6. VA-1Product Information Motorizing globe valves of any make VA
M
Linear actuators, 3-point
Linear actuator, modulating
Modulating linear actuator with inverted lift signal
Retract spindle (into the actuator)
Extend spindle (from the actuator)
Linear actuator with emergency function, with spindleretracted (into the actuator) orextended (from the actuator), de-energized
Closing point, valve upstem fully extended from valve
Closing point, valve downstem fully retracted into valve
7.5 s/mm Actuating time with 3-point linear actuator
4.5 s/mm Actuating time with 3-point linear actuator (shorter actuating time)
Direction of rotation, manual control of linear actuator, clockwise rotation retracts spindle into actuator
Direction of rotation, manual control of linear actuator,counter-clockwise rotation extends spindle from actuator
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
2
Direct-coupled actuators for globe valves
Legend for symbols6.1 NRVDX..Short-stroke actuators for short-lift valves with an integral spring
• 5.5 mm lift for DN 15...40
• Control, 3-point or modulating
See Section 1
6.1 NV..+UNV.. Linear actuators
• 20 mm lift for DN 15...80
• with emergency function (NO or NC)
• Control, 3-point or modulating
See Section 2
Control ball valves, Open/Close ball valvessee Product Information 5. R..
Rotary actuators for mixing valves see Product Information 5. NR..
Globe valves with linear actuators see Product Information 6. H..
SuperCompact control valves with linearactuatorssee Product Information 6. S..
H+
Y2 Y1
H-
H
Y
H
Y
Important:
Use of Belimo direct-coupled actuatorsThe direct-coupled actuators described in this publication areintended for use in the closed water circuits of heating, venti-
lating and air-conditioning systems. Use of the actuators inconjunction with other liquid or gaseous fluids is not allowed.
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
3
Direct-coupled actuators for globe valves
Section 1: Short-stroke actuators 4–7Description of short-lift valves 4Type code, ordering 4Overview of short-stroke actuators 4NRDVX24-3-T-.., NRDVX230-3-T-.. 5NRDVX24-SR-T-.. 6Manual operation, Operating controls, Installation 7
Section 2:Standard linear actuators 8–55Description of standard globe valves 8Type code, actuators / brackets 8Types of construction of globe valves 8Overview, actuators / brackets 9Ordering, actuators / brackets 10NV24-3-T, NV230-3-T 12–13NV24-MFT-T, NVG24-MFT2, NV24-MFT2 14–15NVF24-MFT-T, NVF24-MFT-E-T 16–17Wiring diagrams NV.. 18–19Flow characteristics with NV.. 19Assembly NV../UNV.. 20Manual operation NV.. 21Mounting bracket for globe valves:UNV-001 (Siebe) 22–23UNV-002 (Belimo) 24–25UNV-003 (Siemens) 26–27UNV-012 (Cazzaniga) 28–29UNV-015 (Honeywell) 30–31UNV-017 (tac) 32–33UNV-018 (Sauter) 34–35UNV-019 (Johnson Controls) 36–37UNV-023 (Satchwell) 38–39UNV-024 (HORA) 40–41UNV-025 (Osby) 42–43UNV-027 (Ari) 44–45UNV-030 (Johnson Controls) 46–47UNV-034 (Johnson Controls) 48–49UNV-036 (Controlli) 50–51UNV-038 (Danfoss) 52–53Mounting, pressures, maintenance and disposal; Order form for specialmounting brackets 54–55
Distinguishing between short-lift and standard globe valves
Short-lift valves incorporate a return spring. Consequently, inorder to open the valve the actuator has to overcome the forceof the spring. In turn, in order to close the valve the spring has toovercome the force of the actuator.
Standard globe valves have no return spring. Therefore, the lin-ear actuator must open and close the valve and the spindle mustbe able to exert both a retracting force and an extending forceon the stem of the valve.
Table of contents
0
20
15 20 25 32 40 50 65 80 100 125 150
DN
Lift
Lift (8...20 mm)
Long lift (40 mm)
Short lift (up to 5.5 mm)
Linear actuators for radiators
Valves with an integral spring Valves without an integral spring
Description of short-lift valves
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
4
Temporary or permanent disengagementfor manual operation
Easy-to-readposition indicator
Control, 3-point or modulating
Integral terminals, for easy connection
of cables on-site
10.2
.4 .6 .8
NR.. linear actuators (actuating force 500 N, max. stroke 5.5 mm)
Overview of short-stroke actuators
Easy mounting by valve neck nut
Type code for short-stroke actuators
NRDVX24-SR-T-SI
Mounting bracket suitable for: -SI = Siemens short-lift valves-CA = Cazzaniga short-lift valves-T = Terminal connectionControl-SR = modulating-3 = 3-pointOperating voltage24 = 24 V
230 = 230 VVX = with linear adapter / stroke 5.5 mmNRD = Adapted-rating actuator
modulating 3-point
24 V 230 V 24 V
Type
AC 230 V, 3-point, 5.5 mm, 500 N
AC 24 V, 3-point, 5.5 mm, 500 N
AC / DC 24 V, modulating, 5.5 mm, 500 N
Running time 140 s
Control signal DC 0...10 V
Operating range DC 2...10 V, 0...10 V selectable
Position feedback DC 2...10 V, 0...10 V selectable
Connecting terminals
Make of control valve Type of mounting bracket
Cazzaniga -CA
Siemens (L&S) -SI
Ordering example: Short-stroke actuator 230 V, 3-point with integral Cazzaniga mounting bracket: NRDVX230-3-T-CA
NRDVX24-SR-T NRDVX230-3-T NRDVX24-3-T
•
•
•
• • •
•
•
•
• • •
• • •
• • •
NRDVX24-3-T-.., NRDVX230-3-T-..
5
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsThe NRDVX..-3-T-.. actuator is intendedfor motorizing Cazzaniga and Siemensshort-lift valves.
Mode of operation3-point control is employed for short-liftvalves used in control applications andOpen/Close control for shut-off functions.
Product featuresEasy direct mounting on the body of thevalve. The stroke is adjusted at the factoryto suit the type of valve. The mountingbracket, suitable for the particular type ofvalve, is an integral part of the actuator.
Functional reliabilityThe electric motor is de-energized when theactuator runs on to its internal end-stops.
Manual operationThe actuator can be operated manually witha hand lever (temporary disengagement bysimply depressing the rotary knob on thehousing and permanent disengagement byrotating it).When the manual lever is rotated clockwisethe valve moves in the close direction.
Installation instructions, Page 7
Short-stroke actuators for short-lift valves, max. nominal stroke 5.5 mm
3-point actuatorsNRDVX24-3-T-.. AC 24 VNRDVX230-3-T-.. AC 230 V
Dimensions
H+
Y2 Y1
H-
Wiring diagrams
T ~
AC 24 V Connect viasafety isolatingtransformer
! N L1 AC 230 V
Y1 NRDVX230-3-T-..Y21 2 3
NNRDVX24-3-T-..- +Y1 Y2
T1 2 3
NRDVX....-T-.., suitable for the following makes of valve
Technical data NRDVX24-3-T-.. NRDVX230-3-T-..Nominal voltage AC 24 V 50/60 Hz AC 230 V 50/60 HzFor wire sizing 1.5 VA 2.5 VAPower consumption 1.5 W 2.5 WConnecting terminals 2 x 0.75 mm2 or 1 x 1.5 mm2
Nominal stroke 5.5 mmActuating force 500 NManual operation temporary or permanent disengagement
by rotary knobRunning time 140 sSound power level max. 35 dB (A)Position indication scale plate 0...1Protection class (safety extra-low voltage) II (all-insulated)
Degree of protection IP40Temperature of medium +5°...100°C (including valve)Ambient temp. range 0°...+50°CNon-operating temp. –30°...+80°CHumidity test to EN 60730-1EMC CE according to 89/336/EEC, 92/31/EEC, 93/68/EECLV Directive CE according to 73/23/EECDirection of rotation as-wiredMaintenance maintenance-freeWeight 0.5 kg (without valve) 0.5 kg (without valve)
116.5 (NRDVX..-CA)
124.5 (NRDVX..-SI)
7580
33
93
III
Version Valve type DN (mm) kvs (m3/h) Actuator typeCazzaniga 2-way V02BM.. LN 15...40 3.9...14.5 NRDVX.....-T-CA
3-way V03BM.. LN 15...40 3.9...14.5Siemens 2-way VVG44.. 15...40 0.25...25 NRDVX.....-T-SI
2-way VVI52.. 15 0.25...2,53-way VXG44.. 15...40 0.25...25
NRDVX24-SR-T-..
6
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Short-stroke actuators for short-lift valves, max. nominal stroke 5.5 mm
Modulating actuators (AC/DC 24V)
Modulating control DC 0...10 V
Dimensions
Wiring diagrams
~
Y DC 0...10 V
U DC 2...10 V Measuring voltage U for position indication
Control signal from controller
Connect viasafety isolatingtransformer!-
T ~
AC 24 V+ DC 24 V
- +NRDVX24-SR-T-..
T1 2 3 5
Y U
Technical data NRDVX24-SR-T-.. Nominal voltage AC 24 V 50/60 Hz, DC 24 VNominal voltage range AC 19.2...28.8 V, DC 21.6...28.8 VFor wire sizing 3 VAPower consumption 1.5 WConnecting terminal 2 x 0.75 mm2 or 1 x 1.5 mm2
Control DC 0...10 V @ 100 kΩ input impedenceOperating range DC 2...10 V for 0...100%Position feedback DC 2...10 V (max. 1 mA)Uni-rotation ±5%Nominal stroke 5.5 mmActuating force 500 NManual operation temporary or permanent disengagement
by rotary knobRunning time 140 sSound power level max. 35 dB (A)Position indication scale plate 0...1Protection class (safety extra-low voltage)
Degree of protection IP40Temperature of medium +5°...100°C (including valve)Ambient temperature 0° ...+50°CNon-operating temp. –30°...+80°CHumidity test to EN 60730-1EMC CE according to 89/336/EEC, 92/31/EEC, 93/68/EECLV Directive CE according to 73/23/EECMaintenance maintenance-freeWeight 0.5 kg (without valve)
H
Y
III
NRDVX24-SR-T-.., suitable for the following makes of valve
Version Valve type DN (mm) kvs (m3/h) Actuator typeCazzaniga 2-way V02BM.. LN 15...40 3.9...14,5 NRDVX24-SR-T-CA
3-way V03BM.. LN 15...40 3.9...14,5Siemens 2-way VVG44.. 15...40 0.25...25 NRDVX24-SR-T-SI
2-way VVI52.. 15 0.25...2,53-way VXG44.. 15...40 0.25...25
116.5 (NRDVX..-CA)
124.5 (NRDVX..-SI)
7580
33
93
ApplicationsThe NRDVX24-SR-T-.. actuator is intendedfor motorizing Cazzaniga and Siemensshort-lift valves.
Mode of operationModulating control is employed with astandard control signal of DC 0...10 V. Asynchronizing function is triggered eachtime the power supply is energized. Theactuator runs at high speed to the closedposition (CLOSED limit switch) and syn-chronizes itself.The working range of 2...10 V can bechanged to 0...10 V by removing jumperB2 (see Operating controls, Page 7).
Product featuresEasy direct mounting on the body of thevalve. The stroke is adjusted at the factoryto suit the type of valve. The mountingbracket, suitable for the particular type ofvalve, is an integral part of the actuator.
Functional reliabilityThe electric motor is de-energized when theactuator runs on to its internal end-stops.
Manual operationThe actuator can be operated manually witha hand lever (temporary disengagement bysimply depressing the rotary knob on thehousing and permanent disengagement byrotating it).When the manual lever is rotated clockwisethe valve moves in the close direction.
Installation instructions, Page 7
Manual operation, Operating controls, InstallationE
NG
-930
01-9
3605
-01.
03-.
..M•
Prin
ted
in S
witz
erla
nd •
ZS
D •
Sub
ject
to
tech
nica
l cha
nges
7
Manual operation
If the black rotary knob is depressed andturned from position A (Automatic) to thehand symbol, manual operation will bepermanently engaged. Then, any controlsignal that might be received will not beacted upon.
The manual operating system incorpor-ates a slipping clutch and is overload-proof. When the manual lever (black) ismoved clockwise the actuator spindleretracts and the valve closes (Position 0).
Operating controls of the NRDVX24-SR-T-..
Jumpers B1 and B2 will be found underthe lid of the housing. In order to gainaccess to them first loosen the centralscrew of the black hand lever and removethe two Philips screws securing the lid.
Installing the NRDVX..-T on short-lift valves
1) Set the manual operating lever to«Hand». Rotate the black lever clockwiseto the end-stop. The lever should now bein the «Zero» position. If it is not, loosenthe central screw of the lever, pull it outand turn to the «Zero» position. Then re-secure the lever by tightening the centralscrew finger-tight.
2) Screw the actuator on to the thread ofthe valve neck.
3) Tighten the valve neck connection andreturn the manual operating lever to the«A» position (Automatic).
Jumper B1: RotationB1 connected B1 removed(signal direct) (signal inverted)
[reversed]U5
Y
U5
Y
0 10 V
U5
Y
10 V
00 2 10 V
U5
Y
10 V
2
SIEMENS NRDVX..-SI CAZZANIGA NRDVX..-CA
1 2 1 2
3 3
30
30 mm
Jumper B2: Working rangeB2 connected B2 removed(2...10 V) (0...10 V)
Type code for linear actuators
NV24-MFT-T
-T = Connecting terminalsControl-MFT= multi-functional-3 = 3-point
Operating voltage24 = 24 V
230 = 230 V
NV = Linear actuator
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Description of standard globe valves
8
Manual operation for commissioningand emergencies
Cover in inpact-resistant plastic,housing and mounting bracket instrong die-cast aluminium
Adjustable valve liftfrom 8 to 20 mm
The adapter suppliedwith the actuator is very easy to fit to the valve stem
Control, 3-point or modulating,
parameterizable
Very simple actuator mounting,the bracket comes with allnecessary adapter fittings for the valve concerned
The adapter is very easyto mount on the valve stem
1) Electrical closing force / blocking force
Integral terminals for easy wiring on-site
NV.. linear actuators (1000 N / 800 N 1), max. stroke 20 mm)
Integral easy-to-readposition indicator
Depending on the type of construction ofthe particular valve the closed point canbe in either the up position or the downposition. With most makes of valve, or withspecific ranges of valves from specificmakers, the closed point is in the up posi-tion when the stem of the valve is fully ex-tended from the valve body. The flowalong the control path is 0% and, with 3-way valves, the flow along the bypasspath is 100%. (The sealing part of the valvepoints upwards and is shaped like a cone).
However, there are also 2-way valvesavailable with the closed point in the downposition. With this type of valve the stem isfully retracted into the valve body and theflow along the control path is also 0%.(The sealing part of the valve points down-wards and is shaped like an invertedcone).
Types of construction of globe valves
Type code for mounting brackets
UNV-XXX
XXX = Suitable for valve (consecutive number)
UNV = Mounting bracket forNV actuator
down
up
Val
ve
Val
vecl
osin
g p
oint
Act
uato
r cl
osin
g p
oint
adju
stm
ent
Val
ve d
iagr
am
up
modulating, multi-functional 3-point
24 V 230 V 24 V
Type
AC 230 V, 3-point, 20 mm, 1000 N / 800 N 1)
AC / DC 24 V, 3-point, 20 mm, 1000 N / 800 N 1)
AC / DC 24 V, modulating, multifunctional, 20 mm, 1000 N / 800 N 1)
AC / DC 24 V, modulating, multifunctional, 20 mm, 1600 N 1)
Actuating time 7.5 s/mm, 4,5 mm selectable
Running time 150 s, (35)75...300 s adjustable2)
Running time 150 s, (17)35...300 s adjustabler 2)
Emergency operation <1,5 s/mm (spring)
Emergency control function, retracting (NVF24-MFT-T)
Emergency control function, extending (NVF24-MFT-E-T)
Control, 3-point
Control, DC 0...10 V (0...32 V)
Operating range DC 2...10 V selectable
Position feedback DC 2...10 V adjustable
Integral MP-Bus interface
Linking of active sensors and switches
Linking of active/passive sensors and switches
Closing point, selectable
Automatic stroke adaption
Without connecting lead
With screw terminals
+ / (+ = fitted; / = supplied separately)
Control valve make Mounting bracket see Pages
Ari UNV-027 44–45
Belimo UNV-002 24–25
Cazzaniga UNV-012 28–29
Controlli 3) UNV-036 50–51
Danfoss UNV-038 52–53
Johnson Controls EU 4) UNV-019 36–37
UNV-030 46–47
UNV-034 48–49
HORA UNV-024 40–41
Honeywell EU UNV-015 30–31
Osby UNV-025 42–43
Sauter UNV-018 34–35
Satchwell UNV-023 38–39
Siebe UNV-001 22–23
Siemens (L&S) UNV-003 26–27
tac UNV-017 32–33
1) Electrical closing force / blocking force2) 35/17 s with 10 mm stroke only 3) Can also be used for Trend4) State precise valve type and DN when ordering
NV24-MFT-T NV24-MFT2 NVG24-MFT2 NVF24-MFT-(E-)T NV230-3-T NV24-3-T
•
•
• • •
•
• •
• • •
•
• •
•
•
• •
• • • •
• • • •
• • • •
• • • •
• •
• •
• • • • • •
• • • •
• • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
OverviewE
NG
-930
01-9
3605
-01.
03-.
..M•
Prin
ted
in S
witz
erla
nd •
ZS
D •
Sub
ject
to
tech
nica
l cha
nges
9
Overview of linear actuators and mounting brackets
How to order linear actuators with mounting brackets
10
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Actuator types
The NV.. linear actuator is available in avariety of voltage ratings, with differenttypes of control and also with or withoutMFT multi-function technology for motor-
izing globe valves of many different makes.NVF.. actuators also incorporate an emer-gency control function.
NV linear actuator
NV linear actuatorand UNV mountingbracket
Ordering example Designation: NV24-3-T+UNV-003
➀ Linear actuator type NV24-3-T:
Rated voltage Linear actuator, AC / DC 24 VControl 3-pointConnections Terminals
➁ Combination unit+ Mounting bracket fitted
➂ Mounting bracket Suitable for Siemens valves (e.g.VXG41..)
➀ ➁ ➂
➀ Linear actuator
➁ Combination units
➂ Mounting bracket
NV linear actuator
The following data must be provided:• Control, 3-point or modulating• Rated voltage AC / DC 24 V
or AC 230 V• With or without emergency
control function
Specify the mounting brackets needed forthe different makes and types of valve:
• e.g. Belimo mounting bracket UNV-003Siemens VXG41.25 valves
Linear actuators and mountig bracketscan be supplied to order as follows:
• Mounting bracket fitted (+)• Mounting bracket/actuator supplied
separately ( / )• Different delivery dates for valves and
actuators on request
Mounting bracket XSupplied separatelyfitted
+
Combination units
Each price quoted in the Product and PriceCatalogue refers to a combination unit, i.e.actuator and mounting bracket.
Therefore, a correct order will require thefollowing information to be provided:
Notes
11
Remarks (will be deleted before printing)for Controllers
Ron: when “Hub” refers to “Actuator” it is “stroke”; – when it refers to “valve” it is “lift”P.56 (back side): the addresses are shorted (e.g. Tel., Fax, without www etc.P2: The notice downstairs "Important.." is modified from the base we had before.
So we have to modifie later all other versions like H4 Doc or prospects too. P4 I changed the two titles: Type code..and Overview.. with “stroke” too – OKP8... The old “inhibiting force” is definitely dead for “blocking force”!P10: Instead of "nominal voltage" = "rated voltage" – OKP12: We write shortly: "hexagonal key"! (Only on Page 21: 2x "hexagon socket-head key"P.21: Text upstairs will be later modified for H4 too! P.38: Altough the german title is not nominal lift 10...16 mm. (the same on P.46) – we still use it for uniformityP.54: The legends “Insulation..” not use anymore (existing in several publications)
an Reto: Zum besseren Kontrollvergleich der teils nur minim abweichenden Produktemerkmale empfehle ich die Zuhilfenahme der Übersicht auf 3 PDF-Seiten, die ich Dir bereits vorab mailte. Ausserdem bitte Rons Vorschlag prüfen bezüglich Verwen-dung von einheitlich “Nennhub” statt “Hub” wie auf Seite 38+46 bereits gemacht – OK?
12
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
NV24-3-T, NV230-3-T Direct-coupled actuators for globe valves
Linear actuator for globe valvesof 8...20 mm lift
3-point actuatorsNV24-3-T AC / DC 24 VNV230-3-T AC 230 V
T ~
AC 24 V- + DC 24 V
Connect viasafety isolatingtransformer! N L1 AC 230 V
Y1 NV230-3-TY21 2 3
NNV24-3-T- +Y1 Y2
T1 2 3
Wiring diagram
Technical data NV24-3-T NV230-3-TNominal voltage AC 24 V 50/60 Hz, DC 24 V AC 230 V 50/60 HzNominal voltage range AC 19.2...28.8 V AC 198...264 V
DC 21.6...28.8 VFor wire sizing 5 VA 7 VAPower consumption 3 W 6 WConnecting terminals 2 x 1.5 mm2 or 1 x 2.5 mm2
Nominal stroke 20 mmActuating force 1000 N 1) / (800 N) 2)
Manual operation hexagonal key, self-resetting 3)
Actuating time 7.5 s/mmSound power level max. 35 dB (A)Position indicator mechanical 8...20 mm stroke (mounting bracket)
Protection class (safety extra-low voltage) I (with PE conductor)
Degree of protection IP54Ambient temp. range 0°...+50°CNon-operating temp. –40°...+80°CHumidity test to EN 60730-1EMC CE according to 89/336/EEC, 92/31/EWG, 93/68/EECLV Directive CE according to 73/23/EECMode of operation Type 1 to EN 60730-1Maintenance maintenance-freeWeight 1.7 kg (without mounting bracket UNV)
1) Electrical closing force2) Blocking force3) Permanent manual operation to order
H+
Y2 Y1
H-
III
ApplicationsThe NV..-3-T actuator is intended formotorizing globe valves by exerting anoperating force on the valve stem in eithera retracting or an extending direction.
Mode of operationThe brushless motor is controlled by a3-point control signal.When the actuator is lifting and it reachesthe seat for either VALVE OPEN or VALVECLOSED the supply of current to the act-uator is reduced. Thanks to the use of abrushless motor the control signals Y1and Y2 do not need to be interruptedexternally (therefore, overload protectionis assured).
Functional reliabilityThe electric motor is de-energized when theactuator runs on to its internal end-stops.
Manual operation Inserting a 5 mm hexagonal key and turn-ing it clockwise causes the spindle of theactuator to emerge from the housing (anextending action). The spindle will remainin that position until the power supply isenergized (the controller has first priority).
Position indication The stroke is indicated mechanically onthe UNV-... mounting bracket.
Safety noteThe linear actuator contains no compon-ents which the user can replace or repair.
DimensionsThe dimensions depend on the type ofUNV-... mounting bracket used; see fromPage 22.
13
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
NV24-3-T, NV230-3-T Direct-coupled actuators for globe valves
ON
M S11 2
NV24-3(-T)S1.1
MON
S11 2
NV230-3(-T)
1
ON1
2
ON2
S1.2
Symbol
Symbol
7.5 s/mm
4.5 s/mm
T
Y1 Y2-1 2 3
Y1 Y2N
1 2 3
Wiring diagrams see Page 18
Functional description
The terminals for connecting the lead andthe S1 control device will be found underthe cover of the actuator.
The factory setting of actuating time is 7.5s/mm. By moving the slide switch S1.1 tothe «ON» position this time can be redu-ced by approximately half.
The closing point of the valve is definedwith slide switch S1.2. The factory settingof the closing point is «up». When a Y1signal is present the actuator spindleextends and the valve opens (when the«up» closing point has been selected).
The direction of travel of the actuatingspindle can also be inverted by interchang-ing the Y1 and Y2 conductors.
Arrangement of the operating controls
Function
Actuating time
Closing pointvalve
OFF
S1.1
SwitchDescription
For the nominal stroke function the running time for full strokevaries. (With 20 mm stroke and standard actuating time therunning time is 150 s).
Symbol
7.5 s/mm
4.5 s/mm
Actuating time 7.5 s/mmStandard
ONActuating time 4.5 s/mmHigh speed
The closing point is when the actuated spindle is either retracted orextended. There is no flow through the valve control path (V = 0%).
S1.2
The actuated spindle is retracted into the actuator and thevalve stem is extended from the valve body.
The actuated spindle is extended from the actuator and thevalve stem is retracted into the valve body.
OFF
ON Y1
up
down
Symbol Effect
Y1
Bold type in thetable meansstandard factorysetting.
14
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
NV24-MFT-T, NVG24-MFT2, NV24-MFT2 Direct-coupled actuators for globe valves
ApplicationsThe NV24-MFT-T, NVG24-MFT2 andNV24-MFT2 actuators are intended formotorizing globe valves by exerting anoperating force on the valve stem in eithera retracting or an extending direction.
Mode of operationModulating control is effected by means ofa standard signal of DC 0...10 V.The control signal is produced by themicroprocessor and acts on the brushlessmotor. When the actuator is powered upfor the first time the stroke is acquiredautomatically and stored in the micro-processor.The control signal and the runn-ing time are then adapted to suit that val-ue of stroke. If no correct adaption isperformed at that time (e.g. because thereis no valve mounted) another adaption willbe performed the next time the actuator ispowered up. When the actuator is liftingand it reaches the seat for either VALVEOPEN or VALVE CLOSED the supply ofcurrent to the actuator is reduced. Theactuator has an anti-blocking featurewhich, should dirt on the valve seat pre-vent it from closing properly, causes theactuator to move several times in the openand close directions over 1 to 5% stroke.
High-speed versionWith the Type NV24-MFT2 actuator therunning time can be reduced to 35 s or17 s for 10 mm stroke.
Functional reabilityThe actuator is short-circuit-proof andprotected against polarity reversal. Thestroke is adapted automatically.
Manual operation Inserting a 5 mm hexagonal key and turn-ing it clockwise causes the spindle of theactuator to emerge from the housing (anextending action). The spindle will remainin that position until the power supply isapplied (the controller has first priority).
Position indication The stroke is indicated mechanically onthe UNV-... mounting bracket and themaximum stroke adjusts itself automatic-ally. There is a two-colour LED status indi-cator under the cover of the housing.
Safety noteThe linear actuator contains no compon-ents which the user can replace or repair.
DimensionsThe dimensions depend on the type ofUNV-... mounting bracket used; see fromPage 22.
Linear actuators for globe valvesof 8...20 mm lift
Modulatingactuator(AC/DC24V)
Control signal DC 0...10 V
Y DC 0...10 V
U DC 2...10 V Measuring voltage U for position indication
Control signal from controllerY2
Connect viasafety isolatingtransformer!-
T ~
AC 24 V+ DC 24 V
~
Y/Z U/MPY2+NV24-MFT-TNV24-MFT2NVG24-MFT2
T1 2 3 4 5 6 7
Technical data NV24-MFT-T NV24-MFT2 NVG24-MFT2Nominal voltage AC 24 V, 50/60 Hz, DC 24 VNominal voltage range AC 19.2...28.8 V
DC 21.6...28.8 VFor wire sizing 5 VAPower consumption 3 WConnecting cable: 1 m, 5 x 0.75 mm2 1 m, 5 x 0.75 mm2
terminals: 2 x 1.5 mm2 or 1 x 2.5 mm2
Control DC 0...10 V @ 100 kΩOperating range DC 2...10 V for 0...100% strokePosition checkback 2...10 V @ 0.5 mA Uni-rotation ±5%Nominal stroke 20 mmActuating force 1000 N1) / (800 N) 2) 1600 NManual operation hexagonal key, self resetting 3)
Running time 150 s Sound power level max. 35 dB (A)Position indication mechanical 8...20 mm stroke (mounting bracket)
Protection class (safety extra-low voltage)
Degree of protection IP54Ambient temp. range 0°...+50°CNon-operating temp. –40°...+80°CHumidity test to EN 60730-1EMC CE according to 89/336/EEC, 92/31/EEC, 93/68/EECSoftware Class A to EN 60730-1Mode of operation Type 1 to EN 60730-1Maintenance maintenance-free Weight 1.7 kg (without mounting bracket UNV)
1) Electrical closing force2) Blocking force3) Permanent manual operation to order
Wiring diagram
III
H
Y
15
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
NV24-MFT Direct-coupled actuators for globe valves
Multi-Function Technology allows opti-mum matching of parameters to the differ-ent needs of an installation. The parame-ters are either entered as standard valuesat the factory or altered subsequentlyusing an MFT-H adjuster.
MFT
Parameter Standard VariableControl signal DC 0...10 V 3-point, Open/ClosedOperating range DC 2...10 V Start point DC 0.5...30 V
End point DC 2.5...32 VPosition checkback DC 2...10 V Start point 0.5...8 VU5 End point 1.5...10 V
Parameterizable for fault alarmRunning time 150 s (35)75...300 s 1)
(17) 35...300 s 2)
Actuating force 100% 25...100%
Under the cover of the actuator are the ter-minals for connecting the lead, the controldevices S1, S2 and S3 and the LED indi-cator H1.
By setting the slide switch S3 appropriate-ly or by pressing push-buttons S1 and S2it is possible to configure the actuator verysimply on-site to suit actual requirementswhen changes from the factory settingsare needed.
Functional description S
Arrangement of the operating controls
S3.1
1
ON1
2
ON2
S3.2
Symbol
Symbol
1 2 3 4 5
MON
S31 2
H1 S1S2
H
Y
H
Y
~
+ Y/Z Y2 U/MP
T
–
Bold type in thetable meansstandard factorysetting.
Bold type in the table means standardfactory setting.
Only properly authorised and trained persons may change the settings of slide switch S3 and push-button S2.
1) with NV24-MFT-T, NVG24-MFT2 2) with NV24-MFT2
Symbol Effect
OFF0% control signal corresponds to 0% position checkback.(The actuating spindle is then retracted or extended depend-ing on the choice of closing point).
direct H
Y
ON0% control signal corresponds to 0% position checkback.(The actuating spindle is then retracted or extended dependingon the choice of closing point).
inverted
Closing pointvalve
The closing point is when the actuating spindle is either retractedor extended. There is no flow through the valve control path.
S3.2
The actuating spindle is retracted into the actuator and thevalve stem is extended from the valve body. The positioncheckback shows 0% for direct travel.
The actuating spindle is extended from the actuator and the valvestem is retracted into the valve body. The position checkbackshows 0% for direct travel.(This setting is not necessary with Belimo Type H4.., H5.., H6..and H7.. globe valves.)
OFF
ON
U5 = 0%U5 = 100%
U5 = 100%U5 = 0%
up
down
H
Y
U5
Y
U5
Y
Direction of stroke S3.1The direction of travel in response to the control signal
Function SwitchDescription
Adaptation S2press
The effected stroke (between the two mechanical end-stops ofthe valve) is acquired as 100% stroke and stored in the micro-processor. The control signal and running time are then matchedto this 100% stroke.
Test S1press
The valve covers the full stroke in maximum running time andverifies the adapted stroke to ensure that both end-points arereached (H = 0% and H = 100%).
Symbol Effect
NVF24-MFT-T, NVF24-MFT-E-T Direct-coupled actuators for globe valves
16
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsThe NV..-MFT-(E)T actuator is intended formotorizing globe valves by exerting anoperating force on the valve stem in eithera retracting or an extending direction.
Mode of operationModulating control is effected by means ofa standard signal of DC 0...10 V.The control signal is produced by themicroprocessor and acts on the brushlessmotor. When the actuator is powered upfor the first time the stroke is acquiredautomatically and stored in the micro-processor.The control signal and the runn-ing time are then adapted to suit that val-ue of stroke. If no correct adaption isperformed at that time (e.g. because thereis no valve mounted) another adaption willbe performed the next time the actuator ispowered up. When the actuator is liftingand it reaches the seat for either VALVEOPEN or VALVE CLOSED the supply ofcurrent to the actuator is reduced. Theactuator has an anti-blocking featurewhich, should dirt on the valve seat pre-vent it from closing properly, causes theactuator to move several times in theopen and close directions over 1 to 5%stroke. When de-energized, the spindle ofthe NVF24-MFT-T retracts and that theNVF24-MFT-E-T extends.
Functional reabilityThe actuator is short-circuit-proof andprotected against polarity reversal. Thestroke is adapted automatically.
Manual operationInserting a 5 mm hexagonal key and turn-ing it clockwise causes the spindle of theactuator to emerge from the housing (anextending action). The spindle will remainin that position until the power supply isapplied (the controller has first priority).
Position indicationThe stroke is indicated mechanically onthe UNV-... mounting bracket and themaximum stroke adjusts itself automatic-ally. There is a two-colour LED status indi-cator under the cover of the housing.
Safety noteThe linear actuator contains no compon-ents which the user can replace or repair.
DimensionsThe dimensions depend on the type ofUNV-... mounting bracket used; see fromPage 22.
Linear actuators for globe valvesof 8...20 mm lift
Modulatingactuator(AC/DC24V)
Control signal DC 0...10 V
Y DC 0...10 V
U DC 2...10 V Measuring voltage U for position indication
Control signal fromcontrollerY2
Connect viasafety isolatingtransformer!-
T ~
AC 24 V+ DC 24 V
~
Y/Z U/MPY2+ NVF24-MFT(-E)-T
T1 2 3 4 5
Technical data NVF24-MFT-T NVF24-MFT-E-TEmergency function retracting extendingNominal voltage AC 24 V 50/60 Hz, DC 24 V Nominal voltage range AC 19.2...28.8 V
DC 21.6...28.8 VFor wire sizing 10 VAPower consumption 5.5 WConnecting terminals 2 x 1.5 mm2 or 1 x 2.5 mm2
Control DC 0...10 V @ 100 kΩOperating range DC 2...10 V for 0...100% strokePosition checkback 2...10 V @ 0.5 mA Uni-rotation ±5%Nominal stroke 20 mmActuating force 800 NManual operation hexagonal key, self-resettingRunning time 150 sEmergency operation <1,5 s/mmSound power level max. 35 dB (A)
max. 50 dB (A) emergency operation (spring)
Position indication mechanical 8...20 mm stroke (mounting bracket)
Protection class (safety extra-low voltage)
Degree of protection IP54Ambient temp. range 0°...+50°CNon-operating temp. –40°...+80°CHumidity test to EN 60730-1EMC CE according to 89/336/EEC, 92/31/EEC, 93/68/EECSoftware Class A to EN 60730-1Mode of operation Type 1 to EN 60730-1Maintenance maintenance-freeWeight 2.0 kg (without mounting bracket UNV)
Wiring diagram
III
H
Y
17
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
NVF24-MFT-T, NVF24-MFT-E-T Direct-coupled actuators for globe valves
Multi-Function Technology allows opti-mum matching of parameters to the differ-ent needs of an installation. The parame-ters are either entered as standard valuesat the factory or altered subsequentlyusing an MFT-H adjuster.
MFT
Parameter Standard VariableControl signal DC 0...10 V 3-point, Open/ClosedOperating range DC 2...10 V Start point DC 0.5...30 V
End point DC 2.5...32 VPosition checkback DC 2...10 V Start point 0.5...8 VU5 End point 1.5...10 V
Parameterizable for fault alarmRunning time 150 s (35)75...300 s 1)
Under the cover of the actuator are the ter-minals for connecting the lead, the controldevices S1, S2 and S3 and the LED indi-cator H1.
By setting the slide switch S3 appropriate-ly or by pressing push-buttons S1 and S2it is possible to configure the actuator verysimply on-site to suit actual requirementswhen changes from the factory settingsare needed.
Only properly authorized and trained persons may change the settings of slide switch S3 and push-button S2.
Functional description S
Arrangement of the operating controls
S3.1
1
ON1
2
ON2
S3.2
Symbol
Symbol
1 2 3 4 5
MON
S31 2
H1 S1S2
H
Y
H
Y
~
+ Y/Z Y2 U/MP
T
–
Bold type in thetable meansstandard factorysetting.
Bold type in the table means standardfactory setting..
1) Depending on the type of emergency function chosen, NVF24-MFT-T or NVF24-MFT-E-T, the electrical closing point is either identical to or opposite to thede-energized position of the actuator spindle. The type of actuator chosen depends on the design of valve involved and the required NO function (valve openwhen de-energized) or NC function (valve closed when de-energized).
1)
1)
1) 35 s for 10 mm stroke
Symbol Effect
OFF0% control signal corresponds to 0% position checkback.(The actuating spindle is then retracted or extended depend-ing on the choice of closing point).
direct H
Y
ON0% control signal corresponds to 0% position checkback.(The actuating spindle is then retracted or extended dependingon the choice of closing point).
inverted
Closing pointvalve
The closing point is when the actuating spindle is either retractedor extended. There is no flow through the valve control path.
S3.2
The actuating spindle is retracted into the actuator and thevalve stem is extended from the valve body. The positioncheckback shows 0% for direct travel.
The actuating spindle is extended from the actuator and the valvestem is retracted into the valve body. The position checkbackshows 0% for direct travel.(This setting is not necessary with Belimo Type H4.., H5.., H6..and H7.. globe valves.)
OFF
ON
U5 = 0%U5 = 100%
U5 = 100%U5 = 0%
up
down
H
Y
U5
Y
U5
Y
Direction of stroke S3.1The direction of travel in response to the control signal
Function SwitchDescription
Adaptation S2press
The effected stroke (between the two mechanical end-stops ofthe valve) is acquired as 100% stroke and stored in the micro-processor. The control signal and running time are then matchedto this 100% stroke.
Test S1press
The valve covers the full stroke in maximum running time andverifies the adapted stroke to ensure that both end-points arereached (H = 0% and H = 100%).
Symbol Effect
Wiring diagrams NV..
18
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
In the case of the classic 3-point actuator (NV..-3-T) the actuating time can be reduced from 7.5 s/mm to 4.5 s/mm by moving theslide switch 1.1 to the «ON» position. With less than 20% of the valves used the closing point is in the down position so the slideswitch S1.2 can be set to the «ON» position.
Setting the slide switch S3.1 to the «ON» position inverts the control signal so that the valve closes as the control signal is increased.This is a simple way of matching the sequences in the actuator. With less than 20% of the valves used the closing point is in thedown position so the slide switch S3.2 must be set to the «ON» position. The position checkback signal U5 is also matched to theclosing point.
The MFT linear actuator NV..-MFT.. can also be used as a 3-point control device. However, in this case the actuator must be assignedparameters for 3-point control and be provided with a 4-wire connection. Note: It will only function with an AC 24 V power supply!
Wiring diagram NV24-3-T, NV230-3-T
T ~
AC 24 V
- + DC 24 V
Connect viasafety isolatingtransformer N L1 AC 230 V
NV230-3-TY1 Y2N
baba
!
1 2 3
- +Y1 NV24-3-TY2
T1 2 3
Y (DC 0...10 V)from controller
U5 (DC 2...10 V)
T ~
AC 24 VDC 24 V
Connect viasafety isolatingtransformer+–
~
Y2
T
- +
1 2 3 4 5U⁄MPY⁄Z NV24-MFT(2)-T
NVF24-MFT(2)(-E)-TNVG24-MFT2
!
Modulating
3-point parameterized MFT actuator
3-point
Wiring diagram NV24-MFT(2)-T, NVF24-MFT(2)(-E)-T, NVG24-MFT2
Wiring diagram NV24-MFT(2)-T, NVF24-MFT(2)(-E)-T, NVG24-MFT2
T ~
AC 24 V Connect viasafety isolatingtransformer
!
a b
~
Y2
T1 2 3 4 5U⁄MPY⁄Z NV24-MFT(2)-T
NVF24-MFT(2)(-E)-TNVG24-MFT2
U5 (DC 2...10 V)
H
Y
H
Y
Clo
sing
poi
ntVa
lve
∆
∆
Act
uatin
g tim
e
Symbols
∆
∆
Sig
nal«
dire
ct»
Sig
nal«
inve
rted»
Clo
sing
poi
nt
«up»
Clo
sing
poi
nt
«dow
n»C
ontro
l sig
nal m
in.
(e.g
. Y=
2V)
Con
trol s
igna
l max
.(e
.g. Y
=10
V)M
easu
r. si
gnal
min
.(e
.g. U
=2
V)M
easu
r. si
gnal
max
.(e
.g. U
=10
V)
Actuator spindle moves
S3.1 S3.2
OFF OFFx x IN
x x OUT
OFF ONx x OUT
x x IN
ON 1) OFFx x OUT
x x IN
ON 1) ONx x INx x OUT
Sig
nal«
dire
ct»
Sig
nal«
inve
rted
»
Clo
sing
poi
nt«u
p»
Clo
sing
poi
nt«d
own»
Con
trol
con
tact
a(Y
/Z)
Con
trol
con
tact
b
(Y2)
Mea
sur.
sign
al m
in.
(e.g
.. U
=2
V)
Mea
sur.
sign
al m
ax.
(e.g
.. U
=10
V)
Actuator spindle moves
H+
Y2 Y1
H-
Clo
sing
poi
ntV
alve
∆
∆
H+
Y2 Y1
H-
Dire
ctio
n of
stro
ke«3
-poi
nt»
Symbols
∆
∆
S3.1 S3.20 0 *) *) stationary stationary
OFF OFF1 0 m OUT0 1 m IN
OFF ON1 0 m IN0 1 m OUT
ON OFF1 0 m IN0 1 m OUT
ON ON1 0 m OUT0 1 m IN
1) If the controller produces a negative signal (<0.15 V) the slide switch S3.1 may not be set tothe «ON» position if the parameters for the working range of the actuator have been assigned to2...10 V (except when the start point in the parameterized working range is 0.5 V).
*) Measuring signal U5 according to positionm: When control contact a or b is in position 1 for longer than the running time (150 s)
Clo
sing
poi
ntVa
lve
∆
∆
Act
uatin
g tim
e
Symbols
∆
∆
Sig
nal«
dire
ct»
Sig
nal«
inve
rted»
Clo
sing
poi
nt
«up»
Clo
sing
poi
nt
«dow
n»C
ontro
l sig
nal m
in.
(e.g
. Y=
2V)
Con
trol s
igna
l max
.(e
.g. Y
=10
V)
Actuator spindle moves
S1.1 S1.20 0 stationary stationary
7.5 s/mm OFF OFF1 0 OUT0 1 IN
OFF ON1 0 IN0 1 OUT
4.5 s/mm ON OFF1 0 IN0 1 OUT
ON ON1 0 OUT0 1 IN
Wiring diagrams / Flow characteristics with NV.. actuators
19
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Effect of the actuator spindle on different types of valve (choice of closing point)
Control path valveclosing(0% flow rate)
Valve
Control path valveopening(100% flow rate)
Control path valveopening(100% flow rate)
Control path valveclosing(100% flow rate)
Control path valveclosing(0% flow rate),Bypass 100% open
Control path valveopening (100% flow rate), Bypass 0%closed
Clo
sing
poi
nt v
alve
Clo
sing
poi
nt s
ettin
glin
ear
actu
ator
Actuator spindle retracting Actuator spindle extending
up
down
up
A typical use for 100% override is in a frost protection circuit. Whether or not the frost protection thermostat needs to interrupt thesignal circuit to the controller «d» depends on the particular make of controller used (it is not necessary when the signal output of thecontroller is short-circuit-proof and protected against polarity reversal).
100% override
Wiring diagram NV24-MFT(2)-T, NVF24-MFT(2)(-E)-T, NVG24-MFT2
–
T ~
AC 24 V- + DC 24 V
~
Y2
T
+
c d
Connect viasafety isolatingtransformer
!
1 2 3 4 5
U⁄MPY⁄Z NV24-MFT(2)-TNVF24-MFT(2)(-E)-TNVG24-MFT2
Y (DC 0...10 V)from controller
U5 (DC 2...10 V)
If the power supply is interrupted the actuator spindle will move to the end stop. With Type NVF24-MFT(2)-T actuators the spindleretracts into the housing. With Type NVF24-MFT(2)-E-T actuators the spindle extends from the housing. Depending on the particu-lar design of valve with the closing point in the up or down position, the valve behaves as either an NO device (open when de-energ-ized) or an NC device (closed when de-energized).
Emergency function
Wiring diagram NVF24-MFT(2)-T, NVF24-MFT(2)-E-T
T ~
AC 24 V- + DC 24 V
Connect viasafety isolatingtransformer!
~
Y2
T
- +
1 2 3 4 5U⁄MPY⁄Z
NVF24-MFT(2)-T
s Y (DC 0...10 V)from controller
U5 (DC 2...10 V)
NVF24-MFT(2)-E-T
Sig
nal«
dire
ct»
Sig
nal«
inve
rtie
rt»
Clo
sing
poi
nt «
up»
Clo
sing
poi
nt «
dow
n»
Con
trol
con
tact
s
Mea
sur.
sign
al m
in.(e
.g.U
=2
V)
Mea
sur.s
igna
lmax
.(e.g
.U=
10V) Actuator spindle moves:
Clo
sing
poi
nt v
alve
Dire
ctio
n of
tra
vel
«Em
erge
ncy
func
tion»
Symbols
S3.1 S3.2 NVF24-MFT(2)-T NVF24-MFT(2)-E-T
1) 1) 1) 0 k k IN
1) 1) 1) 0 k k OUT
Clo
sing
poi
nt v
alve
Dire
ctio
n of
str
avel
«Ove
rrid
e»
Sig
nal«
dire
ct»
Sig
nal«
inve
rted
»
Clo
sing
poi
nt«u
p»
Clo
sing
poi
nt«d
own»
Con
trol
con
tact
c
Con
trol
con
tact
d
Mea
sur.
sign
al m
in.(e
.g.U
=2
V)
Mea
sur.s
igna
lmax
.(e.g
.U=
10V) Actuator spindle moves:
∆
H
Y
Symbols
∆
S3.1 S3.2OFF
OFF1 0 x OUT
ON 1 0 x INOFF
ON1 0 x IN
ON 1 0 x OUT
1) The position of the slide switch has no effect on the direction of emergency operationk) No measuring voltages can be detected when de-energized
Assembly NV.. /UNV..
20
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Assembling the actuator and mounting bracket NV../UNV..
➊ If the mounting bracket (B) has beensupplied with the actuator (ordering ex-ample: NV24-3-T / UNV-002), first attachthe coupling (A) to the actuator spindle.
➋ Next, slide the mounting bracket (B) onto the coupling.
➌ Secure the mounting bracket to theactuator with the 4 screws (C). Hexagonsocket-head screws (Torx) are used inorder to ensure properly safe and secureattachment.
➍ Then slide the two «orange riders» [formechanical position indication (D)] on tothe spindle/stem coupling.T25 C
4Nm
BA
1
3
2
D
4
Manual operation NV..
21
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Manual operation of NV.. linear actuators
D
NV24-3NV230-3NV24-MFT
1) Isolate the actuator from the power supply
2) Disengaging manual operation of the NVF24-MFTTurn the hexagonal key clockwise through ca. 45º until resistance is en-countered. Then lift the key (ca. 7 mm) until the black socket for the key is le-vel with the top of the housing cover. The spring mechanism will now rotate the key counter-clockwise and the ac-tuator spindle will retract.
3) Manual operation of the NVF24-MFTTurning the hexagonal key clockwise causes the actuator spindle to extend; it must be stopped at the required po-sition of lift.
4) Locking manual operation of the NVF24-MFTTurn the hexagonal key back 3/4 turn counter-clockwise and then press it down into the cover of the housing (the black socket will move inwards ca. 7 mm). Slight counter-clockwise rotation of the key will then lock themanual operating mechanism in pos-ition.
1) 2)
5 mm
2)4)3)
1)
5 mm
NVF24-MFT
Turning the hexagon socket-head keyclockwise 1) causes the actuator spindleto extend; turning it counter-clockwise 2)causes it to retract.
1) Isolate the actuator from the power supply
2) Disengaging manual operation of the NVF24-MFT-ETurn the hexagonal key counter-clock-wise through ca. 45º until resistance isencountered. Then lift the key (ca. 7mm) until the black socket for the key islevel with the top of the housing cover. The spring mechanism will now rotate the key clockwise, the actuator spindle will extend fully, the postion indicator(D) will move down and the valve can be coupled up.
3) Manual operation of the NVF24-MFT-ETurning the hexagonal key counter-clockwise causes the actuator spindle to retract; it must be stopped at therequired position of lift.
4) Locking manual operation of the NVF24-MFT-ETurn the hexagonal key back 3/4 turn clockwise and then press it down into the cover of the housing (the black socket will move inwards ca. 7 mm). Slight clockwise rotation of the key will then lock the manual operating mecha-nism in position.
2)4)3)
1)
5 mm
NVF24-MFT-E
When an actuator is supplied togetherwith a valve, but the two items are notassembled, the spindle of the actuator isextended to approximately the 3/4 strokeposition. If necessary, the spindle can be
operated with a 5 mm (3/16”) hexagonsocket-head key (the key is not includedwith the actuator).The manual operating mechanism is over-load-proof. The spindle of the actuator will
remain at the manual setting until thepower supply to the actuator is energizedor, the next time the power supply is inter-rupted, it will move to whichever endposition has been selected.
Mounting bracket UNV-001 for Siebe globe valves
22
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsSiebe Series VB7000 and VB9000 valvesare easy to motorize using a Type NV..-Tlinear actuator and a UNV-001 mountingbracket.
Product featuresThe UNV-001 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Siebe valve. Themounting bracket screws directly on to thethread on the neck of the Siebe valve. Thestem adapter attaches to the stem of thevalve and the connection to the actuatorspindle is semi-automatic by means of thestem coupling.
Mounting bracket UNV-001
suitable for Siebe globe valves of nominal lift up to 15 mm (1/2”)
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)NVF24-MFT-E-T AC/DC 24 V (P.16)
Siebe valves
Mounting bracket materials
Valve 2-way DN 3-way DNType with VB7213 1/2”...2” VB7313 1/2”...2”closing point up VB9000 1/2”...11/4”Type with VB7223 1/2”...2”closing point downTemperature of medium 2...120°C
Mounting bracket die-cast aluminiumStem adapter stainless steelStem coupling stainless steel Weight 0.22 kg
H+
Y2 Y1
H–
A
B
AB
VB7213
VB7223
VB7313VB9000
A AB
A AB
A AB
A
B
AB
S1.2SIEBE S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
7.5 s/mm
NV24-3... / NV230-3...
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON ON ON
ON
ON
ON
ON
NVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
NV24-MFT... / NV24LON
H
Y
H
Y4.5 s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Assembly instructions
23
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
11055179
72
221
Assembly instructions NV..+UNV-001
Dimensions with NV..-T linear actuator
S
BC
D
F1
F2
A
46±0
.5m
m
85
7Nm
7mm
8mm
5mm
10
6
7
F1
F2 50Nm
42mm
9
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
Mounting bracket UNV-002 for Belimo globe valves
24
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsBelimo Series H4, H5, H6 and H7 valvesare easy to motorize using a Type NV..-Tlinear actuator and a UNV-002 mountingbracket.
Product featuresThe UNV-002 mounting bracket is securedto the NV.. actuator by means of 4 screws.The mounting bracket screws directly onto the thread on the neck of the Belimovalve. The connection between the valvestem and the actuator spindle is semi-automatic by means of the stem coupling.The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe stroke of the valve is indicated mech-anically on the mounting bracket and themaximum lift adjusts itself automatically.
Mounting bracket UNV-002
suitable for Belimo globe valves of lift 10...20 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)NVF24-MFT-E-T AC/DC 24 V (P.16)
Belimo valves
Mounting bracket materials
Valve 2-way DN 3-way DNType with H4 15...50 H5 15...50 closing point up H6 15...80 H7 15...80Temperature of medium 2...120°C
Mounting bracket die-cast aluminiumStem adapter stainless steel Weight 0.22 kg
H+
Y2 Y1
H–
H
Y
H
Y
A
B
ABH5H7
H4H6
A AB
A AB
A
B
AB
S1.2BELIMO S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Assembly instructions
25
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
11055179
72
205
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-002
BE
LM
O
BC
D
H
A
5mm
10Nm
10mm
H
5 6
7
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
NoteWhen a Belimo valve is ordered togetherwith a Type NV.. linear actuator, themounting bracket UNV-002 is includedwith it.
Mounting bracket UNV-003 for Siemens globe valves
26
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsL&S Series V.F21, V.F31, V.F40, V.F41,V.G41, V.F52 and V.F61 valves are easyto motorize using a Type NV..-T linear ac-tuator and a UNV-003 mounting bracket.
Product featuresThe UNV-003 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a L&S valve. The mounting bracket is bolted directly tothe neck of the valve giving a friction-locked connection. The stem adapter issecured to the valve stem. The connection
Mounting bracket UNV-003
suitable for Siemens(Landis & Staefa) globe valves of nominal lift 20 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)Siemens valves (Landis & Staefa)
Mounting bracket materials
H+
Y2 Y1
H–
H
Y
H
Y
A AB
A
B
AB
S1.2SIEMENS S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
A AB
A
B
AB
VVF21VVF31VVF40VVF41VVF52VVF61VVG41VPF52
VXF21VXF31VXF40VXF41VXF61VXG41
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Valve 2-way DN 3-way DNType with VVF21 20...80 VXF21 25...80 closing point up VVF31 20...80 VXF31 25...80
VVF40 15...80 VXF40 15...80 VVF41 50 VXF41 50...(80) VVG41 15...50 VXG41 15...50 VVF52 15...40 VXF61 15...25 VPF52 15...40VVF61 15...25
Temperature of medium 2...(120)150°C
Mounting bracket die-cast aluminiumStem adapter stainless steel/brass Stem coupling stainless steelWeight 0.34 kg
Assembly instructions
27
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
11055179
72
259
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-003
10Nm
10mm
HG
10Nm
17mm
22mm
F4
F1
F2F3
SS 5
6
8
9
107
BC
D
H
G
F1
F4
F2
F3
A
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
between the valve stem and the actuatorspindle is semi-automatic by means of thestem coupling.The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
Mounting bracket UNV-012 for Cazzaniga globe valves
28
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsCazzaniga Series V2BM and V3BM valvesare easy to motorize using a Type NV..-Tlinear actuator and a UNV-012 mountingbracket.
Product featuresThe UNV-012 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Cazzaniga valve. The mounting bracket is placed on thevalve neck adapter and bolted to it givinga friction-locked connection. The stemadapter is then inserted into the valve stemand locked. The connection between thevalve stem and the actuator spindle issemi-automatic by means of the stemcoupling. The actuator and the mountingbracket can be swivelled through 360° onthe neck of the valve.
Mounting bracket UNV-012
suitable for Cazzaniga globevalves of nominal lift 20 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)
Cazzaniga valves
Mounting bracket materials
H+
Y2 Y1
H–
H
Y
H
Y
A
B
AB
V3BM
V2BMA AB
A
B
AB
S1.2CAZZANIGA S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
A AB
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON ON ON
ON
ON ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Valve 2-way DN 3-way DNType with V2BM 15...50 closing point down Type with V3BM 15...50closing point up Temperature of medium 2...(110)150°C
Mounting bracket die-cast aluminiumStem adapter stainless steel/brassStem coupling stainless steel Weight 0.38 kg
Assembly instructions
29
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
11055179
72
259
8
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-012
CA
ZZ
AN
GA
000
EF
BC
D
H
G
A
10Nm
10mm
HG
96±0
.5m
m
7
E
10Nm
13mm
F9mm
5
6
8
9
10
117
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
Mounting bracket UNV-015 for Honeywell globe valves
30
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsHoneywell Series V5011R, V5049A,V5095A, V5328A, V5013A, V5013R,V5015, V5050A, V5329A and V5329Cvalves are easy to motorize using a TypeNV..-T linear actuator and a UNV-015mounting bracket.
Product featuresThe UNV-015 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Honeywell valve. The mounting bracket is placed on thevalve neck adapter and bolted to it givinga friction-locked connection. The stem ad-apter is then inserted into the valve stemand locked. The connection between thevalve stem and the actuator spindle is semi-automatic by means of the stem coupling.
Mounting bracket UNV-015
suitable for Honeywell (Europe)globe valves of nominal lift 20 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)
Honeywell valves
Mounting bracket materials
H+
Y2 Y1
H–H
Y
H
Y
A
B
AB
HONEYWELL
A AB
A
B
AB
V5011RV5049AV5095AV5328A
V5013AV5013RV5015V5050AV5329AV5329C
S1.2 S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
A AB
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON ON ON
ON
ON ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
4.5s/mm7.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T)..
Settings for NV.. linear actuator
Valve 2-way DN 3-way DNType with V5011R 15...50 closing point down V5049A 15...65
V5095A 20...80 V5328A 15...80
Type with V5013A 15...50 closing point up V5013R 15...50
V5015 25...80 V5050A 15...80 V5329A 15...80 V5329C 15...80
Temperature of medium 2...150°C
Mounting bracket die-cast aluminiumValve neck adapter brassStem adapter stainless steelStem coupling stainless steel Weight 0.5 kg
Assembly instructions
31
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-015
F1
BC
D
H
G
F2
E
A
F1
3mm
8Nm
10Nm
10mm
HG
F2
5
6
8
9
107
E
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
259
12
Mounting bracket UNV-017 for tac globe valves
32
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Applicationstac Series V241, V341 and V294 valvesare easy to motorize using a Type NV..-Tlinear actuator and a UNV-017 mountingbracket.
Product featuresThe UNV-017 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a tac valve. The mounting bracket is bolted directly tothe neck of the valve giving a friction-locked connection. The stem adapter issecured to the valve stem. The connectionbetween the valve stem and the actuatorspindle is semi-automatic by means of thestem coupling.
Mounting bracket UNV-017
suitable for tac globe valves of nominal lift 20 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)
tac valves
Mounting bracket materials
H+
Y2 Y1
H–
H
Y
H
Y
A
B
AB
V241
V294
V341
A AB
A AB
A AB
A
B
AB
S1.2TAC S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
ON ON
ON
ON
ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Valve 2-way DN 3-way DNType with V241 15...50 V341 15...50 closing point up Type with V294 15...32 closing point downTemperature of medium 2...150°C
Mounting bracket die-cast aluminiumStem adapter stainless steelStem coupling stainless steel Weight 0.3 kg
Assembly instructions
33
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-017
TAC
96±0
.5m
m
F1
F2
24Nm
13mm9mm
10Nm
10mm
HG
5
6
8
7
9
10
BC
D
H
G
F1
F2
A
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
259
Mounting bracket UNV-018 for Sauter globe valves
34
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsSauter Series V6.., VX.., B6.. and BX..valves are easy to motorize using a TypeNV..-T linear actuator and a UNV-018mounting bracket.
Product featuresThe UNV-018 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Sauter valve. The valve neck ring is inverted on to theneck of the valve, the mounting bracket isplaced on the valve neck ring and bolteddirectly to the neck of the valve giving afriction-locked connection. The stem ad-Hub
Mounting bracket UNV-018
suitable for Sauter globe valves of nominal lift 14 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)NVF24-MFT-T AC/DC 24 V (P.16)Sauter valves
Mounting bracket materials
H+
Y2 Y1
H–
H
Y
H
Y
A AB
A
B
AB
S1.2SAUTER S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
A AB
A
B
AB
V6R...F...VXD...F...VXE...F...V6F...F...V6G...F...V6S...F...
B6R...F...BXD...F...BXE...F...B6F...F...B6G...F...B6S...F...
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
NV24-3... / NV230–3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Valve 2-way DN 3-way DNType with V6R..F 15...50 B6R..F 15...50 closing point up VXD..F 15...50 BXD..F 15...50
VXE..F 15...50 BXE..F 15...50V6F..F 15...50 B6F..F 15...50 V6G..F 15...50 B6G..F 15...50V6S..F 15...50 B6S..F 15...50
Temperature of medium 2...(130)150°C
Mounting bracket die-cast aluminiumValve neck ring stainless steel Stem adapter stainless steelStem coupling stainless steelWeight 0.38 kg
Assembly instructions
35
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-018
96±0
.5m
m
5 9
EF
BC
D
H
G
A
24Nm
12mm
16mm
6
8
7
E
F
10Nm
10mm
H
G
10
11
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
apter is secured to the valve stem. Theconnection between the valve stem andthe actuator spindle is semi-automatic bymeans of the stem coupling.The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
259
Mounting bracket UNV-019 for Johnson Controls globe valves
36
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsJohnson Controls Series VG72.., VG74..and VG78.. valves until DN 20 are easyto motorize using a Type NV..-T linear ac-tuator and a UNV-019 mounting bracket.
Product featuresThe UNV-019 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Johnson Controlsvalve.The valve neck adapter is screwed on tothe neck of the valve and locked. Themounting bracket is placed on the valveneck adapter and bolted to it giving a fric-tion-locked connection. The stem adapteris secured to the valve stem.
Mounting bracket UNV-019
suitable for Johnson Controlsglobe valves of nominal lift 8 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–H
Y
H
Y
A
B
AB
VG7401VG7403
VG7201VG7203
VG7802VG7804
A AB
A AB
A AB
A
B
AB
S1.2JOHNSON S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
ON ON
ON
ON
ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Mounting bracket materials
Mounting bracket die-cast aluminiumValve neck adapter brass Stem adapter stainless steelStem coupling stainless steelWeight 0.62 kg
Johnson Controls valves
Valve 2-way DN* 3-way DN*Type with VG7401 15...20 VG7802 15...20 closing point up VG7403 VG7804Type with VG7201 15...20 closing point down VG7203Temperature of medium 2...120°C
*DN 25...50 see UNV-030)
Assembly instructions
37
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
11055179
72
205
26
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-019
46±0
.5m
m
5 9
5mm
10Nm
10mm
H
8mm
10Nm
11mm
6
8
10
117
ø4mm
40Nm
E
F1
F2
BC
D
H
E
F1
F2
A
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The connection between the valve stemand the actuator spindle is semi-automat-ic by means of the stem coupling.The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
Mounting bracket UNV-023 for Satchwell globe valves
38
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsSatchwell Series VZ, VSF, MZ and MJFvalves are easy to motorize using a TypeNV..-T linear actuator and a UNV-023mounting bracket.
Product featuresThe UNV-023 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Satchwell valve.The valve neck adapter is screwed on tothe neck of the valve and locked. Themounting bracket is placed on the valveneck adapter and bolted to it giving a fric-tion-locked connection. The stem adapteris secured to the valve stem. The connec-tion between the valve stem and the actu-ator spindle is semi-automatic by meansof the stem coupling.
Mounting bracket UNV-023
suitable for Satchwell globevalves of nominal lift 10...16 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–
H
Y
H
Y
2
3
1MZMJF
VZVSF
2 1
2 1
2
3
1
S1.2SATCHWELL S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Mounting bracket materials
Mounting bracket die-cast aluminiumVentilhalsadapter brass Stem adapter stainless steelStem coupling stainless steelWeight 0.44 kg
Satchwell valves
Valve 2-way DN 3-way DNType with VZ 1/2”...2” MZ 1/2”...2”closing point up VSF 15...25 MJF 15...25Temperature of medium 2...(130)150°C
Assembly instructions
39
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-023
100
±0.5
mm
5 9
10Nm
10mm
HGø4mm
40Nm
10Nm
8mm
12mm
6
8
10
117
E
F
FE
BC
D
H
G
A
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
259
2
Mounting bracket UNV-024 for HORA globe valves
40
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsHORA Series BR206, BR216, BR306,BR316 and BR225 valves are easy tomotorize using a Type NV..-T linear ac-tuator and a UNV-024 mounting bracket.
Product featuresThe UNV-024 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a HORA valve. The valve neck adapter is mounted on theneck of the valve with a friction-lockedconnection. The mounting bracket is plac-ed on the valve neck adapter and boltedto it giving a friction-locked connection.The stem adapter is secured to the valvestem.
Mounting bracket UNV-024
suitable for HORA globe valves of nominal lift 16 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)NVF24-MFT-E-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–
H
Y
H
Y
A
B
AB
BR206GGBR216GGBR216RGA
BR225RG
BR306GGBR316GGBR316RGA
A AB
A AB
A AB
A
B
AB
S1.2HORA S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
ON ON
ON
ON
ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Mounting bracket materials
Mounting bracket die-cast aluminiumValve neck adapter brass Stem adapter stainless steelStem coupling stainless steel Weight 0.48 kg
HORA valves
Valve 2-way DN 3-way DNType with BR206GG 15...50 BR306GG 15...50 closing point up BR216GG 15...50 BR316GG 15...50
BR216RGA 1/2”...2” BR316RGA 1/2”...2”Type with BR225RG 15...25closing point downTemperature of medium 2...120°C
Assembly instructions
41
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
11055179
72
205
18
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-024
46±0
.5m
m
5 9
10Nm
10mm
H
6
7
8
8mm
6mm
10Nm
10
E
F
3mm
8Nm
5mm
11
BC
D
E
HF
A
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The connection between the valve stemand the actuator spindle is semi-autom-atic by means of the stem coupling.The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
Mounting bracket UNV-025 for Osby globe valves
42
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsOsby Series MTV and MTR valves are easyto motorize using a Type NV..-T linear ac-tuator and a UNV-025 mounting bracket.
Product featuresThe UNV-025 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Osby valve. The valve neck adapter is screwed on tothe neck of the valve and locked. Themounting bracket is placed on the valveneck adapter and bolted to it giving afriction-locked connection. The stem ad-apter is secured to the valve stem. Theconnection between the valve stem andthe actuator spindle is semi-automatic bymeans of the stem coupling.
Mounting bracket UNV-025
suitable for Osby globe valves of nominal lift 19 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)NVF24-MFT-E-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–
H
Y
H
Y
2
3
1
MTR
MTVMTR
DN 15 ... 25DN 15 ... 25
MTV2 1
2 1
2
3
1
S1.2OSBY S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
NV24–3... / NV230–3... NV24–MFT... / NV24LON
MFT-H
RS232 M
MFT-H F=75%MFT-H F=75%
F < 750NF < 750N
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Mounting bracket materials
Mounting bracket die-cast aluminiumValve neck adapter brass Stem adapter stainless steelStem coupling stainless steelWeight 0.68 kg
Osby valves
Valve 2-way DN 3-way DNType with MTV 15...50 MTR 15...50 closing point up Temperature of medium 2...150°C
Assembly instructions
43
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-025
10Nm
10mm
HG
24Nm
11mm
15mm
ø4mm
40Nm
96±0
.5m
m
5
6
8
9
10
117
E
F
EF
BC
D
H
G
A
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
259
27
Mounting bracket UNV-027 for Ari globe valves
44
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsAri Series BR485, BR486 and ..487 valvesare easy to motorize using a Type NV..-Tlinear actuator and a UNV-027 mountingbracket.
Product featuresThe UNV-027 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Ari valve.The valve neck adapter is screwed on tothe neck of the valve and locked. Themounting bracket is placed on the valveneck adapter and bolted to it giving afriction-locked connection. The stem ad-apter is secured to the valve stem. Theconnection between the valve stem andthe actuator spindle is semi-automatic bymeans of the stem coupling.
Mounting bracket UNV-027
suitable for Ari globe valves of nominal lift 14 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)NVF24-MFT-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–
H
Y
H
Y
A
B
ABBR485
..487
BR486A AB
A AB
A
B
AB
S1.2ARI S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Mounting bracket materials
Mounting bracket die-cast aluminiumValve neck adapter brass Stem adapter stainless steelStem coupling stainless steelWeight 0.46 kg
Ari valves
Valve 2-way DN 3-way DNType with BR486 15...50 BR485 15...50 closing point up ..487 15...50 Temperature of medium 2...120°C
Assembly instructions
45
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-027
46±0
.5m
m
5 8
5mm
10Nm
10mm
Hø4mm
40Nm
8mm
6mm
10Nm
6
7
9
10
E
F
BC
D
E
HF
A
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
205
15
Mounting bracket UNV-030 for Johnson Controls globe valves
46
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsJohnson Controls Series VG72.., VG74..,VG78.., BM-2XX2, BM-2XX8 valves andDN 25 ...50 are easy to motorize using aType NV..-T linear actuator and a UNV-030mounting bracket.
Product featuresThe UNV-030 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Johnson Controlsvalve. The valve neck adapter is screwedon to the neck of the valve and locked.The mounting bracket is placed on thevalve neck adapter and bolted to it giving
Mounting bracket UNV-030
suitable for Johnson Controlsglobevalves ofnom.lift13...19mm
In combination with Belimo linear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)NVF24-MFT-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–
H
Y
H
Y
A
B
AB
1
2
3
VG7401VG7403
VG7201VG7203
BM–2XX2
VG7802VG7804
A AB
1 2
A AB
A AB
A
B
AB
S1.2JOHNSON S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
ON ON
ON
ON
ON
ON
BM–2XX8
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Johnson Controls valves
Mounting bracket materials
Ventil 2-way DN* 3-way DN*Type with VG7401 25...50 VG7802 25...50 closing point up VG7403 25...50 VG7804 25...50
BM-2XX8 15...50Type with VG7201 25...50 closing point down VG7203 25...50
BM-2XX2 15...50Temperature of medium 2...(140)150°C
*DN 15...20 see UNV-019
Mounting bracket die-cast aluminiumStem adapter stainless steel Stem coupling stainless steelWeight 0.32 kg
Assembly instructions
47
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Dimensions with NV..-T linear actuator
Assembly instructions NV..+UNV-030
E
F1
F2
BC
D
H
G
A
10Nm
10mm
HG
7
F2
96±0
.5m
m
40Nm
ø4mm
10Nm
8mm11mm
5
6
8
9
10
117
E
F1
Typ VG...
Typ VG...
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
a friction-locked connection. The stem ad-apter is secured to the valve stem. Theconnection between the valve stem andthe actuator spindle is semi-automatic bymeans of the stem coupling.The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
259
Mounting bracket UNV-034 for Johnson Controls globe valves
48
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsJohnson Controls Series VBF-0.., VBF-2..,VG84., VBD-4.. and VG82. valves areeasy to motorize using a Type NV..-T lin-ear actuator and a UNV-034 mountingbracket.
Product featuresThe UNV-034 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Johnson Controlsvalve.The valve neck adapter is screwed on tothe neck of the valve and locked. Themounting bracket is placed on the valveneck adapter and bolted to it giving a fric-tion-locked connection.
Mounting bracket UNV-034
suitable for Johnson Controlsglobe valves of nominal lift 13 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–
H
Y
H
Y
A AB
A AB
A
B
AB
A
B
AB
VBF-0XX4VBF-2XX4VG84XXVBD-4XX4
VBF-0XX8VBF-2XX8VG88XXVG89XXVBD-4XX8
VG82XX
S1.2 S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1JOHNSON
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
ON ON
ON
ON
ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
A AB
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Mounting bracket materials
Mounting bracket die-cast aluminiumValve neck adapter brass Stem adapter stainless steelStem coupling stainless steelWeight 0.32 kg
Johnson Controls valves
Valve 2-way DN 3-way DNType with VBF-0XX4 15...50 VBF-0XX8 15...50 closing point up VBF-2XX4 15...50 VBF-2XX8 15...40
VG84XX 15...40 VG88XX 15...40 VG89XX 15...40
VBD-4XX4 15...40 VBD-4XX8 15...40Type with VG82XX 15...40closing point downTemperature of medium 2...(130)150°C
Assembly instructions
49
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Dimensions with NV..-T linear actuator
JOS
O
10Nm
10mm
HG
100
±0.5
mm
8mm
6mm
10Nm
ø4mm
40Nm7
5
6
8
9
10
11
E
F
E
F
BC
D
H
G
A
Assembly instructions NV..+UNV-034
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The stem adapter is secured to the valvestem. The connection between the valvestem and the actuator spindle is semi-automatic by means of the stem coupling.The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
259
2
50
Mounting bracket UNV-036 for Controlli globe valves
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsControlli Series VSB, VMB valves and theTrend Series GIBT and GIBF are easy tomotorize using a Type NV..-T linear ac-tuator and a UNV-036 mounting bracket.
Product featuresThe UNV-036 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Controlli and Trendvalve.The valve neck adapter is screwed on tothe neck of the valve and locked. Themounting bracket is placed on the valveneck adapter and bolted to it giving a fric-tion-locked connection.
Mounting bracket UNV-036
suitable for Controlli globevalves of nominal lift 13 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–
H
Y
H
Y
A AB
A
B
AB
S1.2CONTROLLI/TREND S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
A AB
A
B
AB
CONTROLLIVSBVSBXXF
TRENDGIBT/21/XXGIBF/21/XX
CONTROLLIVMBVMBXXF
TRENDGIBT/31/XXGIBF/31/XX
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
NV24-3... / NV230-3... NV24-MFT... / NV24LONNVF24-MFT... / NVF24LON..NVG24-MFT2 / NVG24LON
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Mounting bracket materials
Mounting bracket die-cast aluminiumValve neck adapter brass Stem adapter stainless steelStem coupling stainless steelWeight 0.5 kg
Controlli valves
Valve 2-way DN 3-way DNType with VSB 15...50 VMB 15...50 closing point up VSBXXF 15...50 VMBXXF 15...50
GIBT/21/XX 1) 15...50 GIBT/31/XX 1) 15...50GIBF/21/XX 1) 15...50 GIBF/31/XX 1) 15...50
Temperature of medium 2...120°C
1) Trend type designation
51
Assembly instructionsE
NG
-930
01-9
3605
-01.
03-.
..M•
Prin
ted
in S
witz
erla
nd •
ZS
D •
Sub
ject
to
tech
nica
l cha
nges
Dimensions with NV..-T linear actuator
F1
F2
BC
D
H
G
A
E
F2
112
±0.5
mm
5 9
10Nm
10mm
HG
F1
10mm13mm
10Nm
E40Nm
ø4mm
6 10
117
8
Assembly instructions NV..+UNV-036
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
The stem adapter is secured to the valvestem. The connection between the valvestem and the actuator spindle is semi-automatic by means of the stem coupling.The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
Position indicationThe lift is indicated mechanically on themounting bracket; the indicator adjustsitself automatically.
11055179
72
259
2
52
Mounting bracket UNV-038 for Danfoss globe valves
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
ApplicationsDanfoss Series (H)VF.., (H)VL.., (H)VR..,(H)VE., VR2 valves are easy to motorizeusing a Type NV..-T linear actuator and aUNV-038 mounting bracket.
Product featuresThe UNV-038 mounting bracket is securedto the NV.. actuator by means of 4 screws.It comes with all necessary adapters need-ed for attaching to a Danfoss valve.The mounting bracket is placed on thevalve neck ring and bolted directly to theneck giving a friction-locked connection.The connection between the valve stemand the actuator spindle is semi-automat-ic by means of the stem coupling.
Mounting bracket UNV-038
suitable for Danfoss globevalves of nominal lift 13 mm
In combination with Belimolinear actuatorsNV24-3-T AC/DC 24 V (P.12)NV230-3-T AC 230 V (P.12)NV24-MFT-T AC/DC 24 V (P.14)NV24-MFT2 AC/DC 24 V (P.14)NVG24-MFT2 AC/DC 24 V (P.14)NVF24-MFT-T AC/DC 24 V (P.16)
H+
Y2 Y1
H–
H
Y
H
Y
A
B
AB
(H)VF2(H)VL2(H)VRB2
(H)VE2(H)VFS2(H)VR2
(H)VF3(H)VL3(H)VRB3(H)VRG3
A AB
A AB
A
B
AB
S1.2DANFOSS S3.1 S3.2 S3.1 S3.2S1.1 S1.2S1.1
1 2 3
M S1
ON1 2
1 2 3
M S1
ON1 2
1 2 3 4 5
S3
ON1 2
M
1 2 3 4 5
S3
ON1 2
M
ON
ON
ON
ON
ON ON
ON
ON
ON
ON
NV24-MFT... / NV24LONNV24-3... / NV230-3...
A AB
7.5s/mm 4.5s/mm
Depending on the particular type of linear actuator and valve being used the slide switch allows easy matching to the actuator (see also NV..-T).
Settings for NV.. linear actuator
Mounting bracket materials
Mounting bracket die-cast aluminiumValve neck adapter brass Stem adapter stainless steelStem coupling stainless steelWeight 0.5 kg
Danfoss valves
Valve 2-way DN 3-way DNType with (H)VF2 25...50 (H)VF3 15...50 closing point up (H)VL2 15...50 (H)VL3 15...50
(H)VRB2 15...25 (H)VRB3 15...50(H)VRG3 15...50
Type with (H)VE2 25...50closing point down (H)VFS2 15...50
VR2 15...25Temperature of medium 2...120°C
53
Assembly instructionsE
NG
-930
01-9
3605
-01.
03-.
..M•
Prin
ted
in S
witz
erla
nd •
ZS
D •
Sub
ject
to
tech
nica
l cha
nges
Dimensions with NV..-T linear actuator
BC
D
EH
A
5mm
10Nm
10mm
H
E
5 7
86
Assembly instructions NV..+UNV-038
Mounting the UNV bracket on the actuator (steps 1 to 4 see Page 20)
NoteThe grey stem coupling A can only be usedfor the UNV-038 (the white stem couplingthat is used for other UNV mounting brack-ets cannot be used here). The actuator and the mounting bracketcan be swivelled through 360° on the neckof the valve.
11055179
72
205
11
Mounting, pressures, maintenance and disposal
54
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Mounting position
Short-lift valvesThe recommended mounting positions for the NRDVX.. areeither vertically upright or horizontal. Upside down mountingis not allowed. The direction of flow must be as indicated by the valve manu-facturer and must be adhered to whatever type of system orloading is being employed.
Globe valvesGlobe valves can be mounted either vertically upright (Fig. 1)or horizontal (Fig. 2). However, it is not recommend that thevalve be mounted with the stem pointing downwards, i.e.upside down (Fig. 3). The direction of flow must be as indica-ted by the valve manufacturer and must be adhered to what-ever type of system or loading is being employed.
Maximum pressures – ∆ps-closing pressure
Short-lift valvesThe ∆ps closing pressure is governed by the return spring inthe short-stroke actuator and cannot be altered through theactuating force generated by the NDRVX actuator.
Globe valvesThe max. closing pressure∆ps, at which the actuator canstill achieve the permittedleakage rate varies accord-ing to the design of the par-ticular valve and the methodof sealing employed.
∆pMAX (max.pressure difference)This is the maximum permitted pressuredifference for long service life using theappropriate control path referred to the fullopening range of the valve. It depends onthe type of materials chosen for the valveseats. Depending on the particular makeand design of valve the value of ∆pMAX canvary for the same nominal size. The in-structions given by the valve manufactur-er should be adhered to.
Max. permitted medium temperatureThis depends on the type of valve mater-ials being used and on the length of themounting bracket. The longer the bracket,the higher the temperature of the mediumallowed.
Therefore, it is actually limited by the max-imum values of temperature permitted forthe components of the valve and the UNVmounting bracket.
MaintenanceThe actuators are maintenance-free.However, if any work needs to be carriedout on them the power supply mustalways be isolated first (by disconnectingthe electrical lead if necessary). Thepumps delivering into the appropriate sec-tions of piping must be isolated and theassociated shut-off valves closed (alloweverything to cool down if necessary andreduce the system pressure to atmos-pheric). Recommissioning should not take
place until the valve and the actuator havebeen reassembled and the pipe runsrefilled in the proper manner.
DisposalIf an actuator needs to be disposed ofit must first be disassembled into partsof different materials which must thenbe sorted before they are disposed ofcorrectly.
As an approximation:
∆ps ≈ · 1100
∆ps: Closing pressure [kPa]DN: Nominal size [mm]F: Actuating force [N]
[F – DN · 3]DN2
Fig. 1 Fig. 2 Fig. 3
Isoliergrenze
X
Lagging
Lagging limit
Lagging limitsWith the NVX the laggingon the mounting bracketmust not exceed <30 mm.
Order form for special mounting brackets
55
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Valve neck dimensions Form No. Although no suitable mounting bracket might be listed here for a particular make of valve it is nevertheless usually possible for Belimoto offer an appropriate solution. In order to provide Belimo with the necessary information please photocopy this page, fill it in andsend it to them by post or fax.
Name: Position:
Company: Dept.:
Address:
Tel.: Fax: E-Mail:
Date: Signed:
Remarks:
The dimensions needed
Figures A: Length of stem1 to 4 showing Mc: Stem end threadthe dimensions MD: Valve neck threadneeded and ØP: Stem diameterlegend E: Lift
Valve specification
Fig. No.
Valve manufacturer
Valve type
DN (nominal size)
Tick type
No. of mounting brackets required
Please restrict one form to one type of valve only !
Enter the dimensions here (in mm)
A =
B =
E =
Ø P1 =
Ø D =
I =
A1 =
MD =
Mc =
Ø P2 =
Ø D =
H =
A2 =
MD =
Mc =
Ø P2 =
Ø K =
G =
A3 =
MD =
Mc =
Ø P2 =
Fig. 1 Fig. 2 Fig. 3 Fig. 4
Now send the completed form to Belimo by post or fax.
EL
A1
A
B
MC
MD
A1
EF
L
A
B
MC
MD
ØJ
ØK
E
GHI
A
BA
1 MC
ØD
ØJ
ØKE
GHI
A
B
A2
A3
A1
ØP2
ØP1
ØD
EN
G-9
3001
-936
05-0
1.03
-...M
• P
rinte
d in
Sw
itzer
land
• Z
SD
• S
ubje
ct t
o te
chni
cal c
hang
es
Air applications Water applications
Standard actuators andspring-return actuators forair control dampers inHVAC systems
Innovation, Quality and Consultancy:A partnership for motorizing HVAC actuators
Safety actuators formotorizing fire and smokeextraction dampers
VAV systems for individualroom air control
Mixing actuators andmotorized ball valves forHVAC water circuits
Globe valves and intelligentlinear actuators – also forleading makes of valve
Contact the following for further information:
Belimo Headquarters
CH BELIMO Holding AGBrunnenbachstrasse 18340 Hinwil, SwitzerlandTel. +41 (0)43 843 61 11Fax +41 (0)43 843 62 [email protected]
Belimo Subsidiaries
AT/ BELIMO AutomationHR/ Handelsgesellschaft m.b.H.HU/ Geiselbergstrasse 26–32SK/ 1110 Wien, AustriaSL Tel. +43 (0)1 749 03 61-0
Fax +43 (0)1 749 03 [email protected]
AU BELIMO Actuators Pty. Ltd.Unit 10, 266 Osborne AvenueClayton South, VIC 3169AustraliaTel. +61 (0)3 9551 0201Fax +61 (0)3 9551 [email protected]
CA BELIMO Aircontrols (CAN), Inc.5716 Coopers Ave., Units 14&15Mississauga, Ontario L4Z 2E8CanadaTel. +1 (1)905 712 31 18Fax +1 (1)905 712 31 [email protected]
CH BELIMO Automation AGSales SwitzerlandBrunnenbachstrasse 18340 Hinwil, SwitzerlandTel. +41 (0)43 843 62 12Fax +41 (0)43 843 62 [email protected]
DE BELIMO Stellantriebe Vertriebs GmbH Welfenstr. 27, Postfach 72 02 3070599 Stuttgart, GermanyTel. +49 (0)711 1 67 83-0Fax +49 (0)711 1 67 [email protected]
ES BELIMO Ibérica de Servomotores, S.A.C/San Romualdo, 12–1428037 Madrid, Spain Tel. +34 91 304 11 11Fax +34 91 327 25 [email protected]
FR BELIMO ServomoteursZ.A. de Courtry33, Rue de la Régale77181 Courtry, FranceTél. +33 (0)1 64 72 83 70Fax +33 (0)1 64 72 94 [email protected]
GB BELIMO Automation UK LimitedThe Lion CentreHampton Road West Feltham, Middlesex, Great Britain TW 13 6DSTel. +44 (0)20 8755 4411Fax +44 (0)20 8755 [email protected]
HK BELIMO Actuators Ltd.Room 208, 2/FNew Commerce Centre19 On Sum Street, Shatin, N.T.Hong KongTel. +852 26 87 17 16Fax +852 26 87 17 [email protected]
PL BELIMO Silowniki S.A.ul. Zagadkl 2102-227 Warszawa, PolandTel. +48 (0)22 886 53 05Fax +48 (0)22 886 53 [email protected]
SG BELIMO Actuators Pte Ltd2, Jurong East Street 21#04-31F IMM BuildingSingapore 609601Tel. +65 6564 9828Fax +65 6564 [email protected]
US BELIMO Aircontrols (USA), Inc.43 Old Ridgebury RoadP.O. Box 2928Danbury, CT 06810 USATel. +1 (1)203 791 99 15Fax +1 (1)203 792 29 [email protected]
Belimo Representatives andAgencies
AE BELIMO AutomationMiddle East OfficeP.O. Box 55427 Dubai, U.A.E.Tel. +971 (0)4 394 7417Fax +971 (0)4 394 [email protected]
IE Safegard Systems Ltd.Systems House, Unit 34Southern Cross Business ParkBray, Co Wicklow, IrelandTel. +353 (0)1 2761600Fax +353 (0)1 [email protected]
IL Shemer RepresentationsP.O. Box 29656101 Yehud, IsraelTel. +972 3 536 51 67Fax +972 3 536 05 [email protected]
IN BELIMO Vitek Air ControlsC-114 Lancelot, First Floor S.V. Road, Borivali (West)Mumbai 400 092, IndiaTel. +91 22 5695 9439Fax +91 22 2806 [email protected]
IS Hitatækni ehf.Langholtsvegi 109104 Reykjavik, IcelandTel. +354 5 88 60 70Fax +354 5 88 60 [email protected]
IT BELIMO Servomotori S.r.l.Via Stezzano, 524050 Zanica BG, ItalyTel. +39 035 67 26 82Fax +39 035 67 02 [email protected]
KR HANMO Corporation3rd Floor, Yeosam Bldg. 648-23Gangnam-Ku, Seoul, KoreaTel. +822 3453 8225Fax +822 3453 8228
LB Energy Center (EC)Hamra, Leon Street, Shatilla, Bldg. 4th Floor, P.O. Box 113-6955Beirut, LebanonTel. +961 (0)1 35 38 23Fax +961 (0)1 35 38 [email protected]
NL/ BELIMO Servomotoren BV BE/ BENELUXLU Postbus 300, 8160 AH Epe
Radeweg 25, 8171 MD VaassenNetherlandsTel. +31 5 78 57 68 36Fax +31 5 78 57 69 [email protected]
NO BELIMO Spjeldmotorer A/SKonowsgate 5 0192 Oslo 1, NorwayTel. +47 22 70 71 71Fax +47 22 70 71 [email protected]
PH BELIMO Actuators PhilippinesRm.# 507 Anita Build., 5th Floor1300 Quezon Ave.,Cor.South Ave.1103 Quezon City, PhilippinesTel. +63 (2)373 5440Fax +63 (2)373 [email protected]
RO SC Mano Construct srlStr. Cameliei nr 5, sector 1Bucuresti, RomaniaTel. +40 212 126 993Fax +40 212 126 [email protected]
RU BELIMO Servomotors Russia Ltd.Nizhnyaya Pervomaiskaya, 46 Bld.1, Office 303105203 Moscow, Russia Tel. +7 095 965 74 64Fax +7 095 965 74 [email protected]
SE BELIMO ABHägerstens Allé 88129 37 Hägersten, SwedenTel. +46 (0)8 88 07 00Fax +46 (0)8 97 85 75 [email protected]
SY Philippe A. JebranP.O. Box 7791Damascus, SyriaTel. +963 11 231 6586Fax +963 11 231 [email protected]
TR BELIMO Otomasyon A.S.Keyap Sitesi No. 20TR-81260 Y. DudulluIstanbul, TurkeyTel. +90 (0)216 527 98 70Fax +90 (0)216 527 98 [email protected]
TW Chianseng Enterprise Co. Ltd.2F, No. 21, Tong Fong StreetTaipei, TaiwanTel. +886 2 27 08 77 80Fax +886 2 27 02 90 [email protected]
UA BELIMO Ukraine S.A.R.34-A, Ul. Yurkovskaya, Appt.No 2254080 Kiev, UkraineTel. /Fax +380 44 463 [email protected]
ZA BELIMO Actuators Southern Africa ccP. O. Box 2483Alberton 1450, South AfricaTel. +27 (0)11 868 5681Fax +27 (0)11 900 [email protected]
BG BELIMO Bulgaria Ltd.j.k. Lagera, 3 Smolyanska Str.bl. 56, entr. B, ap. 501612 Sofia, BulgariaTel. +3592 952 3470/1Fax +3592 545 [email protected]
CN BELIMO Actuators Ltd.Room 1305, Financial SquareNo. 333 Jiujiang Road200001 Shanghai, ChinaTel. +86 21 6360 8980Fax +86 21 6360 [email protected]
CN BELIMO BeijingRm 605, Beijing Hai ChangEdifice, 44, Liang Ma Qiao Road Chao Yang District100016 Beijing, ChinaTel. +86 10 6462 1382Fax +86 10 6462 [email protected]
CY R.E.S. Ltd.P.O. Box 8297Nicosia, CyprusTel. +357 (0)2 51 10 07Fax +357 (0)2 49 65 [email protected]
CZ BELIMO CZ (Ing. Ivar Mentzl)Charkovská 1610100 Praha 10, Czech RepublicTel. +420 (0)2 717 4 0 311Fax +420 (0)2 717 43 [email protected]
DK BELIMO A/SThomas Helstedsvej 7A8660 Skanderborg, DenmarkTel. +45 86 52 44 00Fax +45 86 52 44 [email protected]
EE BELIMO Balticum ASTüri 10 d11313 Tallinn, EstoniaTel. +372 6 140 811Fax +372 6 140 [email protected]
FI Oy Suomen BELIMO AbInsinöörinkatu 200810 Helsinki, FinlandTel. +358 (0)9 75 11 65 00Fax +358 (0)9 75 11 65 [email protected]
GR BELIMO Air Controls29, Tagm. Plessa, KallitheaGR 17674 Athens, GreeceTel. +30 2 10 94 00 766Fax +30 2 10 94 00 [email protected]