
2-∅1360
60
26
26
<Front> <Rear> <Front> <Rear>
A
(Door)**Option
1750
125
500
500
767.
424
434
039
8.6
4541
5
190
454
415
415
415
45
500
125
A
Test B
1000 39 963 320.935
16-∅10(Mounting Hole Side) 10-M8 POP NUT
(DP:18)
25t(2000A)10t(630/1250A)
st:310
M12 TAP(DP:24)
3-∅10
(Earthing)∅6.5
35
74
36
User Bus
968
265 265
265 265175
(Earthing S/W)**Option
35
Test Run
Test
238.8
Cradle(Compartment) - w/ Earthing Switch
��Side ��Rear��Front
��Top <Terminal conductor>
Contents
Ratings H3-4Ratings of Accessories H3-5Accessories H3-6Control circuit diagram H3-8Dimensions H3-9Types and ordering information H3-14
Vacuum Circuit Breaker for Power Plants
Power Plants VCB
H3
A product developed for water and thermal power plants dueto the revision and application of Kepco’s standard (ES150)followed by the IEC standard revision. It has completed thehigh capacity (40~50kA) VCB series for power plants bysecuring higher breaking capacity, safety and reliability.
VCB Full OptionTo prevent fatal error, property and life loss caused from operator duringoperation, it is equipped with safety mechanisms such as shutter padlock.
Bushing applied for Window CT adaptationThe bushing provides sufficient strength to collaborate with the internal insulation and isadaptable with CT offering safety mechanically and electrically when applying large current.
H3-2
Power PlantsVacuum Circuit BreakerVacuum Circuit Breaker
Vacuum Circuit Breakersfor Power Plants
It is recognized for reliability by acquiring newIEC 62271-100 and ES150 (KEPCO standardspecification on AC breakers)
H3-3
Vacuum Circuit Breaker for Power PlantsRatings
H3-4
Type LVB-06G-40H LVB-06G-40J LVB-06G-50J
Rated voltage (kV) 7.2
Rated normal current (A) 1200 2000 3000 1250 2000 2500 3150 1250 2000 3150
Rated frequency (Hz) 60
Rated short-circuit breaking current (kA) 40 50
Rated short-circuit breaking capacity (MVA) 500 624
Rated short-time withstand current (kA/3sec) 40 50
Rated short-circuit making current (kAp) 104 130
Rated breaking time (Cycle) 3
Rated opening time (sec) ≤ 0.04
No-load closing time (sec) ≤ 0.06
Withstand Power frequency (kV/min) 20
voltage Impulse (kV/1.2 ××50㎲㎲ ) 60
Rated operating sequence CO-15s-CO O-0.3s-CO-3min-CO
Rated charging motor current (A) 5 (at DC125V) 5 (at DC110V)
Rated closing coil current (A) 3 (at DC125V) 3 (at DC110V)
Rated shunt coil current (A) 3 (at DC125V) 3 (at DC110V)
Type Mechanical M2
test Electrical E2 (Maintenance free) E2 (List1)
Capacitive current switching C2
Lifetime Mechanical Without maintenance 10000 operations
Maintenance 20000 operations
Electrical Without maintenance 10000 operations
Maintenance 20000 operations
Auxiliary switch 3a3b
Installing Draw-out G-type Visible, Tulip
Weight Breaker G-type (kg) 200 260 200 260 200 260
Cradle G-type (kg) 190 230 190 230 190 230
Applied standard ES150 NOTE) IEC 62271-100
Type test laboratory KERI
Note) ES150: KEPCO's standard in which IEC62271-100 is appliedKERI: Korea Electrotechnology Research Institute
H3-5
Ratings and auxiliary devices
Note) * applied in the VCB of which MOC is operable at the TEST position.
Switch Mechanism MOC TOC
Breaker a b a b a b
CLOSE ON OFF ON OFF ON OFFRUN
OPEN OFF ON OFF ON OFF ON
CLOSE ON OFF ON * OFF * ON OFFTEST
OPEN OFF ON OFF * ON * OFF ON
Position of the Auxiliary switch
Motor
Closing Coil (C)When the rated volt is applied to the coil the breaker is closed.The electrical anti-pumping circuit is built-in it.
Note) Range of the normal operating voltage: 75~125% of rated voltage
Shunt coil (TC)When the rated volt is applied to the coil the breaker is opened.
Note) Range of the normal operating voltage: 60~125% of rated voltage
Auxiliary switchStandard configuration : 3a3b1b of early-b contact function exists inside
Charge indicator ofthe closing springIndicating the condition of the closing spring.
Position indicator of the main contactsIndicating the 'Close' or the 'Open' of the main contacts.Close position: ��ON�� Open position: ��OFF��
CounterMechanically counts the operation of the VCB by 5digits
Charged Discharged
Close position Open position
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
Note) Range of the normal operating voltage: 85~110% of rated voltage
Note) The contact ratings of Mechanical Operated Cell Switch(MOC)are the same with that of the Aux. switch.
The peak value of the Consumption Charging timeRated voltageinrush current (A)
Rated current (A) power (W) (Sec.)
DC 110V 20 3 330 12DC 125V 20 3 330 12
Classification Resistive Inductive Contact load (A) load (A) configuration
Contact Ratings DC110V 10 5
3a3b125V 10 5
Rated voltage Rated current (A)
DC 110V 3DC 125V 3
Rated voltage Rated current (A)
DC 110V 3DC 125V 3
Classification Resistive Inductive Contact load (A) load (A) configuration
Contact Ratings DC110V 10 5
3a3b125V 10 5
Truck Operated Cell Switch(TOC)
Vacuum Circuit Breaker for Power PlantsAccessories
H3-6
Accessories for breakers
��Position padlockIt is located at the screw hole to prevent the draw-in and out of a breakerfrom the present position(Disconnected, Test or Connected)
��Mechanical position indicatorIt is located in the lower part of a breaker to check the present position -Disconnected, Test or Connected- easily.
��Position interlockThe breaker is locked in each position-Disconnected, Test or Connected,thus it is necessory to release the lock before draw-in or out of a breakerfrom the present position.
��Auto connectionWhen the breaker is moved to Test position from Disconnected positionthe connector for control powers is automatically connected. In case ofreverse moving of the breaker the connector is automaticallydisconnected.
��Code plateWhen the breaker is inserted to the cradle, if the ratings does not matchwith the cradle, it mechanically prevents the breaker from being insertedinto the cradle.
H3-7
��Mechanically operated cell switch (MOC)It is auxiliary switch (6a6b), which indicates the 'ON' or 'OFF' condition of aVCB, and operated when the VCB is in 'Run' state.
��Truck operated cell switch (TOC)It is auxiliary switch (6a6b), which indicates the 'Run' state of a VCB and isoperated by the movement of a VCB frame.
Accessories for breakers
Vacuum Circuit Breaker for Power PlantsControl circuit diagram
H3-8
NA2
A4N
A6
MOTOR POWER SOURCE
M
A1
P
8
A3CS
TRIP POWER SOURCE
CLOSING POWER SOURCE
TC
52a
A5CS
P
N
3a
2322
2524Auxi
liary
sw
itch
P
Y
2422
54
2523
5559
58 59
58
2726
272654 55
57
56 57
56
3 4
4 6
1 26 77
C3130511 2 1 2
Ya
Yb 52b
LS1
LS3 3 4
5 6
Early
b
235756
A2 22A1
2725
59585554
B
A4A6 26
24
A5A3 A
17
(FRO
NT V
IEW
OF
RECE
PTAC
LE P
LUG
)
2425
SECO
NDAR
Y D
ISCO
NNEC
T W
IRIN
G5
34
21A1
A3
A2A4
22A5
23A6
1314
1615
1211
89
76
10
22
5455
26271819
2120
5658
5759
2324
(12P
TAP
PLUG
)
LS2 43
LS4
21
3b
Cell
switc
h in
ser
vice
pos
ition
3130
3534
3736
3938
5150
76
2322
2524
2726
2928
2515
2616
2717
2212
2313
2414
<TO
C>
<MO
C>
5352 4140
2515
2616
2717
2212
2313
2414A B
Note
) Diag
ram
show
s the
circ
uit b
reak
er in
pos
ition“
OFF
”wi
th cl
osing
sprin
g“Ch
arge
d”
∅: External term
inal of VCB
52
: Vacu
um c
ircu
it breaker
M: Spring c
harg
ing m
otor
TC
: Trip c
oil
C: Closing c
oil
Y: Anti-
pump relay
52a
: Auxilia
ry switc
h (NO)
52b
: Auxilia
ry switc
h (NC)
LS1
: Closing interlock
lim
it sw
itch
LS2
: Motor stopping
LS3
: Anti-
closing, Anti-
pumping lim
it sw
itch
LS4
: Motor Charg
ing interlock
lim
it sw
itch
H3-9
Dimensions - Breakers
LVB-06G-40H, 40J G class (Visible, Tulip contact)-(1200, 1250, 2000A) (unit : mm)
336
717
745
685.
2
58453
2
686.2
60
10
368.
236
0
722
254254
130
351.
3
815.
2
696
1200/1250/2000A
54(m
ale c
onducto
r)��Side��Front
��Top
<Conductor>
Vacuum Circuit Breaker for Power PlantsDimensions - Breakers
H3-10
LVB-06G-40H, 40J G class (Visible, Tulip contact)-(2500, 3000, 3150A) (unit : mm)
60
10
686.2
336
130
349.
8
815.
2
360
368.
2
254254
722
685.
2
58453
2
745
717
696
2500/3000/3150A
Heat sink(only for 3150A)
79(m
ale c
onducto
r)��Side��Front
��Top
<Conductor>
H3-11
LVB-06G-50J G class (Visible, Tulip contact)-(1250, 2000A) (unit : mm)
336
717
745
58453
2
677.2
60
10
368.
236
0
722
254254
130
815.
7
696
Fixed contact
115.5 140
403.
8
341.
3
Moving contact
54(m
ale c
onducto
r )
676.
2
��Side��Front
��Top
Vacuum Circuit Breaker for Power PlantsDimensions - Breakers
H3-12
LVB-06G-50J G class (Visible, Tulip contact)-(3150A) (unit : mm)
254 254
815.
7
722
115.5 140
267.
813
6.5
336
360
358.
710
150.
2
445.8
541
677.2
58453
2
676.
2Moving contact Fixed contact
79(m
ale c
onducto
r)
696
717
130
341.
8
107
��Side��Front
��Top
H3-13
252
252
37450 24035
374
235.5
150 500 361
Autocon(3a3b)
M.O.C(6a6b)
1134
436.5
544
338
1038.5T.O.C(6a6b)
644
24035
310
816
776
254
254
360
449.
5
75.815
1.5
59 61(레
일폭
)10
35
61
175
103.
5
310
∅79
∅54
∅14
8 ∅14(Earthing)
Mounting 6-∅12
∅14
8
∅21
8∅
218
5036
140 123
140 123
4-M12 DP20
2-M12 DP20
2500/3000/3150A
1200/1250/2000A
Cradles (unit : mm)
Vacuum Circuit Breaker for Power PlantsTypes and ordering information
H3-14
Option
MOC(6a6b)+TOC(6a6b)
A1 MOC active only at RUN
position
MOC(6a6b)+TOC(6a6b)
A2 MOC active only at TEST
and RUN position
Note) 1.Rated current 2500A is available only at 7.2kV 40kA, IEC version(J)2.Control voltage and Auxiliary switch are not applied to Dummy VCB and Earthing Truck
LS VCB
Cradle
Breaker
LCL 06 G 40 J 12
LS Cradle
Rated voltage
06 7.2kV
Installation method
G G class draw-out
Breaking current
40 40kV
50 50kV
Rated current
12 1200/1250A
20 2000A
25 2500A
30 3000/3150A
A1, A2
Rated voltage
06 7.2kV
Installation method
G G class draw-out
Breaking current
40 40kA
50 50kA
Standard
H ESB150
J IEC
Control voltage
1A DC110V
1B DC220V
1E DC125V
Auxiliary switch
2L 3a3b(Autocon)
Option
C1 Button padlock(ON)
C2 Button padlock(OFF)
C3 Button padlock(ON/OFF)
D1 Button Cover(ON)
D2 Button Cover(OFF)
D3 Button Cover(ON/OFF)
EButton padlock(ON)+
Button cover(OFF)
FButton padlock(OFF)+
Button cover(ON)
G Key Lock
P3 Dummy VCB
Q Earthing Truck(lower terminal)
R Earthing Truck(upper terminal)
LVB G 40 J 12 1A 2L P3,Q,R06
standard
H ESB150
J IEC
Rated current
12 1200/1250A
20 2000A
25 2500A
30 3000/3150A
NOTE1)
NOTE2)
Contents
H4
Nuclear Power Plants VCB
Ratings H4-4Ratings of Accessories H4-5Accessories H4-6Control circuit diagram H4-8Dimensions H4-9Types and ordering information H4-11
Vacuum Circuit Breaker for Nuclear Power Plants
H4-2
It was developed for KEPCO nuclear power stations. This breakersatisfies quality, safety measures (secure from earthquake andother environments), and surge protection class complies with“1E-CLASS” ±provisions. It is featured with high breakingtechnologies, safety, and reliability by applying our own vacuuminterrupters (50KA) approved by ANSI standard tests.
Nuclear Power PlantsVacuum Circuit BreakerVacuum Circuit Breaker
VCB Full OptionTo prevent fatal error, property andlife loss caused from operatorduring operation, it is equippedwith safety mechanisms such asshutter padlock.
Bushing applied forWindow CT adaptationThe bushing provides sufficientstrength to collaborate with theinternal insulation and is adaptablewith CT offering safety mechanicallyand electrically when applyinglarge current.
Satisfies earthquake andother internal environmentspecifications During the lifespan of power stations (40yrs),it is designed to operate its fundamentalbreaking functions even under the mostsevere conditions like earthquake, which iscritical from safety perspectives. Thesetechnologies proven through tests thatcomply with KEPIC standard and relevantspecifications are to guarantee nuclearreactor safety.
H4-3
Vacuum Circuit Breakersfor Nuclear Power Plants
Vacuum Circuit Breaker for Nuclear Power PlantsRatings
H4-4
Type LVB-05G-50B LVB-15G-40B
Rated voltage (kV) 4.76 15
1200 1200
Rated normal current (A) 2000 2000
3000 -
Rated frequency (Hz) 60 60
Rated short-circuit breaking current (kA) 50 40
Rated short-circuit breaking capacity (MVA) 410 1040
Rated short-time withstand current (kA/3sec) 50 40
Rated short-circuit making current (kA) 130 104
Rated breaking time (Cycle) 3 3
Rated opening time (sec) ≤ 0.04 ≤ 0.04
No-load closing time (sec) ≤ 0.06 ≤ 0.06
Withstand Power frequency (kV/1min) 19 36
voltage Impulse (kV/1.2××50㎲㎲ ) 60 95
Rated operating sequence 0-0.3s-CO-3min-CO
Rated charging motor current DC 125V (A) 5 5
Rated closing coil current DC 125V (A) 3 3
Rated shunt coil current DC 125V (A) 3 3
LifetimeMechanical(w/o maintenance) 10000 operations 10000
Electrical(w/o maintenance) 10000 operations 10000
Auxiliary switch 5a3b 5a3b
Installing G-type G-type
Weight1200,2000A (kg) 300 300
3000A (kg) 350 -
Applied standard ANSI C37 ANSI C37
Type test laboratory KERI KERI
H4-5
Ratings of Accessories
Note) The contact ratings of Mechanical Operated Cell Switch(MOC)are the same with that of the Aux. switch.
MotorWhen the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
The peak value of Ratedcurrent(A)
Rated voltagethe inrush current (A) Range of the normal Consumption Charging time
4.76kV 15kV 4.76kV 15kV operating voltage power (W) (sec)
50kA 40kA 50kA 40kA
DC 125V 15 15 5 5 90~140 360 8
Closing Coil (C)When the rated volt is applied to the coil the breaker is closed.The electrical anti-pumping circuit is built-in it.
The peak value of
Rated voltagethe inrush current (A)
Range of the normal4.76kV 15kV operating voltage
50kA 40kA
DC 125V 3 3 90 ~ 140
The peak value of
Rated voltagethe inrush current (A)
Range of the normal4.76kV 15kV operating voltage
50kA 40kA
DC 125V 3 3 70 ~ 140
Auxiliary switchStandard configuration : Reversible 8C(5a3b)and 2c(2b) with early-b contact function
CounterMechanically counts the operation of the VCB by 5digits
Shunt Coil (TC)When the rated volt is applied to the coil the breaker isopened.
Switch Mechanism MOC TOC
Breaker a b a b a b
CLOSE ON OFF ON OFF ON OFFRUN
OPEN OFF ON OFF ON OFF ON
CLOSE ON OFF ON OFF ON OFFTEST
OPEN OFF ON OFF ON OFF ON
Position of the Auxiliary switch
Classification Resistive Inductive Contactload(A) load(A) configuration
AC250V 10 5
125V 10 5
Contact Ratings 250V 10 5 8c
DC 125V 10 5
30V 10 5
Charge indicator ofthe closing springIndicating the condition of the closing spring.
Position indicator of the main contactsIndicating the 'Close' or the 'Open' of the main contacts.Close position: ��ON�� Open position: ��OFF��
Charged Discharged
Close position Open position
Vacuum Circuit Breaker for Nuclear Power PlantsAccessories
H4-6
��Position padlockIt is located at the screw hole to prevent the draw-in and out of a breakerfrom the present position(Disconnected, Test or Connected)
��Mechanical position indicatorIt is located in the lower part of a breaker to check the present position -Disconnected, Test or Connected- easily.
��Auto connectionWhen the breaker is moved to Test position from Disconnected position theconnector for control powers is automatically connected.In case of reverse moving of the breaker the connector is automaticallydisconnected.
��Reversible contact10 auxiliary switches are provided. 8 of them consist of reversible 8c whichcan be changed from a(b) to b(a). Factory composition is 5a3b. And theother 2 switches are supplied as 2b with early-b contact function
��Code plateWhen the breaker is inserted to the cradle, if the ratings does not matchwith the cradle, it mechanically prevents the breaker from being insertedinto the cradle.
��Auto dischargeIn case the breaker is drawn-out when the closing spring is charged in theposition-Disconnected, Test or Connected, or the breaker is moved toDisconnected position from Test position the closing spring shall beautomatically released.
Accessories for breakers
H4-7
��Mechanically operated cell switch (MOC)This 6a6b switch indicates the 'ON' or 'OFF' condition of a VCB and isoperated in the positions of 'Run' and 'Test"..
��Truck operated cell switch (TOC)This 6a6b switch indicates the 'Run' state of a VCB and is operated by themovement of a VCB frame.
Accessories for cradles
Vacuum Circuit Breaker for Nuclear Power PlantsControl circuit diagram
H4-8
P NN
N
PP
22
22
LS2
MOTOR POWER SOUREC
CLOSING POWER SOURCE
TRIP POWER SOURCE
3 4
1 1 5 30 313 4
7
6 6’ 1 2
8
1 22
3 4
4 6
5 6
LS3 LS
1
Ya
Yb 52b
52a
3524
3726
3928
5140
5343
5445
5647
58
2334
2536
2738
2950
41
2325
2729
41
5242
5544
5746
59
5557
59
2426
2840
5456
58
Auxil
iary
swi
tch
early
b
5a3b
A1
M
CY
TC
A2A4
A6
A3A5
CSCS
SEC
ON
DAR
Y D
ISC
ON
NEC
T W
IRIN
G(F
RO
NT
VIEW
OF
REC
EPTA
CLE
PLU
G)
13 1A2 A1A3
A522
2426
2840
5456
58
A4A6
2325
2729
4155
5759
23
45
67
89
1011
12
1415
1617
1819
2021
2223
24∅: External term
inal of VCB
52
: Vacu
um c
ircu
it breaker
M : S
pring c
harg
ing m
otor
TC : T
rip c
oil
C : C
losing c
oil
Y : A
nti-
pump relay
52a
: A
uxilia
ry switc
h (NO)
52b
: A
uxilia
ry switc
h (NC)
LS1 : Closing interlock
lim
it sw
itch (only w
ithdrawable typ
e)
LS2
: Motor stopping, closing spring c
harg
ed indicatio
n
LS3 : A
nti-
closing, Anti-
pumping lim
it sw
itch
Note
) Diag
ram
show
s the
circ
uit b
reak
er in
pos
ition“
OFF
”with
clos
ing sp
ring“
Char
ged”
H4-9
Dimensions
1200/2000A
3000A
722
254 254
722745
109 228 109 228
817
109.5 442.586.5
713
369
360
360
816
Breaker
<Front view>
<Side view>
Vacuum Circuit Breaker for Nuclear Power PlantsDimensions
H4-10
936
254 254
644850
343 137
100
1070
360
449
157
195 630
1020
252213
50
310
203
36
4-M12 DP18
2-M12 DP24
2-M12 DP24
1200/2000A
3000A
Cradle
<Front view>
<Side view>
H4-11
Types and ordering information
Breaker
LVB 05 G 40 B 20 1A 2K
LS VCB
Rated voltage
05 4.76kV
15 15kV
Installation method
G G class draw-out
Version
B Pro-MEC
Control voltage
1A DC110V
1B DC220V
1C DC48V
1E DC125V
1
Nuclear class
1 1E class
2 Non 1E class
Nuclear class
1 1E class
2 Non 1E class
Breaking current
40 40kA
50 50kA
Rated current
12 1200A
20 2000A
30 3000A
Auxiliary switch
2K 8c 접점
Cradle
LCL 05 G 40 B 20 1
LS Cradle Installation method
G G class draw-out
Rated current
12 1200A
20 2000A
30 3000A
Rated voltage
05 4.76kV
15 15kV
Breaking current
40 40kA
50 50kA
Version
B Pro-MEC
Note) 1A,1B,1C are only availableat 15kV class
Note)
H4-12
Memo
www.lsis.bizⓒ 2008.11 LSIS Co.,Ltd. All rights reserved.
2011. 10 Vacuum Circuit Breakers /Vacuum Interrupter(E) 2008. 11/(05) 2011. 10 Printed in Korea STAFF
�� For your safety, please read user's manual thoroughly before operating.
�� Contact the nearest authorized service facility for examination, repair, or adjustment.
�� Please contact a qualified service technician when you need maintenance.Do not disassemble or repair by yourself!
�� Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions
�LSIS (Middle East) FZE ��Dubai, U.A.E. Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab EmiratesTel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: [email protected] �Dalian LSIS Co., Ltd. ��Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]�LSIS (Wuxi) Co., Ltd. ��Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: [email protected]�LSIS-VINA Co., Ltd. ��Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet NamTel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]�LSIS-VINA Co., Ltd. ��Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, VietnamTel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: [email protected]�LSIS Shanghai Office ��Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. ChinaTel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: [email protected]�LSIS Beijing Office ��Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,Beijing 100013, P.R. ChinaTel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]�LSIS Guangzhou Office ��Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. ChinaTel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: [email protected]�LSIS Chengdu Office ��Chengdu, China
Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. ChinaTel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: [email protected]�LSIS Qingdao Office ��Qingdao, China
Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. ChinaTel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: [email protected]�LSIS NETHERLANDS Co.Ltd ��Qingdao, Netherlands
Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The NetherlandsTel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: [email protected]�LSIS Gurgaon Office ��Gurgaon ,India
Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India
� HEAD OFFICEKorea Gyeonggi-do Anyang-si dongan-gu LS-ro 127 (Hogye-dong) Tel. (82-2)2034-4887, 4873, 4918, 4148Fax. (82-2)2034-4648
� CHEONG-JU PLANTCheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,Cheong Ju, 361-720, Korea
�Global Network
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.