UPS Calculation

43
Sheet 2 PLC-5 Item Pt. no. Description Qty VA D.F Total Reference 1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H 2 7.5 1 15 Page 6 2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE 4 0.77 1 3.08 Page 7 3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY 2 20 1 40 Page 8 4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9 5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 1 11 1 11 Page 10 6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 2 0.4 1 0.8 Page 11 7 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 5 6.5 1 32.5 Page 12 8 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 2 6.6 1 13.2 Page 13 9 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LINK 1 0 0 0 Page 14 10 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical 42 0.5 1 21 Page 25 14 FIT-201A/B Magnetic flow meters DN 500 2 15 1 30 Page 26 15 LSH-201A/B Level switch for hazarouds 2 2.5 1 5 Page 27 16 LIT-201A/B level indicator transmitter 2 23 1 46 Page 28 17 PIT-201A/B/C/D/E/F Pressure transmitter 6 0.4 1 2.4 Page 29 232.7 0 232.7 300 Al- Wefaq Control System TOTAL IN VA Summation Auxiliary Rate UPS Load Calculation for Industrial Area Pumping Station PLC panel Project: - Rev. 0 Page 1 of 43

description

UPS Calculation For PLC and Instrumentation for material Submittal

Transcript of UPS Calculation

Page 1: UPS Calculation

Sheet 2 PLC-5Item Pt. no. Description Qty VA D.F Total Reference

1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H 2 7.5 1 15 Page 62 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE 4 0.77 1 3.08 Page 73 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY 2 20 1 40 Page 84 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 95 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 1 11 1 11 Page 106 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 2 0.4 1 0.8 Page 117 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 5 6.5 1 32.5 Page 128 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 2 6.6 1 13.2 Page 139 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LINK 1 0 0 0 Page 1410 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical 42 0.5 1 21 Page 2514 FIT-201A/B Magnetic flow meters DN 500 2 15 1 30 Page 2615 LSH-201A/B Level switch for hazarouds 2 2.5 1 5 Page 2716 LIT-201A/B level indicator transmitter 2 23 1 46 Page 2817 PIT-201A/B/C/D/E/F Pressure transmitter 6 0.4 1 2.4 Page 29

232.70

232.7300

Al- Wefaq Control System

TOTAL IN VA

SummationAuxiliary Rate

UPS Load Calculation for Industrial Area Pumping Station PLC panelProject: -

Rev. 0

Page 1 of 43

Page 2: UPS Calculation

Sheet 3,4 PLC-4Item Pt. no. Description Qty VA D.F Total Reference

1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 62 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR 4 0.77 1 3.08 Page 73 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A, WIDERANGE, 120/230V UC 2 20 1 40 Page 84 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 95 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 2 11 1 22 Page 106 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331,OPTICALLY ISOLATED, 8 AI, 13 BIT 2 0.4 1 0.8 Page 117 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED 32DI 8 6.5 1 52 Page 128 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 3 6.6 1 19.8 Page 139 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 74 0.5 1 37 Page 2510 DLIT-301C Differential Level Indicator Transmitters 3 0.5 1 1.5 Page 3011 AIT-401 Hydrocarbon Analyzer 1 0.6 1 0.6 Page 3112 ASS-401 Auto Sampler 1 290 1 290 Page 3213 FIT-401 FIT-401B Open Channel Ultrasonic level type flowmeter 2 23 1 46 Page 28

540.50

540.5600

Al- Wefaq Control System

TOTAL IN VA

SummationAuxiliary Rate

UPS Load Calculation Inlet Works panelProject: -

Rev. 0

Page 2 of 43

Page 3: UPS Calculation

Sheet 5,6,7 SBR-PLCItem Pt. no. Description Qty D.F Total Reference

1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 62 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR PATCH CABLES UP TO 10M 4 0.77 1 3.08 Page 73 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A 2 20 1 40 Page 84 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 95 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 5 11 1 55 Page 106 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 13 0.4 1 5.2 Page 117 6ES7332-5HF00-0AB0 SIMATIC S7-300, ANALOG OUTPUT SM 332 3 6 1 18 Page 158 6ES7321-1BH02-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 25 3.5 1 87.5 Page 169 6ES7322-1BH01-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 9 4.9 1 44.1 Page 1710 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LIN 1 0 0 0 Page 1411 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 104 0.5 1 52 Page 2512 PIT-501A/B PIT601A/B Pressure Transmitter 4 0.5 1 2 Page 3313 LIT-501A/B LIT-601A/B Level Indicator Transmitters 4 23 1 92 Page 2814 Viberation Sensor 10 0.5 1 5 Page 3415 FIT-701A/B Differential Pressure Type 2 0.5 1 1 Page 30

16

AIT-501A/B/C AIT-502A/B/C AIT-601A/B/C AIT-602A/B/C LIT-502A/B LIT-602A-B AIT-503

Analyzers 17 55 1 935 Page 35

1367.60

1367.61400

UPS Load Calculation SBR PLC panelAl- Wefaq Control System

TOTAL IN VA

SummationAuxiliary Rate

Project: -

Rev. 0

VA

Page 3 of 43

Page 4: UPS Calculation

Item Pt. no. Description Qty VA D.F Total Reference

1 6ES7214-1AG31-0XB0 SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC 1 12 1 12 Page 372 6ES7221-1BH30-0XB0 SIMATIC S7-1200, DIGITAL INPUTSM 1221 , 16DI, 24 V DC, S 5 2.5 1 12.5 Page 383 6ES7222-1BH30-0XB0 SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 2 2.5 1 5 Page 394 6ES7231-4HF30-0XB0 SIMATIC S7-1200, ANALOG INPUT, SM 1231, 5 1.5 1 7.5 Page 405 6AV6647-0AB11-3AX0 SIMATIC HMI ,KTP600 BASIC ,MONO PN 1 6 1 6 Page 416 6GK7242-5DX30-0XE0 COMMUNICATION MODULE CM 1242-5 1 0.75 1 0.75 Page 427 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +m. indicator 21 0.5 0.6 6.3 Page 258 55.34.9.024.0040 Relay 24 VDC, 7A ,4 Pole, Lockable test button 14 1 0.6 8.4 Page 439 - Loop Powered Signal 3 0.576 1 1.728 not avaliable

60.178

10 6ES7214-1AG31-0XB0 SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC 1 12 1 1211 6ES7221-1BH30-0XB0 SIMATIC S7-1200, DIGITAL INPUTSM 1221 , 16DI, 24 V DC, S 5 2.5 1 12.512 6ES7222-1BH30-0XB0 SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 2 2.5 1 513 6ES7231-4HF30-0XB0 SIMATIC S7-1200, ANALOG INPUT, SM 1231, 5 1.5 1 7.514 6AV6647-0AB11-3AX0 SIMATIC HMI ,KTP600 BASIC ,MONO PN 1 6 1 615 6GK7242-5DX30-0XE0 COMMUNICATION MODULE CM 1242-5 1 0.75 1 0.7516 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +m. indicator 21 0.5 0.6 6.317 55.34.9.024.0040 Relay 24 VDC, 7A ,4 Pole, Lockable test button 14 1 0.6 8.418 - Loop Powered Signal 3 0.576 1 1.728

60.178120.356

0

120.356200

Odor 1 PLC Panel

Odor 2 PLC Panel

The Same as Odor 1 PLC

Panel

UPS Load Calculation OCU PLC panelAl- Wefaq Control System

TOTAL IN VA

SummationAuxiliary Rate

Project: -

Rev. 0

Page 4 of 43

Abdel-Hamed El-Deeb
Line
Page 5: UPS Calculation

Item Pt. no. Description Qty VA D.F Total Reference1 6ES7405-0KA02-0AA0 SIMATIC S7-400 , PS 405 2 95 1 190 Page 182 6ES7412-3HJ14-0AB0 SIMATIC S7-400H, CPU412H 2 5.5 1 11 Page 193 6ES7960-1AA04-0XA0 SIMATIC S7-400H, SYNC SUB MODULE 2 0.0011 1 0.0022 Page 204 6EP1 333-3BA00 SITOP MODULAR 5A 2 18 1 36 Page 215 6ES7153-2AR03-0XA0 IM153-2 INTERFACE REDUND.BUNDLE 3 5.5 1 16.5 Page 226 6ES7321-1BL00-0AA0 32DI DIGITAL INPUT MODULE 9 6.5 1 58.5 Page 127 6ES7322-1BL00-0AA0 32DO DIGITAL OUTPUT MODULE 8 6.6 1 52.8 Page 138 6ES7331-1KF02-0AA0 8AI ANALOG INPUT MODULE, 4-20mA 4 0.4 1 1.6 Page 239 6GK1503-3CB00 OLM/G12 2 4.8 1 9.6 Page 2410 6ES7197-1LA04-0XA0 Y-Link 1 0 0 0 Page 1411 46.52.9.024.0040 2-CONTACT RELAY 24VDC 300 0.5 1 150 Page 2512 SCADA system computer 1 535 1 535 not avaliable13 Printer 1 70 1 70 not avaliable

14 FIT-1001A/B/C/D/E/F FIT-1002 FIT-1003A/B Magnetic flow meters DN 200/400/500 9 15 1 135 Page 26

15 AIT-1002 TUT-1001 Nitrate/Turbidity analyzers 2 55 1 110 Page 3516 AIT-1001 hydro-carbon analyzer 1 0.6 1 0.6 Page 3117 flow switch low 19 10 1 190 Page 3618 LIT-1001 level transmitter 1 23 1 23 Page 28

19 PIT-1001:6A/BPIT-1001:6C Pressure transmitter 20 0.5 1 10 Page 33

20 Solenoid valve of pneumatic 40 15 1 600 not avaliable

2199.60

2199.62200

UPS Load Calculation Ultrafilters PLC panelAl- Wefaq Control System

TOTAL IN VA

SummationAuxiliary Rate

Project: -

Rev. 0

Page 5 of 43

Abdel-Hamed El-Deeb
Line
Page 6: UPS Calculation

Power losses

Power loss, typ. 7.5 W

Backup battery

Battery operation

Backup current, typ. 180 μA ; Valid up to 40°C

Backup current, max. 1000 μA

Backup time, max. Dealt with in the module data manual with thesecondary conditions and the factors of influence

Feeding of external backup voltage to CPU 5 to 15 VDC

Feeding of external backup voltage to CPU 5 to 15 VDC

Memory

Work memory

integrated 4 Mbyte

integrated (for program) 2 Mbyte

integrated (for data) 2 Mbyte

expandable No

Load memory

expandable FEPROM Yes ; with Memory Card (FLASH)

expandable FEPROM, max. 64 Mbyte

integrated RAM, max. 512 kbyte

expandable RAM Yes

expandable RAM, max. 64 Mbyte

Backup

present Yes

with battery Yes ; all data

without battery No

CPU processing times

for bit operations, min. 18.75 ns

for word operations, min. 18.75 ns

for fixed point arithmetic, min. 18.75 ns

for floating point arithmetic, min. 37.5 ns

CPU-blocks

DB

Number, max. 6000 ; Number range: 1 - 16.000

6ES7414-5HM06-0AB0 Page 2

Date:07/27/2012

subject to modifications© Copyright Siemens AG 201232

Page 6 of 43

Abdel-Hamed El-Deeb
Highlight
Page 7: UPS Calculation

productdatablad 6ES7960-1AA06-0XA0

-

SIMATIC S7-400H,SYNC SUBMODULE V6 FOR PATCH CABLES UP TO 10M

Input current

from CPU, max. 220 mA

Power losses

Power loss, typ. 0,77 W

Dimensions

Breedte 13 mm

Hoogte 14 mm

Diepte 58 mm

Weight

Weight, approx. 14 g

Status 6-jul-2013

6ES7960-1AA06-0XA0Page 1/ 20.07.2013

subject to modifications© Copyright Siemens AG 20131

Page 7 of 43

Abdel-Hamed El-Deeb
Highlight
Page 8: UPS Calculation

Input current

Rated value at 110 V DC 1 A ; at 120 V DC

Rated value at 230 V DC 0.5 A

Rated value at 120 V AC 0.9 A

Rated value at 230 V AC 0.5 A

Inrush current, max. 63 A ; Full width at half maximum 1 ms

Output voltage

Rated value, 5 V DC Yes

Rated value, 24 V DC Yes

Output current

for backplane bus (5 V DC), max. 10 A ; no base load required

for backplane bus (24 V DC), max. 1 A ; idling-proof

Short-circuit protection Yes

Power

Power consumption, typ. 95 W

Power losses

Power loss, typ. 20 W

Backup battery

Backup battery

Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah

Galvanic isolation

primary/secondary Yes

EMC

Compliance with line harmonic distortion limits

Observance of line harmonic distortion acc. to IEC61000-3-2, IEC 61000-3-3

Yes

Degree and class of protection

Protection class 1 ; with protective conductor

Standards, approvals, certificates

FM approval Yes ; Ta: 0 °C to 60 °C T4

Connection method

Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve,external diameter 3 to 9 mm

Dimensions

6ES7407-0KA02-0AA0 Page 2

Date:06/28/2012

subject to modifications© Copyright Siemens AG 2012

26

Page 8 of 43

Abdel-Hamed El-Deeb
Highlight
Page 9: UPS Calculation

Attenuation / of fiber-optic cable transmission link / minimumnecessary

0 dB

Range / at the optical interface / depending on the optical fiber used 0 … 5 km

design of the removable storage / C-PLUG Yes

Inputs/outputs

Operating voltage / of signaling contacts / at DC / rated value 24 V

Operating current / of signaling contacts / at DC / maximum 0.1 A

Supply voltage, current consumption, power loss

Type of voltage / of supply voltage DC

Supply voltage / external 24 V

• minimum 18 V

• maximum 32 V

Product component / fusing at power supply input Yes

Type of fusing / at input for supply voltage 0,6 A / 60 V

Consumed current / maximum 0.265 A

Active power loss / at 24 V / for DC 6.36 W

Permitted ambient conditions

Ambient temperature

• during operating -40 … +60 °C

• during storage -40 … +70 °C

• during transport -40 … +70 °C

Relative humidity / at 25 °C / without condensation / during operating/ maximum

95 %

Protection class IP IP30

Design, dimensions and weight

Design compact

Width 60 mm

Height 125 mm

Depth 124 mm

Net weight 0.78 kg

Type of mounting

• 35 mm DIN rail mounting Yes

• wall mounting Yes

• S7-300 rail mounting Yes

Product properties, functions, components / general

Cascading in the case of a redundant ring / at reconfiguration time of<\~0.3\~s

50

Cascading in cases of star structuring Any (depending only on signal propagation time)

Product function

• CLI Yes

6GK5204-2BB10-2AA3Page 2/ 12/03/2012

subject to modifications© Copyright Siemens AG 20124

108 Page 9 of 43

Abdel-Hamed El-Deeb
Highlight
Page 10: UPS Calculation

I²t 0.1 A²·s

Output voltage

Rated value, 5 V DC Yes

Output current

for backplane bus (5 V DC), max. 1.5 A

Power losses

Power loss, typ. 5.5 W

Address area

Addressing volume

Outputs 244 byte

Inputs 244 byte

Hardware configuration

Number of modules per DP slave interface, max. 12

Time stamping

Accuracy 1 ms ; 1ms at up to 8 modules; 10ms at up to 12modules

Number of message buffers 15

Messages per message buffer 20

Number of stampable digital inputs, max. 128 ; Max. 128 signals/station; max. 32 signals/slot

Time format RFC 1119

Time resolution 0.466 ns

Time interval for transmitting the message buffer if amessage is present

1000 ms

Time stamp on signal change rising / falling edge as signal entering or exiting

Interfaces

Interface physics, RS 485 Yes

Interface physics, FOC No

PROFIBUS DP

Node addresses 1 to 125 permitted

Automatic detection of transmission speed Yes

PROFIBUS DP, output current, max. 70 mA

Transmission procedure RS 485

Transmission rate, max. 12 Mbit/s

SYNC capability Yes

6ES7153-2BA02-0XB0 Page 2

Date:02/14/2012

subject to modifications© Copyright Siemens AG 2012

60

Page 10 of 43

Abdel-Hamed El-Deeb
Highlight
Page 11: UPS Calculation

Product data sheet 6ES7331-1KF02-0AB0

SIMATIC S7-300, ANALOG INPUT SM 331,OPTICALLY ISOLATED, 8 AI,13 BIT RESOLUTION,U/I/RESISTANCE/PT100, NI100, NI1000,LG-NI1000, PTC / KTY,66 MS MODULE UPDATE, 1 X 40 PIN

Input current

from backplane bus 5 V DC, max. 90 mA

Power losses

Power loss, typ. 0.4 W

Analog inputs

Number of analog inputs 8

Number of analog inputs for resistancemeasurement

8

permissible input voltage for voltage input(destruction limit), max.

30 V ; 12 V continuous, 30 V for max. 1 s

permissible input current for current input(destruction limit), max.

40 mA

Input ranges

Voltage Yes

Current Yes

Thermocouple No

6ES7331-1KF02-0AB0 Page 1

Date:01/09/2012

subject to modifications© Copyright Siemens AG 2012

73

6ES7331-1KF02-0AB0

Page 11 of 43

Abdel-Hamed El-Deeb
Highlight
Page 12: UPS Calculation

Product data sheet 6ES7321-1BL00-0AA0

SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED 32DI, 24 V DC,1 X 40 PIN

Supply voltage

Load voltage L+

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 15 mA

Power losses

Power loss, typ. 6.5 W

Digital inputs

Number/binary inputs 32

Input characteristic curve acc. to IEC 61131, Type 1 Yes

Number of simultaneously controllable inputs

horizontal installation

up to 40 °C, max. 32

6ES7321-1BL00-0AA0 Page 1

Date:01/29/2012

subject to modifications© Copyright Siemens AG 201265-1

6ES7321-1BL00-0AA0

Page 12 of 43

Abdel-Hamed El-Deeb
Highlight
Page 13: UPS Calculation

Product data sheet 6ES7322-1BL00-0AA0

SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 32DO, 24V DC, 0.5A,1 X 40 PIN,SUM OF OUTPUT CURRENTS 4A/GROUP(16A/MODULE)

Supply voltage

Load voltage L+

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from load voltage L+ (without load), max. 160 mA

from backplane bus 5 V DC, max. 110 mA

Power losses

Power loss, typ. 6.6 W

Digital outputs

Number/binary outputs 32

Limitation of inductive shutdown voltage to L+ (-53 V)

Lamp load, max. 5 W

Load resistance range

6ES7322-1BL00-0AA0 Page 1

Date:01/29/2012

subject to modifications© Copyright Siemens AG 2012

69-1

6ES7322-1BL00-0AAAAA0

Page 13 of 43

Abdel-Hamed El-Deeb
Highlight
Page 14: UPS Calculation

Product data sheet 6ES7197-1LA04-0XA0

-

SIMATIC S7-400H,Y-LINK FOR CONNECTING SINGLE-CHANNEL DPSLAVES TO S7-400H BASED ON IM153-BA02 (NOT FITFOR PCS7 V6.1)

Dimensions

Width 40 mm

Height 125 mm

Depth 130 mm

Status Jul 1, 2013

6ES7197-1LA04-0XA0Page 1/ 07/20/2013

subject to modifications© Copyright Siemens AG 20131

Page 14 of 43

Page 15: UPS Calculation

Product data sheet 6ES7332-5HF00-0AB0

SIMATIC S7-300, ANALOG OUTPUT SM 332,OPTICALLY ISOLATED, 8 AO, U/I;DIAGNOSTICS;RESOLUTION 11/12 BITS, 40 PIN,REMOVE/INSERT W. ACTIVE, BACKPLANE BUS

Supply voltage

Load voltage L+

Rated value (DC) 24 V

Input current

from load voltage L+ (without load), max. 340 mA

from backplane bus 5 V DC, max. 100 mA

Power losses

Power loss, typ. 6 W

Analog outputs

Number of analog outputs 8

Voltage output, short-circuit protection Yes

Voltage output, short-circuit current, max. 25 mA

Current output, no-load voltage, max. 18 V

Output ranges, voltage

0 to 10 V Yes

6ES7332-5HF00-0AB0 Page 1

Date:02/09/2012

subject to modifications© Copyright Siemens AG 2012

85

6ES7332-5HF00-0AB0

Page 15 of 43

Abdel-Hamed El-Deeb
Highlight
Page 16: UPS Calculation

Product data sheet 6ES7321-1BH02-0AA0

SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED, 16DI, 24 V DC,1 X 20 PIN

Supply voltage

Load voltage L+

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 10 mA

Power losses

Power loss, typ. 3.5 W

Digital inputs

Number/binary inputs 16

Input characteristic curve acc. to IEC 61131, Type 1 Yes

Number of simultaneously controllable inputs

horizontal installation

up to 60 °C, max. 16

6ES7321-1BH02-0AA0 Page 1

Date:02/12/2012

subject to modifications© Copyright Siemens AG 2012

66-1

6ES7321-1BH02-0AA0

Page 16 of 43

Abdel-Hamed El-Deeb
Highlight
Page 17: UPS Calculation

Product data sheet 6ES7322-1BH01-0AA0

SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 16 DO, 24V DC,0.5A,1 X 20 PIN SUM OF OUTPUT CURRENTS4A/GROUP (8A/MODULE)

Supply voltage

Load voltage L+

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from load voltage L+ (without load), max. 80 mA

from backplane bus 5 V DC, max. 80 mA

Power losses

Power loss, typ. 4.9 W

Digital outputs

Number/binary outputs 16

Limitation of inductive shutdown voltage to L+ (-53 V)

Lamp load, max. 5 W

Load resistance range

6ES7322-1BH01-0AA0 Page 1

Date:02/12/2012

subject to modifications© Copyright Siemens AG 2012

70-1

6ES7322-1BH01-0AAAAA0

Page 17 of 43

Abdel-Hamed El-Deeb
Highlight
Page 18: UPS Calculation

for backplane bus (24 V DC), max. 1 A ; idling-proof

Short-circuit protection Yes

Power

Power consumption, typ. 95 W

Power losses

Power loss, typ. 20 W

Battery

Backup battery

Backup battery

Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah

Galvanic isolation

primary/secondary Yes

Degree and class of protection

Protection class 1 ; with protective conductor

Standards, approvals, certificates

FM approval Yes ; Ta: 0 °C to 60 °C T4

Connection method

Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve, externaldiameter 3 to 9 mm

Dimensions

Width 50 mm

Height 290 mm

Depth 217 mm

Required slots 2

Weight

Weight, approx. 1200 g

Status Jul 11, 2013

6ES7405-0KA02-0AA0Page 2/ 07/16/2013

subject to modifications© Copyright Siemens AG 20132

Page 18 of 43

Abdel-Hamed El-Deeb
Highlight
Page 19: UPS Calculation

Product data sheet 6ES7412-3HJ14-0AB0

-

SIMATIC S7-400H,CPU 412-3H CENTRAL UNIT FOR S7-400H AND S7-400F/FH,3 INTERFACES: 1 MPI/DP AND 2 FOR SYNC MODULES768 KB MEMORY (256 KB DATA/512 KB CODE)

General information

Hardware product version 1

Firmware version V4.5

Engineering with

Programming package STEP7 V 5.3 SP2 or higher with HW update

CiR - Configuration in RUN

CiR synchronization time, basic load 150 ms

CiR synchronization time, time per I/O slave 40 μs

Supply voltage

24 V DC No ; Power supply via system power supply

Input current

from backplane bus 5 V DC, typ. 1.2 A

from backplane bus 5 V DC, max. 1.5 A

from backplane bus 24 V DC, max. 150 mA ; Per DP interface

from interface 5 V DC, max. 90 mA ; At each DP interface

Power losses

Power loss, typ. 5.5 W

Memory

6ES7412-3HJ14-0AB0Page 1/ 07/16/2013

subject to modifications© Copyright Siemens AG 201310

Page 19 of 43

Abdel-Hamed El-Deeb
Highlight
Page 20: UPS Calculation

Product data sheet 6ES7960-1AA04-0XA0

-

SIMATIC S7-400H,SYNC SUBMODULE V4 FOR PATCH CABLES UP TO 10M

Input current

from CPU, max. 210 mA

Power losses

Power loss, typ. 1.1 mW

Dimensions

Width 25 mm

Height 53 mm

Depth 140 mm

Weight

Weight, approx. 65 g

Status Jul 6, 2013

6ES7960-1AA04-0XA0Page 1/ 07/16/2013

subject to modifications© Copyright Siemens AG 20131

Page 20 of 43

Abdel-Hamed El-Deeb
Highlight
Page 21: UPS Calculation

• Note > 60 °C Derating

delivered active power / typ. 120 W

constant overload current / at short-circuit during run-up / typical

5.5 A

short-term overload current / at short-circuit duringoperation / typical

15 A

Duration of overloading ability for excess current / onshort-circuiting during the operational phase

25 ms

Parallel switching for enhanced performance Yes

• Note switchable characteristic

Numbers of parallel switchable units for enhancedperformance

2

Efficiency

Efficiency at Vout rated, Iout rated, approx. 87 %

Power loss at Vout rated, Iout rated, approx. 18 W

Closed-loop control

Dynamic mains compensation (Vin rated ±15 %), max. 0.1 %

Dynamic load smoothing (Iout: 50/100/50 %), Uout ±typ.

3 %

Load step setting time 50 to 100%, typ. 2 ms

Load step setting time 100 to 50%, typ. 2 ms

Setting time / maximum 5 ms

Protection and monitoring

Output overvoltage protection < 35 V

Current limitation, typ. 5.5 A

Characteristic feature of the output / short-circuitprotected

Yes

Short-circuit protection Alternatively, constant current characteristic approx.5.5 A or latching shutdown

Enduring short circuit current / Effective level / typical 5.5 A

Overload/short-circuit indicator LED yellow for "overload", LED red for "latchingshutdown"

Safety

Primary/secondary isolation Yes

Potential separation Safety extra low output voltage Vout according to EN60950-1 and EN 50178

6EP1333-3BA00 Page 3

Date:02/09/2012

subject to modifications© Copyright Siemens AG 2012

12

Page 21 of 43

Abdel-Hamed El-Deeb
Highlight
Page 22: UPS Calculation

I²t 0.1 A²·s

Output voltage

Rated value, 5 V DC Yes

Output current

for backplane bus (5 V DC), max. 1.5 A

Power losses

Power loss, typ. 5.5 W

Address area

Addressing volume

Outputs 244 byte

Inputs 244 byte

Hardware configuration

Number of modules per DP slave interface, max. 12

Time stamping

Accuracy 1 ms ; 1ms at up to 8 modules; 10ms at up to 12modules

Number of message buffers 15

Messages per message buffer 20

Number of stampable digital inputs, max. 128 ; Max. 128 signals/station; max. 32 signals/slot

Time format RFC 1119

Time resolution 0.466 ns

Time interval for transmitting the message buffer if amessage is present

1000 ms

Time stamp on signal change rising / falling edge as signal entering or exiting

Interfaces

Interface physics, RS 485 Yes

Interface physics, FOC No

PROFIBUS DP

Node addresses 1 to 125 permitted

Automatic detection of transmission speed Yes

PROFIBUS DP, output current, max. 70 mA

Transmission procedure RS 485

Transmission rate, max. 12 Mbit/s

SYNC capability Yes

6ES7153-2BA02-0XB0 Page 2

Date:02/14/2012

subject to modifications© Copyright Siemens AG 2012

60

Page 22 of 43

Abdel-Hamed El-Deeb
Highlight
Page 23: UPS Calculation

73

Page 23 of 43

Abdel-Hamed El-Deeb
Highlight
Page 24: UPS Calculation

• for glass FOC with 50/125 μm / at 3 dB/km / maximum 10 dB

• for glass FOC with 62.5/125 μm

• at 3.5 dB/km / maximum 12 dB

Signal delay time in bit time 6.5 bit

Injectable optical power relating to 1 mW

• for glass FOC with 50/125 μm / at 3 dB/km -16 dB

• for glass FOC with 62.5/125 μm

• at 3.5 dB/km -13 dB

Optical sensitivity relating to 1 mW

• for glass FOC with 50/125 μm / at 3 dB/km -28 dB

• for glass FOC with 62.5/125 μm

• at 3.5 dB/km -28 dB

Wavelength

• for glass FOC with 50/125 μm / compatible with interface / at 3dB/km

860 nm

• for glass FOC with 62.5/125 μm / compatible with interface

• at 3.5 dB/km 860 nm

Cable length

• for glass FOC with 50/125 μm / at 3 dB/km / maximum 3 km

• for glass FOC with 62.5/125 μm at 3.5 dB/km maximum

• 3 km

Inputs/outputs

Operating voltage / of signaling contacts / at DC / rated value 24 V

Operating current / of signaling contacts / at DC / maximum 0.1 A

Supply voltage, current consumption, power loss

Type of voltage / of supply voltage DC

Supply voltage / for DC

• rated value 24 V

• minimum 18.8 V

• maximum 28.8 V

Product component / fusing at power supply input Yes

Consumed current / At 24 V / with DC / maximum 0.2 A

Permitted ambient conditions

Ambient temperature

• during operating 0 … 60 °C

• during storage -40 … +70 °C

• during transport -40 … +70 °C

Relative humidity

• at 25 °C / without condensation / during operating / maximum 95 %

Protection class IP IP40

6GK1503-3CB00Page 2/ 07/16/2013

subject to modifications© Copyright Siemens AG 20133

0.2 AAt 24 V

Page 24 of 43

Page 25: UPS Calculation

32.8

29 12.4

20

4.75 0.5 4.75

6.5

46.52 46.61

• 2 Pole CO, 8 A• Plug-in/Solder terminals

2 CO (DPDT)

8/15

250/440

2,000

350

0.37

6/0.5/0.15

300 (5/5)

AgNi

1.2/0.5

(0.8...1.1)UN

(0.73...1.1)UN

0.8UN /0.4UN

0.2UN /0.1UN

10 · 106

100 · 103

10/3

6 (8 mm)

1,000

–40 ... +70

RT II

Contact specification

Contact configuration

Rated current/Maximum peak current A

Rated voltage/Maximum switching voltage V AC

Rated load AC1 VA

Rated load AC15 (230 V AC) VA

Single phase motor rating (230 V AC) kW

Breaking capacity DC1: 30/110/220 V A

Minimum switching load mW (V/mA)

Standard contact material

Coil specification

Nominal voltage (UN) V AC (50/60 Hz)

V DC

Rated power VA/W

Operating range AC

DC

Holding voltage AC/DC

Must drop-out voltage AC/DC

Technical data

Mechanical life AC/DC cycles

Electrical life at rated load AC1 cycles

Operate/release time ms

Insulation between coil and contacts (1.2/50 μs)kV

Dielectric strength between open contacts V AC

Ambient temperature range °C

Environmental protection

Approvals (according to type)

Features1 & 2 Pole relay range

46.52 - 2 Pole 8 A46.61 - 1 Pole 16 A

• Socket mount or direct connection via Fastonconnectors

• AC coils & DC coils• Available with: lockable test button,

mechanical indicator & LED indicator• 8 mm, 6 kV (1.2/50 μs) isolation, coil-contacts• Cadmium Free contacts

• 1 Pole CO, 16 A• Plug-in/Faston 187

1 CO (SPDT)

16/25

250/440

4,000

750

0.55

12/0.5/0.15

300 (5/5)

AgNi

1.2/0.5

(0.8...1.1)UN

(0.73...1.1)UN

0.8UN /0.4UN

0.2UN /0.1UN

10 · 106

100 · 103

15/5

6 (8 mm)

1,000

–40 ... +70

RT II

12 - 24 - 48 - 110 - 120 - 230 - 240

12 - 24 - 48 - 110 - 125

1

46.52

46.61

FOR UL HORSEPOWER AND PILOT DUTY RATINGSSEE “General technical information” page V

46 Series - Miniature industrial relays 8 - 16 A

138

46.52

2 Pole CO, 8 A•

Plug-in/Solder terminals•

/0.5

Page 25 of 43

Abdel-Hamed El-Deeb
Highlight
Abdel-Hamed El-Deeb
Highlight
Page 26: UPS Calculation

Proline Promag 50W, 53W

10 Endress+Hauser

A0003194

a Signal cableb Coil current cable

1 Core2 Core insulation3 Core shield4 Core jacket5 Core reinforcement6 Cable shield7 Outer jacket

Operation in zones of severe electrical interference

The measuring device complies with the general safety requirements in accordance with EN 61010 and

the EMC requirements of IEC/EN 61326 and NAMUR recommendation NE 21.

" Caution!

Grounding is by means of the ground terminals provided for the purpose inside the connection housing.

Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible.

Power consumption • AC: < 15 VA (incl. sensor)

• DC: < 15 W (incl. sensor)

Switch-on current:

• Max. 3 A (< 5 ms) for 260 V AC

• Max. 13.5 A (< 50 ms) for 24 V DC

Power supply failure Lasting min. ½ cycle frequency: EEPROM saves measuring system data

• EEPROM or T-DAT (Promag 53 only) retain the measuring system data in the event of a power supply failure

• S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal diameter, serial number,

calibration factor, zero point etc.)

1234567

a b

Page 26 of 43

Abdel-Hamed El-Deeb
Highlight
Page 27: UPS Calculation

Nivotester FTL 325 N

8 Endress+Hauser

Power supplyElectrical connection Terminal blocks

The removable terminal blocks are separated into intrinsically safe connections (at top of the instrument) and non-instrinsically safe connections (at bottom of the instrument). Also, the terminal blocks have different colours to make them more easily recognisable. Blue for the intrinsically safe section and grey for the non-intrinsically safe section. This difference helps to ensure safe wiring.

Connecting the measuring sensor

(at upper, blue terminal blocks)The two-wire connecting line between the Nivotester FTL 325 N and the Liquiphant, Nivopuls or Soliphant measuring sensor can be either a commercially available installation cable or wires in a multi-wire cable for measuring purposes. Line resistance may be a maximum of 25 Ω per wire.If strong electromagnetic interference is expected, e.g. from machines or radio devices, a screened cable must be used. Only connect the screen to the ground connection, and not to the Nivotester.

Using the measuring sensor in explosion hazardous areas

Please observe all local regulations on explosion protection concerning the type and installation of intrinsically safe signal cabling. Please refer to the Safety Instructions XA 134F for maximum permissible values of capacitance and inductance.

Connecting signal and control devices

(at lower, grey terminal blocks)The relay function is dependent on the level and fail-safe circuit.If an instrument is connected at high inductance (e.g. contactor, solenoid valve etc.), a spark suppressor must be installed to protect the relay contact.

Connecting the supply voltage

(at lower, grey terminal blocks)For voltage variants, see the Ordering Information on page 14.A fuse is built into the supply current circuit. This obviates the need to connect a fine-wire fuse in series. The Nivotester is equipped with reverse polarity protection.

Supply voltage AC version:

• Voltage ranges: 85...253 V AC, 50/60 Hz

DC version:

• Voltage ranges: 20...30 V AC / 20...60 V DC• DC supply: max. 60 mA (1-channel)• DC supply: max. 115 mA (3-channel)• Permissible residual ripple within tolerance: Uss = max. 2 V

The Nivotester is equipped with reverse polarity protection.

Power consumption AC

1-channel: max. 1.75 W3-channel: max. 2.75 W

DC

1-channel: max. 1.2 W (bei Umin 20 V)3-channel: max. 2.25 W (bei Umin 20 V)

Page 27 of 43

Abdel-Hamed El-Deeb
Highlight
Page 28: UPS Calculation

Prosonic S FMU90

10 Endress + Hauser

PROFIBUS DP interface

Auxiliary energy

Supply voltage/Power consumption/Current consumption

Galvanic isolation The following terminals are galvanically isolated from each other:

• auxiliary energy

• sensor inputs

• analogue output 1

• analogue output 2

• relay outputs

• bus connection (PROFIBUS DP)

Fuse • 2 A T /DC

• 400 mA T /AC

accesible in the terminal compartment

Profile 3.0

Transmittable values • main value (level or flow, depending on the instrument version)

• distances

• counters

• temperatures

• average/difference/sum

• relay states

• rake control

• pump control

Function blocks • 10 Analog Input Blocks (AI)

• 10 Digital Input Blocks (DI)

• 10 Digital Output Blocks (DO)

Supported baud rates • 9.6 kbaud

• 19.2 kbaud

• 45,45 kbuad

• 93.75 kbaud

• 187.5 kbaud

• 500 kbaud

• 1.5 Mbaud

• 3 Mbaud

• 6 Mbaud

• 12 Mbaud

Service Access Points (SAPs) 1

ID number 1540 (hex) 1540 (hex) = 5440 (dec)

GSD file EH3x1540.gsd

Addressing via dip switches at the instrument or via software (e.g. FieldCare)

Default address: 126 per software

Termination can be activated/deactivated in the instrument

Locking The device can be locked by hardware or software.

Instrument version Supply voltage Power consumption Current consumption

AC voltage

(FMU90 - ****A****)90 ... 253 VAC (50/60 Hz) max. 23 VA max. 100 mA at 230 VAC

DC voltage

(FMU90 - ****B****)10,5 ... 32 VDC max. 14 W (typically 8 W) max. 580 mA at 24 VDC

Page 28 of 43

Abdel-Hamed El-Deeb
Highlight
Page 29: UPS Calculation

Cerabar M PMC51, PMP51, PMP55

Endress+Hauser 19

FOUNDATION Fieldbus

• Version for non-hazardous areas: 9 to 32 V DC

Start-up current HART 12 mA or 22 mA (selectable)

Current consumption • PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

• FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Cable entry ä 75 ff, feature 50 "Electrical connection".

Cable specification • Endress+Hauser recommends using twisted, shielded two-wire cables.

• Terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)

• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)

Residual ripple No influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range [according to

HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]

Influence of power supply 0.001% of URL/1 V

Page 29 of 43

Abdel-Hamed El-Deeb
Highlight
Page 30: UPS Calculation

Deltabar S

18 Endress+Hauser

Supply voltage Note!

• When using the measuring device in hazardous areas, installation must comply with the corresponding

national standards and regulations and the Safety Instructions or Installation or Control Drawings.

• All explosion protection data are given in separate documentation which is available upon request. The

Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.

ä 85, "Safety Instructions" and "Installation/Control Drawings" sections.

4 to 20 mA HART

• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position

(delivery status): 11.5 to 45 V DC

• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position:

10.5 to 45 V DC

PROFIBUS PA

• Version for non-hazardous areas: 9 to 32 VDC

FOUNDATION Fieldbus

• Version for non-hazardous areas: 9 to 32 V DC

Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Cable entry ä 69 ff, feature 30 "Housing; Cable entry; Protection".

Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables.

• Terminals for core cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)

• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)

Residual ripple Without influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range

[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]

Influence of power supply 0.0006% of URL/1 V

Page 30 of 43

Abdel-Hamed El-Deeb
Highlight
Page 31: UPS Calculation

Power requirement 220 VAC Power consumption: 0.48 Watts Analog outputs: 4-20mA isolated Analog loop resistance: 500 Ohms, nominally @ 24V Alarms: Optional Certification: Available upon request

Mechanical

Transmitter weight: 3 lbs. Enclosure: Extruded aluminum (optional NEMA or purged enclosures) 8" H x 3-7/8" W x 1-1/2" D

UV Lamp

Type: Xenon flash lamp Wavelength range: 200 - 650 nm Lamp Life: Typically 3 years Size: 2" H x 4" W x 1-1/2" D Power requirements: 24 VDC (9-32 VDC)

6650 UVF Probe

Materials: 316SS Max temperature rating: 315.5° C (600° F) Max pressure rating: 5000 psig

Sample Conditioning System

All wetted parts of SCS components will be SS316 Ultrasonic Homogenizer for sample mix Sample shut off valve Sample and fast loop bypass Pressure regulator with viewing gauge Sample flow meter with precision needle valves Extra Cuno filter

Mounting:

NEMA 4 (IP65) free standing enclosure

Area Class

Ex”d” certified Enclosure for Class 1 Div 2

Page 31 of 43

Abdel-Hamed El-Deeb
Highlight
Page 32: UPS Calculation

Liquistation CSF34

22 Endress+Hauser

Mains fuse Optional fuses on DIN rail• T10A (for 24V power supply)• T3.15A (for 230V power supply)• T10A (fuse for battery backup)

Power consumption • Version with vacuum pump: 290 VA• Version with peristaltic pump: 290 VA

Power failure • Power supply via battery (optional): 2 x 12 V, 7.2 Ah, with additional charge controller

Replace batteries with battery type Panasonic LC-R127R2PG1.

• Real-time clock: lithium battery, type CR2032

Performance characteristicsSampling methods Vacuum pump / peristaltic pump:

• Event sampling• Single and multiple samples• Sampling table

Vacuum pump:• In proportion to time• In proportion to volume

Peristaltic pump:• In proportion to time• In proportion to volume• In proportion to flow

Dosing volume • Vacuum pump:20 to 350 ml (0.7 to 12 fl.oz.)

• Peristaltic pump:10 to 10,000 ml (0.3 to 340 fl.oz.)

A sample volume < 20 ml can vary in dosing accuracy and repeatability, depending on the application.

Dosing accuracy • Vacuum pump:±5 ml (0.17 fl.oz.) or 5 % of the set volume

• Peristaltic pump:±5 ml (0.17 fl.oz.) or 5 % of the set volume

Repeatability • Vacuum pump: 5 %• Peristaltic pump: 5 %

Intake speed > 0.5 m/s (> 1.6 ft/s) for 13 mm (1/2") ID, in accordance with EN 25667, ISO 5667> 0.6 m/s (> 1.9 ft/s) for 10 mm (3/8") ID, in accordance with Ö 5893 (Austrian standard); US EPA

Suction height Max. 8 m (26 ft)

Hose length Max. 30 m (98 ft)

Page 32 of 43

Abdel-Hamed El-Deeb
Highlight
Abdel-Hamed El-Deeb
Highlight
Page 33: UPS Calculation

Cerabar S

18 Endress+Hauser

Supply voltage Note!

• When using the measuring device in hazardous areas, installation must comply with the corresponding

national standards and regulations and the Safety Instructions or Installation or Control Drawings.

• All explosion protection data are given in separate documentation which is available upon request. The

Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.

ä 89 ff, "Safety Instructions" and "Installation/Control Drawings" sections.

4 to 20 mA HART

• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position

(delivery status): 11.5 to 45 V DC

• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position:

10.5 to 45 V DC

PROFIBUS PA

• Version for non-hazardous areas: 9 to 32 V DC

FOUNDATION Fieldbus

• Version for non-hazardous areas: 9 to 32 V DC

Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Cable entry ä 76 ff, feature 30 "Housing; Cable entry; Protection".

Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables.

• Terminals for core cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)

• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)

Residual ripple Without influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range

[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]

Influence of power supply 0.0006% of URL/1 V

Page 33 of 43

Abdel-Hamed El-Deeb
Highlight
Page 34: UPS Calculation

Page 34 of 43

eldeeb91
Rectangle
Page 35: UPS Calculation

Liquiline CM442

10 Endress+Hauser

Cable specification

Power consumption Depending on supply voltage

• 100 to 230 V AC and 24 V AC:

Max. 55 VA

• 24 V DC:

Max. 22 W

Fuse For all versions:5x20 mm, 250 V, 4.0 A, slow-blow (T4.0A)

Performance characteristics

Response time Current outputs

t90 = max. 500 ms for an increase from 0 to 20 mA

Reference temperature 25 C (77 F)

Maximum measured error of inputs

--> Documentation of the connected sensor

Maximum measured error of current outputs

< 20 A at 4 mA

< 50 A at 20 mA

at 25 C (77 F) each

Additional measured error depending on the temperature:

< 1.5 A/K

Resolution of current output < 5 A

Repeatability --> Documentation of the connected sensor

Cable gland Permitted cable diameter

M16x1.5 mm 4 to 8 mm (0.16 to 0.32")

M12x1.5 mm 2 to 5 mm (0.08 to 0.20")

M20x1.5 mm 6 to 12 mm (0.24 to 0.48")

NPT3/8" 4 to 8 mm (0.16 to 0.32")

G3/8 4 to 8 mm (0.16 to 0.32")

NPT1/2" 6 to 12 mm (0.24 to 0.48")

G1/2 7 to 12 mm (0.28 to 0.47")

Page 35 of 43

Abdel-Hamed El-Deeb
Highlight
Page 36: UPS Calculation

Limit reed switch ZE 951 for DFM 165 - 350bistable

Advantage• reliable limit value determination using reed switches• direct power control of consumers with contact protection relay

ZE 3061• 2-point control for monostable switches with ZE 3060• freely adjustable flow limit value - fastened with a clamping

piece to the measuring tube dovetail guide• reliable, simple installation, easy to retrofit in existing plants

Description• The limit reed switch ZE 951 serves as signal transmitters of the

flow values. They are clamped to the dovetail guides and signalwhen the magnetic float in the measuring tube has reached orexceeded the signal transmitter position. As soon as thishappens, a contact in the signal transmitter, as the actualswitching element (reed switch), opens or closes.

Function• Type ZE 951 bistable (normally open contact/normally closed

contact) The contact is closed (normally open contact) or opened(normally closed contact), as soon as the magnetic float movesup from below or is at the direct height of the signal transmitter.If the float goes above the signal transmitter, the switching stateremains unaffected. The switching state is only cancelled if thefloat goes below the signal transmitter.

Body• ABS

Connector Plug• according to DIN EN 175301-803

Voltage• 2 V C

Switching Current• max. 0,5 A

Electric Switching Capacity• max. 10 VA

Resistance• < 150 mOhm

Insulation Resistance• > 1010 Ohm

Ambient Temperature• 0°C to +55°C

Hysteresis• 10 mm

Type Of Protection• IP 65 with mounted connector plug

Connection Cable• nominal cross-section: 1.5 mm²• cable outside diameter: 4…6 mm

Pin Assignment• the polarity of the connections has no influence on the function

Colour• anthracite grey

Accessories• 2-Point Control Unit ZE 3060 (Article number 136245, 1326244)• Contact Protection Relay ZE 3061 (Article number 136240,

136239)

1All rights for technical modifications withheld> data sheet no.: 330207 - 2010/05/05ASV Stübbe GmbH & Co. KG · Hollwieser Str. 5 · D-32602 Vlotho · Tel. +49(0)5733. 799-0 · Fax +49(0)5733. 799-5000 · [email protected] · www.asv-stuebbe.de

• 22 VV C

ZE 951 for DFM 165 - 350

Page 36 of 43

Page 37: UPS Calculation

Current output to backplane bus (DC 5 V), max. 1600 mA ; Max. 5 V DC for SM and CM

Power losses

Power loss, typ. 12 W

Memory

Usable memory for user data 75 kbyte

Work memory

integrated 75 kbyte

expandable No

Load memory

integrated 4 Mbyte

Backup

present (maintenance-free)

without battery Yes

CPU processing times

for bit operations, typ. 0.085 µs ; / instruction

for word operations, typ. 1.7 µs ; / instruction

for floating point arithmetic, typ. 2.5 µs ; / instruction

CPU-blocks

Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number ofaddressable blocks ranges from 1 to 65535. There is no restriction,the entire working memory can be used

OB

Number, max. Limited only by RAM for code

Data areas and their retentivity

retentive data area in total (incl. times, counters, flags), max. 10 kbyte

Flag

Number, max. 8 kbyte ; Size of bit memory address area

Address area

I/O address area

I/O address area, overall 1024 bytes for inputs / 1024 bytes for outputs

Process image

Inputs, adjustable 1 kbyte

Outputs, adjustable 1 kbyte

Hardware configuration

Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules

Time of day

Clock

Hardware clock (real-time clock) Yes

6ES7214-1AG31-0XB0Page 2/ 07/20/2013

subject to modifications© Copyright Siemens AG 20138

Page 37 of 43

Abdel-Hamed El-Deeb
Highlight
Page 38: UPS Calculation

Product data sheet 6ES7221-1BH30-0XB0

-

SIMATIC S7-1200, DIGITAL INPUT SM 1221,16 DI, 24VDC, SINK/SOURCE INPUT

Supply voltage

24 V DC Yes

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 130 mA

Digital inputs

from load voltage L+ (without load), max. 4 mA ; per channel

Output voltage

Power supply to the transmitters

present Yes

Power losses

Power loss, typ. 2.5 W

Digital inputs

Number/binary inputs 16

In groups of 4

Input characteristic curve acc. to IEC 61131, Type 1 Yes

Number of simultaneously controllable inputs

6ES7221-1BH30-0XB0Page 1/ 07/20/2013

subject to modifications© Copyright Siemens AG 20133

Page 38 of 43

Abdel-Hamed El-Deeb
Highlight
Page 39: UPS Calculation

Product data sheet 6ES7222-1BH30-0XB0

-

SIMATIC S7-1200,DIGITAL OUTPUT SM 1222, 16 DO, 24V DC,TRANSISTOR 0.5A

Supply voltage

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 140 mA

Power losses

Power loss, typ. 2.5 W

Digital inputs

Number/binary inputs 0

Digital outputs

Number/binary outputs 16

In groups of 1

Functionality/short-circuit strength No ; to be provided externally

Limitation of inductive shutdown voltage to typ. (L+) -48 V

Switching capacity of the outputs

with resistive load, max. 0.5 A

on lamp load, max. 5 W

Output voltage

6ES7222-1BH30-0XB0Page 1/ 07/20/2013

subject to modifications© Copyright Siemens AG 20133

Page 39 of 43

Abdel-Hamed El-Deeb
Highlight
Page 40: UPS Calculation

Product data sheet 6ES7231-4HF30-0XB0

-

SIMATIC S7-1200, ANALOG INPUT, SM 1231,8 AI, +/-10V, +/-5V, +/-2.5V,OR 0-20 MA 12 BIT + SIGN OR (13 BIT ADC)

Supply voltage

24 V DC Yes

Input current

Current consumption, typ. 45 mA

from backplane bus 5 V DC, typ. 90 mA

Power losses

Power loss, typ. 1.5 W

Analog inputs

Number of analog inputs 8 ; Current or voltage differential inputs

permissible input frequency for current input (destruction limit),max.

± 35 V

permissible input voltage for voltage input (destruction limit), max. 35 V

permissible input current for voltage input (destruction limit), max. 40 mA

permissible input current for current input (destruction limit), max. 40 mA

Cycle time (all channels) max. 625 µs

Input ranges

Voltage Yes ; ±10 V, ±5 V, ±2.5 V

Current Yes ; 0 to 20 mA

Thermocouple No

6ES7231-4HF30-0XB0Page 1/ 07/20/2013

subject to modifications© Copyright Siemens AG 20134

Page 40 of 43

Abdel-Hamed El-Deeb
Highlight
Page 41: UPS Calculation

Alphanumeric keyboard Yes ; Onscreen keyboard

Touch operation

Design as touch screen Yes

Installation type/mounting

Mounting in portrait format possible Yes

Mounting in landscape format possible Yes

Supply voltage

Type of supply voltage DC

Rated voltage/DC 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Input current

Current consumption (rated value) 0.24 A

Inrush current A²s 0.5 A²·s

Power

Power consumption, typ. 6 W

Processor

Processor type

X86 No

ARM Yes ; RISC 32-bit

Memory

Flash Yes

RAM Yes

Usable memory for user data 1 Mbyte

Type of output

Acoustics

Buzzer Yes

Speaker No

Time of day

Clock

Hardware clock (real-time clock) No

Software clock Yes

Battery-backed No

Synchronizable Yes

Interfaces

Number of RS 485 interfaces 0

Number of USB interfaces 0

Number of SD card slots 0

6AV6647-0AB11-3AX0Page 2/ 07/20/2013

subject to modifications© Copyright Siemens AG 20139

Page 41 of 43

Abdel-Hamed El-Deeb
Highlight
Page 42: UPS Calculation

Product data sheet 6GK7242-5DX30-0XE0

Product-type designation CM 1242-5

COMMUNICATION MODULE CM 1242-5;FOR CONNECTION OF SIMATIC S7-1200 TO PROFIBUSAS DP SLAVE MODULE

Transmission rate

Transmission rate / at interface 1 / in accordance with PROFIBUS 9.6 kbit/s … 12 Mbit/s

Interfaces

Number of electrical connections

• at interface 1 / in accordance with PROFIBUS 1

• for power supply 0

Design of electrical connection

• at interface 1 / in accordance with PROFIBUS 9-pin Sub-D socket (RS485)

Supply voltage, current consumption, power loss

Type of voltage / of supply voltage DC

Supply voltage

• 1 / from backplane bus 5 V

Consumed current

• from backplane bus / at 5 V / for DC / Typical 0.15 A

Resistive loss 0.75 W

Permitted ambient conditions

Ambient temperature

• for vertical installation / during operating phase 0 … 45 °C

• for horizontal installation / during operating phase 0 … 55 °C

• during storage -40 … +70 °C

6GK7242-5DX30-0XE0Page 1/ 07/20/2013

subject to modifications© Copyright Siemens AG 20132

Page 42 of 43

Abdel-Hamed El-Deeb
Highlight
Page 43: UPS Calculation

55.32 55.33 55.34

2 CO (DPDT) 3 CO (3PDT) 4 CO (4PDT)

10/20 10/20 7/15

250/400 250/400 250/250

2,500 2,500 1,750

500 500 350

0.37 0.37 0.125

10/0.25/0.12 10/0.25/0.12 7/0.25/0.12

300 (5/5) 300 (5/5) 300 (5/5)

AgNi AgNi AgNi

6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240

6 - 12 - 24 - 48 - 60 - 110 - 125 - 220

1.5/1 1.5/1 1.5/1

(0.8…1.1)UN (0.8…1.1)UN (0.8…1.1)UN

(0.8…1.1)UN (0.8…1.1)UN (0.8…1.1)UN

0.8 UN/0.5 UN 0.8 UN/0.5 UN 0.8 UN/0.5 UN

0.2 UN/0.1 UN 0.2 UN/0.1 UN 0.2 UN/0.1 UN

20 · 106/50 · 106 20 · 106/50 · 106 20 · 106/50 · 106

200 · 103 200 · 103 150 · 103

10/5 10/5 11/3

4 4 4

1,000 1,000 1,000

–40…+85 –40…+85 –40…+85

RT I RT I RT I

2

Contact specification

Contact configuration

Rated current/Maximum peak current A

Rated voltage/Maximum switching voltage V AC

Rated load AC1 VA

Rated load AC15 (230 V AC) VA

Single phase motor rating (230 V AC) kW

Breaking capacity DC1: 30/110/220 V A

Minimum switching load mW (V/mA)

Standard contact material

Coil specification

Nominal voltage (UN) V AC (50/60 Hz)

V DC

Rated power AC/DC VA (50 Hz)/W

Operating range AC

DC

Holding voltage AC/DC

Must drop-out voltage AC/DC

Technical data

Mechanical life AC/DC cycles

Electrical life at rated load AC1 cycles

Operate/release time ms

Insulation between coil and contacts (1.2/50 μs) kV

Dielectric strength between open contacts V AC

Ambient temperature range °C

Environmental protection

Approvals (according to type)

FeaturesPlug-in mount, general purpose 2, 3 & 4 Pole relays

55.32 - 2 Pole 10 A55.33 - 3 Pole 10 A 55.34 - 4 Pole 7 A

• Lockable test button and mechanical flagindicator as standard on 2 & 4 pole types

• AC coils & DC coils• UL Listing (certain relay/socket combinations)• Cadmium Free contacts (preferred version)• Contact material options• 94 series sockets• Coil EMC suppression• Timer accessories 86 series• European Patent

• 2 pole, 10 A• Plug-in 94 series sockets

• 3 pole, 10 A• Plug-in 94 series sockets

• 4 pole, 7 A• Plug-in 94 series sockets

FOR UL RATINGS SEE: “General technical information” page V

55.32 55.33 55.34

55 Series - General purpose relays 7 - 10 A

VII-2

012,

ww

w.fi

nder

net.c

om

Page 43 of 43

Abdel-Hamed El-Deeb
Highlight
Abdel-Hamed El-Deeb
Highlight
Abdel-Hamed El-Deeb
Highlight
Abdel-Hamed El-Deeb
Highlight