STATE OF THE ART PRODUCTS AND SERVICES FOR STATE OF THE ART PRODUCTS AND SERVICES FOR NON-DESTRUCTIVE TESTING INSPECTION OF PRESSURE VESSEL V-636 Kraton Dover, Ohio July 9, 2019 Inspection Performed By: www.testex-ndt.com Inspection Performed By: Dave Glass API-510 Certification # 64252

Transcript of V-636 Kraton Dover, Ohio July 9, 2019 Inspection Performed ...

STATE OF THE ART PRODUCTS AND SERVICES FOR STATE OF THE ART PRODUCTS AND SERVICES FOR

NON-DESTRUCTIVE TESTING

INSPECTION OF PRESSURE VESSEL

V-636

Kraton

Dover, Ohio

July 9, 2019

Inspection Performed By:

www.testex-ndt.com

Inspection Performed By:

Dave Glass

API-510 Certification # 64252

General Vessel Design Information

Location:

Date:

Manufacturer Serial Number

Design Code National Board No.:

Date Constructed

Dimensions

Shell Length 276 in

Shell Diameter 46 in

Orientation

Shell Material

Head Material

Shell Type

in

Shell Nominal Thickness 0.375 in

Head Nominal Thickness 0.375 in

Tube Outside Diameter N/A in

Tube Nominal Thickness N/A in

Joint Efficiency 0.85

Factor of Safety

Design Specific Gravity

Shell Corrosion Allowance 0 in

Head Corrosion Allowance 0 in

Shell Min. Tensile Strength 73,000 lbf/in2 Head Type

Shell Min. Yield Strength 37,000 lbf/in2 Support Type

Head Min. Tensile Strength

Head Min. Yield Strength

MAWP 250 psi N/A psi at max temp 150 °F N/A °F

(Internal) (External) (Internal) (External)

Min. Design Metal Temp. -20 °F at 250 psi

Years of Service 36.5 Vessel Contents

Last Internal Inspection Service Type

Last External Inspection Capacity Gal

Last UTT Inspection Insulated No

Inspector

Signature API-510 Certification No.

Dover, Ohio

Evaluation Code API-510 January 1, 1983

Client:

Vessel: V-626

Kraton

Master Tank & Welding

34650

July 9, 2019

Insert Picture Here

Horizontal

Cylindrical

PA 72125

ASME VIII 1980

February 2, 2017

SA-455-1

SA-455-1

Ammonia

Dave Glass

Ellipsoidal

64252

January 19, 2005

Legs

Non-corrosive

February 2, 2017

2000

0.3630.362

0.3750.375

0.95

V-636

CLIENT:

LOCATION:

TANK NO:

SERVICE:

External

Inspection

Internal

Inspection

Ultrasonic

Thickness

Liquid

Penetrant

Magnetic

Particle

Ultrasonic

Shearwave

X X

Floor Scan Vacuum Box Pressure

Test

Pneumatic

Test

Other: Other:

Visual

STATUS: In Service

1. The Vessel V-636 was inspected by TesTex, Inc. for an API-510 external evaluation. All thickness readings

collected for this inspection exhibited little to no corrosion from previous inspection. No mandatory repairs

were noted during this inspection. Several non-mandatory items were noted. Attached pressure gauge dial

lenses were noted to be cracked, but can still be read. Some cracking in the containment dike wall over the

containment drain is present. The dike drain is partially clogged with debris and dirt. The top concrete blocks

of the dike are missing cement and are crumbling. The vessel is not grounded. Pressure relief piping exhibits

surface corrosion, and should be cleaned and painted.

2. Ultra Sonic thickness readings and visual inspection were the primary non destructive methods used to

inspect the vessel.

3. Industry standards used to inspect and evaluate the vessel were

API-510 (pressure vessel inspection code)

ASME Sec. VIII Div. 1.(rules for construction of pressure vessels)

EXECUTIVE SUMMARY

EXECUTIVE SUMMARY

INSPECTIONS

PERFORMED:

Non-corrosive DATE: July 9, 2019

Dover, Ohio INSPECTOR: Dave Glass

V-626 API -510 CERT NO. 64252

GENERAL INFORMATION

Kraton

*V-636 is Fit For Continued Service.

Out of Service

V-636

Item No. Condition Code

1 3

2 3

3 3

4 3

5 3

6 3

RECOMMENDATIONSGENERAL INFORMATION

Dover, Ohio INSPECTOR: Dave Glass

CLIENT:

LOCATION:

Kraton STATUS: Out of Service

The action items listed below are recommended and should be addressed by the owner. Condition codes for

actionable items are as follows:

Non-corrosive

V-626 API -510 CERT NO. 64252TANK NO:

DATE: July 9, 2019SERVICE:

Recommendations:

Condition 2 Condition 3

Damage and/or failure noted. Requires

repair and/or re-inspection prior to

returning to service.

Minor damage noted with low

likelyhood of failure/risk. Repair

per industry best paractice.

Condition 1

Major damage/failure or safety related

item noted; requires immediate

attention. Vessel not fit for service.

Action to be taken

The vessel is not grounded. Grounding is not

required by ASME BPVC Sec. VIII but is

recommended by RP API-571.

Attach a grounding strap of no more than

25 Ohms electrical resistance.

Action Items:

Description

The walkway platform shows mild surface

corrosion.

The discharge piping should be cleaned

and painted.

Consider cleaning and painting the

walkway platform.

Considere replacing the cracked dial

glasses.

A crack is located in the concrete

containment dike wall above the dike drain.

Considere repairing the crack in the dike

wall.

The containment dike drain is partially

clogged with dirt and debris

Considere cleaning the dike drain.

Pressure relief discharge piping shows signs

of paint failure and surface corrosion.

Dial glasses of both mechanical pressure

gauges are cracked, but still can be read.

V-636

Reference

SERVICE: Non-corrosive DATE: July 9, 2019

INSPECTOR: Dave Glass

TANK NO: V-626 API -510 CERT NO.

EXTERNAL INSPECTION CONDITIONGENERAL INFORMATION

CLIENT: Kraton STATUS: Out of Service

64252

LOCATION: Dover, Ohio

Access and Cleanliness

Shell

Condition

Dead, dried vegetation was present in the vessels secondary

containment area. The vessel is clean and accessible.

The shell plate signs of previous external pitting. The pitting is currently

painted. External pitting has arrested since the application of its

external coating.

Item

External Inspected Condition by Component:

Welds

East Head

West Head

The West head shows no signs of buckling, cravking, or previous

leaking. Previous external pitting is visible beneath the external

coating.

The East head shows no signs of buckling, cravking, or previous

leaking. Previous external pitting is visible beneath the external

coating.

Welds, examined through the vessel external coating, are in good

condition.

Support Structures

The vessel is supported by four v-shaped legs on top of 2 concrete

pedestals. The legs are attached by painted anchorbolts.

V-636

Reference

SERVICE: Non-corrosive DATE: July 9, 2019

INSPECTOR: Dave Glass

TANK NO: V-626 API -510 CERT NO.

EXTERNAL INSPECTION CONDITIONGENERAL INFORMATION

CLIENT: Kraton STATUS: Out of Service

64252

LOCATION: Dover, Ohio

ConditionItem

External Inspected Condition by Component:

Grounding

Pressure Releif Devices

The vessel is not grounded. Grounding is not required by the vessel's

construction code, but is recommended by RP API-571.

V-636 is protected from over-pressurization by 2 PSVs set at 250 psi

and 2 rupture discs set at 250 psi.

Associated Piping

Attachments

Instruments

Nozzles

Attached electrical conduit support is in good condition.

PSV discharge piping paint has failed. The piping shows paint failure

and signs of surface corrosion.

All vessel nozzles were visually examined and found to be in good

conditon. UT thickness readings could not be taken due to the nozzles

threading.

Attached mechanical pressure gauges have cracks in the glass lenses

covering the dial. The gauges can still be read. The digital gauge is in

good condition. Piping associated with the digital pressure gauge

shows signs of surface corrosion.

V-636

Reference

SERVICE: Non-corrosive DATE: July 9, 2019

INSPECTOR: Dave Glass

TANK NO: V-626 API -510 CERT NO.

EXTERNAL INSPECTION CONDITIONGENERAL INFORMATION

CLIENT: Kraton STATUS: Out of Service

64252

LOCATION: Dover, Ohio

ConditionItem

External Inspected Condition by Component:

Documentation

Secondary Containment

The dike wall top concrete blocks are missing cementand are not

secured to the rest of the wall. A crack is above the dike drain. The

dike drain is partially clogged.

A U-1 and manufacture's drawing were available at the time of

inspection. Previous inspection reports were also available.

V-636

VESSEL CALCULATIONS, API 510

Client: Location:

Tank: Date:

t= PR where: P= 250 Design pressure, psi

SE-0.6P R= 23.00 Inside radius of shell, inches

S= 20,900 Maximum allowable stress, psi

E= 0.85 Joint efficiency

t= 0.326 inches

Head Type: Ellipsoidal ts/L ≥ 0.002 If No, refer to ASME Sec VIII Appendix 1-4(f)

t= PD where: P= 250.0 design pressure, psi

2SE - 0.2P D= 46.0 Inside diameter of head skirt, inches

S= 20,900.0 Maximum allowable stress, psi

E= 0.85 Joint efficiency

t= 0.324 inches

0.000 inches

inches

Long Term Corrosion Rate =

Long Term Corrosion Rate = 0.0103 in/yr

Short Term Corrosion Rate =

Short Term Corrosion Rate = N/A in/yr

Shell Corrosion Rate Calculations Based on Lowest Recorded Thickness

time between tinitial and tactual

tinitial - tactual

time between tprevious and tactual

tprevious - tactual

Lowest observed UT Thickness (From Current Shell UT Survey):

Lowest observed UT Thickness (From Previous Shell UT Survey):

Ellipsoidal Head Minimum Required Thickness (t) Per ASME Section VIII UG-32(d)

Shell Minimum Required Thickness (t) for Internal Pressure (per ASME Sec VIII UG-27(c)

Kraton

V-626 July 9, 2019

Dover, Ohio

<0.001

0.3710.375" tini0.362

V-636

East End Cap 0 11.83333 23.66667 35.5 47.33333 59.16667 71 82.83333

MIN 0.426 0.423 0.434 0.431 0.415 0.435 0.434 0.430

MAX 0.468 0.469 0.436 0.469 0.456 0.461 0.473 0.472

AVERAGE 0.440 0.441 0.435 0.449 0.435 0.447 0.450 0.445

3.0 0.468 0.469 0.436 0.469 0.415 0.446 0.473 0.472

2.0 0.426 0.430 0.434 0.447 0.456 0.461 0.444 0.434

1.0 0.427 0.423 0.436 0.431 0.434 0.435 0.434 0.430

West End Cap 0 11.83333 23.66667 35.5 47.33333 59.16667 71 82.83333

MIN 0.420 0.408 0.419 0.430 0.431 0.445 0.444

MAX 0.473 0.432 0.451 0.461 0.461 0.495 0.452

AVERAGE 0.442 0.423 0.434 0.445 0.444 0.463 0.447

3.0 0.420 0.408 0.451 0.461 0.461 0.449 0.452

2.0 0.433 0.430 0.419 0.443 0.439 0.445 0.444

1.0 0.473 0.432 0.433 0.430 0.431 0.495 0.446

Tank Wall 0 1 2 3 4 5 6 7

MIN 0.368 0.380 0.384 0.381 0.381 0.374 0.371 0.384

MAX 0.468 0.479 0.474 0.468 0.464 0.453 0.488 0.463

AVERAGE 0.409 0.401 0.414 0.402 0.399 0.395 0.403 0.405

19.0 0.368 0.385 0.386 0.385 0.388 0.380 0.390

18.0 0.374 0.393 0.388 0.386 0.387 0.387 0.386

17.0 0.379 0.390 0.393 0.389 0.390 0.377 0.389

16.0 0.455 0.391 0.393 0.390 0.391 0.384 0.388 0.392

15.0 0.458 0.390 0.389 0.389 0.394 0.387 0.389 0.385

14.0 0.448 0.387 0.384 0.390 0.392 0.387 0.388 0.392

13.0 0.392 0.380 0.454 0.385 0.390 0.383 0.388 0.389

12.0 0.377 0.380 0.469 0.381 0.386 0.382 0.377 0.385

11.0 0.394 0.390 0.457 0.390 0.392 0.391 0.386 0.397

10.0 0.389 0.395 0.395 0.397 0.394 0.388 0.389 0.398

9.0 0.391 0.395 0.391 0.398 0.398 0.393 0.393 0.395

8.0 0.391 0.399 0.399 0.396 0.398 0.388 0.389 0.396

7.0 0.397 0.398 0.391 0.399 0.394 0.385 0.387 0.398

6.0 0.392 0.394 0.393 0.395 0.391 0.386 0.388 0.396

5.0 0.390 0.388 0.390 0.392 0.381 0.374 0.371 0.384

4.0 0.390 0.391 0.391 0.392 0.392 0.391 0.376 0.399

3.0 0.394 0.396 0.395 0.397 0.393 0.394 0.388 0.404

2.0 0.395 0.396 0.393 0.393 0.393 0.396 0.398

1.0 0.468 0.391 0.446 0.468 0.467

0.0 0.446 0.451 0.474 0.452 0.452 0.447 0.488 0.461

-1.0 0.462 0.453 0.466 0.436 0.464 0.453 0.477 0.463

-2.0 0.442 0.479 0.466 0.453 0.420 0.433 0.473 0.450

V-636 UT THICKNESS READINGS

Tank Wall 0 1 2 3 4 5 6 7

MIN 0.368 0.380 0.384 0.381 0.381 0.374 0.371 0.384

MAX 0.468 0.479 0.474 0.468 0.464 0.453 0.488 0.463

AVERAGE 0.409 0.401 0.414 0.402 0.399 0.395 0.403 0.405

19.0 0.368 0.385 0.386 0.385 0.388 0.380 0.390

18.0 0.374 0.393 0.388 0.386 0.387 0.387 0.386

17.0 0.379 0.390 0.393 0.389 0.390 0.377 0.389

16.0 0.455 0.391 0.393 0.390 0.391 0.384 0.388 0.392

15.0 0.458 0.390 0.389 0.389 0.394 0.387 0.389 0.385

14.0 0.448 0.387 0.384 0.390 0.392 0.387 0.388 0.392

13.0 0.392 0.380 0.454 0.385 0.390 0.383 0.388 0.389

12.0 0.377 0.380 0.469 0.381 0.386 0.382 0.377 0.385

11.0 0.394 0.390 0.457 0.390 0.392 0.391 0.386 0.397

10.0 0.389 0.395 0.395 0.397 0.394 0.388 0.389 0.398

9.0 0.391 0.395 0.391 0.398 0.398 0.393 0.393 0.395

8.0 0.391 0.399 0.399 0.396 0.398 0.388 0.389 0.396

7.0 0.397 0.398 0.391 0.399 0.394 0.385 0.387 0.398

6.0 0.392 0.394 0.393 0.395 0.391 0.386 0.388 0.396

5.0 0.390 0.388 0.390 0.392 0.381 0.374 0.371 0.384

4.0 0.390 0.391 0.391 0.392 0.392 0.391 0.376 0.399

3.0 0.394 0.396 0.395 0.397 0.393 0.394 0.388 0.404

2.0 0.395 0.396 0.393 0.393 0.393 0.396 0.398

1.0 0.468 0.391 0.446 0.468 0.467

0.0 0.446 0.451 0.474 0.452 0.452 0.447 0.488 0.461

-1.0 0.462 0.453 0.466 0.436 0.464 0.453 0.477 0.463

-2.0 0.442 0.479 0.466 0.453 0.420 0.433 0.473 0.450

8 9 10 11 12

0.386 0.382 0.384 0.388 0.367

0.457 0.447 0.448 0.449 0.446

0.407 0.399 0.403 0.407 0.400

0.367

0.384

0.396

0.435 0.394 0.397

0.457 0.388 0.392 0.394 0.396

0.390 0.384 0.391 0.397 0.397

0.389 0.387 0.391 0.396 0.394

0.386 0.382 0.384 0.388 0.389

0.394 0.392 0.397 0.396 0.397

0.402 0.394 0.392 0.400 0.399

0.396 0.393 0.399 0.405 0.401

0.395 0.393 0.400 0.402 0.400

0.393 0.388 0.400 0.401 0.399

0.395 0.391 0.398 0.400 0.397

0.389 0.387 0.396 0.398 0.386

0.394 0.389

0.397 0.392

0.387 0.395 0.398 0.393

0.386 0.394 0.390 0.393

0.445 0.442 0.436 0.448 0.443

0.449 0.447 0.442 0.443 0.446

0.411 0.445 0.448 0.449 0.446

Location:

Date:

Date of last internal inspection:

Date of last external inspection:

Date of last UTT inspection:

Internal

External

January 19, 2005

5 years

10 years

July 9, 2024

Overdue

Inspection Intervals Based on API 510 Section 6

Inspection Frequency Required Date

July 9, 2019

July 9, 2019

INSPECTION INTERVALS

Client:

Tank:

Kraton

July 9, 2019

Dover, Ohio

V-626

External 5 years July 9, 202410 years July 31, 2024

V-636

An on-stream inspection may be substituted for an internal inspection when vessel entry is not physicallypossible per API-510 6.5.2.1.

20295 years , 2024

General view of V-636.

This photo shows the vessel’s NB name plate.

View of the vessel’s label.

View of the vessel’s East head.

V-636 is protected from over-pressurization by a combination of PSVs and rupture discs.

The pressure gauge dial glasses are cracked, but can still be read.

This photo shows a crack in the concrete containment wall.

Some debris is present in the containment drain.

Pressure relief discharge piping paint failure and surface corrosion.

The platform has mild surface corrosion.

Surface corrosion of the associated piping.