User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046...

28
BNI IOL-302-002-Z046 IO-Link 1.1 sensor/actuator hub with extension port User's Guide

Transcript of User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046...

Page 1: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

BNI IOL-302-002-Z046

IO-Link 1.1 sensor/actuator hub

with extension port

User's Guide

Page 2: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

2

Contents

1 General 4 Structure of the Manual 4 1.1. Typographical Conventions 4 1.2.

Enumerations 4 Actions 4 Syntax 4 Cross-references 4

Symbols 4 1.3. Abbreviations 4 1.4.

2 Safety 5 Intended use 5 2.1. Installation and Startup 5 2.2. General Safety Notes 5 2.3. Resistance to Aggressive Substances 5 2.4.

Dangerous Voltage 5

3 First Steps 6 Connection Overview 6 3.1. Mechanical Connection 7 3.2. Electrical Connection 7 3.3.

Function ground 7 IO-Link connection 7 Connecting the sensor hub 8 Module variants 8 Sensor/actuator interface 8 Extension port 8

4 General Configuration 9 Extension port 9 4.1.

Configuration of the extension port 55hex) 9 Setting the serial number 54hex 9

5 Configuration: "Extension Off" 10 IO-Link data 10 5.1. Process Data/Input Data 10 5.2. Process Data/ Output Data 10 5.3. Parameter Data / Demand Data 11 5.4.

Inversion of the inputs (40hex) 12 Configuration of inputs/outputs (41hex) 12 Safe state of Outputs 42hex 12 Voltage monitoring 44hex 14 Monitoring the outputs (45hex) 14 Actuator warning (46hex) 14

6 Configuration: Extanded with BNI IOL-104-002-Z046 15 IO-Link data 15 6.1. Process Data/Input Data 15 6.2. Process Data/ Output Data 16 6.3. Parameter Data / Demand Data 17 6.4.

Inversion of the inputs (40hex) 18 Configuration of inputs/outputs (41hex) 18 Safe state of Outputs 42hex 19 Safe state of the outputs on Pin 4 42hex) 19 Voltage monitoring 44hex 20 Monitoring the outputs (45hex) 21 Actuator warning (46hex) 21 Setting the serial number 54hex 21

7 Diagnostics 22

Page 3: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

3

Errors 22 7.1. Events 22 7.2.

8 IO-Link functions 23 IO-Link Version 1.0 / 1.1 23 8.1. Data Storage 23 8.2. Block Configuration 23 8.3.

Resetting to Factory Settings 23

9 Technical Data 24 Dimensions 24 9.1. Mechanical Data 24 9.2. Electrical Data 24 9.3. Operating conditions 24 9.4.

10 Function indicators 25 Function indicators 25 10.1.

LED indicator module status 25 Digital LED indicators for inputs/outputs 26 Extension port 26

11 Appendix 27 Type code 27 11.1. Ordering information 27 11.2.

Page 4: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

4

1 General

Structure of the 1.1.Manual

The manual is organized so that the sections build on one another. Chapter 2: Basic Safety Information. ……..

Typographical 1.2.Conventions

The following typographical conventions are used in this manual.

Enumerations Enumerations are shown as a list with an en-dash.

Entry 1,

Entry 2.

Actions Action instructions are indicated by a preceding triangle. The result of an action is indicated by an arrow.

Action instruction 1. Action result. Action instruction 2.

Syntax Numbers:

Decimal numerals are shown without an additional indicator (e.g. 123), Hexadecimal numerals are shown with the additional indicator hex (e.g. 00hex).

Cross-references Cross-references indicate where additional information on the topic can be found.

Symbols 1.3. Attention!

This symbol indicates a security instruction which most be observed.

Note

This symbol indicates general notes.

Abbreviations 1.4. BNI

DPP I/O port EMC FE IOL LSB MSB SPDU

Balluff Network Interface Direct Parameter Page Digital input/output port Electromagnetic compatibility Function ground IO-Link Least Significant Bit Most Significant Bit Service Protocol Data Unit

Page 5: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

5

2 Safety

Intended use 2.1. The BNI IOL-… acts as a decentralized input/output sensor module, which is connected to a higher-level IO-Link master module through an IO-Link interface.

Installation and 2.2.Startup

Attention!

Installation and startup must only be carried out by trained technical personnel. Qualified personnel are people who are familiar with installation and operation of the product and have the necessary qualifications for these tasks. Any damage resulting from unauthorized tampering or improper use voids the manufacturer's guarantee and warranty. The operator must ensure that appropriate safety and accident prevention regulations are observed.

General Safety 2.3.Notes

Commissioning and inspection

Before commissioning, carefully read the user's guide. The system must not be used in applications in which the safety of persons is dependent upon proper functioning of the device. Authorized personnel

Installation and startup must only be carried out by trained technical personnel. Intended use

Warranty and liability claims against the manufacturer are rendered void by:

Unauthorized tampering

Improper use

Use, installation or handling contrary to the instructions provided in this user's

guide Obligations of the operating company

The device is a piece of equipment in accordance with EMC Class A. This device can

produce RF noise. The operator must take appropriate precautionary measures. The device

may only be used with an approved power supply. Use only approved cables. Malfunctions

In the event of defects and device malfunctions that cannot be rectified, the device must be

taken out of operation and protected against unauthorized use.

Intended use is ensured only when the housing is fully installed.

Resistance to 2.4.Aggressive Substances

Attention!

The BNI modules always have good chemical and oil resistance. When used in aggressive media (such as chemicals, oils, lubricants and coolants, each in a high concentration (i.e. too little water content)), the material must first be checked for resistance in the particular application. No defect claims may be asserted in the event of a failure or damage to the BNI modules caused by such aggressive media.

Dangerous Voltage

Attention!

Before maintenance, disconnect the device from the power supply.

Note

In the interests of product improvement, Balluff GmbH reserves the right to change the technical data of the product and the content of this manual at any time without notice.

Page 6: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

6

3 First Steps

Connection 3.1.Overview

Figure 3-1: Connection overview BNI IOL-302-002-Z046

1 Ground connection 2 Mounting hole 3 Status LED: communication 4 Part label 5 Port 1 6 Port 3 7 Port 5 8 Port 7 9 Port 9 10 Port 11 11 Port 13

12 Port 15, extension port 13 Pin/Port LED: signal status 14 Port 14 15 Port 12 16 Port 10 17 Port 8 18 Port 6 19 Port 4 20 Port 2 21 Port 0 22 IO-Link Interface

1

2

3

4

5

6

7

9

13

14

19

20

22

8

10

11

12

2

15

16

17

18

21

Page 7: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

7

3 First Steps

Mechanical 3.2.Connection

The BNI IOL modules are attached using 2 max. M4 screws and 2 washers.

Electrical 3.3.Connection

The BNI IOL-302-002-Z046 modules do not require a separate supply voltage connection. Supply voltage is provided via the IO-Link interface and the higher-level IO-Link master module.

Function ground The modules are equipped with a ground connection.

Ground connection BNI IOL-..

Note!

The function ground connection from the housing to the machine must have low-impedance and be kept as short as possible.

IO-Link connection

The IO-Link connection is established via an M12 connector (A-coded, male). IO-Link (M12, A-coded, male)

Pin Requirement

1 Supply voltage for controller Us, +24 V

2 Supply voltage for actuators Ua, +24 V

3 GND, reference potential

4 C/Q, IO-Link data transmission channel

Page 8: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

8

3 First Steps

Connecting the sensor hub

Connect ground conductor to the functional ground connection, if available. Connect the incoming IO-Link cable to the sensor hub.

Note

A standardized sensor cable is used to connect to the higher-level to the IO-Link master module. Maximum length of 20 m.

Module variants Sensor hub variants Digital port

BNI IOL-302-002-Z046 IN / OUT

Sensor/actuator interface

Standard in-/output M8

Pin Function

IN / OUT

1 +24V

4 Input / Output

3 0V

Note

For the digital inputs, the input guideline specified in EN 61131-2, Type 3 applies

Note

Unused input port sockets must be fitted with blind caps to ensure the IP67 degree of protection.

Extension port Extension port (M8, female)

The port acts like a sensor/actuator interface if the extension function is disabled.

Pin Function

IN / OUT

1 +24V

4 Communication

3 0V

Note

A standardized sensor cable is used to connect to the device/sensor to be expanded. Maximum length of 20 m.

Page 9: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

9

4 General Configuration

Extension port 4.1. The BNI IOL-302-002-Z046 module gives you the ability to use the No. 15 slot in various ways. The standard setting is use as a digital I/O slot, where Pin 4 can be used as a digital input or output. This slot can be used as an extension port by making a corresponding entry in the parameter with an index of 55hex. This makes it possible to operate one of the following modules using the No. 7 slot.

BNI IOL-104-002-Z046

Configuration of the extension port 55hex)

Configuration Value Index 55hex

BNI IOL-302-002-Z046 0

BNI IOL-302-002-Z046 with BNI IOL-104-002-Z046 1

Note

The "Factory reset" command does not affect the configuration of the extension port in any way.

Note

The process data length depends on the configuration.

The extension port can be configured using the parameter 55hex (see table). If data storage

or validation is used, validation (identical) must be used for configuring. Depending on the system, the Device ID has to be entered (parameter data table) or the Device ID is read out from the IODD.

Setting the serial number 54hex

The serial number has a default value of 16x00hex.

In order to use the "Identity" master validation mode, a serial number can be set using this parameter. This prevents a device from connecting to the wrong master port.

Page 10: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

10

5 Configuration: "Extension Off"

IO-Link data 5.1.

BNI IOL-302-002-Z046 Extension off

Transmission rate COM2 (38.4 kBaud)

Minimum cycle time 4.0 ms

Process data length 2 byte input, 2 byte output

Process 5.2.Data/Input Data

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Descri

pti

on

Input P

ort

7 P

in 4

Input P

ort

6 P

in 4

Input P

ort

5 P

in 4

Input P

ort

4 P

in 4

Input P

ort

3 P

in 4

Input P

ort

2 P

in 4

Input P

ort

1 P

in 4

Input P

ort

0 P

in 4

Input P

ort

15 P

in 4

Input P

ort

14 P

in 4

Input P

ort

13 P

in 4

Input P

ort

12 P

in 4

Input P

ort

11 P

in 4

Input P

ort

10 P

in 4

Input P

ort

9 P

in 4

Input P

ort

8 P

in 4

Process Data/ 5.3.Output Data

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Descri

pti

on

Outp

ut P

ort

7 P

in 4

Outp

ut P

ort

6 P

in 4

Outp

ut P

ort

5 P

in 4

Outp

ut P

ort

4 P

in 4

Outp

ut P

ort

3 P

in 4

Outp

ut P

ort

2 P

in 4

Outp

ut P

ort

1 P

in 4

Outp

ut P

ort

0 P

in 4

Outp

ut P

ort

15 P

in 4

Outp

ut P

ort

14 P

in 4

Outp

ut P

ort

13 P

in 4

Outp

ut P

ort

12 P

in 4

Outp

ut P

ort

11 P

in 4

Outp

ut P

ort

10 P

in 4

Outp

ut P

ort

9 P

in 4

Outp

ut P

ort

8 P

in 4

Page 11: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

11

5 Configuration: "Extension Off"

Parameter Data 5.4./ Demand Data

DPP ISDU Parameter Data width

Access rights

Default value Index Index Subin

dex

Ide

nti

ficati

on

da

ta

07hex Vendor ID 2 bytes

Read o

nly

0378hex 08hex

09hex

Device ID 3 bytes 05 0D 20hex 0Ahex

0Bhex

10hex 0 Vendor Name - BALLUFF

11hex 0 Vendor text - www.balluff.com

12hex 0 Product Name

- BNI IOL-302-002-Z046

13hex 0 Product ID - BNI00AU

14hex 0 Product text - M8 sensor/actuator hub

15hex 0 Serial number 16 bytes 0hex

16hex 0 Hardware revision

17hex 0 Firmware revision

18hex 0 Application-specific tag

32 bytes 0hex

DPP ISDU Parameter Data width Access rights Default

Value Index Index Subindex

Para

mete

r d

ata

40hex 64

0 1-16

Inversion of the inputs 2 bytes Read/write 0hex

41hex 65

0 1-16

Config. inputs/outputs 2 bytes Read/write 0hex

42hex 66

0 1-16

Safe state on Pin 4 4 bytes Read/write 0hex

44hex 68

0 1-24

Voltage monitoring 3 bytes Read -

45hex 69

0 1-16

Output monitoring 2 bytes Read -

46hex 70

0 1-16

Actuator warning 2 bytes Read -

54hex 84

0 Serial number 16 bytes Read/write 16x00hex

55hex

85 0 Extension port 1 byte Read/write -

Page 12: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

12

5 Configuration: "Extension Off"

Inversion of the inputs (40hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Subindex

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Invers

ion o

f P

ort

7 P

in 4

Invers

ion o

f P

ort

6 P

in 4

Invers

ion o

f P

ort

5 P

in 4

Invers

ion o

f P

ort

4 P

in 4

Invers

ion o

f P

ort

3 P

in 4

Invers

ion o

f P

ort

2 P

in 4

Invers

ion o

f P

ort

1 P

in 4

Invers

ion o

f P

ort

0 P

in 4

Invers

ion o

f P

ort

15 P

in 4

Invers

ion o

f P

ort

14 P

in 4

Invers

ion o

f P

ort

13

Pin

4

Invers

ion o

f P

ort

12 P

in 4

Invers

ion o

f P

ort

11 P

in 4

Invers

ion o

f P

ort

10 P

in 4

Invers

ion o

f P

ort

9 P

in 4

Invers

ion o

f P

ort

8 P

in 4

Inversion of port (x):

0 – Normal 1 - Inverted.

Configuration of inputs/outputs (41hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Subindex

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Directio

n P

ort

7 P

in 4

Directio

n P

ort

6 P

in 4

Directio

n P

ort

5 P

in 4

Directio

n P

ort

4 P

in 4

Directio

n P

ort

3 P

in 4

Directio

n P

ort

2 P

in 4

Directio

n P

ort

1 P

in 4

Directio

n P

ort

0 P

in 4

Directio

n P

ort

15 P

in 4

Directio

n P

ort

14 P

in 4

Directio

n P

ort

13 P

in 4

Directio

n P

ort

12 P

in 4

Directio

n P

ort

11 P

in 4

Directio

n P

ort

10 P

in 4

Directio

n P

ort

9 P

in 4

Directio

n P

ort

8 P

in 4

Direction of port (x):

0 – Input 1 – Output

Safe state of Outputs 42hex

The safe state parameter makes it possible to configure the outputs in case of a fault. If no IO-Link communication is possible or the "valid flag" of the output process data has not been set by the master, then each output adopts the configured status. The following statuses can be configured for each pin.

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

4 3 2 1 8 7 6 5

Descri

pti

on

Safe

sta

te P

ort

3 P

in 4

Safe

sta

te P

ort

2 P

in 4

Safe

sta

te P

ort

1 P

in 4

Safe

sta

te P

ort

0 P

in 4

Safe

sta

te P

ort

7 P

in 4

Safe

sta

te P

ort

6 P

in 4

Safe

sta

te P

ort

5 P

in 4

Safe

sta

te P

ort

4 P

in 4

Page 13: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

13

5 Configuration: "Extension Off"

Byte 2 3

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

12 11 10 9 16 15 14 13

Descri

pti

on

Safe

sta

te P

ort

11 P

in 4

Safe

sta

te P

ort

10 P

in 4

Safe

sta

te P

ort

9 P

in 4

Safe

sta

te P

ort

8 P

in 4

Safe

sta

te P

ort

15 P

in 4

Safe

sta

te P

ort

14 P

in 4

Safe

sta

te P

ort

13 P

in 4

Safe

sta

te P

ort

12 P

in 4

Value

Output state bin dec

00 0 Output is 0V

01 1 Output is 24V

10 2 Current status is maintained

11 3 Not permitted

Page 14: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

14

5 Configuration: "Extension Off"

Voltage monitoring 44hex

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 D

escri

pti

on

Short

-circuit P

ort

7 P

in 1

Short

-circuit P

ort

6 P

in 1

Short

-circuit P

ort

5 P

in 1

Short

-circuit P

ort

4 P

in 1

Short

-circuit P

ort

3 P

in 1

Short

-circuit P

ort

2 P

in 1

Short

-circuit P

ort

1 P

in 1

Short

-circuit P

ort

0 P

in 1

Short

-circuit P

ort

15 P

in 1

Short

-circuit P

ort

14 P

in 1

Short

-circuit P

ort

13 P

in 1

Short

-circuit P

ort

12 P

in 1

Short

-circuit P

ort

11 P

in 1

Short

-circuit P

ort

10 P

in 1

Short

-circuit P

ort

9 P

in 1

Short

-circuit P

ort

8 P

in 1

Byte 2

Bit 7 6 5 4 3 2 1 0

Sub- Index

20 19 17

Descri

pti

on

- - - -

Outp

uts

off

(UA

too lo

w)

Underv

oltage U

A

-

Underv

oltage U

S

Monitoring the outputs (45hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Short

-circuit P

ort

7 P

in 4

Short

-circuit P

ort

6 P

in 4

Short

-circuit P

ort

5 P

in 4

Short

-circuit P

ort

4 P

in 4

Short

-circuit P

ort

3 P

in 4

Short

-circuit P

ort

2 P

in 4

Short

-circuit P

ort

1 P

in 4

Short

-circuit P

ort

0 P

in 4

Short

-circuit P

ort

15 P

in 4

Short

-circuit P

ort

14 P

in 4

Short

-circuit P

ort

13 P

in 4

Short

-circuit P

ort

12 P

in 4

Short

-circuit P

ort

11 P

in 4

Short

-circuit P

ort

10 P

in 4

Short

-circuit P

ort

9 P

in 4

Short

-circuit P

ort

8 P

in 4

Actuator warning (46hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Warn

ing P

ort

7 P

in 4

Warn

ing P

ort

6 P

in 4

Warn

ing P

ort

5 P

in 4

Warn

ing P

ort

4 P

in 4

Warn

ing P

ort

3 P

in 4

Warn

ing P

ort

2 P

in 4

Warn

ing P

ort

1 P

in 4

Warn

ing P

ort

0 P

in 4

-

Warn

ing P

ort

14 P

in 4

Warn

ing P

ort

13 P

in 4

Warn

ing P

ort

12 P

in 4

Warn

ing P

ort

11 P

in 4

Warn

ing P

ort

10 P

in 4

Warn

ing P

ort

9 P

in 4

Warn

ing P

ort

8 P

in 4

Page 15: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

15

6 Configuration: Extanded with BNI IOL-104-002-Z046

IO-Link data 6.1.

BNI IOL-302-002-Z046 extanded with BNI IOL-104-002-Z046

Transmission rate COM2 (38.4 kBaud)

Minimum cycle time 4.5 ms

Process data length 4 byte input, 2 byte output

Process 6.2.Data/Input Data

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Descri

pti

on

Input P

ort

7 P

in 4

Input P

ort

6 P

in 4

Input P

ort

5 P

in 4

Input P

ort

4 P

in 4

Input P

ort

3 P

in 4

Input P

ort

2 P

in 4

Input P

ort

1 P

in 4

Input P

ort

0 P

in 4

-

Input P

ort

14 P

in 4

Input P

ort

13 P

in 4

Input P

ort

12 P

in 4

Input P

ort

11 P

in 4

Input P

ort

10 P

in 4

Input P

ort

9 P

in 4

Input P

ort

8 P

in 4

Byte 2 3

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Extension port

Descri

pti

on

Input P

ort

7 P

in 4

Input P

ort

6 P

in 4

Input P

ort

5 P

in 4

Input P

ort

4 P

in 4

Input P

ort

3 P

in 4

Input P

ort

2 P

in 4

Input P

ort

1 P

in 4

Input P

ort

0 P

in 4

Input P

ort

15 P

in 4

Input P

ort

14 P

in 4

Input P

ort

13 P

in 4

Input P

ort

12 P

in 4

Input P

ort

11 P

in 4

Input P

ort

10 P

in 4

Input P

ort

9 P

in 4

Input P

ort

8 P

in 4

Page 16: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

16

6 Configuration: Extanded with BNI IOL-104-002-Z046

Process Data/ 6.3.Output Data

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 D

escri

pti

on

Outp

ut P

ort

7 P

in 4

Outp

ut P

ort

6 P

in 4

Outp

ut P

ort

5 P

in 4

Outp

ut P

ort

4 P

in 4

Outp

ut P

ort

3 P

in 4

Outp

ut P

ort

2 P

in 4

Outp

ut P

ort

1 P

in 4

Outp

ut P

ort

0 P

in 4

-

Outp

ut P

ort

14 P

in 4

Outp

ut P

ort

13 P

in 4

Outp

ut P

ort

12 P

in 4

Outp

ut P

ort

11 P

in 4

Outp

ut P

ort

10 P

in 4

Outp

ut P

ort

9 P

in 4

Outp

ut P

ort

8 P

in 4

Page 17: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

17

6 Configuration: Extanded with BNI IOL-104-002-Z046

Parameter Data 6.4./ Demand Data

DPP ISDU Parameter Data width

Access rights

Default value Index Index Subin

dex

Ide

nti

ficati

on

da

ta

07hex Vendor ID 2 bytes

Read o

nly

0378hex 08hex

09hex

Device ID 3 bytes 05 0D 21hex 0Ahex

0Bhex

10hex 0 Vendor Name - BALLUFF

11hex 0 Vendor text - www.balluff.com

12hex 0 Product Name

- BNI IOL-302-002-Z046 with BNI IOL-104-002-

Z046

13hex 0 Product ID - BNI00AU

with BNI00AY

14hex 0 Product text - Sensor/Actor hub M8 extended with Sensor

hub M8

15hex 0 Serial number 16 bytes 0hex

16hex 0 Hardware revision

17hex 0 Firmware revision

18hex

0

Application-specific tag

32 bytes 0hex

DPP ISDU Parameter Data width Access rights Default Value Index Index Subind

ex

Para

mete

r d

ata

40hex 64

0 1-16

Inversion of the inputs 4 bytes Read/write 0hex

41hex 65

0 1-16

Config. inputs/outputs 2 bytes Read/write 0hex

42hex 66

0 1-16

Safe state on Pin 4 4 bytes Read/write 0hex

44hex 68

0 1-48

Voltage monitoring 6 bytes Read -

45hex 69

0 1-16

Output monitoring 2 bytes Read -

46hex 70

0 1-16

Actuator warning 2 bytes Read -

54hex 84

0 Serial number 16 bytes Read/write 16x00hex

55hex

85 0 Extension port 1 byte Read/write 1hex

Page 18: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

18

6 Configuration: Extanded with BNI IOL-104-002-Z046

Inversion of the inputs (40hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Invers

ion o

f P

ort

7 P

in 4

Invers

ion o

f P

ort

6 P

in 4

Invers

ion o

f P

ort

5 P

in 4

Invers

ion o

f P

ort

4 P

in 4

Invers

ion o

f P

ort

3 P

in 4

Invers

ion o

f P

ort

2 P

in 4

Invers

ion o

f P

ort

1 P

in 4

Invers

ion o

f P

ort

0 P

in 4

-

Invers

ion o

f P

ort

14 P

in 4

Invers

ion o

f P

ort

13 P

in 4

Invers

ion o

f P

ort

12 P

in 4

Invers

ion o

f P

ort

11 P

in 4

Invers

ion o

f P

ort

10 P

in 4

Invers

ion o

f P

ort

9 P

in 4

Invers

ion o

f P

ort

8 P

in 4

Byte 2 3

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

24 23 22 21 20 19 18 17 32 31 30 29 28 27 26 25

Extension port

Descri

pti

on

Invers

ion o

f P

ort

7 P

in 4

Invers

ion o

f P

ort

6 P

in 4

Invers

ion o

f P

ort

5 P

in 4

Invers

ion o

f P

ort

4 P

in 4

Invers

ion o

f P

ort

3 P

in 4

Invers

ion o

f P

ort

2 P

in 4

Invers

ion o

f P

ort

1 P

in 4

Invers

ion o

f P

ort

0 P

in 4

Invers

ion o

f P

ort

15 P

in 4

Invers

ion o

f P

ort

14 P

in 4

Invers

ion o

f P

ort

13 P

in 4

Invers

ion o

f P

ort

12 P

in 4

Invers

ion o

f P

ort

11 P

in 4

Invers

ion o

f P

ort

10 P

in 4

Invers

ion o

f P

ort

9 P

in 4

Invers

ion o

f P

ort

8 P

in 4

Inversion of port (x): 0 - Normal 1 - Inverted

Configuration of inputs/outputs (41hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Subindex

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Directio

n P

ort

7 P

in 4

Directio

n P

ort

6 P

in 4

Directio

n P

ort

5 P

in 4

Directio

n P

ort

4 P

in 4

Directio

n P

ort

3 P

in 4

Directio

n P

ort

2 P

in 4

Directio

n P

ort

1 P

in 4

Directio

n P

ort

0 P

in 4

-

Directio

n P

ort

14 P

in 4

Directio

n P

ort

13 P

in 4

Directio

n P

ort

12 P

in 4

Directio

n P

ort

11 P

in 4

Directio

n P

ort

10 P

in 4

Directio

n P

ort

9 P

in 4

Directio

n P

ort

8 P

in 4

Direction of port (x): 0 – Input 1 – Output

Page 19: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

19

6 Configuration: Extanded with BNI IOL-104-002-Z046

Safe state of Outputs 42hex

The safe state parameter makes it possible to configure the outputs in case of a fault. If no IO-Link communication is possible or the "valid flag" of the output process data has not been set by the master, then each output adopts the configured status. The following statuses can be configured for each pin.

Safe state of the outputs on Pin 4 42hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

4 3 2 1 8 7 6 5

Descri

pti

on

Safe

sta

te P

ort

3 P

in 4

Safe

sta

te P

ort

2 P

in 4

Safe

sta

te P

ort

1 P

in 4

Safe

sta

te P

ort

0 P

in 4

Safe

sta

te P

ort

7 P

in 4

Safe

sta

te P

ort

6 P

in 4

Safe

sta

te P

ort

5 P

in 4

Safe

sta

te P

ort

4 P

in 4

Byte 2 3

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

12 11 10 9 16 15 14 13

Descri

pti

on

Safe

sta

te P

ort

11 P

in 4

Safe

sta

te P

ort

10 P

in 4

Safe

sta

te P

ort

9 P

in 4

Safe

sta

te P

ort

8 P

in 4

-

Safe

sta

te P

ort

14 P

in 4

Safe

sta

te P

ort

13 P

in 4

Safe

sta

te P

ort

12 P

in 4

Value

Output state bin dec

00 0 Output is 0V

01 1 Output is 24V

10 2 Current status is maintained

11 3 Not permitted

Page 20: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

20

6 Configuration: Extanded with BNI IOL-104-002-Z046

Voltage monitoring 44hex

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Short

-circuit P

ort

7 P

in 1

Short

-circuit P

ort

6 P

in 1

Short

-circuit P

ort

5 P

in 1

Short

-circuit P

ort

4 P

in 1

Short

-circuit P

ort

3 P

in 1

Short

-circuit P

ort

2 P

in 1

Short

-circuit P

ort

1 P

in 1

Short

-circuit P

ort

0 P

in 1

Short

-circuit P

ort

15 P

in 1

Short

-circuit P

ort

14 P

in 1

Short

-circuit P

ort

13 P

in 1

Short

-circuit P

ort

12 P

in 1

Short

-circuit P

ort

11 P

in 1

Short

-circuit P

ort

10 P

in 1

Short

-circuit P

ort

9 P

in 1

Short

-circuit P

ort

8 P

in 1

Byte 2

Bit 7 6 5 4 3 2 1 0

Sub- Index

20 19 17

Descri

pti

on

- - - -

Outp

uts

off

(UA

too lo

w)

Underv

oltage U

A

-

Underv

oltage U

S

Byte 3 4

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

32 31 30 29 28 27 26 25 40 39 38 37 36 35 34 33

Extension port

Descri

pti

on

Short

-circuit P

ort

7 P

in 1

Short

-circuit P

ort

6 P

in 1

Short

-circuit P

ort

5 P

in 1

Short

-circuit P

ort

4 P

in 1

Short

-circuit P

ort

3 P

in 1

Short

-circuit P

ort

2 P

in 1

Short

-circuit P

ort

1 P

in 1

Short

-circuit P

ort

0 P

in 1

Short

-circuit P

ort

15 P

in 1

Short

-circuit P

ort

14 P

in 1

Short

-circuit P

ort

13 P

in 1

Short

-circuit P

ort

12 P

in 1

Short

-circuit P

ort

11 P

in 1

Short

-circuit P

ort

10 P

in 1

Short

-circuit P

ort

9 P

in 1

Short

-circuit P

ort

8 P

in 1

Page 21: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

21

6 Configuration: Extanded with BNI IOL-104-002-Z046

Byte 5

Bit 7 6 5 4 3 2 1 0

Sub- Index

41

Extension port

Descri

pti

on

- - - - - - -

Underv

oltage U

S

Monitoring the outputs (45hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Short

-circuit P

ort

7 P

in 4

Short

-circuit P

ort

6 P

in 4

Short

-circuit P

ort

5 P

in 4

Short

-circuit P

ort

4 P

in 4

Short

-circuit P

ort

3 P

in 4

Short

-circuit P

ort

2 P

in 4

Short

-circuit P

ort

1 P

in 4

Short

-circuit P

ort

0 P

in 4

-

Short

-circuit P

ort

14 P

in 4

Short

-circuit P

ort

13 P

in 4

Short

-circuit P

ort

12 P

in 4

Short

-circuit P

ort

11 P

in 4

Short

-circuit P

ort

10 P

in 4

Short

-circuit P

ort

9 P

in 4

Short

-circuit P

ort

8 P

in 4

Actuator warning (46hex)

Byte 0 1

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Sub- Index

8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Descri

pti

on

Warn

ing P

ort

7 P

in 4

Warn

ing P

ort

6 P

in 4

Warn

ing P

ort

5 P

in 4

Warn

ing P

ort

4 P

in 4

Warn

ing P

ort

3 P

in 4

Warn

ing P

ort

2 P

in 4

Warn

ing P

ort

1 P

in 4

Warn

ing P

ort

0 P

in 4

-

Warn

ing P

ort

14 P

in 4

Warn

ing P

ort

13 P

in 4

Warn

ing P

ort

12 P

in 4

Warn

ing P

ort

11 P

in 4

Warn

ing P

ort

10 P

in 4

Warn

ing P

ort

9 P

in 4

Warn

ing P

ort

8 P

in 4

Setting the serial number 54hex

The serial number has a default value of 16x00hex.

In order to use the "Identity" master validation mode, a serial number can be set using this parameter. This prevents a device from connecting to the wrong master port.

Page 22: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

22

7 Diagnostics

Errors 7.1. Error Code Description

0x8011 Index not available

0x8012 Subindex not available

0x8023 Access Denied

0x8033 Parameter length overrun

0x8034 Parameter length underrun

0x8035 Function not available

Events 7.2. IO-Link Revision 1.0

Event Code Description

0x5112 Low sensor voltage (US)

0x5114 Low actor voltage (UA)

0x5410 Output Stages

0x8DF0 Retry at the extension port 0x8DF1 Device lost at the extension port 0x8DF2 Wrong device at the extension port

IO-Link Revision 1.1

Event Code Description

0x5111 Low sensor voltage (US)

0x5112 Low actor voltage (UA)

0x7710 Short circuit

0x8DF0 Retry at the extension port 0x8DF1 Device lost at the extension port 0x8DF2 Wrong device at the extension port

Page 23: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

23

8 IO-Link functions

IO-Link 8.1.Version 1.0 / 1.1

This device can be operated with an IO-Link master according to IO-Link version 1.0 and version 1.1. Version-specific functions such as data storage (version 1.1) are only supported in combination with a suitable IO-Link master.

Data Storage 8.2. Each IO-Link master of IO-Link version 1.1 features data storage in which an image of the

IO-Link device configuration can be stored. When a device is replaced, the stored configuration is automatically transferred to the new device. This guarantees minimal downtime. Validation must be switched on in order to use the data storage. For information about the configuration of data storage and validation, please refer to the user's guide of the respective IO-Link master.

Block 8.3.Configuration

The device supports block configuration. This allows all parameters in a data block to be consistently imported from a controller or a configuration tool into the device.

Resetting to Factory Settings

The factory settings on the device can be restored by carrying out the "restore factory settings" system command. 0x82 must be written to Index 2 Subindex 0 for the command. The extension port setting is not reset in this process.

Page 24: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

24

9 Technical Data

Dimensions 9.1.

Mechanical 9.2.Data

Housing material Die-cast zinc, matte nickel-plated

IO-Link port M12, A-coded, plug

Input/output port 16x M8, female

Weight 406 g

Dimensions (L×W×H) 30 x 220 x 32.8 (mm)

Electrical Data 9.3. Operating voltage 18–30.2 V DC, corresponding to EN 61131-2

Ripple < 1%

Current consumption without load (extension off)

≤ 90 mA

Load current (PIN 1) Max. 200 mA (temperature-dependent)

Load current per output (PIN 4) Max. 300 mA (temperature-dependent)

Inputs PNP, type 3

Operating 9.4.conditions

Operating temperature –5 °C … +70 °C

Storage temperature –25 °C … +70 °C

EMC - Immunity - Emission

EMC-directive 2004/108/EEC - EN 61000-6-2 - EN 61000-6-4

Degree of protection IP67 (only when plugged-in and screwed together using Balluff cable)

Vibration/shock EN 60068-2-6, EN 60068-2-27 EN 60068-2-29, EN 60068-2-64

Page 25: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

25

10 Function indicators

Function 10.1.indicators

LED indicator module status

LED Status Function

COM/ US/UA

Green Communication error, US and UA OK

Green, flashing Communication OK, US and UA OK

Red Undervoltage actuator

Red, flashing quickly Undervoltage module

COM/ US/UA

Page 26: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046

www.balluff.com

26

10 Function indicators

Digital LED indicators for inputs/outputs

LED 0, input/output Pin 4

Status Function

Off Input/output signal = 0

Yellow Input/output signal = 1

Red Sensor power supply short-circuit, Actuator warning Actuator short-circuit

Extension port The table is valid if the extension port is active. If the extension port is used as a standard I/O, then the description from "Digital LED indicators for inputs/outputs" can be used.

Status Function

Green IO-Link – connection active

Green, flashing No IO-Link connection or faulty IO-Link device

Red, flashing Incorrect IO-Link device or incorrect configuration (0x55)

Red IO-Link short-circuit on Pin 4

Page 27: User´s Guide: BNI IOL-302-002-Z046 EN · Balluff Network Interface / IO-Link BNI IOL-302-002-Z046 2 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions

www.balluff.com

27

11 Appendix

Type code 11.1.

Ordering 11.2.information

Type code Order code

BNI IOL-302-002-Z046 BNI00AU

BNI IOL-302-002-Z046

Balluff Network Interface

IO-Link interface

Functions 302 = 16 inputs/outputs

Variants 002 = with IO-Link 1.1 extension port

Mechanical configuration Z046 = Die-cast zinc, matte nickel plated Bus connection: 1x M12x1 external threads,

I/O ports: 16 x M8x1, internal threads