AnyWire POKAYOKE TERMINAL (CC-Link Connection)

User’s Guide

First version 10/November/2009

Anywire Corporation

UMA-0A

○R ○R

Page 2: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 3: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

i

Caution Items The cautions to this manual

1. This manual should be sends to last user.

2. Please perform operation of this product after often reading this manual and

understanding the contents.

3. This manual explains the functional details included in this product, and does not

guarantee suiting a visitor's specific purpose.

4. Reproducing and reproducing some or of this device without notice refuses.

5. It may change without a preliminary announcement about the contents of this manual in

the future. Warning Indication

"Warning" shows the contents a possibility of getting death or seriously injured is assumed to be, when handling is mistaken. "Caution" indicates that the failure to follow this instruction can result in minor injury or property damage.

In order to use it safely

◆ An AnyWire system is not a thing having a control function aimed for safe security. ◆ When as follows, while having care special about safety measures which

had a margin to rating and a function and to be used, such as a way and fail-safe, carried out, please consult to our company.

(1) The use for which high safety is needed - The use it is predicted to be to have big influence to a human life or

property - Device for medical treatments, device for safe, etc.

(2) When used for the system by which higher reliability is demanded - Use to vehicles control, combustion control device, etc.

� Please be sure to turn off a system before installation or exchange work.

� Please use an AnyWire system within the limits of the specification and

the conditions that were set to this manual.

CAUTION !!!!

WARNING !!!!

WARNING !!!!

Page 4: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

ii

◆ Be sure not to turn on the 24V power before completing wiring and connecting in AnyWire System.

◆ Use a regulated power supply of 24V DC. Non-regulated power supply may cause a trouble to the system.

◆ Keep transmission cables and I/O cables away from high-voltage and power cables, though the AnyWire System has high noise margin.

◆ Be careful not to allow metal bits into the unit, the connectors or the terminal blocks, especially when wiring.

◆ Mis-wiring may cause failure. Consider the length and installation of cable wiring to keep connectors and cables from disconnecting or excessive distortion.

◆ Never solder the stranded wire to be connected with the terminal block, otherwise causing a defective contact.

◆ In case of long cable length of power line along the transmission lines, large voltage drops will occur and may cause voltage shortage for the distant Slave Units. In that circumstance, connect the local power supply units so that the prescribed voltage is secured at each local Slave Unit.

◆ Be careful of the following items about installation environment. · No exposing directly to the sunlight and ambient temperature is 0 to +55 ˚C. · Operating relative humidity is 10 to 90 % and no dew condensation by sudden temperature change

· No corrosive or inflammable gases · No direct vibration or impact

◆ Fasten terminal screws securely to avoid malfunction. ◆ In case of storage of the product, keep away from high temperature and

high humidity. (Storage temperature is –20 to 75˚C.) ◆ When the emergency stop circuit or the interlock circuit for safety are

arranged, provide these circuits outside the AnyWire System.

CAUTION !!!!

Page 5: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

iii

Contents

1 Target Machines .............................................................................................................................................................1-1

2 Installation Processes ..................................................................................................................................................2-1

3 Transmission Line and Node ...................................................................................................................................3-2

4 AT0 (terminator) ..............................................................................................................................................................4-2

5 Parts Name........................................................................................................................................................................5-1

6 Connection.........................................................................................................................................................................6-1

6.1. CC-Link side (A) ....................................................................................................................................................6-1

6.2. POKAYOKETERMINAL side..........................................................................................................................6-3

6.3. AT0 side ....................................................................................................................................................................6-3

7 General Cautions about installation......................................................................................................................7-1

8 Set to AB023-C1L ....................................................................................................................................................... 8-1

9 Sho-haisen Bus Monitoring Function ...................................................................................................................9-1

10 Basic operating Indication of Each Device................................................................................................ 10-1

10.1. Basic indicator operation of AB023-C1L ............................................................................................... 10-2

10.2. Basic Indication Operation about A027XB-02G2-P......................................................................... 10-4

10.3. Standard indication operation of AT0...................................................................................................... 10-4

11 Attachment pipe of A027XB-02G2-P ........................................................................................................... 11-1

12 Exchanging lever of A027XB-02G2-P ......................................................................................................... 12-1

13 Exchange of Address Setting Switch Cover of A027XB-02G2-P.................................................. 13-1

14 Checklist...................................................................................................................................................................... 14-1

15 Reference..................................................................................................................................................................... 15-1

Page 6: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

iv

AnyWire System Warranty

> Warranty period

The warranty of the Product delivered shall continue effective for one (1) year after the delivery

thereof to a location as designated by the original owner.

> Scope of warranty

Should a defect occur in any part of the Product during the foregoing warranty period when it is

used normally in accordance with specifications described in this User's Manual. The

Company shall replace or repair the defect without charge, except when it arises out of:

(1) The misuse or abuse of the Product by the owner;

(2) Other cause than the Product delivered;

(3) The unauthorized alternation or repair of the Product by any person other than the

Company's personnel;

(4) Any unusual force of nature, disasters and other causes beyond the Company's control.

The word "warranty" as used herein, means the warranty applicable to the delivered product

alone, and the Company is not liable for consequential or incidental damages induced by any

malfunction.

Page 7: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

1-1

1111 Target Machines

Here is the target machine in this guide.

AB023-C1L (Bit distributed I/O Terminal for CC-Link)

A027XB-02G2-P (Lever changed type POKAYOKETERMINAL)

AT0 (Terminator for AnyWire Bitty series)

Page 8: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

1-2

1....AB023-C1L should be used as the CC-Link remote device station

(up to four stations occupied).

2....Use remote register for I/O.

3....Usable transmission signal (DP or DN) cables Use AnyWire dedicated flat cable(Anywire type: FK4-075-100 cable with a size of 0.75mm2/4 wires).

4....Transmission line and power supply

Do not attempt to combine multi-cabtyre cable. It may lead to a malfunction.

Power suppy (DC24V, 0V) to all 027XB-02G2-P and AB023-C1L should be used commonly.

Prepare an AnyWire-dedicated power supply (24-VDC stabilized power supply).

Volatage applied to AB023-C1L should be set within 24V - 27.6V. A measure of power supply capacity(W); [0.035(A)×A027XB-02G2-P number of connection units+0.2(A)]×1.3×24(V)

5....Transmission Distance

Total extension including a branch is up to 100 m.

6....Set to Transmission Speed Set to transmission speed is unnecessary. ( For more details of transmission delay time, refer to User’s Manual of

AB023-C1L)

7....Number of Connecting Units A total of A027XB-02G2-P can be connected 128 units to the AB023-C1L. However, it should be within the number of transmission points can select in four patterns. (it is related to occupied stations of CC-Link). Add AB023-C1L when using more than 128 units. .

!!!! For your continued safety

Page 9: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

1-3

→ Refer to Section 8 of Use’s Manual.

8....Terminator This terminator (AT0) contains a circuit that makes a transmission wave. Therefore, it is different between general “registers”. Note that a terminator has polarities. Connect properly.

DP::::White, DN::::Black

→For more details, refer to Section 3.

9....Address setting (Reference)

“Address setting” is the setting where should be allocated to “No. 0” of each terminal from the head address of AnyWire transmission frame. Each A027XB-02G2-P occupies each one point of I/O from the address.

Address is on decimal number system. Make destination number to add switch weight.(set to per one point) Set the address not to be orverlaped.

Ex))))

10....Address automatic recognition operation Operate address automatic recognition before first rststarting when branch

detection function being used.

Transmission of I/O data is operated by conduction.

Address “0” Occupied input # 0 and output # 0 in transmission frame

Address “1” Occupied input # 1 and output # 1 in transmission frame

Page 10: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 11: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

2-1

2222 Installation Processes

Flow until start-up shows as below as a reference.

System design

Design

Meet terms and conditions

(A total extended distance or address setting)

Selection of connection devices

Set to each unit or connection device

の設置 Install Cables

Set to the maximum transmission distance (transmission clock) of Master Unit

Install and wiring each unit or connection devices

Set to the maximum transmission distance of slave units (transmission

clock) or address

Temporary system start-up (Address automatic recognition)

Error occurred (Error indication)

Setup the system

To change the switch setting, first turn off the power to the system.

Page 12: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

4-2

3333 Transmission Line and Node

The number of connecting devices (A027XB-02G2-P) per one system should be in a following

condition.

・Number of connection units: up to 128 nodes

・Transmission line length: a total expanded 100m or less

・Number of a total transmission points:up to 256 points each I/O

No condition of wiring branch. An example of power-efficient configuration is shown below.

4444 AT0 (terminator)

Please keep the following conditions of AT1 connections.

AT0 is a unit for forming transmission waveforms.

Note that an AT0 has polarities. Incorrect connections may cause malfunctions or failures.

Connect a terminator to the transmission line at the farthest end from AB023-C1L in one system.

Connect to the end of terminal if the branch is 40m or more.

The branch over 40m is available up to 2 systems.

Page 13: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

4-3

Page 14: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 15: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

5-1

5555 Parts Name

■AB023-C1L

CC-Link Connection terminal

Station No Setting switch

SET Switch

Monitor Connection Port

MODE Setting Switch

Indicator LED Indicator LED

AnyWire Connection Terminal

Page 16: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

5-2

■A027XB-02G2-P

■AT0

Eject Indicator

LINK indication

Eject check switch

Hexagon head bolt, fixed

Fixed tool

Connector for transmission line connection

LED

Cable for transmission line connection AWG18(0.75mm2

) 2 wires Insulation outer diameter Φ2.3

Address setting switch cover

Input indicator of eject check switch

Page 17: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

6-1

6666 Connection

6.1.6.1.6.1.6.1. CC-Link side (A)

Connector terminal is attachable easily.

Type: MVSTBW2.5/5-STF-5.08AUM

(Manufactured by Phoenix Contact)

Connectable electric wire: 0.2 - 2.5m㎡ (AWG24 – 12)

Tightening Torque: 0.5 - 0.6N・m

Terminals Signals Line

Color

DA Communication cable Blue

DB Communication cable White

DG Communication Ground Yellow

SLD Shield of communication

cable

-

FG Frame Ground -

* SLD and FG are connected inside the unit.

For more details of CC-Link side of connecting method,

refer to each CC-Link Master Manual.

When detaching “CC-Link side connectors”, check to see that the fixation screws on both ends are

loosened (unplugged from the sockets) before pulling them off.

The devices could be damaged if the connectors are forcedly pulled off while they are still locked.

When installing the device, check to see that there will be no short-circuits due to feasings or

cast-off of the wires and securely tighten the screws at the both ends. (Tightening torque 0.5N-m)

In the case where AB023-C1L is to be the end station, the terminal that is provided with the Master Unit must be attached in between DA and DB. This terminating resistance is needed in addition to the one that is inserted in between DA and DB of the Master Unit. The communication might not be successfully completed on the CC-Link side if not these terminals are not used.

Communication cables and terminal should be crimped together by ferrule. They should be

connected to connectors. Make sure that the cable is not loose and insert to the one terminal.

Otherwise, the cable may come off the connector.

Screw, fixed

AAAA

Page 18: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

6-2

Sho-haisen Bus side (B)

Terminal board is 8-pole-M3 terminal board.

Connectable electric wire: AWG22 - 14

Tightening Torque: 0.8N・m

24V

0V

Connect to DC24V stabilized power supply.

35mA×number of connecting units of A027XB-02G2-P+200mA]×the

capacity must be more than 1.3×24V

DP Transmission line (positive side)

DN Transmission line (negative side)

LG Connected to the neutral point of the noise filter.

Ground if any malfunctions due to the 24V related power source noise are

experienced.

In that case, the grounding work of Class D rating must be conducted

individually.

Page 19: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

6-3

6.2.6.2.6.2.6.2. POKAYOKETERMINAL side

A027XB-02G2-P is attached LP connectors.

Wiring is set by insulation displacement contact in any position of dedicated flat cable

(FK4-075-100) and being combined with connector of A027XB-02G2-P. LP connector

(LP4-BK-10P) can be branch or linking between the same types of connector.

For more details of insulation displacement contact work, refer to “Link Connector insulation

displacement method of Flat Cable.

6.3.6.3.6.3.6.3. AT0 side

To operate insulation displacement contact of a link connector to the end of AT0 cable.

It is recommended that dedicated tools use.

For more details of insulation displacement contact, refer to “Link Connector insulation

displacement method of Flat Cable”.

LP connector PIN

No. Contents

AT0 cable

color

1 DN Black

2 DP White

LP connector of the unit side (attached)

LP connector (LP4-BK-10P), the trunk side of Sho-haisen Bus

Use of LP connector (LP4-OR-10P)

Page 20: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

6-4

3 Spare -

4 Spare -

Page 21: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

7-1

7777 General Cautions about installation

� Select the terminal board and connector according to the kinds of cables or purpose of usage. � Check to see whether the core wire color for connecting the cable is correct. � Do not reuse the connector that has been crimped once as this may lead to contact failure. � Related devices should be turned off when:

- mounting devices or units - detaching devices such as Master units or slave units - setting or changing address - processing or connecting cables - connecting I/O devices, including sensors or actuators

� Always cables in AnyWire System away from high-voltage and power cables. (recommended avoiding 100mm or longer)

� Do not use cable with coiling as transmission condition may not be guaranteed.

* Do not use plural transmission Line (D, G) with many cable lines together. It has the possibility that the equipment operates faultily due to the cross talk when it is transmitted together.

G

G

D

D

G

G

D

D

* Set the diameter of the transmission line at more than 0.75 mm2. * Connect to DP or DN properly. * Be careful of the voltage drop by the cable. Equipment operates faultily due to the voltage drop. * A line to connect to the connector terminal isn't to do solder. A line causes a looseness contact defect

� MONITOR Connector

This connector is for connecting maintenance monitor.

System 1 System 1

System 2 System 2

Page 22: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 23: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

8-1

8888 Set to AB023-C1L

CC-Link side setting((((C))))

Station number is set by “Station No.” setting switch (C).

It can be set from 1 to 64.

If the node address is the same as that of another node, a duplicate node address error occurs,

making it impossible to establish communication.

Maximum setting stations by number of occupied stations are

shown below.

Communication speed is set by “B. RATE” setting switch (D)(D)(D)(D).

When set “5” or more, “ERR” LED is flashing.

Sho-haisen Bus side setting (D)

The transmission distance can be selected using MODE setting switch.

(The following “SW-*” responds to labels 1-6).

SW-2,1 Set a transmission points (=occupied station number) by ON/OFF of switch-1 or 2.

“ STATION No.” setting switches STATION No.

×10 ×1

1 0 1

2 0 2

3 0 3

・ ・ ・

62 6 2

63 6 3

64 6 4

Number of

occupied stations Maximum Setting Station Number

1 64

2 63

3 62

4 61

B.RATE

Setting Switch Communication speed

0 156Kbps

1 625Kbps

2 2.5Mbps

3 5Mbps

4 10Mbps

5 -F Error

DDDD

CCCC

Page 24: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

8-2

SW-3-6 Reserved. Use when the setting is OFF.

MODE

setting

switches

Number of Transmission

points

1 2 Input Output Total

Number of CC-Link

occupied stations

OFF OFF 256

points

256

points

512

points 4

ON OFF 192

points

192

points

384

points 3

OFF ON 128

points

128

points

256

points 2

ON ON 64

points

74

points

128

points 1

Always turn off the power before setting the DIP switches.

Setting changes when applying current are not valid.

Page 25: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

9-1

9999 Sho-haisen Bus Monitoring Function

Summary

AB027-C1L has a memory function to memorize the address of A027XB-02G2-P connected to

AB027-C1L to E2PROM. This memory information has been stored when power is turned off.

This memorized address is sent sequentially during operation. If there is no response from

A027XB-02G2-P, “ALM” LED indicates as disconnection. By using this function, it is possible to

disconnection detection if transmission line is branched.

Automatic Address Identification((((E))))

”Automatic Address Identification” is the operation to have the addresses

of connected Slave Units memorized in E2PROM.

Procedure

1. Check to see that all the Slave Units are properly operating.

2. Press “SET” Switch until the “SET” LED (orange) is lights up.

3. Address memorization is completed when the “SET” LED are flashing

(Flashing quickly) after it has lit for a while.

“Address automatic recognized order as following situations.

- When all A027XB-02G2-P are connecting and operating.

- When A027XB-02G2-P are added.

- When address of A027XB-02G2-P are deleted

- When address of A027XB-02G2-P are changed.

� Input/Output might not be possible while Automatic Address Identification is in operation.

Operate Automatic Address Identification in the condition that will not interfere with the

operation of devices such as to stop the PLC Program execution, etc.

� Automatic Address Identification does not operate when there are any errors of Sho-haisen Bus

or for approximately five seconds after tuning on the power or resetting the error status.

� Do not operate address automatic recognition when disconnection error is occurred in operation.

The information of disconnection may be lost.

Monitoring operation

The addresses registered will be sent out one by one and when the response is not returned, it will be

displayed as disconnection by “ALM” LED.

This error information will be retained until the power is turned off or error status is reset.

(Refer to section “LED Indications”.)

EEEE

Page 26: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 27: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

10-1

10101010 Basic operating Indication of Each Device

Status indication (F)

Each device has monitor indication for operating state. Check that each device work properly after

connection and conduction.

Each setting or connection may correct, device indicator shows in the table below.

Indication Status Indication Status

RUN Lights

up LINK Flashing

ERR Goes

out RDY

Lights up

SD Lights

up SET

Goes out

CC-Link side

RD Lights

up

Sho-haisen Bus side

After checking this status, operate “Automatic address recognition” and register connecting terminal.

(See User’s Manual of AB023-C1L.)

In the beginning of conducting, “LINK” indication turns on "Lights up". It means

A027XB-02G2-P is not registered by “Automatic address recognition”.

When registered “Automatic address recognition” operation, disconnecting monitoring function of transmission

line becomes effective.

Data transmission is operating regardless “Automatic address recognition”

After operating “Automatic address recognition”, “LINK” indicator turns on "Flashing". It means

operating in normal status. In the case of indicated status other than those listed above, remove the

failure according to the following contents.

FFFF

Page 28: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

10-2

10.1.10.1.10.1.10.1. Basic indicator operation of AB023-C1L

Green LED shows the operation of normal status. ■ Status of CC-Link-side Indicators

LED Lights up Goes out Flashing

RUN

(Green) Successfully transmitting

Transmission cable is disconnected. Transmission cable wiring is wrong. Transmission speed Setting is wrong. The hardware is being reset.

ERR

(Red)

− CRC Error − Error detected in Station Setting SW (Set to either 0 or any number larger than 62) − Error detected in Baud Rate SW Setting • (Set to any number larger

than 5)

Successfully transmitting The hardware is being reset.

When Baud Rate or

station number switch

changed from the setting

of reset (flashing for four

second), restore setting

and then may go out.

SD

(Yellow) Sending Data

−Transmission cable is disconnected. − Transmission cable wiring is wrong. − Transmission speed Setting is wrong. The hardware is being reset.

RD

(Yellow) Sending Data

− Transmission Cable is disconnected. − Transmission Cable wiring is wrong. The hardware is being reset.

■Indication of the status of Sho-haisen Bus

Indication Name Color Meanings

Lights

up

This unit is in operation.

RDY Ready Green Goes

out

The power is not supplied, or this unit is faulty.

Flashing Data is being transmitted normally.

LINK Transmission

distance Green Goes

out

This unit is faulty.

SET Automatic

address Orange

Lights

up

Automatic address recognition is in progress.

Page 29: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

10-3

Goes

out

Data is being transmitted normally. recognition

indication

Flashing The recognized address is being written to

EEPROM.

Confirm the next first.

(1) The "RDY" LED of AB023-C1L should be lighted on.

(2) The "LINK" LED of all POKAYOKETERMINAL (A027XB-02G2-P) should be flashed.

(3) The power supply voltage of AB023-C1L should be a thing in a range of 24 - 27.6V.

(4) Wiring and connection should be certain.

(5) The address establishment should be accurate, not overlapping.

(6) Use transmission line with a size of at least 0.75mm2.

(7) Total extension of transmission length should be up to 100m.

(8) Umber of connecting units of POKAYOKETERMINAL (A027XB-02G2-P) should be up to 128

units and used points should be up to 256 points.

Page 30: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

10-4

10.2.10.2.10.2.10.2. Basic Indication Operation about A027XB-02G2-P

A027XB-02G2-P has a monitoring function.

LINK lamp indicates a system status.

Eject indicator lamp indicates an eject position in green.

■Indications of Sho-haisen Bus side

10.3.10.3.10.3.10.3. Standard indication operation of AT0

When transmission signal is received in normal connecting status,

Red LED (J) lights up (low brightness).

Indicate LED Indicate

status Monitor contents

Flashing Transmission

signal reception

Turn Lights

up LINK: Red (G)

Goes out

Disconnection of

power,

Transmission

error

(Disconnection or

short-circuit)

Lights up Eject indicator lamp:Green

(H) Goes out Eject order

IIII

GGGG HHHH

Page 31: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

10-5

JJJJ

Page 32: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 33: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

11-1

11111111 Attachment pipe of A027XB-02G2-P

POKAYOKETERMINAL (A027XB-02G2-P) is attachable to Φ28 pipe. (ex: creform or creform pipe

of Yazaki Kako Corporation).

[1] Hook the boss of fitting B onto the Hinji part of the body.

[2] Hook fitting B onto the pipe, and then pull the body to make the connection. When the body pawl snaps into the flute of fitting B, a temporary fixing has been made.

[3] Slide to the body and adjust the position.

[4] Once the position has been determined, fasten fitting B to the pipe with the provided bolts. M6 bolt Tightening Torque: 1.5 -2N・m

Body

Fitting B

Hinji part

Flute of Fitting B

Body tab

Hexagon head bolt (M6×15) attached with one on the body

Pipe

Page 34: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 35: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

12-1

12121212 Exchanging lever of A027XB-02G2-P

“Rubber lever” of eject recognized switch of A027XB-02G2-P is changeable.

Changing procedure is as follows.

[1111] Disinstallation of Rubber Lever

Rubber lever holding ring

Rubber lever

Front view

(1) Put a black part of rubber lever holding ring to direction B and loosen the ring after removing a mating.

Rubber lever fixture

[1] Rubber lever

[2] Rubber lever holding ring

(2) Remove the rubber lever in numerical order, [1] → [2].

Page 36: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

12-2

[2] Installation of Rubber Lever

Rubber lever fixture

[1] New rubber lever

[2] Rubber lever holding ring

■Exchange rubber lever set Type: A027XB-LSE-06B-01-5P (Packs of 5 sets)

Rubber lever

Rubber lever holding ring

[1]Put a new rubber lever in holing fitting properly and put a tuber lever holding ring through a lever. Use new holding ring.

Rubber lever Holding ring attach position (D)

Rubber lever

Mating status at tightening

Rubber lever holding ring

External diameter of

rubber lever

(2)Attach a rubber lever holding ring to a position on the front side. After tightening, check that lever is fixed properly.

Front view

Page 37: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

13-1

13131313 Exchange of Address Setting Switch Cover of A027XB-02G2-P

Exchange address setting switch covers which are lost or damaged for new one. Attachment

method is as follows.

Address setting switch cover is opened when it slides to the left. And the cover is removed when

it slides more. When attached switch cover, put the cover flitter in the main body’s rail and slide to

the right.

Address setting switch cover

Open

Put a pawl of the part of ○ in a rail and slide it.

Cross-section view

Put a tab of cover one by one.

Page 38: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 39: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

14-1

14141414 Checklist

Main check items are as follows.

[1] Link indicator of A027XB-02G2-P does not light up. It may have a loose connection of transmission line.

・Is selected proper connector for cable size?

・Do all hooks of insulation displacement contact of LP connector put properly?

・Do connectors put each other properly?

・Is screw terminal board of AB023-C1L loosen?

A027XB-02G2-P connection may be improper.

・Are 128 units or more connected?

・Eject indicator does not light up.

[2] Eject indicator lamp of A027XB-02G2-P is flashing at random times. Transmission signal is not reached to predetermined duration or voltage as a result of

external factor.

・Is a total length of transmission lines up to 100m?

・Is the voltage being supplied to AB023-C1L low?

・Is power capacity being supplied to AB023-C1L not enough?

・Is A027XB-02G2-P set properly?

[3]Input signal of eject check switch of A027XB-02G2-P does not turn on. Transmission signal is not reached to predetermined duration or voltage as a result of

external factor including a failure of lever.

・Is a lever of eject check switch broken?

・Are input CH number or bit position correct?

・Is the total length of transmission lines over 100m?

・Is the voltage being supplied to AB023-C1L low?

[4] Error information on AB023-C1L Indications about CC-Link

Communication is completed if both SR and RD light up.

In the case of indicated pattern other than those listed above, remove the failure according to the

table of section 10.1.

Indication about AnyWire

Receiving and sending of transmission signal is completed if RDY lights up or LINK is flashing.

Remove the failure as following section 10.1if LINK may light up or flash.

[5] LED of AT0 does not light up.

Connection of DP and DN is connected properly or transmission signal id no reached.

Check if the cable wirings are correctly completed.

****If there are problems other than those listed above, contact us.

Page 40: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R
Page 41: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

15-1

15151515 ReferenceReferenceReferenceReference

Parameter Setting is required in order for the communication between Master Station and Remote I/O

station, remote device station as well as local station on CC-Link.

A parameter setting example of AB023-C1L (remote device station) is shown below:

Moreover, refer to “CC-Link System Master/Local Unit User’s Manual (detailed version)” and related documents by Mitsubishi Electric.

1. Parameter setting example by CPU of Q series

CC-Link Master Unit : The head I/O number is “0”.

AB023-C1L : When station number is “1”.

A1S62PN

A2USCPU

A1SJ61BT11 CC-Link Master unit X/Y00 - X/Y1F

Ver.1.1

CC-Link Bit distributed I/O terminal AB023-C1L Station No. 1 (Set to four stations occupied from the station No 1 to No 4.)

Page 42: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

15-2

CC-Link parameter can be set from the Parameter Setting Screen of Programming Software GX

Developer on the Q CPU, QnA, Q4AR, QnAS or QnASH CPU.

[Setting Example] Check the [Project Data List] on the Displayed Menu. The screen shown below will appear by clicking

[Parameter] → [Network Parameter] → [CC-LINK] in the displayed Project Window.

Enlarged screen of what is shown in the frame will be shown in the next section.

Page 43: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

15-3

■when connected to AB023-C1L (one unit)

Set each field to meet the specification of the system that is used by the customer.

Setting Items Contents

Head I/O No. Input the head I/O number that the CC-Link is attached by the unit

of 16 points.

Mode setting Select from remote net-ver.1 mode, remote net-ver.2 mode and

Remote Net – Additional mode to meet the customer’s system.

The total Number of Connections Input the total number of units that include the reserved stations

and inactivated stations in the range from 1 to 64. Remote Input (RX) Refresh Device

Enter the device name and device number of X, M, L, B, D, W, R

and ZR. Remote output (RY) Refresh device

Enter the device name and device number of Y, M, L, B, T, C, ST,

D, W, R and ZR. Remote Register (RWr) Refresh

Device

Enter the device name and device number of M, L, B, D, W, R,

and ZR

Remote Register (RWr) Refresh

Device

Enter the device name and device number of M, L, B, T, C, ST, D,

W, R and ZR. Special Relay (SB) Refresh

device

Enter the device name and device number of M, L, B, D, W, R, SB

and ZR. Special Register (SW) Refresh

device

Enter the device name and device number of M, L, B, D, W, R,

SW and ZR.

Page 44: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

15-4

■Station Information Setting [Station Information Setting] Window shown below will open by a double click on [Station Information].

Set [Station Type] to [Remote Device Station] and [Occupied Number of Station] to [4-Station

Occupation].

The response of each signal and device are shown below.

Signals Corresponding device

Error flag X17A note 1)

Error reset required flag Y17A note 2)

Input (256 points) M0 - M255

Output (256 points) M400 - M655

Input and output are provided by the remote register. In this case, MO - M255 are for inputs and M400 -

M655 are for outputs. X100 - X17F and Y100 – Y17F are occupied when X17A is used as error status

flag and Y17A is used as error reset required flag. note1), note2)

Page 45: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R

15-5

■When connected to AB023-C1L (2 units)

The response of each signal and device will be as are shown below.

Signals Corresponding device

station No. 1

Corresponding device

station No. 5

Error status flag X17A note 1) X1FA note 1)

Error reset required flag Y17A note 2) Y1FA note 2)

Input (256 points) MO - M255 M256 - M511

Output (256 points) M800 - M1055 M1056 - M1311

Input and output are provided by the remote register. In this case, MO - M511 are for inputs and M800

–M1311 are for outputs. X100 - X1FF and Y100 – Y1FF are occupied when X17A is used as error

status flag and Y17A is used as error reset required flag. note1), note2)

Page 46: User’s Guide · AnyWire POKAYOKE TERMINAL (CC-Link Connection ) User’s Guide First version 10/November/2009 Anywire Corporation UMA-0A R R