User Manual - Huawei UPS · 2017-08-31 · UPS5000-A. The installation position of RMS-RELAY01A...
Transcript of User Manual - Huawei UPS · 2017-08-31 · UPS5000-A. The installation position of RMS-RELAY01A...
Part Number: 31505548
RMS-RELAY01A
User Manual
Issue 05
Date 2015-12-25
HUAWEI TECHNOLOGIES CO., LTD.
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd. i
Copyright © Huawei Technologies Co., Ltd. 2015. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website: http://e.huawei.com
RMS-RELAY01A
User Manual About This Document
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
ii
About This Document
Purpose
This document describes the RMS-RELAY01A card in terms of its appearance, functions,
ports, and installation. The card is an optional communications component of the
UPS2000-G-(6 kVA–20 kVA), UPS2000-A-(6 kVA–10 kVA), and UPS5000-A-(30 kVA–120
kVA). UPS is short for uninterruptible power system.
The Modbus card has an exquisite, advanced, and unique design, and features high
performance and reliability.
Intended Audience
This document is intended for:
Sales engineer
Technical support engineer
System engineer
Hardware installation engineer
Commissioning engineer
Data configuration engineer
Maintenance engineer
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Conventions
Symbol Description
Indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
RMS-RELAY01A
User Manual About This Document
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
iii
Symbol Description
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to
personal injury.
Calls attention to important information, best practices
and tips.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 05 (2015-12-25)
Updated the issue of this document, as the pictures in chinese document changed.
Issue 04 (2015-06-25)
Support UPS2000-A-(6 kVA–10 kVA) and UPS5000-A-(30 kVA–120 kVA).
Issue 03 (2014-05-15)
Updated the pictures in this document.
Issue 02 (2013-08-24)
Updated the pictures in this document.
Issue 01 (2013-05-15)
This is the first release.
RMS-RELAY01A
User Manual Contents
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
iv
Contents
About This Document .................................................................................................................... ii
1 Safety Precautions ......................................................................................................................... 1
2 Overview ......................................................................................................................................... 2
2.1 Introduction .................................................................................................................................................................. 2
2.2 Functions ...................................................................................................................................................................... 2
2.3 Typical Application Scenario ........................................................................................................................................ 3
3 Function Description .................................................................................................................... 5
3.1 Pins on the DB25 Port .................................................................................................................................................. 5
3.2 DB25 Cable .................................................................................................................................................................. 7
3.3 Electrical Specifications of the Output Dry Contact Relay .......................................................................................... 7
4 Installation...................................................................................................................................... 9
4.1 Unpacking and Checking .............................................................................................................................................. 9
4.2 Tool Preparation ............................................................................................................................................................ 9
4.3 Installation Procedure ................................................................................................................................................. 10
4.4 Setting the Dry Contact Parameters ............................................................................................................................ 11
A Acronyms and Abbreviations .................................................................................................. 14
RMS-RELAY01A
User Manual 1 Safety Precautions
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1
1 Safety Precautions
1. Only professional technical personnel designated by Huawei are allowed to install and
operate the RMS-RELAY01A card.
2. Carefully read this document before operating the RMS-RELAY01A card. Keep this
document for future use.
3. Before handling the RMS-RELAY01A card, get tools insulated, and take off metal
articles such as watches and rings.
4. To avoid damage, move the RMS-RELAY01A card gently.
5. Connect the DB25 port to safety low-voltage circuits. Otherwise, the RMS-RELAY01A
card may be damaged, or even security accidents may occur.
6. External devices must meet the electrical specifications of the RMS-RELAY01A card.
RMS-RELAY01A
User Manual 2 Overview
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
2 Overview
2.1 Introduction
The RMS-RELAY01A card is installed in an optional card slot on the UPS and supports hot
swap. The dry contact card provides six alarm dry contact outputs (normal mode, battery
mode, bypass mode, battery undervoltage, bypass backfeed, and UPS faults) and two dry
contract control inputs (one is for shutdown signals, and the other is reserved).
For UPS5000-A-(30 kVA–120 kVA), the output dry contacts are available, and input dry contacts are
unavailable.
Table 2-1 lists basic specifications of the RMS-RELAY01A card.
Table 2-1 Basic specifications
Model Appearance Specifications
RMS-RELAY01A
Applicable UPS: UPS2000-G-(6
kVA–20 kVA), UPS2000-A-(6
kVA–10 kVA), and UPS5000-A-(30
kVA–120 kVA).
Ambient temperature and humidity:
–40°C to +65°C; 5%–95% RH.
2.2 Functions
The RMS-RELAY01A card has six alarm outputs, as described in Table 2-2. Set the dry
contacts on the liquid crystal display (LCD). Each dry contact can be associated with a type of
alarms.
RMS-RELAY01A
User Manual 2 Overview
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3
Table 2-2 RMS-RELAY01A card functions
Dry Contact Type Function Dry Contact No. Dry Contact Definition
Output Normal mode 1 Normal mode, or
normal mode in
ECO mode
Battery mode 2 Battery mode, or
battery mode in
ECO mode
Bypass mode 3 Bypass mode or
ECO mode
Battery undervoltage 4 The monitoring
system determines
that the battery
voltage is low
according to the
battery management
solution.
Bypass backfeed 5 The UPS reports
bypass feedback
alarms.
UPS faults 6 Critical alarms are
generated.
Input Shutdown 1 An inverter
shutdown instruction
is delivered.
Reserved 2 Reserved
For UPS2000-G-(6 kVA–20 kVA), the output dry contact No. of the RMS-RELAY01A card is
configurable on the LCD. For details, see 4.4 Setting the Dry Contact Parameters.
2.3 Typical Application Scenario
Figure 2-1 shows a typical application scenario in which the RMS-RELAY01A card reports
five working modes of the UPS.
RMS-RELAY01A
User Manual 2 Overview
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4
Figure 2-1 Typical application scenario
RMS-RELAY01A
User Manual 3 Function Description
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5
3 Function Description
3.1 Pins on the DB25 Port
Figure 3-1 Pins on the DB25 port
Table 3-1 Description of the pins on the DB25 port
Pin No. Signal Input/Output Description
1 AGND Output External analog
ground
2 INPUT2 Input External Boolean
value 2 input
3 None None Unused
4 None None Unused
RMS-RELAY01A
User Manual 3 Function Description
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6
Pin No. Signal Input/Output Description
5 OUTPUT6– Output Dry contact 6
common terminal
6 OUTPUT5_B Output Dry contact 5
normally closed
(NC) contact
7 OUTPUT5_A Output Dry contact 5
normally open (NO)
contact
8 OUTPUT4– Output Dry contact 4
common terminal
9 OUTPUT3_B Output Dry contact 3 NC
contact
10 OUTPUT3_A Output Dry contact 3 NO
contact
11 OUTPUT2– Output Dry contact 2
common terminal
12 OUTPUT1_B Output Dry contact 1 NC
contact
13 OUTPUT1_A Output External dry contact
1 NO contact
14 INPUT1 Input External Boolean
value 1 input
15 None None Unused
16 None None Unused
17 OUTPUT6_B Output Dry contact 6 NC
contact
18 OUTPUT6_A Output Dry contact 6 NO
contact
19 OUTPUT5– Output Dry contact 5
common terminal
20 OUTPUT4_B Output Dry contact 4 NC
contact
21 OUTPUT4_A Output Dry contact 4 NO
contact
22 OUTPUT3– Output Dry contact 3
common terminal
23 OUTPUT2_B Output Dry contact 2 NC
contact
24 OUTPUT2_A Output Dry contact 2 NO
RMS-RELAY01A
User Manual 3 Function Description
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7
Pin No. Signal Input/Output Description
contact
25 OUTPUT1– Output Dry contact 1
common terminal
3.2 DB25 Cable
Figure 3-2 DB25 cable
The DB25 cable, which is delivered along with the RMS-RELAY01A card, is 1.5 meters long.
To increase the length, add a magnetic ring to the connector of the DB25 cable. Table 3-2 lists
the specifications of magnetic rings from three vendors.
Table 3-2 Specifications of magnetic rings from three vendors
Vendor Magnetic Ring
DMEGC R10K
TDK HS10
TDG TS10
The initial magnetic conductivity of manganese and zinc magnetic rings is greater than 10,000. The
recommended internal diameter of magnetic rings is greater than 10 mm (easy for wire coiling). The
number of coiling circles is 5 or more.
3.3 Electrical Specifications of the Output Dry Contact Relay
Table 3-3 lists electrical specifications of the output dry contact relay.
RMS-RELAY01A
User Manual 3 Function Description
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8
Table 3-3 Electrical specifications of the output dry contact relay
Item Specifications
Maximum contact power 30 W
Rated contact voltage 30 V DC
Rated contact current 1 A
Input dry contact voltage 12–24 V DC
RMS-RELAY01A
User Manual 4 Installation
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9
4 Installation
4.1 Unpacking and Checking
After you receive the RMS-RELAY01A card, unpack the case and check as follows:
Visually inspect the appearance for shipping damage. If it is damaged, notify the carrier
immediately.
Check that the fittings comply with the order. If some fittings are missing or do not
comply with the packing list, record the information and contact your local Huawei
office immediately.
4.2 Tool Preparation
Table 4-1 Tools
Tools
Insulated Phillips
screwdriver
Multimeter Labels Polyvinyl chloride
(PVC) insulation
tape
Protective gloves ESD gloves Cable ties N/A
N/A
RMS-RELAY01A
User Manual 4 Installation
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10
4.3 Installation Procedure
The methods for installing RMS-RELAY01A cards are the same on different UPSs. The
RMS-RELAY01A card is installed in the optional card slot INTELLISLOT at the rear panel
of the UPS2000 and installed in the slot for dry contact card at the rear panel of the
UPS5000-A. The installation position of RMS-RELAY01A cards based on actual conditions.
Procedure
Step 1 Check that the following items are available. One RMS-RELAY01A card, one DB25 cable,
and one RMS-RELAY01A User Manual.
Step 2 Remove the optional card slot cover from the UPS, as shown in Figure 4-1. Keep the screws
for use in Step 3, and the cover for future use.
Figure 4-1 Removing the optional card slot cover
Step 3 Insert the RMS-RELAY01A into the optional card slot along the guide rails, as shown in
Figure 4-2, and then tighten the screws.
The card uses M3 screws. The recommended torque is 0.5 N·m.
RMS-RELAY01A
User Manual 4 Installation
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
11
Figure 4-2 Inserting the RMS-RELAY01A into the optional card slot
Step 4 Connect one end of the cable to the DB25 port on the RMS-RELAY01A card and the other
end to the customer equipment, as shown in Figure 4-3, and then tighten the screws.
Figure 4-3 Connecting the RMS-RELAY01A card to customer equipment
----End
4.4 Setting the Dry Contact Parameters
UPS2000-A-(6 kVA–10 kVA) and UPS5000-A-(30 kVA–120 kVA) can not set monitoring
parameter on the LCD.
RMS-RELAY01A
User Manual 4 Installation
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
12
For UPS2000-G-(6 kVA–20 kVA), after you install the RMS-RELAY01A card, set the dry
contact on the LCD.
Procedure
Step 1 Press on the LCD. On the main menu, choose Settings.
Step 2 Enter a password. (The preset password is 000001.)
Step 3 Select Communication Card.
Step 4 Press , the Communication Card screen is displayed. Set the dry contact parameters
for RMS-RELAY01A card.
Multiple statuses can be associated with one dry contact, but one status cannot be associated with
multiple dry contacts.
Normal mode parameter
Set the output dry contact associated with normal mode. When the UPS is in normal or
ECO mode, this dry contact is enabled. The value ranges from Dry contact1 to Dry
contact6. The default value is Dry contact1.
Battery mode parameter
RMS-RELAY01A
User Manual 4 Installation
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
13
Set the output dry contact associated with battery mode. When the UPS is in battery or
battery ECO mode, this dry contact is enabled. The value ranges from Dry contact1 to
Dry contact6. The default value is Dry contact2.
Bypass mode parameter
Set the output dry contact associated with bypass mode. When the UPS is in bypass or
ECO mode, this dry contact is enabled. The value ranges from Dry contact1 to Dry
contact6. The default value is Dry contact3.
Batt. undervolt parameter
Set the output dry contact associated with low battery voltage. When the system battery
voltage is low, this dry contact is enabled. The value ranges from Dry contact1 to Dry
contact6. The default value is Dry contact4.
BPS backfeed parameter
Set the output dry contact associated with bypass backfeed. When a bypass backfeed
alarm is generated, this dry contact is enabled. The value ranges from Dry contact1 to
Dry contact6. The default value is Dry contact5.
Faulty UPS parameter
Set the output dry contact associated with UPS faults. When a critical alarm is generated,
this dry contact is enabled. The value ranges from Dry contact1 to Dry contact6. The
default value is Dry contact6.
----End
RMS-RELAY01A
User Manual A Acronyms and Abbreviations
Issue 05 (2015-12-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
14
A Acronyms and Abbreviations
E
ECO economy control operation
ESD electrostatic discharge
L
LCD liquid crystal display
N
NC normally closed
NO normally open
P
PVC polyvinyl chloride
U
UPS uninterruptible power system